Pages from 20241108_USDA_DFRC_RTA_Dwgs_V3_4.pdf
PDF 13 MB Posted
- Solicitation number
- W9128F25R0014
About this file
This file contains architectural, structural, mechanical, electrical and plumbing drawings for Buildings B14 (Fuel Storage), B15 (Commodity), and C2 (Solid Stack Building) and C3 (Solids/Sand Separation Facility) at the USDA Dairy Forage Research Center in Prairie du Sac, WI.
The drawings show detailed construction plans including foundation details, wall sections, floor plans, elevations, and utility systems for these support facilities. Key specifications include pre-engineered metal building construction with concrete foundations and slabs, insulated metal panel walls and roofing, overhead doors, and integrated mechanical/electrical systems. Building B14 is designed for fuel storage with containment measures. B15 serves as a commodity storage building. C2 is a solid stack building for manure storage with 5,760 SF. C3 contains settling tanks and sand separation systems with associated pumps and controls. The drawings include complete dimensions, materials, and installation details needed for construction, with sheets numbered using standard architectural conventions (A for architectural, S for structural, M for mechanical, etc.).
View the file
Other files
Show 40 more
Latest 50 of 94 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B14.A B14.B B14.C B14.D B14.E B14.F B14.G B14.H B14.I B14.J B14.K
B14.1
B14.2
B14.3
B14.4
B14.5
B14.6
B14.7
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
N
EW
D
AI
R Y
FO
R
AG
E
R
ES
EA
R
C H
C
EN
TE
R
Au to de sk
D oc s:
//1
5_
U
SD
A_ D
FR
C
_2
2/
A _S
_M
EP
-B
.rv t
/2
8/
:3 4:
A
M
I-101-B14
R O
O M
F
IN
IS
H
S C
H
ED
U
LE
AR
EA
B
FU
EL
ST
O
R
AG
E
PR
AI
R
IE
D U
S
AC
, W I
O M
AH
A
D
IS
TR
IC
T
H D
R
AR
LI
N
G
TO
N , V
IR
G
IN
IA
J.
W ille
M . B ro w ns te in
R . R in eh ar t
/0
8/
W
F2
0C
W
F2
1C
NORTH
KEY PLAN
B14
1/4" = 1'-0"1 ROOM FINISH PLAN - AREA B14
FINISH SCHEDULE
ROOM NO ROOM NAME
FLOOR
NOTES & REMARKS (SEE NOTES)MAT FIN
B14-100 FUEL STORAGE CONC LBRF
R
TA
/0
8/
1.
PROVIDE #10 WIRE FOR ALL 20A 120V CIRCUITS EXCEEDING 75 FEET AND FOR 20A 277V
CIRCUITS THAT EXCEED 150 FEET.
2.
RECEPTACLES SHALL BE WIRED AS FOLLOWS: 3 CIRCUIT, 20A, HOMERUNS TO PANELS
SHALL BE 3#12 PHASE CONDUCTORS, 3#12 NEUTRAL CONDUCTORS AND 1#12 GROUND. 2
CIRCUIT, 20A, HOMERUNS TO PANELS SHALL BE 2#12 PHASE CONDUCTORS, 2#12 NEUTRAL
CONDUCTORS, AND 1 #12 GROUND. 1 CIRCUIT, 20A, HOMERUNS TO PANEL SHALL BE 1#12
PHASE CONDUCTOR, 1#12 NEUTRAL CONDUCTOR AND 1#12 GROUND.
3.
VERIFY LOCATION AND CONNECTIONS REQUIREMENTS FOR EQUIPMENT PROVIDED BY
OTHER TRADES PRIOR TO ROUGH-IN.
4.
COORDINATE CEILING MOUNTED LIGHTS AND DEVICES WITH CEILING CONTRACTOR AND
INSTALL AS SHOWN ON THE REFLECTED CEILING PLANS.
5.
ALL FLOOR MOUNTED ELECTRICAL EQUIPMENT (SWITCHGEAR, FREE STANDING
PANELBOARDS, TRANSFORMERS) SHALL BE INSTALLED ON 4" HIGH CONCRETE PAD.
6.
COORDINATE ALL DIMENSIONS & WIRING REQUIREMENTS ON ALL PRE-PURCHASED
EQUIPMENT WITH FINAL APPROVED SHOP DWGS.
7.
FIRE SEAL ALL CONDUIT PENETRATIONS THROUGH FIRE RATED WALLS & SLABS. SEAL FIRE
RATING SHALL BE EQUAL TO OR GREATER THAN THE FIRE RATING OF THE WALL OR SLAB
THROUGH WHICH THE CONDUIT PASSES.
8.
COORDINATE THE LOCATION AND MOUNTING HEIGHTS OF OUTLETS AND MULTI-OUTLET
ASSEMBLIES WITH ARCHITECTURAL FLOOR PLANS AND ELEVATION DRAWINGS..
9.
CONTRACTOR SHALL VERIFY ALL DOOR SWINGS BEFORE INSTALLING SWITCH BOXES.10.
FOR MOUNTING HEIGHT OF UNDER-SHELF/CABINET LIGHTING FIXTURES REFER TO
ARCHITECTURAL DRAWINGS.
11.
COORDINATE EXACT LOCATION OF SUSPENDED LIGHTING FIXTURES IN MECHANICAL AND
STORAGE AREAS WITH OTHER TRADES.
12.
RACEWAYS, SLEEVES, AND BOXES FOR IT CABLING SHALL COMPLY WITH COMMERCIAL
BUILDING STANDARD FOR TELECOMMUNICATION PATHWAYS AND SPACES,
ANSI/TIA/EIA-569-A.
13.
BOND FLAMMABLE LIQUID STORAGE CABINETS WITH #10 AWG WIRE TO THE NEAREST STEEL
COLUMN. INSTALL WIRE IN CONDUIT.
GENERAL NOTES
MOTOR CONTROL CENTER
PANEL DESIGNATION
EMCC1S1-XX
SYSTEM DESIGNATION
N NORMAL
E EMERGENCY
C CRITICAL
LS LIFE SAFETY
EQ EQUIPMENT
R RELAY
U U.P.S.
D DIMMING
VOLTAGE DESIGNATION
L 208/120V M 240/120V
H 480/277V, 480V, OR 380/220V
PANEL TYPE
D DISTRIBUTION PANEL
(DISTRIBUTION PANELS ONLY)
CLOSET LOCATION
N NORTH
S SOUTH
E EAST
W WEST
C CENTRAL UTILITY PLANT
FLOOR DESIGNATION
0 LOWER LEVEL
1 1ST FLOOR
2 2ND FLOOR
3 3RD FLOOR
DESIGNATION
CIRCUIT NUMBER
CLOSET LOCATION
(SEE PANEL DESIGNATION)
FLOOR DESIGNATION
(SEE PANEL DESIGNATION)
DESIGNATION
CIRCUIT NUMBER
TRANSFORMER
ET2S1
SYSTEM DESIGNATION
N NORMAL
E EMERGENCY
C CRITICAL
LS LIFE SAFETY
EQ EQUIPMENT
U U.P.S.
CLOSET LOCATION
(SEE PANEL DESIGNATION)
FLOOR DESIGNATION
(SEE PANEL DESIGNATION)
DESIGNATION
SYSTEM DESIGNATION
N NORMAL
E EMERGENCY
C CRITICAL
LS LIFE SAFETY
EQ EQUIPMENT
U U.P.S.
EHD2S1-XX
ALL DEVICE MOUNTING HEIGHTS INDICATED ON THIS LEGEND ARE FROM FINISHED FLOOR
TO CENTER OF OUTLET BOX.
14.
PS
GENERAL
XX
XX
XX
XX
1,3,5
1LN1PANEL NAME
CIRCUIT NUMBER(S)
CIRCUIT NUMBER(S)
PANEL NAME
1LN1-1,3,5
BRANCH CIRCUIT HOMERUN. PROVIDE #12 PHASE, #12 NEUTRAL
AND #12 GROUND CONDUCTORS FOR EACH INDICATED CIRCUIT
OR
MULTI WIRE BRANCH U.O.N. PROVIDE SWITCH LEGS FOR SWITCH
CIRCUITING AS REQUIRED. PROVIDE EQUIPMENT GROUND WIRE
IN
ALL BRANCH CIRCUIT RACEWAYS. PROVIDE SEPARATE
ISOLATED
GROUND WIRE TO ALL ISOLATED GROUND DEVICES.
CONDUIT RISER UP
CONDUIT RISER DOWN
INDICATES CIRCUIT CONTINUATION
STUB INTO ACCESSIBLE CORRIDOR CEILING SPACE UNLESS
OTHERWISE NOTED
CONDUIT SEAL FITTING FOR HAZARDOUS AREAS
CONDUIT SLEEVE
CAP END OF CONDUIT
CONDUIT RUN BELOW GRADE, UNDER OR CONCEALED IN FLOOR
SLAB, UNDER RAISED FLOOR
SYSTEM CIRCUIT. SUBSCRIPT "XX" DENOTES SYSTEM TYPE
CONDUIT TO TERMINAL CABINET. SUBSCRIPT "XX" DENOTES
SYSTEM TYPE
CIRCUIT DESIGNATIONS
CONDUIT RUN CONCEALED IN CEILING OR WALL
XXXX-XXXX
XXXX-XXXX
J TV
POWER SUPPLY
EMERGENCY POWER OFFEPO
MEDICAL GAS ALARMMGA
PHYSIOLOGICAL MONITOR
REMOTE CONTROL
TEMPERATURE CONTROL
CLOSED CIRCUIT TELEVISIONCCTV
GROUNDING ELECTRODE CONDUCTOR
SECURITYSEC
TELEVISION
TELEPHONE
PUBLIC ADDRESS SYSTEM
INTRUSION DETECTION
DOOR CONTROL
INTERCOM
FIRE ALARM
DATA TECHNOLOGY
NURSE CALL
DOCTORS REGISTER
DOCTORS DICTATION
CARDIAC ARREST (CODE BLUE)
THE FOLLOWING SUBSCRIPTS ARE USED TO INDICATE
DIFFERENT SYSTEM TYPES
FOOT ON DEVICE INDICATES WALL MOUNTED
MARK NUMBER FOR FIXED EQUIPMENT
MARK NUMBER FOR MECHANICAL EQUIPMENT
KEY NOTE REFERENCE SYMBOL.
PM
RC
TC
G
TV
TEL
PA
ID
DC
IC
FA
DT
NC
DR
DD
CA
PARAPET MOUNTED AIR TERMINAL REFER TO
DETAILS.
SCREEN WALL MOUNTED AIR TERMINAL REFER TO
DETAILS.
FLAT ROOF MOUNTED AIR TERMINAL REFER TO
DETAILS.
