This solicitation package is for the construction of a new 28,000 square foot Fighter Alert Shelter to house four universal fighter aircraft at Truax Field in Madison, Wisconsin. The shelter requires special construction including automatic opening front and rear aircraft doors, heating, fire detection and ultra-high pressure fire suppression systems. Support must also be provided for an Intrusion Detection System and a backup emergency generator. The facility must be designed in accordance with DoD and Air Force standards for unified facilities criteria, antiterrorism, and force protection requirements. This bifurcated solicitation follows FAR Part 15 and initially requests only Volume I technical proposals, as the project is at the 95% design specification stage. Final proposals will be due on March 12, 2021 at 1200 hours. The soliciting agency is the Department of the Army Corps of Engineers Engineering District Omaha.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE
3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
7. ADMINISTERED BY (If other than Item 6) CODE
STANDARD FORM 30 (REV. 11/2016)
Prescribed by GSA FAR (48 CFR) 53.243
FACILITY CODE
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.
12. ACCOUNTING AND APPROPRIATION DATA (If required) copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
15C. DATE SIGNED
15A. NAME AND TITLE OF SIGNER (Type or print)
16C. DATE SIGNED
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
PAGE OF PAGES
6. ISSUED BY CODE
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X)
CODE
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
Previous edition unusable
2. AMENDMENT/MODIFICATION NUMBER
W9128F
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
FIGHTER ALERT SHELTER, PN XGFG189004 (FY20), 115TH FIGHTER WING, TRUAX FIELD, WI
See attached documentation for content of the amendment revisions to solicitation
Date for receipt of proposals is 12 MAR 2021 at 1200 hours
Government Point of Contact: Melissa Harlon, Contract Specialist, Melissa.R.Harlon@usace.army.mil
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
U.S.ARMY CORPS OF ENGINEERS, OMAHA
CONTRACTING OFFICE
1616 CAPITOL AVENUE
OMAHA, NE 68102-4901
See Item 6
9A. AMENDMENT OF SOLICITATION NUMBER
W9128F20R0068
03-Mar-2021
9B. DATED (SEE ITEM 11)
104-Nov-2020
03-Mar-2021
Am #0004 - 1
Am #0004 - 2 (Continuation SF 30)
03 March 2021 Solicitation No. W9128F 20 R 0068
Date of Issue: 04 NOV 2020 Date of Receiving Proposals: 12 MAR 2021
SUBJECT: Amendment No. 0004 to Request for Proposal Solicitation Package for Construction of FIGHTER ALERT SHELTER, PN XGFG189004 (FY20), 115TH FIGHTER
WING.
TO: Prospective Offerors and Others Concerned
1. The specifications and drawings for subject project are hereby modified as follows (revise all specification indices, attachment lists, and drawing indices accordingly).
a. Specifications. (Descriptive Changes.) NONE
b. Specifications (New and/or Revised and Reissued). Delete and substitute or add specification pages or sections as noted below. The substituted pages or sections are revised and reissued with this amendment. For convenience, on the revised specification pages, changes have been identified with highlighting, all portions of the revised specification pages apply regardless of whether changes are shown with highlighting.
Pages or Sections Deleted Pages or Sections Substituted or Added 08 11 13 08 11 13 08 34 16.20 08 34 16.20 08 71 00 08 71 00
c. Drawings (Reissued). The following drawings are revised with latest revision date as shown in the drawing border and reissued with this amendment.
(1) SHEET G-002, INDEX (1 OF 2)
(2) SHEET A-140, COMPOSITE ROOF PLAN
(3) SHEET A-431, INTERIOR ELEVATIONS
(4) SHEET A-517, ROOF DETAILS
(5) SHEET A-700, DOOR DETAILS
(6) SHEET P-101, COMPOSITE PLUMBING PLAN
(7) SHEET P-102, COMPOSITE ROOF PLAN
(8) SHEET P-401, ENLARGED SUPPORT AREA PLUMBING PLANS
(9) SHEET EP002, POWER KEYED NOTES
(10) SHEET EP102, POWER PLAN
(11) SHEET EP103, POWER PLAN
(12) SHEET EP540, AGE ELECTRICAL DETAILS
(13) SHEET EP621, PANEL SCHEDULE
(14) SHEET EP622, PANEL SCHEDULE
(15) SHEET EP623, PANEL SCHEDULE
(16) SHEET EY001, POWER NOTES AND SUPPLEMENTAL LEGEND
(17) SHEET EY102, SPECIAL SYSTEMS PLAN
Am #0004 - 3 (Continuation SF 30)
(18) SHEET EY103, SPECIAL SYSTEMS PLAN
(19) SHEET TN132, TELECOMMUNICATIONS ROOF PLAN
2. This amendment is a part of the proposing papers and its receipt shall be acknowledged. All other conditions and requirements of the request for proposal remain unchanged.
3. Electronic Proposals. Provide proposals via the instructions provided in Section 00 21 00 of the Request for Proposal.
