This document contains questions and answers regarding inspections of two aboveground storage tanks at Military Ocean Terminal Sunny Point in North Carolina. The tanks are new to the Defense Logistics Agency system and have not been previously inspected by DLA. Details provided include that the tanks are Convault models and are UL-2085 certified. Pictures of the tanks and surrounding areas are attached, as well as a map from the installation. It is confirmed that UT testing is not required for either tank according to Attachment B, and manufacturers of the tanks are Convault, INC. Questions regarding automatic tank gauges and testing were unanswered as of the date. Installation records do not indicate when the tanks were installed.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W9128F21R0029 Inspections at Military Ocean Terminal Sunny Point.

21 Jan 2021

Please see the questions below for Solicitation # W9128F21R0029 STI SP001 Inspections at Military Ocean Terminal Sunny Point.

1) Are the two tanks UL-142 or UL-2085 tanks?

Answer: Per the Convault website the tanks are UL-2085.

2) When were the tanks last inspected?

Answer: The tanks are new to the Defense Logistics Agency (DLA) system and have not been inspected by DLA.

3) Can you provide previous inspection reports?

Answer: No inspection reports available.

4) Can you provide pictures of the two tanks?

Answer: Please see the attached.

5) Can you provide pictures of the areas surrounding each of the two tanks?

Answer: Please see attached maps from the installation.

6) Can you confirm that UT testing is not required for either tank?

Answer: Please reference Attachment B for the UT testing requirement.

7) Who are the manufacturers of the tanks?

Answer: Convault, INC

8) Do the tanks have Automatic Tank Gauges (ATG’s)?

Answer: No response as of yet.

9) Is ATG testing required for either or both of the tanks?

Answer: No response as of yet.

10) When were the tanks installed?

Answer: Installation does not know.