THRU ROOF DOWN CONDUCTOR TO GROUNDING
SYSTEM
MAIN CONDUCTOR
SECONDARY CONDUCTOR
BONDING CONNECTION
GROUND CONDUCTOR
COPPER GROUND ROD 3/4"DIA. X 10'-0"
LONG
G
S
P
LIGHTNING PROTECTION
A
B
A
A
6A
RC
A
TYPICAL OUTLET SYMBOL NOTES
"*" -MOUNTED 4" ABOVE COUNTER, CASEWORK, BACKSPLASH OR 46" IF NOTHING BELOW.
COORDINATE WITH ARCHITECTURAL DETAILS AND CASEWORK CONTRACTOR.
"+84" -INDICATES MOUNTING HEIGHT ABOVE FINISHED FLOOR.
"GF" -GROUND FAULT CIRCUIT INTERRUPTER.
"ST" -SAFETY TYPE
"IG" -ISOLATED GROUND
"WP" -WEATHERPROOF
"XP" -EXPLOSION PROOF
"SW" -TOP HALF OF DUPLEX RECEPTACLE SWITCHED
"CL" -CLOCK RECEPTACLE
20A, 125V, 2 POLE, 3 WIRE GROUNDING DUPLEX RECEPTACLE, RED
20A, 125V, 2 POLE, 3 WIRE GROUNDING SINGLE RECEPTACLE
20A, 125V, 2 POLE, 3 WIRE GROUNDING SINGLE RECEPTACLE, RED
20A, 125V, 2 POLE, 3 WIRE GROUNDING DOUBLE DUPLEX RECEPTACLE
20A, 125V, 2 POLE, 3 WIRE GROUNDING DOUBLE DUPLEX RECEPTACLE, RED
PEDESTAL - BENCH MOUNTED BACK-TO-BACK DUPLEX CONVENIENCE
RECEPTACLE.
PEDESTAL - BENCH MOUNTED DUPLEX CONVENIENCE RECEPTACLE.
PEDESTAL - BENCH MOUNTED BACK-TO-BACK DOUBLE DUPLEX
CONVENIENCE RECEPTACLE
PEDESTAL - BENCH MOUNTED DOUBLE DUPLEX CONVENIENCE RECEPTACLE.
SPECIAL OUTLET. REFER TO SCHEDULE FOR REQUIREMENTS.
20A, 125V, 2 POLE, 3 WIRE GROUNDING DOUBLE DUPLEX RECEPTACLE. SPECIAL
PURPOSE I.E. UPS
20A, 125V, 2 POLE, 3 WIRE GROUNDING DUPLEX RECEPTACLE.
SPECIAL PURPOSE I.E. UPS
FLOOR BOX - REFER TO SCHEDULE FOR REQUIREMENTS
POKE THROUGH - REFER TO SCHEDULE FOR REQUIREMENTS
ONE PREWIRED DUPLEX RECEPTACLE, 125 VOLTS, 20 AMP. MOUNTED IN
CAST BOX SUPPLIED WITH CABLE BY COMPUTER POWER CENTER
MANUFACTURER. INSTALLED UNDER RAISED FLOOR. REFER TO COMPUTER
ROOM EQUIPMENT SCHEDULE.
TWO PREWIRED DUPLEX RECEPTACLES (QUAD), 125 VOLTS, 20 AMP. MOUNTED
IN CAST BOX SUPPLIED WITH CABLE BY COMPUTER POWER CENTER
MANUFACTURER. INSTALLED UNDER RAISED FLOOR. REFER TO COMPUTER
ROOM EQUIPMENT SCHEDULE.
SPECIAL PURPOSE PREWIRED RECEPTACLE OR CONNECTOR AS INDICATED IN
COMPUTER ROOM EQUIPMENT SCHEDULES, SUPPLIED WITH CABLE BY
COMPUTER POWER CENTER MANUFACTURER. INSTALLED UNDER RAISED
FLOOR BY E.C.
MULTIOUTLET ASSEMBLY, - INDICATES TYPE, - INDICATES QUANTITY
OF DUPLEX RECEPTACLES. SEE MULTIOUTLET ASSEMBLY SCHEDULE. SEE
DETAIL DRAWINGS FOR INSTALLATION REQUIREMENTS.
POWER / TELECOMM POLE. PROVIDE JUNCTION BOX ABOVE CEILING FOR
POWER CONNECTION, CONNECT TO WIRING IN POWER POLE. SEE SCHEDULE
EXTENSION CORD REEL
TYPICAL OUTLET SYMBOL CIRCUITING NOTES
NOTES
1. OUTLETS LOCATED AT COUNTERS SHALL BE LOCATED 18" AFF IN KNEE SPACE IF PROVIDED
OR 4" ABOVE COUNTER OR BACK SPLASH AS APPLICABLE IF NO KNEE SPACE IS PROVIDED
UON.
POWER OUTLETS
20A, 125V, 2 POLE, 3 WIRE GROUNDING DUPLEX RECEPTACLE
CEILING MOUNTED RECEPTACLE, TYPE AS INDICATED ABOVE
GF
+30"
PANEL NAME
CIRCUIT NUMBER
ELEVATION
TYPE
LP-1
GF
+30"
PANEL NAME
CIRCUIT NUMBER
ELEVATION
TYPE
LP-1
1,3,5
"OC" -OCCUPANCY CONTROLLED
EPO
T
30/3
30/6
30/3
20AF
30/3
12x3
CP
T
C
ASD
JJ
J
J
M
480/277V OR 480V PANEL
208/120V PANEL
120/240V PANEL
RELAY PANEL
COMBINATION FULL VOLTAGE MOTOR STARTER
REV REVERSING
COMBINATION FULL VOLTAGE MOTOR STARTER / DISCONNECT
REV REVERSING
ADJUSTABLE SPEED DRIVE
JUNCTION BOX, MOUNTED ABOVE CEILING IN AREAS WITH
SUSPENDED CEILING, MOUNTED EXPOSED IN AREAS WITH NO
SUSPENDED CEILING
JUNCTION BOX WITH FLEXIBLE CONNECTION TO EQUIPMENT
INDICATED AND REQUIRED
JUNCTION BOX, FLUSH WALL MOUNTED
T JUNCTION BOX FOR VOICE/DATA
BUS DUCT, FEEDER OR PLUG-IN TYPE AS INDICATED
EMERGENCY POWER OFF' BREAK GLASS STATION.
POWER DISTRIBUTION
DISCONNECT SWITCH
6 POLE DISCONNECT SWITCH (FOR ALL 2 SPEED MOTORS)
FUSED DISCONNECT SWITCH
MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD
PROTECTION.
CONTACTOR
ENCLOSED CIRCUIT BREAKER
COMBINATION REDUCED VOLTAGE MOTOR STARTER
COMBINATION REDUCED VOLTAGE MOTOR STARTER/DISCONNECT
COMBINATION 2 SPEED MOTOR STARTER/DISCONNECT
MOTOR - NUMBER INDICATES HORSEPOWER
2 SPEED MOTOR - NUMBER INDICATES HORSEPOWER
CONTROL PANEL FURNISHED BY OTHERS, INSTALLED BY
DIVISION 16, UON
PUSHBUTTON STATIONS. ONE, TWO, OR THREE AS INDICATED
CABLE TRAY - WIDTH x HEIGHT AS NOTED, OR KEY NOTED
UNDER FLOOR DUCT SYSTEM
DRY TYPE TRANSFORMER
NOTE:
SYMBOLS SHOWN ARE FOR REFERENCE ONLY
AND DO NOT CONSTITUTE A CHECK LIST OF
DEVICES REQUIRED BY THE CONTRACT
A
NOTES:
1. MULTI-CIRCUIT RACEWAYS SHALL BE ALTERNATELY CIRCUITED. LABEL ALL RECEPTACLES
WITH PANEL NAME AND CIRCUIT NUMBER.
B
C
ONE DUPLEX CONVENIENCE RECEPTACLE, 125 VOLTS, 20 AMP,
GROUNDING TYPE
ONE DUPLEX CONVENIENCE RECEPTACLE, 125 VOLTS, 20 AMP,
GROUNDING TYPE AND ONE VOICE/DATA OUTLET
ONE DUPLEX CONVENIENCE RECEPTACLE, 125 VOLTS, 20 AMP,
GROUNDING TYPE
ONE DUPLEX CONVENIENCE RECEPTACLE, 125 VOLTS, 20 AMP,
GROUNDING TYPE AND ONE VOICE/DATA OUTLET
DESCRIPTIONSYMBOL
FLUSH FLOOR BOX/POKE-THRU SCHEDULE
REMARKS
A
B
A
B
WIREMOLD SERIES G-3000
WIREMOLD SERIES G-4000
WIREMOLD SERIES G-6000
2'-0"
2'-0"
2'-0"
NA
PLANS
AS SHOWN
AS SHOWN
PLANS
REMARKSTELE/DATA
OUTLET CENTERS
POWERDESCRIPTION
MULTIOUTLET ASSEMBLY SCHEDULE
TYPE
A
B
SYMBOL NEMA
CONFIGURATION
WIRE/CONDUIT
(UON)
VOLTAGE
RATING
C.B. OR FUSE
AMPS/POLES REMARKS
2#12 & 1#12G-3/4"C
2#10 & 1#10G-3/4"C
250V
250V
20/2
30/2
L6-20R
L6-30R
SPECIAL OUTLETS SCHEDULE
E
M
ER
E
M
ER
EX
B
EXISTING ELECTRICAL ITEM TO BE REMOVED AND PROVIDED WITH A
BLANK COVER PLATE
EXISTING ELECTRICAL OR SYSTEMS CIRCUIT TO REMAIN.
NOTES:
THE FOLLOWING SYMBOLS ARE EXAMPLES INTENDED TO SHOW METHODOLOGY FOR
DEMOLITION. THIS APPROACH IS APPLICABLE TO ALL SYMBOLS INDICATED ON THIS
SCHEDULE.
EXISTING ELECTRICAL ITEM TO REMAIN
EXISTING ELECTRICAL ITEM TO BE RELOCATED
EXISTING ELECTRICAL ITEM TO BE REMOVED
EXISTING ELECTRICAL RELOCATED. NEW LOCATION
EXISTING ELECTRICAL OR SYSTEMS CIRCUIT TO BE REMOVED. SHOWN
ONLY
WHERE CLARIFICATION BETWEEN EXISTING TO REMAIN AND REMOVED IS
REQUIRED.
