This document contains questions and answers regarding a federal solicitation for tank inspections at Fort Novosel. The solicitation, number W9128F24Q0007, was issued by the Department of the Army Corps of Engineers Engineering District Omaha for corrosion inspections and paint removal and recoating of lead and hex chrome on the fort's tanks. The work will require sampling and recoating in accordance with specified standards. A total of three coating samples must be taken from different areas on the interior and exterior of each tank. The individual performing the investigations must be a NACE Level II or higher certified corrosion specialist.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Ques�on Set 2 Fort Novosel
Sec�on 5.1.5 of PWS:
Ques�on 1. Will a NACE Level III sa�sfy the requirements for the CCS personnel?
Answer 1. The individual inves�gator should be Cer�fied NACE Level II or higher.
Ques�on 2 a, b. For tes�ng lead and hex chrome:
Ques�on 2a. This will require paint removal, lab sampling and recoa�ng. What are the specifica�ons for the recoa�ng material?
Answer 2a. Repair sample loca�ons in accordance with UFGS 09 97 13.27 and UFGS 09 97 13.17.
Ques�on 2 b. How many and where are samples to be taken?
Answer 2 b. A total of three coa�ng samples must be taken: one from the exterior shell, one on the interior shell within three feet of the botom, and one on the interior shell above the IFR.