4. Offers will be received until 12:00 p.m., local time at place of receiving proposals, 12 MAR 2021.
Attachments:
Specifications listed in 1.b., above Drawings listed 1.c., above
U.S. Army Corps of Engineers, Omaha District 1616 Capitol Avenue Omaha, Nebraska 68102-4901
03 MAR 2020
nep/2160
F35 Aircraft Shelters 115th Fighter Wing - Truax Field, WI TX05
SECTION TABLE OF CONTENTS
DIVISION 08 - OPENINGS
SECTION 08 11 13
STEEL DOORS AND FRAMES
02/10
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 DELIVERY, STORAGE, AND HANDLING
PART 2 PRODUCTS
2.1 STANDARD STEEL DOORS
2.1.1 Classification - Level, Performance, Model
2.1.1.1 Heavy Duty Doors
2.1.1.2 Extra Heavy Duty Doors
2.1.1.3 Maximum Duty Doors
2.2 CUSTOM HOLLOW METAL DOORS
2.3 INSULATED STEEL DOOR SYSTEMS
2.4 ACCESSORIES
2.4.1 Louvers
2.4.1.1 Exterior Louvers
2.4.2 Astragals
2.4.3 Moldings
2.5 INSULATION CORES
2.6 STANDARD STEEL FRAMES
2.6.1 Welded Frames
2.6.2 Knock-Down Frames
2.6.3 Mullions and Transom Bars
2.6.4 Stops and Beads
2.6.5 Anchors
2.6.5.1 Wall Anchors
2.6.5.2 Floor Anchors
2.7 FIRE DOORS AND FRAMES
2.7.1 Labels
2.7.2 Oversized Doors
2.7.3 Astragal on Fire Doors
2.8 WEATHERSTRIPPING
2.9 HARDWARE PREPARATION
2.10 FINISHES
2.10.1 Factory-Primed Finish
2.10.2 Electrolytic Zinc-Coated Anchors and Accessories
2.11 FABRICATION AND WORKMANSHIP
2.11.1 Grouted Frames
2.12 PROVISIONS FOR GLAZING
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Frames
SECTION 08 11 13 Page 1Am #0004
3.1.2 Doors
3.1.3 Fire Doors and Frames
3.2 PROTECTION
3.3 CLEANING
-- End of Section Table of Contents --
SECTION 08 11 13 Page 2Am #0004
SECTION 08 11 13
STEEL DOORS AND FRAMES
02/10
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2020) Structural Welding Code - Steel
ASTM INTERNATIONAL (ASTM)
ASTM A879/A879M (2012) Standard Specification for Steel Sheet, zinc Coated by the Electrolytic Process for Applications Requiring Designation of the Coating Mass on Each Surface
ASTM C578 (2019) Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation
ASTM C591 (2019) Standard Specification for Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation
ASTM C612 (2014) Mineral Fiber Block and Board Thermal Insulation
ASTM D2863 (2017a) Standard Test Method for Measuring the Minimum Oxygen Concentration to Support Candle-Like Combustion of Plastics (Oxygen Index)
ASTM E1300 (2016) Standard Practice for Determining Load Resistance of Glass in Buildings
ASTM F2248 (2012) Standard Practice for Specifying an Equivalent 3-Second Duration Design Loading for Blast Resistant Glazing Fabricated with Laminated Glass
BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)
ANSI/BHMA A156.115 (2016) Hardware Preparation in Steel Doors and Steel Frames
NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
NAAMM HMMA 810 (2009) Hollow Metal Doors
SECTION 08 11 13 Page 3Am #0004
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 80 (2016; TIA 16-1) Standard for Fire Doors and Other Opening Protectives
NFPA 252 (2017) Standard Methods of Fire Tests of Door Assemblies
STEEL DOOR INSTITUTE (SDI/DOOR)
SDI/DOOR 111 (2009) Recommended Selection and Usage Guide for Standard Steel Doors, Frames and Accessories
SDI/DOOR 113 (2001; R2006) Standard Practice for Determining the Steady State Thermal Transmittance of Steel Door and Frame Assemblies
SDI/DOOR A250.4 (2011) Test Procedure and Acceptance Criteria for Physical Endurance for Steel Doors and Hardware Reinforcing
SDI/DOOR A250.6 (2003; R2009) Recommended Practice for Hardware Reinforcing on Standard Steel Doors and Frames
SDI/DOOR A250.8 (2003; R2008) Recommended Specifications for Standard Steel Doors and Frames
SDI/DOOR A250.11 (2001) Recommended Erection Instructions for Steel Frames
UNDERWRITERS LABORATORIES (UL)
UL 10C (2016) UL Standard for Safety Positive Pressure Fire Tests of Door Assemblies
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Doors; G, DO
Frames; G, DO
Accessories
Show elevations, construction details, metal gages, hardware provisions, method of glazing, and installation details.
Schedule of Doors; G, DO
SECTION 08 11 13 Page 4Am #0004
Schedule of Frames; G, DO
Submit door and frame locations.
SD-03 Product Data
Doors; G, DO
Frames; G, DO
Accessories
Weatherstripping
Submit manufacturer's descriptive literature for doors, frames, and accessories. Include data and details on door construction, panel (internal) reinforcement, insulation, and door edge construction. When "custom hollow metal doors" are provided in lieu of "standard steel doors," provide additional details and data sufficient for comparison to SDI/DOOR A250.8 requirements.
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver doors, frames, and accessories undamaged and with protective wrappings or packaging. Provide temporary steel spreaders securely fastened to the bottom of each welded frame. Store doors and frames on platforms under cover in clean, dry, ventilated, and accessible locations, with 1/4 inch airspace between doors. Remove damp or wet packaging immediately and wipe affected surfaces dry. Replace damaged materials with new.
PART 2 PRODUCTS
2.1 STANDARD STEEL DOORS
SDI/DOOR A250.8, except as specified otherwise. Prepare doors to receive door hardware as specified in Section 08 71 00. Undercut where indicated. Provide exterior doors with top edge closed flush and sealed to prevent water intrusion. Provide doors at 1-3/4 inch thick, unless otherwise indicated. Provide door material that uses a minimum of 25 percent recycled content. Provide exterior glazing in accordance with ASTM F2248 and ASTM E1300.
2.1.1 Classification - Level, Performance, Model
2.1.1.1 Heavy Duty Doors
SDI/DOOR A250.8, Level 2, physical performance Level B, Model 1, with core construction as required by the manufacturer for interior doors, of size(s) and design(s) indicated. Where vertical stiffener cores are required, the space between the stiffeners must be filled with mineral board insulation. Provide Level 2 for doors No. 106, 107.