DEMOLITION AND REMODEL
A, AMP AMPERES
AF AMP FUSE OR AMP FRAME
AFC AVAILABLE FAULT CURRENT (SYMMETRICAL)
AFF ABOVE FINISHED FLOOR
AIC AMPERE INTERRUPTING CAPACITY
AM AMMETER
AS AMP SWITCH OR AMMETER SWITCH
ASYM ASYMMETRICAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BOF BOTTOM OF FIXTURE
B.S.C BARE STRANDED COPPER CONDUCTOR
C CONDUIT
CAP CAPACITY OR CAPACITOR
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT ,CCT CIRCUIT
CL CURRENT LIMITING
C.O. CONDUIT ONLY
CONN CONNECT OR CONNECTION
CU COPPER
DA DURESS ALARM
DB DOOR BELL
DISC DISCONNECT
DPST DOUBLE POLE SINGLE THROW
EC ELECTRICAL CONTRACTOR
EWC ELECTRIC WATER COOLER
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATION OR ELEVATOR
EMERG, EM EMERGENCY
EPO EMERGENCY POWER OFF
EMT ELECTRICAL METAL TUBING
EG ENGINE GENERATOR
FDR FEEDER
FIXT FIXTURE
FLA FULL LOAD AMPERES
FLUOR FLUORESCENT
GRC,GCR GALVANIZED RIGID CONDUIT
GEC GROUNDING ELECTRODE CONDUCTOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFI,GF GROUND FAULT INTERRUPTER
GRD,GND,G GROUND
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTO
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HZ HERTZ
IMC INTERMEDIATE METAL CONDUIT
IG ISOLATED GROUND
INCAND INCANDESCENT
JB JUNCTION BOX
KAIC THOUSAND AMPERE INTERRUPTING CAPACITY
KVA KILOVOLT AMPERES
KW KILOWATT
KWH KILOWATT HOUR
LTG LIGHTING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MH MANHOLE, METAL HALIDE OR MOUNTING HEIGHT
MLO MAIN LUGS ONLY
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NIC NOT IN CONTRACT
NF NON FUSIBLE
NL NIGHT LIGHT
N.O. NORMALLY OPEN
NTS NOT TO SCALE
OCP OVER CURRENT PROTECTION
OL OVERLOADS
P POLE
PB PULLBOX
PH OR Ø PHASE
PNL PANEL
POC POINT OF CONNECTION
PR PAIR
PVC POLYVINYL CHLORIDE
PWR POWER
REC RECEPTACLE
RGS RIGID GALVANIZED STEEL
RX REQUEST TO EXIT
SOL SOLENOID
SPTD SINGLE POLE DOUBLE THROW
SPKR SPEAKER
SPST SINGLE POLE SINGLE THROW
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
TEL TELEPHONE
TGB TELECOMMUNICATIONS GROUNDING BUSBAR
TRANSF TRANSFORMER
TTB TELEPHONE TERMINAL BACKBOARD
TV TELEVISION
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
V VOLT
VA VOLT AMPERES
VD VOLTAGE DROP
VM VOLT METER
VS VOLT METER SWITCH
W WATTS OR WIRE
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
XFORM TRANSFORMER
XP EXPLOSION PROOF
ABBREVIATIONS
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
N
EW
D
AI
R Y
FO
R
AG
E
R
ES
EA
R
C H
C
EN
TE
R
Au to de sk
D oc s:
//1
5_
U
SD
A_ D
FR
C
_2
2/
A _S
_M
EP
-B
.rv t
/2
8/
:3 4:
A
M
E-001-B14
EL
EC
TR
IC
AL
G
EN
ER
AL
N
O
TE
S, S
YM
BO
LS
L
IS
T, AN
D
A
BB
R
EV
IA
TI
O N
S
- A
R
EA
B
FU
EL
ST
O R
AG
E
PR
AI
R
IE
D U
S
AC
, W I
O M
AH
A
D
IS
TR
IC
T
H D
R
AR
LI
N
G
TO
N , V
IR
G
IN
IA
J.
W ille
M . B ro w ns te in
R . R in eh ar t
/0
8/
W
F2
0C
W
F2
1C
1/8" = 1'-0"1 E001
R
TA
/0
8/
G
KWHD
GFI
GFP
GRA
ALT
VM
AM
WM
FM
DM
T-1 15kVA
3PH, 4W
480-208/120V
#8G
T-1 T15
800A 3P
800 AF
800 AT
3P
XXXXAF XXXXAT 3P
AS
VS
WS
CIRCUIT BREAKER. AMP/POLES AS INDICATED
FUSE. SIZE AS INDICATED
FUSIBLE SWITCH. AMP/POLES/FUSE SIZE AS INDICATED
AUTOMATIC TRANSFER SWITCH
TRANSFORMER - SEE SCHEDULE FOR REQUIREMENTS
GROUND CONNECTION
GENERATOR
AMMETER PHASE SELECTOR SWITCH
VOLTMETER PHASE SELECTOR SWITCH
WATTMETER ON-OFF SWITCH
A.C. VOLTMETER
A.C. AMMETER
WATTMETER
FREQUENCY METER
DIGITAL METERING
KILOWATT HOUR/DEMAND METER
GENERATOR GROUND FAULT INDICATION
GROUND FAULT PROTECTION
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
GENERATOR REMOTE ANNUNCIATOR
ALTERNATOR FURNISHED BY OTHER THAN DIVISION 16
DISCONNECT SWITCH. SIZE AS INDICATED
MEDIUM VOLTAGE DRAWOUT CIRCUIT BREAKER.
LOW VOLTAGE DRAWOUT CIRCUIT BREAKER.
LIGHTNING ARRESTERS
TRANSFORMER
XXX
3 LA'S
POWER ONE-LINE DIAGRAM
D D
OS
WS
PC
OS
OS
PC
a
WP
a
U
1NC5
M
3WA6
R
S
P
DWP
WP
1NC5
2EA4
LIGHTING
LOW VOLTAGE WALL STATION DEVICE PUSHBUTTON
PUSHBUTTON TYPE DESIGNATION
WP - MOUNTED IN WEATHERPROOF ENCLOSURE
PUSHBUTTON DESIGNATION CODE
FLOOR NUMBER
BUILDING LOCATION/AREA
RELAY PANEL SEQUENCE
PUSHBUTTON SEQUENCE
LOW VOLTAGE CEILING MOUNTED RELAY CONTROL SYSTEM OCCUPANCY SENSOR
DEVICE TYPE DESIGNATION
P - PASSIVE INFRARED
U - ULTRASONIC
D - DUAL TECHNOLOGY
WP - MOUNTED IN WEATHERPROOF ENCLOSURE
DEVICE DESIGNATION CODE
FLOOR NUMBER
BUILDING LOCATION/AREA
RELAY PANEL SEQUENCE
DEVICE SEQUENCE
DIRECTIONAL ARROWS (ONLY INCLUDED WHEN ZONE
OF DETECTION IS NOT 360°)
LOW VOLTAGE RELAY CONTROL SYSTEM PHOTOCELL
DEVICE TYPE DESIGNATION
WP - WEATHERPROOF
DEVICE DESIGNATION CODE
FLOOR NUMBER
BUILDING LOCATION/AREA
RELAY PANEL SEQUENCE
DEVICE SEQUENCE
DIRECTIONAL ARROW
CENTRAL/THEATRICAL DIMMING SYSTEM WALL AND CEILING MOUNTED DEVICES
DEVICE TYPE DESIGNATION
M - MAIN CONTROL STATION
S - SECONDARY CONTROL STATION
P - PARTITION CONTROL
R - INFRARED RECEIVER
V - AUDIO/VISUAL INTERFACE
DEVICE DESIGNATION CODE
FLOOR NUMBER
BUILDING LOCATION/AREA
DIMMING PANEL SEQUENCE
DEVICE SEQUENCE
LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR
LUMINAIRE CONTROL DESIGNATION
SENSOR TYPE DESIGNATION
P - PASSIVE INFRARED
U - ULTRASONIC
D - DUAL TECHNOLOGY
WP - MOUNTED WITHIN WEATHERPROOF ENCLOSURE
DIRECTIONAL ARROWS (ONLY INCLUDED WHEN ZONE OF DETECTION IS NOT 360°)
LINE VOLTAGE WALL MOUNTED OCCUPANCY SENSOR
LUMINAIRE CONTROL DESIGNATION
SENSOR TYPE DESIGNATION
P - PASSIVE INFRARED
U - ULTRASONIC
D - DUAL TECHNOLOGY
WP - MOUNTED WITHIN WEATHERPROOF ENCLOSURE
DIRECTIONAL ARROWS
LINE VOLTAGE DAYLIGHT HARVESTING PHOTOCELL
PHOTOCELL TYPE DESIGNATION
S - SWITCHING
D - DIMMING
VS
U
1NC5
LOW VOLTAGE CEILING MOUNTED RELAY CONTROL SYSTEM VACANCY SENSOR
DEVICE TYPE DESIGNATION
P - PASSIVE INFRARED
U - ULTRASONIC
D - DUAL TECHNOLOGY
WP - MOUNTED IN WEATHERPROOF ENCLOSURE
DEVICE DESIGNATION CODE
FLOOR NUMBER
BUILDING LOCATION/AREA
RELAY PANEL SEQUENCE
DEVICE SEQUENCE
DIRECTIONAL ARROWS (ONLY INCLUDED WHEN ZONE
OF DETECTION IS NOT 360°)
LUMINAIRE CONNECTED TO EMERGENCY LIFE SAFETY BRANCH AND
FURNISHED WITH EMERGENCY SELF-DIAGNOSTIC BATTERY INVERTER
BALLAST
GENERAL LIGHTING FIXTURE NORMAL AND EMERGENCY BRANCH DESIGNATIONS (TYPICAL
FOR ALL LIGHTING FIXTURES)
LUMINAIRE CONNECTED TO NORMAL BRANCH
LUMINAIRE CONNECTED TO EMERGENCY EGRESS / NIGHT LIGHT / LIFE
SAFETY BRANCH
LUMINAIRE CONNECTED TO EMERGENCY CRITICAL BRANCH
LUMINAIRE CONNECTED TO NORMAL BRANCH AND FURNISHED WITH
EMERGENCY SELF-DIAGNOSTIC BATTERY INVERTER BALLAST
LUMINAIRE CONNECTED TO EMERGENCY CRITICAL BRANCH AND
FURNISHED WITH EMERGENCY SELF-DIAGNOSTIC BATTERY INVERTER
BALLAST
DUAL BALLAST LUMINAIRE CONNECTED TO NORMAL BRANCH AND
EMERGENCY LIFE SAFETY BRANCH
DUAL BALLAST LUMINAIRE CONNECTED TO NORMAL BRANCH AND
EMERGENCY CRITICAL BRANCH
DUAL BALLAST LUMINAIRE CONNECTED TO EMERGENCY LIFE SAFETY
BRANCH AND EMERGENCY CRITICAL BRANCH
DUAL BALLAST LUMINAIRE CONNECTED TO NORMAL BRANCH AND
EMERGENCY CRITICAL BRANCH. AN EMERGENCY SELF-DIAGNOSTIC
BATTERY INVERTER BALLAST IS FURNISHED ON CRITICAL BRANCH
CONNECTION.
DUAL BALLAST LUMINAIRE CONNECTED TO NORMAL BRANCH AND
EMERGENCY LIFE SAFETY BRANCH. AN EMERGENCY SELF-DIAGNOSTIC
BATTERY INVERTER BALLAST IS FURNISHED ON LIFE SAFETY BRANCH
CONNECTION.
