B.08.04 Revised Appx B - Existing PLC IO.pdf

PDF 80 KB Posted

Attached to
Truman Lake Station Drainage Replacement Federal contract opportunity
Solicitation number
W912DQ22B1015
Issued by
Department of the Army Corps of Engineers Engineering District Kansas City

About this file

This document contains an appendix describing existing programmable logic controller input/output points and a solicitation notice for a drainage replacement project. The appendix lists input and output cards along with input and output point descriptions for station and unwatering control systems. The solicitation is from the Department of the Army Corps of Engineers Engineering District Kansas City for the Truman Lake Station Drainage Replacement project. Bids are due on September 7, 2022. The opportunity is for replacement of existing equipment described in the appendix with new drainage infrastructure at the Truman Lake facility.

View the file

Other files for this federal contract opportunity

Other files attached to Truman Lake Station Drainage Replacement, newest first.
File Type Posted
HST OF 1419A.pdf PDF
B.08.04 Solicitation Amendment 03.pdf PDF
B.08.04 Solicitation Amendment 02.pdf PDF
B.08.04 Solicitation Amendment 01.pdf PDF
B.07.01 Site Visit Sign in.pdf PDF
HST Drain Pump Specs.PDF PDF
HST DRAINAGE - RTA.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Appendix B

IO POINT DESCRIPTION TYPE COMMENT

I:5/0 Station Transducer Float Selected 100/120 VAC I:5/1 Unwatering Transducer Float Selected 100/120 VAC I:5/2 Pump 1 Auto Selected 100/120 VAC I:5/3 Pump 2 Auto Selected 100/120 VAC I:5/5 Pump 4 Auto Selected 100/120 VAC I:5/6 Pump 5 Auto Selected 100/120 VAC I:5/7 U1 Valve Closed 100/120 VAC I:5/8 Oil Detected 100/120 VAC

1746-NI4 - Analog 4 Channel Input Module I:1.0 Station Transducer 1 (4-20mA) I:1.1 Unwatering Transducer (4-20mA) I:1.2 Header Transducer (4-20mA) I:1.3 Station Transducer 2 (4-20mA)

OUTPUT CARDS

1746-OW8 - 8-Output (RLY) O:3/0 Station Pump Stop (RLY) 240 VAC O:3/1 Station Pump 1 Run (RLY) 240 VAC O:3/2 Station Pump 2 Run (RLY) 240 VAC O:3/3 Station High Level Alarm (RLY) 240 VAC ALARM O:3/4 Station Emergency High Level Alarm (RLY) 240 VAC ALARM O:3/5 Station Extended Run Time Alarm (RLY) 240 VAC ALARM O:3/6 Unwatering Pump 3 Stop (RLY) 240 VAC O:3/7 Unwatering Pump 3 Run (RLY) 240 VAC

1746-OW8 - 8-Output (RLY) O:4/0 Unwatering High Level Alarm (RLY) 240 VAC ALARM O:4/1 Unwatering Emergency High Level Alarm (RLY) 240 VAC ALARM O:4/2 Unwatering Extended Run Time Alarm (RLY) 240 VAC ALARM O:4/3 Oil Detected Alarm (RLY) 240 VAC ALARM O:4/4 Unwatering Pump 4 Run (RLY) 240 VAC O:4/5 Unwatering Pump 5 Run (RLY) 240 VAC O:4/6 Unwatering Pump 4 Stop (RLY) 240 VAC O:4/7 Unwatering Pump 5 Stop (RLY) 240 VAC

INPUT CARDS

1746-IA16 - 16-Input 100/120 VAC

Brad Brack Text Box Appendix B - Existing - note: to be replaced by new equipment in Appendix A

Existing PLC IO