2.1.1.2 Extra Heavy Duty Doors
SDI/DOOR A250.8, Level 3, physical performance Level A, Model 1, with core construction as required by the manufacturer for interior doors, of size(s) and design(s) indicated. Where vertical stiffener cores are
SECTION 08 11 13 Page 5Am #0004 required, the space between the stiffeners must be filled with mineral board insulation. Provide Level 3 for doors No. 103, 104, 108A, 108D, 122C, 122E.
2.1.1.3 Maximum Duty Doors
SDI/DOOR A250.8, Level 4, physical performance Level A, Model 1, with core construction as required by the manufacturer for indicated exterior doors, of size(s) and design(s) indicated. Where vertical stiffener cores are required, the space between the stiffeners must be filled with mineral board insulation.Provide Level 4 for doors No. 101, 102, 105, 108B, 109, 110, 121A, 121B, 121C, 121D, 122A, 122B, 122F, 122G.
2.2 CUSTOM HOLLOW METAL DOORS
Provide custom hollow metal doors where nonstandard steel doors are indicated. At the Contractor's option, custom hollow metal doors may be provided in lieu of standard steel doors. Provide standard steel doors in the door size(s), design(s), materials, construction, gages, and finish as specified for standard steel doors and complying with the requirements of NAAMM HMMA 810. Fill all spaces in doors with insulation. Close top and bottom edges with steel channels not lighter than 16 gage. Close tops of exterior doors flush with an additional channel and seal to prevent water intrusion. Prepare doors to receive hardware specified in Section 08 71 00 DOOR HARDWARE.Undercut doors where indicated. Provide doors at 1-3/4 inch thick, unless otherwise indicated.
2.3 INSULATED STEEL DOOR SYSTEMS
At the option of the Contractor, insulated steel doors and frames may be provided in lieu of Level 1 standard steel doors and frames. Provide insulated steel doors in the door size(s), design, and material as specified for standard steel doors. Provide insulated steel doors with a core of polyurethane foam; face sheets, edges, and frames of galvanized steel not lighter than 23 gage, 16 gage, and 16 gage respectively;
magnetic weatherstripping; nonremovable-pin hinges; thermal-break aluminum threshold; and vinyl door bottom. Provide to doors and frames a phosphate treatment, rust-inhibitive primer, and baked acrylic enamel finish. Test doors in accordance with SDI/DOOR A250.4 and meet the requirements for Level C. Prepare doors to receive specified hardware. Provide doors 1-3/4 inch thick.Provide insulated steel doors and frames at building entrances.
2.4 ACCESSORIES
2.4.1 Louvers
2.4.1.1 Exterior Louvers
Provide louvers of the inverted "V" type with minimum of 55 percent net-free opening. Weld or tenon louver blades to continuous channel frame and weld assembly to door (or transom frame, as applicable)to form watertight assembly. Form louvers of hot-dip galvanized steel of same gage as door facings. At louvers provide steel-framed insect screens secured to room side and readily removable. Provide aluminum wire cloth, 18 by 18 or 18 by 16 inch mesh, for insect screens. Net-free louver area to be before screening.
SECTION 08 11 13 Page 6Am #0004
2.4.2 Astragals
For pairs of exterior steel doors which will not have aluminum astragals or removable mullions, as specified in Section 08 71 00 DOOR HARDWARE provide overlapping steel astragals with the doors. For interior pairs of fire rated doors, provide stainless steel astragals complying with NFPA 80 for fire rated assemblies.
2.4.3 Moldings
Provide moldings around glass of interior and exterior doors and louvers of interior doors. Provide nonremovable moldings on outside of exterior doors and on corridor side of interior doors. Other moldings may be stationary or removable. Secure inside moldings to stationary moldings, or provide snap-on moldings. Provide muntins that interlock at intersections and are fitted plus welded to stationary moldings.
2.5 INSULATION CORES
Provide insulating cores of the type specified, and provide an apparent U-factor of .48 in accordance with SDI/DOOR 113 and conforming to:
a. Rigid Cellular Polyisocyanurate Foam: ASTM C591, Type I or II, foamed-in-place or in board form, with oxygen index of not less than 22 percent when tested in accordance with ASTM D2863; or
b. Rigid Polystyrene Foam Board: ASTM C578, Type I or II; or
c. Mineral board: ASTM C612, Type I.
2.6 STANDARD STEEL FRAMES
SDI/DOOR A250.8, Level 2, except as otherwise specified. Form frames to sizes and shapes indicated, with welded corners or knock-down field-assembled corners. Provide steel frames for doors unless otherwise indicated. Provide frame product that uses a minimum of 25 percent recycled content.
SDI/DOOR A250.8, Level 3 and 4, except as otherwise specified. Form frames to sizes and shapes indicated, with welded corners. Provide steel frames for doors, and transoms, unless otherwise indicated. Provide frame product that uses a minimum of 25 percent recycled content.
2.6.1 Welded Frames
Continuously weld frame faces at corner joints. Mechanically interlock or continuously weld stops and rabbets. Grind welds smooth.
Weld frames in accordance with the recommended practice of the Structural Welding Code Sections 1 through 6, AWS D1.1/D1.1M and in accordance with the practice specified by the producer of the metal being welded.
2.6.2 Knock-Down Frames
Design corners for simple field assembly by concealed tenons, splice plates, or interlocking joints that produce square, rigid corners and a tight fit and maintain the alignment of adjoining members. Provide locknuts for bolted connections.
SECTION 08 11 13 Page 7Am #0004
2.6.3 Mullions and Transom Bars
Provide mullions and transom bars of closed or tubular construction with heads and jambs butt-welded together. Bottom of door mullions must have adjustable floor anchors and spreader connections.