LIGHTING FIXTURE DESCRIPTIONS
CEILING MOUNTED EXIT SIGN
· INDICATES DIRECTIONAL CHEVRON(S)
· DENOTES LOCATION(S) OF ILLUMINATED EXIT FACE
WALL MOUNTED EXIT SIGN
· INDICATES DIRECTIONAL CHEVRON(S)
· DENOTES LOCATION(S) OF ILLUMINATED EXIT FACE
EMERGENCY TWIN HEAD FLOOD LIGHTING UNIT WITH INTEGRAL
BATTERY PACK
EMERGENCY TWIN HEAD FLOOD LIGHTING UNIT WITH REMOTE
BATTERY PACK
EMERGENCY SINGLE HEAD FLOOD LIGHTING UNIT WITH REMOTE
BATTERY PACK
LIGHTING
L3 a
GENERAL LIGHTING FIXTURE DESIGNATIONS (TYPICAL FOR ALL LIGHTING FIXTURES)
LUMINAIRE TYPE.
· DENOTED BY UPPER CASE ALPHANUMERIC DESIGNATION. REFER TO
LIGHTING FIXTURE SCHEDULE.
· “ER” DENOTES EXISTING RELOCATED FIXTURE. REFER TO
DEMOLITION DRAWINGS FOR EXISTING TO BE RELOCATED FIXTURES.
SWITCHING CONTROL ZONE
· LOWER LETTER SUBSCRIPT MATCHES DESIGNATION OF
CORRESPONDING SWITCHING CONTROL DEVICE (USED ONLY
WHERE NECESSARY FOR CLARIFICATION).
NOTE: LUMINAIRE TYPE AND CIRCUIT NUMBER INDICATED AT A
CONTINUOUS ROW OF FIXTURES SHALL BE CONSIDERED TO BE
TYPICAL FOR ALL FIXTURES IN THAT ROW. UNLESS NOTED OTHERWISE.
a
OD LINE VOLTAGE WALL MOUNTED SWITCH
LUMINAIRE CONTROL DESIGNATION
SWITCH TYPE DESIGNATION
NO SUBSCRIPT - SINGLE POLE
3 - THREE WAY
4 - FOUR WAY
K - KEY OPERATED
L - PILOT LIGHT "ON" WITH LIGHTS
M - MOMENTARY CONTACT
OP - OCCUPANCY SENSOR SWITCH, PASSIVE INFRARED
OU - OCCUPANCY SENSOR SWITCH, ULTRASONIC
OD - OCCUPANCY SENSOR SWITCH, DUAL TECHNOLOGY
OR - OCCUPANCY SENSOR SWITCH, DUAL TECHNOLOGY W/ DUAL RELAY
OL - OCCUPANCY SENSOR SWITCH, PILOT/NIGHT LIGHT
T - TIME SWITCH
T3 - THREE WAY TIME SWITCH
D - DIMMER SWITCH
D3 - THREE WAY DIMMER SWITCH
XP - EXPLOSION PROOF
WP - MOUNTED WITHIN WEATHERPROOF ENCLOSURE
VP - VACANCY SENSOR SWITCH, PASSIVE INFRARED
VU - VACANCY SENSOR SWITCH, ULTRASONIC
VD - VACANCY SENSOR SWITCH, DUAL TECHNOLOGY
VR - VACANCY SENSOR SWITCH, DUAL TECHNOLOGY W/ DUAL RELAY
VL - VACANCY SENSOR SWITCH, PILOT/NIGHT LIGHT
LIGHTING CONTROL DESIGNATIONS
LIGHTING CONTROL DESIGNATIONS
SITE LIGHTING FIXTURE DESCRIPTIONS
POLE MOUNTED SINGLE ARM LUMINAIRE
POLE MOUNTED TWIN ARM LUMINAIRE
POLE MOUNTED TRIPLE ARM LUMINAIRE
POLE MOUNTED QUAD ARM LUMINAIRE
GROUND MOUNTED TWIN FLOOD LUMINAIRE
POLE MOUNTED POST TOP LUMINAIRE
GROUND MOUNTED LOW LEVEL LUMINAIRE - BOLLARD
INGRADE UPLIGHT LUMINAIRE
· DENOTES DIRECTION OF LIGHT DISTRIBUTION
POLE MOUNTED SINGLE FLOOD LUMINAIRE
POLE MOUNTED TWIN FLOOD LUMINAIRE
GROUND MOUNTED SINGLE FLOOD LUMINAIRE
HHMH
TEL
UE
AE
GROUND ROD AND SYSTEM TEST WELL
GROUND ROD CONNECTION
ELECTRICAL MANHOLE OR HANDHOLE
MH=MANHOLE, HH=HANDHOLE
COMBINED POWER AND TELEPHONE UTILITY POLE
GROUND BUS ON STANDOFFS
EXOTHERMIC COMPRESSION CONNECTION
OVERHEAD ELECTRICAL WIRING
UNDERGROUND TELEPHONE CONDUIT
UNDERGROUND CONDUIT AND WIRING
SITE POWER AND TELECOMMUNICATIONS
0.0"
18"
6'-0"
4'-0"
FINISHED FLOOR
10'-0"
EXIT, WARNING, AND SIGNALING FIXTURES/SIGNS ( IF
FIXTURE/SIGN IS NOT DIRECTLY ABOVE A DOOR, USE HEIGHT OF
AN ADJACENT DOOR AS A GUIDE)
6'-8"
TOP OF WALL MOUNTED LIGHTING SWITCHES, MANUAL MOTOR
STARTERS, FIRE ALARM PULL STATIONS, WALL MOUNTED
TELEPHONES. (PER ADA REQUIREMENTS, NO "OPERABLE
PARTS" SHALL BE ABOVE +4'-0".)
TOP OF FLUSH AND SURFACE MOUNTED LIGHTING
PANELBOARDS AND TELEPHONE CABINETS.
TOP OF HIGHEST DISCONNECT SWITCHES, MAGNETIC
STARTERS, CONTACTORS, ATS.
ELECTRICAL RECEPTACLES, VOICE/DATA OUTLETS, DATA
OUTLETS, UON
BOTTOM LENS FOR WALL MOUNTED FIRE ALARM
STROBES
SPEAKERS, HORNS AND COMBINATION HORN/STROBES
BATTERY LIGHTING UNITS AND REMOTE WALL MOUNTED LIGHT
HEADS (OR 1'-0" BELOW FINISHED CEILING AT TOP OF UNIT)
MOUNT BOTTOM OF
FIXTURE/SIGN 4"
ABOVE TOP OF DOOR
FRAME UNLESS
OTHERWISE NOTED.
1. MOUNTING HEIGHTS FROM FINISHED FLOOR TO CENTER OF OUTLETS, UNLESS
OTHERWISE NOTED.
7'-0" CLOCK RECEPTACLES
5'-6" GENERATOR REMOTE ANNUNCIATOR
24" GARAGE RECEPTACLES
MOUNTING HEIGHT NOTES
MOUNTING HEIGHT NOTES
SITE EXTERIOR
NOTE:
SYMBOLS SHOWN ARE FOR REFERENCE ONLY
AND DO NOT CONSTITUTE A CHECK LIST OF
DEVICES REQUIRED BY THE CONTRACT
UNDERGROUND ELECTRICAL CONDUIT AND WIRING
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
N
EW
D
AI
R Y
FO
R
AG
E
R
ES
EA
R
C H
C
EN
TE
R
Au to de sk
D oc s:
//1
5_
U
SD
A_ D
FR
C
_2
2/
A _S
_M
EP
-B
.rv t
/2
8/
:3 4:
A
M
E-002-B14
EL
EC
TR
IC
AL
S
YM
BO
LS
L
IS
T
- A R
EA
B
FU
EL
ST
O
R
AG
E
PR
AI
R
IE
D U
S
AC
, W I
O M
AH
A
D
IS
TR
IC
T
H D
R
AR
LI
N
G
TO
N , V
IR
G
IN
IA
J.
W ille
M . B ro w ns te in
R . R in eh ar t
/0
8/
W
F2
0C
W
F2
1C
1/8" = 1'-0"1 E002
R
TA
/0
8/
EPB14
LED AREA LIGHT AT THE TOP OF
POLE ABOVE PANEL
B14.A B14.B B14.C B14.D B14.E B14.F B14.G B14.H B14.I B14.J B14.K
B14.1
B14.2
B14.3
B14.4
B14.5
B14.6
B14.7
40' - 0"
4x4 TREATED POST, 12'-0"
ABOVE CONCRETE SLAB
WITH 4'-0" EMBEDMENT,
BASE IN 12" CONCRETE
L1
EPB14-2
EPB14-1
EPB14-5
EPB14-3
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
N
EW
D
AI
R Y
FO
R
AG
E
R
ES
EA
R
C H
C
EN
TE
R
Au to de sk
D oc s:
//1
5_
U
SD
A_ D
FR
C
_2
2/
A _S
_M
EP
-B
.rv t
/2
8/
:3 4:
A
M
E-101-B14
FI
R
ST
F
LO
O
R E
LE
C
TR
IC
AL
P
LA
N
AR
EA
B
FU
EL
S
TO
R
AG
E
PR
AI
R
IE
D U
S
AC
, W I
O M
AH
A
D
IS
TR
IC
T
H D
R
AR
LI
N
G
TO
N , V
IR
G
IN
IA
J.
W ille
M . B ro w ns te in
R . R in eh ar t
/0
8/
W
F2
0C
W
F2
1C
NORTH
KEY PLAN
B14
1/4" = 1'-0"D8
FIRST FLOOR ELECTRICAL PLAN - AREA
B14
1 PANEL EPB14 TO BE FED FROM
PANEL EPB9 FROM B9
NOTES:
2 DIESEL PUMP
3 GASOLINE PUMP
4 PANEL EPB14 TO BE FED FROM
PANEL EPB11 FROM B11
R
TA
/0
8/
EPB14
4'
-0 " M
IN
IM
U M
'-0 " M
AX
IM
U M
GRADE
6" 5'
0"
1' - 2"
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
N
EW
D
AI
R Y
FO
R
AG
E
R
ES
EA
R
C H
C
EN
TE
R
Au to de sk
D oc s:
//1
5_
U
SD
A_ D
FR
C
_2
2/
A _S
_M
EP
-B
.rv t
/2
8/
:3 4:
A
M
E-601-B14
EL
EC
TR
IC
AL
S
C H
ED
U
LE
S
- A R
EA
B
FU
EL
ST
O
R
AG
E
PR
AI
R
IE
D U
S
AC
, W I
O M
AH
A
D
IS
TR
IC
T
H D
R
AR
LI
N
G
TO
N , V
IR
G
IN
IA
J.