2.6.4 Stops and Beads
Form stops and beads from 20 gage steel. Provide for glazed and other openings in standard steel frames. Secure beads to frames with oval-head, countersunk Phillips self-tapping sheet metal screws or concealed clips and fasteners. Space fasteners approximately 12 to 16 inch on center.
Miter molded shapes at corners. Butt or miter square or rectangular beads at corners.
2.6.5 Anchors
Provide anchors to secure the frame to adjoining construction. Provide steel anchors, zinc-coated or painted with rust-inhibitive paint, not lighter than 18 gage.
2.6.5.1 Wall Anchors
Provide at least three anchors for each jamb. For frames which are more than 7.5 feet in height, provide one additional anchor for each jamb for each additional 2.5 feet or fraction thereof.
a. Masonry: Provide anchors of corrugated or perforated steel straps or 3/16 inch diameter steel wire, adjustable or T-shaped;
b. Stud partitions: Weld or otherwise securely fasten anchors to backs of frames. Design anchors to be fastened to closed steel studs with sheet metal screws, and to open steel studs by wiring or welding; and
c. Precast Concrete Panel: Secure frames to previously placed concrete with expansion bolts in accordance with SDI/DOOR 111;
2.6.5.2 Floor Anchors
Provide floor anchors drilled for 3/8 inch anchor bolts at bottom of each jamb member.
2.7 FIRE DOORS AND FRAMES
NFPA 80 and this specification. The requirements of NFPA 80 takes precedence over details indicated or specified.
2.7.1 Labels
Provide fire doors and frames bearing the label of Underwriters Laboratories (UL), Factory Mutual Engineering and Research (FM), or Warnock Hersey International (WHI) attesting to the rating required.
Testing must be in accordance with NFPA 252 or UL 10C. Provide labels that are metal with raised letters, bearing the name or file number of the door and frame manufacturer. Labels must be permanently affixed at the factory to frames and to the hinge edge of the door. Do not paint door
SECTION 08 11 13 Page 8Am #0004 and labels.
2.7.2 Oversized Doors
For fire doors and frames which exceed the size for which testing and labeling are available, furnish certificates stating that the doors and frames are identical in design, materials, and construction to a door which has been tested and meets the requirements for the class indicated.
2.7.3 Astragal on Fire Doors
On pairs of labeled fire doors, conform to NFPA 80 and UL requirements.
2.8 WEATHERSTRIPPING
As specified in Section 08 71 00 DOOR HARDWARE.
2.9 HARDWARE PREPARATION
Provide minimum hardware reinforcing gages as specified in SDI/DOOR A250.6.
Drill and tap doors and frames to receive finish hardware. Prepare doors and frames for hardware in accordance with the applicable requirements of SDI/DOOR A250.8 and SDI/DOOR A250.6. For additional requirements refer to ANSI/BHMA A156.115. Drill and tap for surface-applied hardware at the project site. Build additional reinforcing for surface-applied hardware into the door at the factory. Locate hardware in accordance with the requirements of SDI/DOOR A250.8, as applicable. Punch door frames, with the exception of frames that will have weatherstripping gasketing, to receive a minimum of two rubber or vinyl door silencers on lock side of single doors and one silencer for each leaf at heads of double doors. Set lock strikes out to provide clearance for silencers.
2.10 FINISHES
2.10.1 Factory-Primed Finish
Thoroughly clean all surfaces of doors and frames then chemically treat and factory prime with a rust inhibiting coating as specified in SDI/DOOR A250.8., or paintable A25 galvannealed steel without primer.
Where coating is removed by welding, apply touchup of factory primer.
2.10.2 Electrolytic Zinc-Coated Anchors and Accessories
Provide electrolytically deposited zinc-coated steel in accordance with ASTM A879/A879M, Commercial Quality, Coating Class A. Phosphate treat and factory prime zinc-coated surfaces as specified in SDI/DOOR A250.8.
2.11 FABRICATION AND WORKMANSHIP
Provide finished doors and frames that are strong and rigid, neat in appearance, and free from defects, waves, scratches, cuts, dents, ridges, holes, warp, and buckle. Provide molded members that are clean cut, straight, and true, with joints coped or mitered, well-formed, and in true alignment. Dress exposed welded and soldered joints smooth. Design door frame sections for use with the wall construction indicated. Corner joints must be well-formed and in true alignment. Conceal fastenings where practicable. Design frames in exposed masonry walls or partitions to allow sufficient space between the inside back of trim and masonry to receive caulking compound.
SECTION 08 11 13 Page 9Am #0004
2.11.1 Grouted Frames
[*Am-4] Frames to be installed in exterior walls shall be filled with mortar or grout. Fill the stops with strips of rigid insulation to keep the grout out of the stops and to facilitate installation of stop-applied head and jamb seals. Coordinate the filling of frames with grout or mortar with the installation of rough-ins for door access controls and door access control assemblies.[**Am-4]
2.12 PROVISIONS FOR GLAZING
Materials are specified in Section 08 81 00, GLAZING.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Frames
Set frames in accordance with SDI/DOOR A250.11. Plumb, align, and brace securely until permanent anchors are set. Anchor bottoms of frames with expansion bolts or powder-actuated fasteners. Build in or secure wall anchors to adjoining construction. [*Am-4]Coordinate the filling of frames with grout or mortar with the installation of rough-ins for door access controls and door access control assemblies.[**Am-4]
3.1.2 Doors
Hang doors in accordance with clearances specified in SDI/DOOR A250.8.
After erection and glazing, clean and adjust hardware.
3.1.3 Fire Doors and Frames
Install fire doors and frames, including hardware, in accordance with
NFPA 80.
3.2 PROTECTION
Protect doors and frames from damage. Repair damaged doors and frames prior to completion and acceptance of the project or replace with new, as directed. Wire brush rusted frames until rust is removed. Clean thoroughly. Apply an all-over coat of rust-inhibitive paint of the same type used for shop coat.
3.3 CLEANING
Upon completion, clean exposed surfaces of doors and frames thoroughly.
Remove mastic smears and other unsightly marks.
-- End of Section --
SECTION 08 11 13 Page 10Am #0004
[*Am-4] Frames to be installed in exterior walls shall be filled with mortar or grout. Fill the stops with strips of rigid insulation to keep the grout out of the stops and to facilitate installation of stop-applied head and jamb seals. Coordinate the filling of frames with grout or mortar with the installation of rough-ins for door access controls and door access control assemblies.[**Am-4]
[*Am-4]Coordinate the filling of frames with grout or mortar with the installation of rough-ins for door access controls and door access control assemblies.[**Am-4]
DIVISION 08 - OPENINGS
SECTION 08 34 16.20
VERTICAL LIFT FABRIC DOORS
05/14
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 DESIGN REQUIREMENTS
1.3.1 Door Design and Components
1.3.1.1 Steel Door Components
1.3.1.2 Aluminum Door Components
1.3.2 Loads
1.3.2.1 Wind Loads
1.3.2.2 Other Loads
1.3.3 Door Speed
1.3.4 Door Weight
1.4 QUALITY ASSURANCE
1.4.1 Manufacturer's Qualifications
1.4.2 Installer's Qualifications
1.4.3 Warranty
1.4.3.1 Maintenance and Repair Action Plan
1.4.4 Delivery, Storage and Handling
1.5 WELDING PROCEDURES AND QUALIFICATIONS
PART 2 PRODUCTS
2.1 MATERIALS
2.1.1 Steel Plate and Bars
2.1.2 Steel Sheet
2.1.3 Steel Shapes
2.1.4 Aluminum Extrusions
2.1.5 Aluminum Sheets and Strips
2.1.6 Aluminum Welding Rods and Bare Electrodes
2.1.7 Door Fabric
2.1.8 Steel Cable and Wire Rope
2.2 DOORS
2.2.1 Fabric Door Panels
2.2.2 Door Beams
2.2.3 Door Guides
2.3 ELECTRIC OPERATORS
2.3.1 Drive Units
2.3.2 Belt/Cable System
2.3.3 Safety Arresters
2.3.4 Slack Belt/Cable Breaker
2.3.5 Motors
2.3.6 Controls
2.3.6.1 Control Panel Enclosures
2.3.7 Limit Switches
2.3.8 Door Control Alarms
SECTION 08 34 16.20 Page 1Am #0004
2.3.9 Safety Device
2.3.10 Control Transformers
2.3.11 Electrical Components
2.3.12 User Interface with Diagnostics
2.4 HEADER BOX
2.5 BOTTOM BEAM
2.6 WIND LOCK
2.7 SWING-UP MULLION WHERE INDICATED
2.7.1 Mullion Pit and Cover where Indicated
2.7.2 Retractable Mullion Pin and Floor Strike when Utilized
2.8 PERSONNEL DOOR
2.9 OPERATION
2.9.1 Door Operation
2.9.2 Electrical Operation
2.10 FINISHES
2.10.1 Ferrous Metal
2.10.2 Aluminum
2.11 SIGNAGE
PART 3 EXECUTION
3.1 PROTECTIVE COATINGS
3.1.1 Cleaning
3.1.2 Shop Painting
3.1.3 Metal Protection
3.2 ERECTION
3.2.1 Assembly
3.2.2 Cleaning
3.2.3 Control Panel Installation
3.3 ACCEPTANCE TESTING PROCEDURE AND REPORT
3.3.1 General
3.3.2 Safety Arresters
3.3.3 Personnel Training
3.4 EXTRA MATERIALS
3.5 ELECTRICAL WORK
SECTION 08 34 16.20 Page 2Am #0004
SECTION 08 34 16.20
VERTICAL LIFT FABRIC DOORS
05/14
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only. When a date or edition is not listed in the title, use the most recent edition/version.
ALUMINUM ASSOCIATION (AA)
AA ADM (2015) Aluminum Design Manual
AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 2604 (2017a) Voluntary Specification, Performance Requirements and Test Procedures for High Performance Organic Coatings on Aluminum Extrusions and Panels
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 325 (2017) Steel Construction Manual
AISC 360 (2016) Specification for Structural Steel Buildings
AMERICAN WELDING SOCIETY (AWS)
AWS A5.10/A5.10M (2017) Welding Consumables - Wire Electrodes, Wires and Rods for Welding of Aluminum and Aluminum-Alloys - Classification
AWS D1.1/D1.1M (2020) Structural Welding Code - Steel
AWS D1.2/D1.2M (2014) Structural Welding Code - Aluminum
ASTM INTERNATIONAL (ASTM)
ASTM A36/A36M (2019) Standard Specification for Carbon Structural Steel
ASTM A653/A653M (2020) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A992/A992M (2011; R 2015) Standard Specification for
SECTION 08 34 16.20 Page 3Am #0004
Structural Steel Shapes
ASTM A1023/A1023M (2019) Standard Specification for Stranded Carbon Steel Wire Ropes for General Purposes
ASTM B209 (2014) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM D2136 (2002; R 2012) Coated Fabrics - Low-Temperature Bend Test
ASTM E84 (2020) Standard Test Method for Surface Burning Characteristics of Building Materials
NATIONAL ASSOCIATION OF ARCHITECTURAL METAL MANUFACTURERS (NAAMM)
NAAMM AMP 500 (2006) Metal Finishes Manual
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA AB 1 (2002) Molded-Case Circuit Breakers, Molded Case Switches, and Circuit-Breaker Enclosures
NEMA ICS 1 (2000; R 2015) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 2 (2000; R 2005; Errata 2008) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 5 (2017) Industrial Control and Systems:
Control Circuit and Pilot Devices
NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures
NEMA KS 1 (2013) Enclosed and Miscellaneous Distribution Equipment Switches (600 V Maximum)
NEMA MG 1 (2018) Motors and Generators
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14; TIA 17-15; TIA 17-16; TIA 17-17 )
National Electrical Code
NFPA 79 (2015) Electrical Standard for Industrial
SECTION 08 34 16.20 Page 4Am #0004
Machinery
NFPA 220 (2018) Standard on Types of Building Construction
NFPA 409 (2016; ERTA 2016) Standard on Aircraft Hangars
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 1-200-01 DoD Building Code (General Building Requirements)
UFC 3-301-01 (2019) Structural Engineering
UNDERWRITERS LABORATORIES (UL)
UL 98 (2016) UL Standard for Safety Enclosed and Dead-Front Switches
UL 248-1 (2011) Low Voltage Fuses - Part 1: General Requirements
UL 248-12 (2011) Low Voltage Fuses - Part 12: Class R Fuses
UL 489 (2016) UL Standard for Safety Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures
UL 508 (2018) UL Standard for Safety Industrial Control Equipment
UL 1449 (2017) UL Standard for Safety Surge Protective Devices
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00.