W ille
M . B ro w ns te in
R . R in eh ar t
/0
8/
W
F2
0C
W
F2
1C
NORTH
KEY PLAN
B14
Notes:
Total Estimated Demand... 2 Total Connected Current: 2 Total Estimated Demand: 868 Total Connected Load: 810
Lights 30 125% 37.5 Receptacles 180 100% 180 M 400 100% 400
LM 200 125% 250
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 555.2 555.7 555.2 Total Load: 200.03 200.2 200
11 12 9 10 7 8 5 12 Gas Pump 20 1 200 6 3 12 Def Pump 20 1 200 0.2 1 20 Receptacle 12 4 1 12 Diesel... 20 1 200 0.03 1 20 Light 12 2
Key Note CKT Feeder Load Name Trip Rating Poles A (kva) B (kva) C (kva) Poles Trip Rating Load Name Feeder CKT Key Note
Enclosure: Type 1 MCB... 30A Mounting: Surface Wires: 4 Mains... 60A
Supply From: Panel... Phases: 3 Mains...
Location: B14 Power Pole Volts: 120/208 Wye AIC Rating: 22 kaic
Panel: EPB14
L1 Power Pole Exterior wall pack Orion FLGA3-F1UNVND750BRF76SFTPCSP LED 129 ND 120V/3P
Mark Location Description Manufacturer Model Lamp Wattage (Nominal)
Driver Type
Electrical Data
Acceptable Manufacturers Notes
Lighting Fixture Schedule
1/2" = 1'-0"1 E-POWER/LIGHT POLE DETAIL
R
TA
/0
8/
DESIGN CRITERIA
1) CODES
INTERNATIONAL BUILDING CODE,
AMERICAN CONCRETE INSTITUTE,
AMERICAN INSTITUTE OF STEEL CONSTRUCTION,
NATIONAL FOREST PRODUCTS ASSOCIATION, NDS
2) LATERAL LOADS
WIND: WIND
SPEED 105 mph
EXPOSURE C
IMPORTANCE FACTOR Ls=1.00 GROUND ELEVATION FACTOR, Ke=1.00 TOPOGRAPHIC FACTOR, Kzt=1.00 WIND DIRECTIONAL FACTOR, Kd=0.85
GUST EFFECT FACTOR, 0.85
INTERNAL PRESSURE COEFFICIENT, VARIES
3) LIVE LOADS:
GROUND SNOW LOAD: 30 psf Pf=0.8 Ce Ct Ls Pg
SNOW DRIFT LOAD: ASCE-7
Ce=1.0 Ct=1.2 Is=1.0 ROOF LIVE LOAD (MINIMUM): 20 psf MECHANICAL: 100 psf SUSPENDED ROOF LOAD (MINIMUM): 10 psf
4) NET ALLOWABLE SOIL BEARING PRESSURES PER
GEOTECHNICAL REPORT DATED NOVEMBER 28, 2022: 3,000
PSF
5) CONCRETE STRENGTHS-MINIMUM 28 f'c=4,000 PSI (145 pcf DENSITY UNLESS NOTED OTHERWISE)
6) REINFORCING STEEL SHALL BE HIGH STRENGTH
NEW BILLET STEEL CONFORMING TO THE FOLLOWING:
DEFORMED BARS: ASTM A615,
GR. 60 (UNLESS NOTED OTHERWISE)
WELDABLE REINFORCING: ASTM A706, GR. 60
PLAIN BARS: ASTM A82
WELDED WIRE FABRIC: ASTM A185
EPOXY COATING: ASTM A775
7) STRUCTURAL STEEL
W-SHAPES: ASTM A992
OTHER ROLLED SHAPES AND
CONNECTION MATERIAL: ASTM A992
STIFFENER PLATES: ASTM A36
ANCHOR BOLTS: ASTM A307
(MINIMUM)
HIGH STRENGTH BOLTS A325/A490
PIPE: ASTM
A53, GR. B
STRUCTURAL TUBES: ASTM A500, GR. B
SPECIAL INSPECTION REQUIREMENTS
1) THE FOLLOWING TYPES OF WORK REQUIRE SPECIAL
INSPECTION BASED ON SECTION 1701 OF THE
INTERNATIONAL BUILDING CODE. THE OWNER WILL EMPLOY
SPECIAL INSPECTIONS WHO SHALL PROVIDE SPECIAL
INSPECTIONS DURING:
a. EARTH WORK
b. CAST-IN-PLACE CONCRETE
c. STRUCTURAL STEEL
d. POST INSTALLATION
GENERAL NOTES
1) ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS
FOR MECHANICAL, ELECTRICAL, AND PLUMBING WITH
APPROPRIATE TRADE CONTRACTORS. OPENING SIZES AND
LOCATIONS SHOWN FOR DUCTS, PIPES, INSERTS, ETC.,
WHEN SHOWN ARE FOR GENERAL INFORMATION ONLY AND
SHALL BE VERIFIED PRIOR TO FORMING.
2) BEFORE SUBMITTING A PROPOSAL FOR THIS WORK,
EACH BIDDER SHALL VISIT THE PREMISES AND ACQUAINT
THEMSELVES FULLY WITH THE EXISTING CONDITIONS,
TEMPORARY CONSTRUCTION REQUIRED, QUANTITIES AND
TYPES OF EQUIPMENT, ETC. THE BID SHALL INCLUDE ALL
SUMS REQUIRED TO DO THE WORK WITHIN THE EXISTING
CONDITIONS.
3) SHOP DRAWINGS PREPARED BY SUPPLIERS,
SUBCONTRACTORS, ETC. SHALL BE REVIEWED AND
COORDINATED PRIOR TO SUBMITTING TO THE ENGINEER.
EACH SHOP DRAWING SUBMITTED SHALL BE STAMPED,
INITIALED, AND DATED AS BEING REVIEWED BY THE
CONSTRUCTION MANAGER/GENERAL CONTRACTOR.
4) SHOP DRAWINGS PREPARED BY THE
SUBCONTRACTORS, SUPPLIERS, ETC. SHALL BE REVIEWED
BY THE ENGINEER FOR CONFORMANCE WITH DESIGN
CONCEPT ONLY. REVIEW BY THE ENGINEER SHALL NOT
BEGIN WITHOUT THE PRIOR COORDINATION AND REVIEW BY
THE CONSTRUCTION MANAGER/GENERAL CONTRACTOR.
WORK SHALL NOT BEGIN WITHOUT THE REVIEW BY THE
ARCHITECT.
5) DETAILS AND NOTES ON THE STRUCTURAL
DRAWINGS ARE INTENDED TO BE TYPICAL FOR SIMILAR
SITUATIONS ELSEWHERE. VERIFY ALL DIMENSIONS WITH
THE ARCHITECTURAL DRAWINGS. DO NOT SCALE
DRAWINGS; USE DIMENSIONS PROVIDED ONLY.
6) THE COST OF ADDITIONAL DESIGN WORK DUE TO
ERRORS OR OMISSIONS IN CONSTRUCTION SHALL BE
BORNE BY THE CONTRACTOR.
7) ANY ENGINEERING DESIGN PROVIDED BY OTHERS
AND SUBMITTED FOR REVIEW OR RECORD SHALL BEAR THE
STAMP SIGNATURE OF A PROFESSIONAL ENGINEER
LICENSED IN THE STATE OF IOWA.
8) ALL ELEVATIONS GIVEN THUS (+10'-0”) ARE TO TOP
OF FOOTING, JOIST BEARING, TOP OF STEEL, TOP OF SLAB,
ETC. WITH REFERENCED TO THE FINISHED FLOOR SLAB OR
TOP OF FLUSH FLUME.
CONSTRUCTION PROCEDURES AND SAFETY
REQUIREMENTS
1) COMPLY WITH ALL APPLICABLE CITY, COUNTY,
STATE, AND FEDERAL LAWS, INCLUDING OCCUPATIONAL
SAFETY AND HEALTH ACT (OSHA) AND REGULATIONS
ADOPTED PURSUANT THERETO.
2) THE CONTRACT STRUCTURAL DRAWINGS AND
SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE
UNLESS OTHERWISE INDICATED, THEY DO NOT INDICATE
THE MEANS OR METHODS OF CONSTRUCTION.
3) PROVIDE ALL MEASURES NECESSARY TO PROTECT
THE WORKERS AND OTHER PERSONS DURING
CONSTRUCTION. PROVIDE ALL NECESSARY MEASURES TO
AVOID EXCESSIVE STRESSES AND TO HOLD THE
STRUCTURAL ELEMENTS IN PLACE DURING CONSTRUCTION.
SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO,
BRACING, SHORING FOR CONSTRUCTION EQUIPMENT,
SHORING FOR EARTH BANKS FORMS, SCAFFOLDING,
PLANKING, SAFETY NETS, SUPPORT AND BRACING FOR
CRANES AND HOISTS, GUYING, ETC.
4) ENGAGE PROPERLY QUALIFIED PERSONS TO
DETERMINE WHERE AND HO TEMPORARY PRECAUTIONARY
MEASURES SHALL BE USED. OBSERVATION VISITS TO THE
SITE BY ENGINEER'S FIELD REPRESENTATIVES SHALL NOT
INCLUDE THE ITEMS NOTED ABOVE.
5) SUPERVISE AND DIRECT THE WORK SO AS TO
MAINTAIN SOLE RESPONSIBILITY FOR ALL CONSTRUCTION
MEANS, METHODS, TECHNIQUES, SEQUENCES, AND
PROCEDURES. RETAIN THE SERVICES OF A PROFESSIONAL
ENGINEER LICENSED IN THE STATE OF IOWA TO DESIGN
AND SUPERVISE ANY SCAFFOLDING FOR WORKMEN, AND
ALL SHORING OF FORMS AND ELEMENTS OF THE
CONSTRUCTION.
6) ANY ENGINEERING DESIGN PROVIDED BY OTHERS
AND SUBMITTED FOR REVIEW AND/OR RECORD SHALL BEAR
THE STAMP AND SIGNATURE OF A PROFESSIONAL
ENGINEER LICENSED IN THE STATE OF IOWA.
FOOTINGS AND FOUNDATIONS
1) ALL FOOTINGS SHALL BE PLACED ONTO FIRM
UNDISTURBED SOIL OR CONTROLLED COMPACTED FILL AS
DIRECTED BY THE PROJECT SOILS CONSULTANT REPORT
RECOMMENDATIONS. FOOTING ELEVATIONS SHOWN
DESIGNATE A MINIMUM DEPTH OF FOOTINGS WERE A SAFE
SOIL BEARING PRESSURE IS EXPECTED (SEE DESIGN
CRITERIA). FOOTINGS SHALL BE LOWERED OR EXTENDED
AND WALLS EXTENDED AS REQUIRED TO REACH THE
DESIGN BEARING PRESSURE.
2) WHERE EXISTING FILL IS ENCOUNTERED, REMOVE
EXISTING FILL FROM UNDER FOUNDATIONS AND REPLACE
WITH STRUCTURAL FILL PER GEOTECHNICAL REPORT.
3) GENERAL MACHINE EXCAVATION FOR FOOTINGS
SHALL STOP NOT LESS THAN 4” ABOVE THE ELEVATION OF
BOTTOMS OF FOOTINGS. FINAL EXCAVATION TO THE
REQUIRED UNDISTURBED SOIL ELEVATION SHALL BE DONE
NOT MORE THAN 12 HOURS BEFORE FOOTING IS PLACED.