SD-01 Preconstruction Submittals
Manufacturer's Qualifications; G, DO
Installer's Qualifications; G, DO
SD-02 Shop Drawings specific to this project, sealed by the Door Manufacturer's Registered Professional Engineer
Shop drawings of motors, all electrical control devices, and all electrical control panels, including schematic diagrams, dimensional drawings of control panels, details of control panel installations, internal wiring diagrams of control panels, and wiring diagrams indicating all external connections between control panels and from control panels to remote control devices.
SECTION 08 34 16.20 Page 5Am #0004
Furnish list of materials for all control devices, both inside and remote from control panels including manufacturer's model number, electrical ratings, location, and quantity of each item furnished.
Door Design; G, DO
Show all vertical lift fabric doors and components, including types, sizes, locations, fabric, supporting, bracing and framing steel and aluminum members, metal gages, fasteners, speed, hardware provisions, signage, installation details, insulation R-Values, and other details of construction. Include supporting brackets for motors, location of motors, and safety devices.
Include personnel door, mullion pit and cover or retractable pin and strike if utilized. Provide details for the closure between bulkhead and doors. Include details for supporting and bracing the door assembly from the structure. Indicate finishes to be used.
SD-03 Product Data
Diagrams, performance curves and characteristic curves of equipment and systems.
Electric Operator; G, DO
Drive unit system horsepowers, belt type, and locations. Safety arrestor type, test reports, and brake system details.
Motors; G, DO
Motor characteristics including horsepower, service factor, safety factor and standards compliance.
Doors; G, DO
Controls; G, DO
Controls characteristics including all electrical components and devices used in the control system, enclosures, safety devices, transformer size and voltage, and emergency power connection.
Door Fabric; G, DO
Submit fabric panel samples for weight, strength and color approval.
Surge Protection Device (SPD) data for each incoming/outgoing power feeder and each control circuit; G, DO
SD-05 Design Data
Calculations sealed by the Door Manufacturer's Registered Professional Engineer; G, DO
Door Load Diagrams (Open/Closed positions); G, DO
SD-06 Test Reports
Safety Arrester Operation Test; G, DO
SECTION 08 34 16.20 Page 6Am #0004
Door Fabric: ASTM D2136; G, DO
Door Fabric: ASTM E84; G, DO
SD-07 Certificates
Manufacturer's Qualifications; G, DO
Installers Qualifications; G, DO
Welding Procedures and Qualifications; G, DO
SD-09 Manufacturer's Field Reports
Acceptance Testing Procedure and Report; G, DO
SD-10 Operation and Maintenance Data
Door Operation, Data Package 2; G, DO
Submit in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA. Including wiring diagrams and the complete manufacturer's instructions for operation and maintenance of the doors, door mullions where indicated, and accessories, including emergency operation, in the event of general building power failure to the doors.
Emergency and Routine Preventative Maintenance Plan; G, DO
SD-11 Closeout Submittals
Acceptance Testing Procedure and Report; G, RO
Manufacturer's Warranty; G, RO
1.3 DESIGN REQUIREMENTS
1.3.1 Door Design and Components
The vertical lift fabric doors and components indicated in the construction documents are representative of commercially-available doors. Design and fabricate the door to fit within the space allocated and in accordance with the criteria specified herein. Door must operate properly without binding, interference, or damage to the adjacent structure. The door shall have an R-value of less than 3.0. Door must be of limited combustible construction in accordance with NFPA 220 and
NFPA 409.
1.3.1.1 Steel Door Components
All supporting, bracing and framing steel members must be designed by the door manufacturer's registered professional engineer for the specified loads according to the requirements of AISC 325 and AISC 360. Steel welding must be in accordance with the AWS D1.1/D1.1M Standards. Refer to Section 05 12 00 STRUCTURAL STEEL for requirements.
1.3.1.2 Aluminum Door Components
All supporting, bracing and framing aluminum members must be designed by
SECTION 08 34 16.20 Page 7Am #0004 the door manufacturer's registered professional engineer for the specified loads according to the requirements of the Aluminum Association (AA ADM).
Aluminum welding must be in accordance with AWS D1.2/D1.2M standards.
1.3.2 Loads
The loads for the design of the door must be in accordance with UFC 1-200-01, UFC 3-301-01 and all other applicable criteria.
1.3.2.1 Wind Loads
In the closed position, doors and all components must be designed to withstand the wind pressures as indicated by the Engineer of Record. All door components must be designed to withstand both the highest positive and negative pressures based on actual tributary area from the wind load indicated.
In addition, doors and all components must be designed to be operational during wind events which cause a positive or negative service load pressure of 15 psf on the surface of the door. Also the door mullions where indicated and jambs must be designed for an unbalanced positive or negative service load pressure of 15 psf load on the surface of a closed adjacent door with the other adjacent door being open.
Calculations sealed by the door manufacturer's registered professional engineer must be submitted for review.
1.3.2.2 Other Loads
The door mullions where indicated must be of adequate strength to transmit the forces from design wind load, in addition to the other loads resulting from door operations or the door's action as a tributary element, with no detrimental effect on the operation of the door. The door manufacturer must submit the loads imposed upon the building structure by the vertical lift fabric door and its components.
1.3.3 Door Speed
Door must open fully at a speed of 6 inches per second minimum under all design conditions. The door mullion when required must rotate with a cable retraction speed of 6 inches per second minimum.
1.3.4 Door Weight
The door manufacturer must provide load diagrams of the door in the closed and open positions. Details must also be provided showing clearance and attachment requirements for coordination with the structural steel and miscellaneous steel shop drawings.
1.4 QUALITY ASSURANCE
1.4.1 Manufacturer's Qualifications
Use a vertical lift fabric door product from a manufacturer who is regularly engaged in the design, fabrication, erection, and service of vertical lift fabric doors of type and size required for this project.
The manufacturer must have at least 5 years of similar vertical lift fabric door design experience. Similar doors must have comparable function and design including size, configuration, type of use, SECTION 08 34 16.20 Page 8Am #0004 retractable or moving elements, safety features, controls, and other key engineering elements as the door being specified. It is acceptable to show that a series of similar doors collectively meet all comparable elements to the door being specified, although not necessarily individually. Manufacturer must submit written evidence on similar past door designs and installations listing the name, location, contact information of owners, installation dates, overall sizes, features, and other relevant information for experience and qualifications evaluation.
Only manufacturers who can submit this evidence of actual installations where the products have proven practical, durable, and require a minimum of maintenance, will be qualified under this specification.
1.4.2 Installer's Qualifications
Installation of the door(s) must be supervised by a manufacturer's representative and must be in accordance with approved shop drawings.
Installers must be skilled and experienced in the erection of vertical lift fabric doors of the type specified herein. Installers must submit written evidence of similar past door installations listing the name, locations, contacts information of owners, installation dates, overall sizes, features, and other relevant information for experience and qualifications evaluation.
1.4.3 Warranty
The door manufacturer must provide a three-year warranty for all mechanical and electrical components against defects in material and workmanship beginning on the date of Project Acceptance. The warranty for fabric must be ten years against defect in material.
1.4.3.1 Maintenance and Repair Action Plan
The door manufacturer must provide an Emergency and Routine Preventative Maintenance Plan. In addition to Data Package SD-10 "Operation and Maintenance Data", provide a list of phone numbers and personnel contacts. Also provide a list of suggested spare parts materials and tools to be purchased by the Contracting Officer. Submit vertical lift fabric door manuals in accordance with Section 01 78 23 OPERATION AND
MAINTENANCE DATA.
1.4.4 Delivery, Storage and Handling
The door manufacturer must provide shipment of all materials required for door installation in protective packaging. Protect door and accessories from damage during delivery, storage, and handling. Mark all packaging clearly with manufacturer's brand name, door model and job site location.
Store in dry location with adequate ventilation, and free from dust and water. Storage must permit easy access for inspection and handling.
Remove damaged items that cannot be restored to like new condition or provide new items.
1.5 WELDING PROCEDURES AND QUALIFICATIONS
Prior to welding, submit certification for each welder stating the type of welding and positions qualified for, the code and procedure qualified under, date qualified, and the firm and individual certifying the qualification tests.
Comply with applicable provisions of AWS D1.1/D1.1M for Steel.
SECTION 08 34 16.20 Page 9Am #0004
Comply with applicable provisions of AWS D1.2/D1.2M for Aluminum.
PART 2 PRODUCTS
2.1 MATERIALS
Materials must be selected based on durability, low maintenance, weather resistance and strength (permanent deformation from loading not allowed).
Doors must comply with ASTM E84 for limited combustible construction.
2.1.1 Steel Plate and Bars
ASTM A36/A36M
2.1.2 Steel Sheet
ASTM A653/A653M
2.1.3 Steel Shapes
ASTM A992/A992M
2.1.4 Aluminum Extrusions
ASTM B221, Alloy 6063-T6, Alloy 6005-T5 or 6000 Series Aluminum
2.1.5 Aluminum Sheets and Strips
ASTM B209, alloy and temper best suited for the purpose.
2.1.6 Aluminum Welding Rods and Bare Electrodes
AWS A5.10/A5.10M.
2.1.7 Door Fabric
The fabric material must be a one piece heavy-duty vinyl coated polyester fabric weighing not less than 19 oz/square yard, capable of carrying 250 lb/in per panel. Fabric must be impervious and resistant to solvents, fuel, lubricants and other similar fluids commonly found in aircraft maintenance hangars. It must be UV stabilized, self-extinguishing (0-75 flame spread), and suitable to withstand temperatures between plus 158 to minus 31 degrees F in compliance with ASTM D2136. Use an opaque material in a color selected by the government from the manufacturer's standard colors for the lowest two panels of each door. In the panels above, use a translucent material to allow day-lighting of the hangar high bay area.
The translucent material must also meet the same requirements and loadings as the standard door fabric. The door fabric must be pulled tight between the intermediate beams when the door is fully closed and the wind locks engaged. The fabric must have been tested to meet the criteria of ASTM E84 -94 (flame spread - Class A interior wall and ceiling finish) and ASTM D2136 (cold cracking, brittleness and temperature).
2.1.8 Steel Cable and Wire Rope
ASTM A1023/A1023M.
SECTION 08 34 16.20 Page 10Am #0004
2.2 DOORS
Doors must consist of hoist up fabric doors with intermediate aluminum beams or trusses. Fabric must be gathered above the head of the opening.