THE EXCAVATION SHALL BE CRUMBED CLEAN.
4) ALL FOUNDATION EXCAVATIONS SHALL BE
INSPECTED AND CERTIFIED BY A QUALIFIED INDEPENDENT
SOILS TESTING FIRM.
5) NO FOOTING SHALL BE PLACED ONTO OR AGAINST
SUBGRADES CONTAINING FREE WATER, FROST, OR ICE.
6) UNLESS NOTED OTHERWISE, ALL FOOTINGS SHALL
BE CENTERED UNDER WALLS, PIERS, OR COLUMNS.
7) WHERE REQUIRED, ALL NECESSARY CHANGES IN
ELEVATION OF WALL FOOTINGS SHALL BE MADE IN STEPS
OF 1 VERTICAL TO 2 HORIZONTAL. LOCATION OF STEPS
SHALL BE COORDINATED WITH THE WALL FORMING SYSTEM
AND AT LEAST 2'-0” APART.
8) LONGITUDINAL REINFORCING IN WALL FOOTINGS
SHALL BE CONTINUOUS AT STEP DOWNS. SLOPE OR STEP
BOTTOM BARS IN WALL TO FOLLOW STEPS IN FOOTING
UNLESS OTHERWISE SHOWN.
9) LAP WALL FOOTING REINFORCING 24 BARS
DIAMETERS OR A MINIMUM OF 1'-6” AT SPLICES, UNLESS
OTHERWISE NOTED.
10) PROVIDE CORNER BARS IN FOOTINGS THE SAME
SIZE AND NUMBER AS THE CONTINUOUS REINFORCING,
LAPPED 2'-0” WITH MAIN STEEL.
11) REINFORCING IN WALL FOOTINGS BETWEEN
COLUMNS SHALL EXTEND INTO COLUMN FOOTINGS A
MINIMUM OF 2'-0”.
12) REINFORCING IN FOOTINGS SHALL BE ACCURATELY
PLACED, SPACED, SUPPORTED, AND SECURED BEFORE
PLACING CONCRETE (DO NOT “FLOAT” REINFORCING INTO
FOOTINGS.
13) PIPES EXTENDED UNDER FOOTINGS SHALL BE
PLACED BEFORE FOOTING IS PLACED AND THE VOID
PRODUCED IN LAYING THE PIPE SHALL BE FILLED WITH
CONCRETE.
14) CROSS REFERENCE ARCHITECTURAL AND
STRUCTURAL DRAWINGS TO ASSURE PROPER DIMENSIONS
AND PLACEMENT OF ALL ANCHOR BOLTS, INSERTS,
NOTCHES, AND EDGES IN FOUNDATION WALLS.
15) BACKFILL PLACED AGAINST WALLS SHALL BE DONE
EVENLY ON BOTH SIDES.
16) BACK FILL AGAINST BASEMENT (SUBWAY)
FOUNDATION WALLS SHALL NOT BE PLACED UNTIL GROUND
LEVEL FLOOR AND LOWER LEVEL SLABS ARE IN PLACE AND
CURED UNLESS THE WALL IS PROPERLY BRACED. ALL
BRACING, IF USED, SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
17) BACKFILL PLACED DIRECTLY ADJACENT TO
BASEMENT AND RETAIN WALLS SHALL BE COMPACTED
CLEAN FREE DRAINING GRANULAR MATERIAL. FOR A
MINIMUM OF 2'-6” FROM FACE OF WALL. AT EXTERIOR
LOCATIONS PROVIDE A 1'-6” DEEP CAP OF COMPACTED
APPROVED IMPERVIOUS COHESIVE MATERIAL AT TOP OF
GRANULAR BACKFILL. ALL BACKFILL SHALL BE COMPACTED
USING HAND OPERATED EQUIPMENT; NOT HEAVY
EQUIPMENT SHALL BE ALLOWED WITHIN 5'-0 ” OF ANY WALL.
18) ALL UNACCEPTABLE FILL AND TOP SOIL SHALL BE
REMOVED FROM BELOW ALL PROPOSED SLABS-ON-GRADE
AND THE EXPOSED NATURAL SOIL SHALL BE PROOF ROLLED
AND COMPACTION VERIFIED BY A QUALIFIED INDEPENDENT
SOILS TESTING FIRM PRIOR TO PLACING FILL. AREAS
EXHIBITING WEAKNESS SHALL BE REMOVED AND REPLACED
BY ACCEPTABLE COMPACTED FILL.
19) A MINIMUM 6” OF COMPACTED GRANULAR FILL
SHALL BE PLACED UNDER ALL SLABS-ON-GRADE. ALL FILL
REQUIRED TO ATTAIN FINAL SUB-GRADE FOR SLABS AND
WALLS SHALL BE AN ACCEPTABLE MATERIAL PLACED AND
COMPACTED AS DIRECTED BY THE PROJECT SOILS
CONSULTANT REPORT RECOMMENDATIONS.
20) A VAPOR BARRIER WITH MINIMUM 6 MIL THICKNESS
SHALL BE PLACED UNDER ALL INTERIOR SLAB-ON-GRAD OR
BELOW GRANULAR FILL; SEE ARCHITECTURAL DRAWINGS.
LAP AND SEAL ALL EDGES.
CONCRETE AND REINFORCING
1) ALL CONCRETE WORK SHALL CONFORM TO THE
LATEST EDITION OF THE AMERICAN CONCRETE INSTITUTE
PUBLICATIONS: ACI 301, ACI 304, ACI 311, ACI 315, ACI 318,
AND ACI 347 UNLESS OTHERWISE NOTED ON THE
DRAWINGS.
2) CONCRETE SHALL CONSIST OF THE FOLLOWING:
ASTM C150 TYPE 1 PORTLAND CEMENT
ASTM C33 NORMAL WEIGHT AGGREGATES
(LIMESTONE AGGREGATE AT EXPOSED LOCATIONS)
POTABLE WATER
CHLORIDES CONTENT SHALL BE LIMITED BY ACI
REQUIREMENTS FOR TYPE OF EXPOSURE.
CONCRETE WHICH WILL BE SUBJECTED TO REPEATED
CYCLES OF FREEZE-THAW DURING THE LIFE OF THE
STRUCTURE SHALL HAVE A WATER-CEMENT RATIO NOT
EXCEEDING 0.53 AND SHALL CONTAIN ENTRAINED AIR. SEE
ACI 301 FOR ADDITIONAL REQUIREMENTS
3) UNLESS OTHERWISE NOTED, PRINCIPAL
REINFORCEMENT SHALL HAVE THE FOLLOWING
PROTECTION:
SURFACES CAST AGAINST & PERMANENTLY EXPOSED TO
EARTH: 3 INCHES
FORMED SURFACES EXPOSED TO EARTH OR WATER:
2 INCHES
SLABS:
1 INCH (TOP)
3/4" INCH (BOT.)
WALLS (INTERIOR SURFACES ONLY): 1 INCH
TIES/STIRRUPS: 1 ½ INCHES
4) ALL SLABS-ON-GRADE, PADS, FILLS, AND TOPPINGS
SHALL HAVE A MINIMUM OF 6x6 - W1.4 x W1.4 WWF, UNLESS
NOTED OTHERWISE, PLACED 1” FROM TOP OF SLAB. LAP
WWF MINIMUM 2 PANELS AT EDGES AND ENDS AND
PROVIDE ADDITIONAL REINFORCING WHERE SHOWN ON
THE DRAWINGS.
5) ALL SLABS-ON-GRAD SHALL BE PLACED ON
COMPACTED GRANULAR FILL. PITCH SLABS TO DRAINS AND
PROVIDE DEPRESSIONS, WHERE SHOWN ON THE
STRUCTURAL AND ARCHITECTURAL DRAWINGS, WITHOUT
REDUCING THE THICKNESS OF SLAB INDICATED. FOR
SLABS-ON-GRADE DEPRESSIONS GREATER THAN 1 ”, SEE
DETAILS FOR ADDITIONAL REINFORCING.
6) PROVIDE SLAB-ON-GRADE CONSTRUCTION JOINTS,
AGAINST INTERIOR WALLS, AND BETWEEN WALLS. PROVIDE
JOINTS TO FORM AREAS NOT TO EXCEED 15' IN LENGTH IN
EACH DIRECTION. SEE TYPICAL DETAILS. SUBMIT DETAILED
DRAWINGS SHOWING LOCATIONS OF ALL CONSTRUCTION
JOINTS.
7) PROVIDE VERTICAL CONSTRUCTION JOINTS IN
EXPOSED CONCRETE WALLS AT A MAXIMUM UNIFORM
SPACING NOT TO EXCEED 30'-0”. COORDINATE JOINT
LOCATIONS WITH ARCHITECTURAL DRAWINGS.
8) PROVIDE ADEQUATE BOLSTERS, HI-CHAIRS,
SUPPORT BARS, ETC., TO MAINTAIN SPECIFIED
CLEARANCES FOR THE ENTIRE LENGTH OF ALL
REINFORCING BARS. PROVIDE ACCESSORIES WHICH ARE
PLASTIC TIPPED OR GALVANIZED WITH TURNED UP ENDS
FOR REINFORCEMENT AL ALL FACES OF EXPOSED
CONCRETE, INTERIOR OR EXTERIOR.
9) TYPICAL CONCRETE WALL REINFORCING SHALL BE
AS FOLLOWS UNLESS OTHERWISE NOTED:
THICKNESS HORIZ. VERT. LOCATION
6 INCHES #4@18” #4@18” CENTERED
8 INCHES #4@12” #4@18”
CENTERED
10 INCHES #4@10” #4@16”
CENTERED
12 INCHES #4@16” #4@18” EACH
FACE
16 INCHES #4@12” #4@16” EACH
FACE
10) CONTINUOUS REINFORCING SHALL BE LAPPED AS
FOLLOWS UNLESS OTHERWISE NOTED:
ALL LAPS SHOWN ON THE DRAWINGS AND NOT
DIMENSIONED SHALL BE 24 BAR DIAMETERS. ADDITIONAL
LAPS REQUIRED FOR CONSTRUCTION SHALL BE CLASS BB
11) ALL FIELD BENDING OF REINFORCING SHALL BE
DONE COLD. HEATING OF BARS WILL NOT BE PERMITTED.
12) NO ALUMINUM OF ANY TYPE SHALL BE ALLOWED IN
CONCRETE WORK UNLESS COATED TO PREVENT
ALUMINUM-CONCRETE REACTION.
13) MAXIMUM O.D. OF EMBEDDED CONDUIT SHALL BE
NO LARGER THAN 1/3 OF THE SLAB THICKNESS. NO
CONDUIT SHALL BE PLACED ABOVE THE WELDED WIRE
FABRIC OR REINFORCING IN SLABS-ON-GRADE.
14) MECHANICALLY VIBRATE CONCRETE EXCEPT THAT
SLABS-ON -GRADE NEED ONLY BE VIBRATED AROUND
EMBEDDED ITEMS.
15) DO NOT CAST UNEXPOSED WALL OR IN LENGTHS
OVER 60'-0”. WAIT 48 HOURS BETWEEN ADJACENT POURS.
16) ALL CONSTRUCTION JOINTS BETWEEN ADJACENT
CONCRETE POURS SHALL BE KEYED. JOINTS MUST BE KEPT
FREE OF DIRT, DEBRIS, FROM OILS, ETC. TO ASSURE
PROPER BOND WITH ADJACENT POUR.
17) FLOOR TOLERANCES:
SURFACE TOLERANCE: CLASS B. (SEE ACI 301)
THICKNESS: PLUS 1”, MINUS ½” SLAB ON GRADE PLUS 1”,
MINUS ¼” STRUCTURAL AND COMPOSITE SLABS. REPLACE
ANY SLAB WITH A THICKNESS DEVIATION AS DIRECTED BY
THE EOR.
18) MAXIMUM FREE DROP OF ANY CONCRETE = 6'-0 ”
19) ALL BAR DETAILING AND ACCESSORIES TO BE
FURNISHED SHALL CONFORM TO TYPICAL DETAILS AND
STANDARDS IN THE LATEST ACI STANDARD 315 DETAILING
MANUAL, EXCEPT AS OTHERWISE SHOWN, NOTED, OR
SPECIFIED.
STRUCTURAL STEEL
1) STRUCTURAL STEEL DETAILS, FABRICATION, AND
ERECTION SHALL CONFORM TO THE LATEST EDITION OF
THE AISC “STEEL CONSTRUCTION MANUAL” UNLESS
OTHERWISE SHOWN OR SPECIFIED.
2) HIGH STRENGTH BOLTS SHALL BE INSTALLED IN
ACCORDANCE WITH AISC “SPECIFICATIONS FOR
STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS”
LATEST EDITION. BOLTS ARE DESIGNED AS BEARING-TYPE
CONNECTIONS, UNLESS NOTED OTHERWISE.
3) USE TENSION CONTROL BOLTS WITH ALL HIGH
STRENGTH BOLTS REQUIRING FULLY TIGHTENED
CONDITIONS.
4) ALL WELDING SHALL BE DONE BY AWS CERTIFIED
WELDERS WITH EXPERIENCE AND CERTIFICATION IN THE
TYPES OF WELDING INDICATED. CERTIFICATES SHALL NOT
HAVE LAPSED DUE TO DISUSE FOR 6 MONTHS.
5) ALL WELDS TO BE E70XX ELECTRODES AND/OR
0.035” SOLID WIRE.
6) FIELD CONNECTIONS SHALL BE WELDED OR
BOLTED. SHOP CONNECTIONS SHALL BE WELDED UNLESS
OTHERWISE INDICATED OR APPROVED. WELDS INDICATED
WITH A SHOP WELD SYMBOL MAY BE MADE IN THE FIELD
WITH THE APPROVAL OF THE EOR.
7) UNLESS NOTED OTHERWISE, ALL WELDS SHALL BE
CONTINUOUS 3/16” THROAT. ALL FULL AND/OR PARTIAL
PENETRATIONS WELDS SHALL BE FULLY DETAILED ON THE
SHOP DRAWINGS.
8) FABRICATOR SHALL SELECT AISC SIMPLE SHEAR
CONNECTIONS FOR STEEL BEAMS CAPABLE OF CARRYING
THE REACTION FORCE WHEN INDICATED OR 75% OF THE
TOTAL UNIFORM LOAD FOR THE GIVEN SIZE, SPAN, AND
GRADE OF BEAM, AS TABULATED IN THE AISC TABLES FOR
ALLOWABLE LOADS.
9) SIMPLE SHEAR CONNECTIONS SHALL BE STANDARD
DOUBLE ANGLE OR SINGLE SHEAR PLATES, UNLESS NOTED
OTHERWISE. SELECT CONNECTIONS FROM THE AISC,
SIMPLE SHEAR CONNECTIONS DESIGN AID, LATEST EDITION
WHENEVER POSSIBLE. ALL BOLTED CONNECTIONS SHALL
HAVE MINIMUM 2 BOLTS, UNLESS NOTED OTHERWISE.
10) SHOP PAINT STRUCTURAL STEEL WITH A STANDARD
PRIMER.
11) GROUT UNDER BEAM BERING PLATES AND COLUMN
BASE PLATES.
12) CUTS, HOLES, OPENINGS, ETC., REQUIRED IN
STRUCTURAL STEEL MEMBERS FOR THE WORK OF
OTHER TRADES SHALL BE SHOWN ON THE SHOP
DRAWINGS. BURNING HOLES AND CUTS IN THE
FIELD SHALL NOT BE PERMITTED., EXCEPT BY
WRITTEN AUTHORIZATION FROM THE EOR.
13) FURNISH AND INSTALL MISCELLANEOUS
STEEL (CURBS, HANGERS, EXPANSION JOINT
ANGLES, STRUTS, ETC.) AS CALLED FOR OR AS
NECESSARY PER ARCHITECTURAL AND
MECHANICAL/ELECTRICAL DRAWINGS.
14) CAMBER BEAMS AS INDICATED ON THE
DRAWINGS. FABRICATE AND INSTALL BEAMS WITH
NATURAL CAMBER UPWARDS.
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
N
EW
D
AI
R Y
FO
R
AG
E
R
ES
EA
R
C H
C
EN
TE
R
Au to de sk
D oc s:
//1
5_
U
SD
A_ D
FR
C
_2
2/
A _S
_M
EP
-B
.rv t
/2
8/
:2 2:
A
M
S-001-B15
G
EN
ER
AL
N O
TE
S, A
BB
R
EV
IA
TI
O N
S
- A
R
EA
B
C
O M
M O
D
IT
Y
ST
O R
AG
E
PR
AI
R
IE
D U
S
AC
, W I
O M
AH
A
D
IS
TR
IC
T
H D
R
AR
LI
N
G
TO
N , V
IR
G
IN
IA
J.
W ille
M . B ro w ns te in
R . R in eh ar t
/0
8/
W
F2
0C
W
F2
1C
1" = 1'-0"1 S-001
NORTH
KEY PLAN
B15
R
TA
/0
8/
A-202-B15 H11
A-201-B15 C10
A-202-B15 C11
A-201-B15 H10
B15.A B15.B B15.C B15.D B15.E B15.F B15.G
B15.1
B15.2
72' - 0"
H8 S-501-B15
C9 S-301-B15
H9 S-301-B15
C L
H2 S-501-B15
4"
4" 72' - 8"
4"
C L
C L
C L
C L
C L
C L
S-501-B15 C12
8" 11' - 8" 12' - 0" 12' - 0" 12' - 0" 12' - 0" 11' - 8" 8"
D14
A-310-B15
BUNKER
CONCRETE WALLS
H8 S-501-B15
S-501-B15
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
N
EW
D
AI
R Y
FO
R
AG
E
R
ES
EA
R
C H
C
EN
TE
R
Au to de sk
D oc s:
//1
5_
U
SD
A_ D
FR
C
_2
2/
A _S
_M
EP
-B
.rv t
/2
8/
:2 2:
A
M
S-101-B15
FI
R
ST
F
LO
O
R S
TR
U
C
TU
R
AL
P
LA
N
AR
EA
B
C
O M
M O
D
IT
Y
ST
O R
AG
E
PR
AI
R
IE
D U
S
AC
, W I
O M
AH
A
D
IS
TR
IC
T
H D
R
AR
LI
N
G
TO
N , V
IR
G
IN
IA
J.
W ille
M . B ro w ns te in
R . R in eh ar t
/0
8/
W
F2
0C
W
F2
1C
NORTH
KEY PLAN
B15
1/8" = 1'-0"D10
FIRST FLOOR STRUCTURAL PLAN - AREA
B15
R
TA
/0
8/
A-201-B15 C10
A-202-B15 C11
A-201-B15 H10
B15.A B15.B B15.C B15.D B15.E B15.F B15.G
B15.1
B15.2
72' - 0"
12' - 0" 12' - 0" 12' - 0" 12' - 0" 12' - 0" 12' - 0"
ROOF PURLINS
DOUBLE 2x8 PLATE
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
N
EW
D
AI
R Y
FO
R
AG
E
R
ES
EA
R
C H
C
EN
TE
R
Au to de sk
D oc s:
//1
5_
U
SD
A_ D
FR
C
_2
2/
A _S
_M
EP
-B
.rv t
/2
8/
:2 2:
A
M
S-102-B15
R O
O F
FR
AM
IN
G
P
LA
N
AR
EA
B
C
O M
M O
D
IT
Y
ST
O R
AG
E
PR
AI
R
IE
D U
S
AC
, W I
O M
AH
A
D
IS
TR
IC
T
H D
R
AR
LI
N
G
TO
N , V
IR
G
IN
IA
J.
W ille
M . B ro w ns te in
R . R in eh ar t
/0
8/
W
F2
0C
W
F2
1C
NORTH
KEY PLAN
B15
1/8" = 1'-0"D9 STRUCTURAL ROOF PLAN - B15
GENERAL NOTES:
1. PURLINS 16" o.c. 2x12
R
TA
/0
8/
LEVEL 0 B15_TOFF
867' - 6"
LEVEL -1 B15 TOF
863' - 2"
B15.1B15.2
LEVEL 1 B15 TOW
875' - 6"
1' - 4"
8" 39' - 10"
8'
0" 8"
3'
8" 8"
8"
S-501-B15 H8
LEVEL 0 B15_TOFF
867' - 6"
LEVEL -1 B15 TOF
863' - 2"
B15.A B15.B B15.C B15.D B15.E B15.F B15.G
LEVEL 1 B15 TOW
875' - 6"
72' - 8"
8"
8'
0" 8"
3'
8"
12' - 0" 12' - 0" 12' - 0" 12' - 0" 12' - 0" 12' - 0"
3 5/8" 3 5/8"
8" TYP 8" TYP
S-501-B15 H8 S-501-B15
H2
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
N
EW
D
AI
R Y
FO
R
AG
E
R
ES
EA
R
C H
C
EN
TE
R
Au to de sk
D oc s:
//1
5_
U
SD
A_ D
FR
C
_2
2/
A _S
_M
EP
-B
.rv t
/2
8/
:2 2:
A
M
S-301-B15
FO
U
N D
AT
IO
N S
EC
TI
O N
S
- A
R
EA
- C O
M M
O D
IT
Y
ST
O
R
AG
E
PR
AI
R
IE
D U
S
AC
, W I
O M
AH
A
D
IS
TR
IC
T
H D
R
AR
LI
N
G
TO
N , V
IR
G
IN
IA
J.