Maximum wind load deflection of steel structural members of the door must not exceed the member length divided by 120. Maximum wind load deflection of extruded aluminum members of the door must not exceed the member length divided by 30.
2.2.1 Fabric Door Panels
The fabric must be attached to both sides of the intermediate beams, top beam, and bottom beam with self-tapping screws through corrosion resistant anodized or coated aluminum batten strips. Provide batten strip covers of PVC material to snap over the aluminum batten strips and be full width of the door fabric. Coated aluminum batten strips and PVC batten strip covers must be selected from the manufacturer's standard colors, which must offer a variety of options including colors to match the Standard Door Fabric color.
2.2.2 Door Beams
The intermediate beams must be corrosion resistant, extruded aluminum and have a suitable depth dependent on the door width and the wind load requirements. They must be spaced 35 to 75 inches apart, dependent upon the wind load. At each end of the beams there must be a guide block of self-lubricating material or rollers that run along the guides. Built-up members meeting these requirements are acceptable. The intermediate door beams and guide block or rollers must be designed to carry the full design wind load without failure and being pulled from the door guides. The guide block or roller design must not put the intermediate beam into tension which would cause pulling forces on door jambs. Guide block material must be nylon, polyoxymethylene (POM), or Ultra High Molecular Weight (UHMW) polyethylene. Rollers must be galvanized steel with maintenance free, lifetime sealed ball-bearings in case-hardened steel races.
2.2.3 Door Guides
The vertical guides must be an integral part of the door, made of extruded aluminum with a suitable depth and width dependent on the size of the intermediate beams and wind load requirements. The guides must be designed to provide weather sealing on the inside and outside faces.
There must also be a space inside the guides for the nylon belt, polyester belt, or steel cable of the drive unit and safety arresters. The installer must provide jamb anchorage of size and type required for attachment of the guide rails as shown on the approved shop drawings. The jamb anchorage and door guides must be designed to carry the full design wind load without failure and without permanent deformation.
2.3 ELECTRIC OPERATORS
2.3.1 Drive Units
Each door leaf must have a single or dual motor drive system with horsepower sized as appropriate for the weight of the door leaf. The gear motor must be equipped with a drum on which the nylon belt, polyester belt, or steel cables are wound. If a single motor drive is used, the belts and cables must be wound on the same drum. Cables must be wound on
SECTION 08 34 16.20 Page 11Am #0004 a grooved drum. The belts and cables must be attached to the bottom beam via the safety arresters. A hand crank device or other manual means must be provided on the motor for manual operation of the door in the event of a power failure. The gear motor must be removable without disturbing limit switch adjustment. The drive units will be coordinated with the location of aircraft such that the drive units are accessible while aircraft are in the hangar.
2.3.2 Belt/Cable System
A maximum of two belts/cables per door, running inside the door guides, must be used to transmit motive force to the door unit. Similarly, the quantity of sheaves used to guide the belts/cables must be minimized to reduce maintenance requirements and spare parts inventories. Belts/cables must be installed free of any kinks and the system design and sheave diameter must be such to prevent the occurrence of any kinks and abnormal stress in the operating belts/cables. Where belts/cables pass through openings of the building structure, the openings must be constructed so as to prevent abrasion, wear, or damage to the belts and cables. Sheave units must be provided in accessible locations that allow inspection and preventive maintenance. Sheaves must not be located in enclosed locations, which are not readily accessible for visual inspection.
2.3.3 Safety Arresters
Each door leaf must be supplied with two safety arresters that automatically activate and support the door in case the door lifting system fails similar to a belt or cable breaking. A "Safety Arrestor �Operation Test" must be performed on each set of safety arresters by an independent testing source to withstand at least 110 percent of the maximum door leaf weight.
The "Safety Arrestor Operation Test" must be deemed successful when it contains at least the minimum following criteria:
a. Test door weight must be at least 110 percent of the specific project's door weight.
b. Test must simulate the door lifting system abruptly disengaging similar to a belt or cable breaking.
c. The Safety Arresters must automatically engage.
d. The test door weight must be brought to rest after an initial downward movement (or drop) of not more than 12 inches and held firmly in this position.
e. Damage from activation of the Safety Arrestors must be limited to localized replaceable components and not cause a system failure which would require repair or replacement of the entire VLFD or the structural door jambs.
f. Independent testing source must submit documentation of successful " Safety Arrester Operation Test".
The moveable mullions, when provided, must be provided with a lifting motor that includes a backup arresting system or secondary brake system to prevent the mullion form falling in case of motor or primary brake failure.
SECTION 08 34 16.20 Page 12Am #0004
2.3.4 Slack Belt/Cable Breaker
A safety device must be used on all door leaf belts/cables that will send a slack belt/cable condition and cut power to the appropriate drive unit to prevent an unsafe condition.
2.3.5 Motors
NEMA MG 1, high-starting torque, reversible type with sufficient horsepower and torque output to move the door in either direction from any position. Motor must produce a door travel speed of not less than 6 inches per second without exceeding the rated capacity. Motors must operate on voltage of the characteristics indicated at not more than 1800 rpm. Motor enclosures must be drip-proof type or NEMA totally-enclosed, fan-cooled (TEFC) type. A hand crank must be supplied which fits the motor for manual operation of the door in the event of a power failure. Install motors in approved locations. Motors must have a minimum service factor of 1.2 at continuous duty under maximum full load. The design of the door motor and door drive gear box must each have a safety factor of 2.5.
Motors must be provided in accordance with Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM and requirement listed above.
Motors shall be provided with adjustable speed drives (ASDs) in accordance with Section 26 29 23 ADJUSTABLE SPEED DRIVE (ASD) SYSTEMS UNDER 600 VOLTS. ASDs shall be sized to permit a 300% current limit.