W ille
M . B ro w ns te in
R . R in eh ar t
/0
8/
W
F2
0C
W
F2
1C
NORTH
KEY PLAN
B15
1/4" = 1'-0"H9 FOUNDATION SECTION - B15
1/8" = 1'-0"C9 FOUNDATION SECTION - B15
BUNKER
WALLS
R
TA
/0
8/
LEVEL -1 B15 TOF
863' - 2"
B15.E
LEVEL 1 B15 TOW
875' - 6"
#6 VERTICAL BARS
@ 12" o.c. 2 MATTS
#4 HORIZONTAL BARS
@ 12" o.c. 2 MATTS
#5 BARS @ 12" o.c.
#6 HOOK BARS
@ 12" o.c.
9"
18"
8'
0" 8"
3'
8" 8"
8"
4" 4"
1' - 4"
#5 BARS @ 12" o.c.
BOTH WAYS
3" COVER
#5 BARS @ 12" o.c.
BOTH WAYS
3" COVER
8" 8"
LEVEL 0 B15_TOFF
867' - 6"
LEVEL -1 B15 TOF
863' - 2"
B15.2
LEVEL 1 B15 TOW
875' - 6"
8'
0" 8"
3'
8" 8"
8"
1' - 4"
4" 4"
#6 VERTICAL BARS
@ 12" o.c. 2 MATTS
#4 HORIZONTAL BARS
@ 12" o.c. 2 MATTS
#5 BARS @ 12" o.c.
#6 HOOK BARS
@ 12" o.c.
9"
18"
#5 BARS @ 12" o.c.
BOTH WAYS
3" COVER
8"
B15.E
B15.2
#4 HORIZONTAL
BARS @ 12" o.c.
BOTH MATTS
#6 VERTICAL BARS @
12" o.c. BOTH MATTS
#4 HOOK BARS
@ 12" o.c.
20"
20"
8"
8"
#5 BARS @ 12" O.C.
#5 HOOKS @ 12" O.C.
24"
24"
1'
0"
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
N
EW
D
AI
R Y
FO
R
AG
E
R
ES
EA
R
C H
C
EN
TE
R
Au to de sk
D oc s:
//1
5_
U
SD
A_ D
FR
C
_2
2/
A _S
_M
EP
-B
.rv t
/2
8/
:2 2:
A
M
S-501-B15
FO
U
N D
AT
IO
N D
ET
AI
LS
AR
EA
- C O
M M
O D
IT
Y
ST
O
R
AG
E
PR
AI
R
IE
D U
S
AC
, W I
O M
AH
A
D
IS
TR
IC
T
H D
R
AR
LI
N
G
TO
N , V
IR
G
IN
IA
J.
W ille
M . B ro w ns te in
R . R in eh ar t
/0
8/
W
F2
0C
W
F2
1C
NORTH
KEY PLAN
B15
1/2" = 1'-0"H2 FOUNDATION DETAIL 1 - B15
1/2" = 1'-0"H8 FOUNDATION DETAIL 2 - B15
1" = 1'-0"C12
FOUNDATION INTERIOR DETAIL PLAN -
B15
1/2" = 1'-0"1 WALL FOUNDATION DETAIL
R
TA
/0
8/
DRAWING ABBREVIATIONS
INDEX OF DRAWINGS
BUILDING SUMMARY
NUMBERING SYSTEM:
XX100
DISCIPLINE:
C - CIVIL
L - LANDSCAPE
A - ARCHITECTURE
M - MECHANICAL
E - ELECTRICAL
P - PLUMBING
S - STRUCTURAL
K - FOOD SERVICE
DISCIPLINE MODIFIER
ANNOTATION CALLOUTS/DRAWING SYMBOLS
GENERAL NOTES
A ---------------------
A LABEL CLASS A DOOR
A/C AIR CONDITION
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
ACC ACCESSIBLE
ACS AUTOMATIC CONTROL SYSTEM
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADMIN ADMINISTRATION
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AIB AIR INFILTRATION BARRIER
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZE
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
AR AS REQUIRED
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING
ASSY ASSEMBLY
ATC ACOUSTICAL TILE CEILING
AVG AVERAGE
AW ARCHITECTURAL WOODWORK
AWT ACOUSTICAL WALL TREATMENT
B ---------------------
B LABEL CLASS B DOOR
BALC BALCONY
BB BASEBOARD
BC BOOKCASE
BD BOARD
BDRY BOUNDARY
BFF BELOW FINISH FLOOR
BHMA BUILDER'S HARDWARE
MANUFACTURER'S ASSOCIATION
BLDG BUILDING
BLKG BLOCKING
BLT IN BUILT-IN
BN BULLNOSE
BOS BOTTOM OF STEEL
BOT BOTTOM
BP BUILDING PAPER
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT-UP ROOFING
C ---------------------
C CONC CAST CONCRETE
C LABEL CLASS C DOOR
CAB CABINET
CATW CATWALK
CAV CAVITY
CBB CEMENTITIOUS (BACKER) BOARD
CD CONSTRUCTION DOCUMENTS
CDW CHILLED DRINKING WATER
CEM PLAS CEMENT PLASTER
CER CERAMIC
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR
FURNISHED/CONTRACTOR INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CFLG COUNTERFLASHING
CFM CUBIC FEET PER MINUTE
CFMF COLD-FORMED METAL FRAMING
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CI CAST IRON
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG DIFF CEILING DIFFUSER
CLG HT CEILING HEIGHT
CLL COLUMN LINE
CLO CLOSET
CLR COLOR
CLRM CLASSROOM
CMU CONCRETE MASONRY UNIT
CNDS CONDENSATE
CDR CARD READER
CO CLEANOUT
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONC FLR CONCRETE FLOOR
CONF CONFERENCE
CONT CONTINUE
COORD COORDINATE
CORR CORRIDOR
CP CONCRETE PIPE
CPT CARPET
CR CONTROL ROOM
CRT CURTAIN
CS CAST STONE
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTR CENTER
CU FT CUBIC FEET
CW CASEMENT WINDOW
D ---------------------
D DEPTH
D LABEL CLASS D DOOR
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DGR DIAMOND GROOVE
DIA DIAMETER
DIR DIRECTION
DIST DISTANCE
DOC DOCUMENT
DR DOOR
DS DOWNSPOUT
E ---------------------
E LABEL CLASS E DOOR
EA EACH
EF EACH FACE
EIFS EXTERIOR INSULATION AND FINISH
SYSTEM
EJ EXPANSION JOINT
ES EACH SIDE
EL ELEVATION
ELEV ELEVATOR
ENTR ENTRANCE
EPS EXPANDED POLYSTYRENE BOARD
(INSULATION)
EQ EQUAL
EWC ELECTRIC WATER COOLER
EXP EXPOSED
EXT EXTERIOR
EXT EXTINGUISHER
EXT GR EXTERIOR GRADE
F ---------------------
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FAS BD FASCIA BOARD
FC BRK FACE BRICK
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FED FEDERAL
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FF INSUL FOIL BACKED INSULATION
FGL FIBERGLASS
FH FIRE HOSE
FHP FULL HEIGHT PARTITION
FIN FINISH
FIN BS FINISH BOTH SIDES
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIXT FIXTURE
FLDG FOLDING
FLEX FLEXIBLE
FLG FLOORING
FLMT FLUSH MOUNT
FLR FLOOR
FM FACTORY MUTUAL
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FR FIRE RESISTANT
FRG FIBER REINFORCED GYPSUM
FRMG FRAMING
FRP FIBERGLASS REINFORCED PLASTIC
FRTW FIRE RETARDANT TREATED WOOD
FS FEDERAL SPECIFICATION
FSTNR FASTENER
FT FEET
FTG FOOTING
FWC FABRIC WALLCOVERING
G ---------------------
G NATURAL GAS
GALV GALVANIZED
GB GRAB BAR
GFCI GOVERNMENT FURNISHED
CONTRACTOR INSTALLED
GFGI GOVERNMENT INSTALLED
GOVERNMENT INSTALLED
GFRG GLASS-FIBER-REINFORCED GYPSUM
GLZ GLAZING
GR GROOVED
GR FL GROUND FLOOR
GUT GUTTER
GV GRAVEL
GYP BD GYPSUM BOARD
GYP PLAS GYPSUM PLASTER
H ---------------------
HB HOSE BIBB
HBRF HEAVY BROOM FINISH
HDPE HIGH DENSITY POLYETHYLENE
HDW HARDWARE
HDWD HARDWOOD
HEPA HIGH EFFICIENCY PARTICULATE AIR
(FILTER)
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HORIZ HORIZONTAL
HT HEIGHT
HYDR HYDRAULIC
I ---------------------
IBC INTERNATIONAL BUILDING CODE
INSUL INSULATION
INT INTERIOR
ILO IN LIEU OF
J ---------------------
JAN JANITOR
K ---------------------
KPD KEYPAD
KIT KITCHEN
KPL KICKPLATE
L ---------------------
LAM LAMINATE
LAV LAVATORY
LBR LUMBER
LBRF LIGHT BROOM FINISH
LBS POUND
LDG LANDING
LF LINEAR FEET (FOOT)
LIB LIBRARY
LIN LINEAR
LKR LOCKER
LOC LOCATION
LT LIGHT
LVDR LOUVER DOOR
LVR LOUVER
M ---------------------
MACH RM MACHINE ROOM
MATL MATERIAL
MAX MAXIMUM
MC MOISTURE CONTENT
MD METAL DECK
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MEMB MEMBRANE
MF MILL FINISH
MFR MANUFACTURER
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM, MINUTE
MIRR MIRROR
MISC MISCELLANEOUS
MLDG MOLDING (MOULDING)
MO MASONRY OPENING
MOD MODIFY
MB MOISTURE BARRIER
MTG MOUNTING
MTL METAL
MVBL MOVABLE
MWP MEMBRANE WATERPROOFING
N ---------------------
N NORTH
NANOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NP NO PAINT
NRC NOISE REDUCTI
O -------------------
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OFF OFFICE
OGL OBSCURE GLASS
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPQ OPAQUE
OWSJ OPEN WEB STEEL JOIST
OPR OPERABLE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
P --------------------
PA PUBLIC ADDRESS
PAR PARAPET
PAT PATTERN
PB PULL BOX
PBD PARTICLEBOARD
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PCT PERCENT
PERF PERFORATED
PERIM PERIMETER
PH PHASE
PIL PILASTER
PL PROPERTY LINE
PL GL PLATE GLASS
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLG PILING
PLYWD PLYWOOD
PNL PANEL
PP PL PUSH/PULL PLATE
PR PAIR
PRCST PRECAST
PRKG PARKING
PS CONC PRESTRESSED CONCRETE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTDR PAPER TOWEL DISPENSER AND
RECEPTACLE
PTN PARTITION
PWR POWER
Q --------------------
QT QUARRY TILE
QTY QUANTITY
R --------------------
RB RESILIENT BASE
RBM REINFORCED BRICK MASONRY
RBR RUBBER
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RDG INS RIGID INSULATION, SOLID
REC RECESSED