Amend_0001_McAllen_Specs_Appendix-C_thru_G.pdf
PDF 13 MB Posted
- Attached to
- McAllen CPC RENOVATION Federal contract opportunity
- Solicitation number
- W9126G-15-B-0029
About this file
AMENDMENT 0001 - APPENDIX C_Thru_G
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| C1_BID_ABSTRACT_W9126G-15-B-0029.pdf | ||
| B3_AMENDMENT_0005.pdf | ||
| B3_AMENDMENT_0004.pdf | ||
| B3_AMENDMENT__0003.pdf | ||
| B3_Amendment_0002_.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-B_part-1.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-B_part-2.pdf | ||
| Amendment_0001_B_CLIN_Changes.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-B_part-5.pdf | ||
| Amendment_0001.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-B_part-3.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-B_part-4.pdf | ||
| McAllen_22K_CPC_Warehouse_FINAL_design_Drawings.pdf | ||
| W9126G-15-B-0029-Specs.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Model:400REOZJ
Diesel
Standard Features
208--600 V
Ratings Range 60 Hz
Standby: kW 315--400 kVA 394--500
Prime: kW 285--365 kVA 356--456
� Kohler Co. provides one-source responsibility for the generating system and accessories.
� The generator set and its components are prototype-tested, factory-built, and production-tested.
� The 60 Hz generator set offers a UL 2200 listing.
� The generator set accepts rated load in one step.
� The 60 Hz emergency generator set meets NFPA 110, Level 1, when equipped with the necessary accessories and installed per NFPA standards.
� A one-year limited warranty covers all systems and components. Two- and five-year extended warranties are also available.
� Alternator features:
� The pilot-excited, permanent magnet (PM) alternator provides superior short-circuit capability.
� The brushless, rotating-field alternator has broadrange reconnectability.
� Other features:
� Kohler designed controllers for guaranteed system integration and remote communication. See Controllers on page 3.
� The low coolant level shutdown prevents overheating (standard on radiator models only).
� Integral vibration isolation eliminates the need for under-unit vibration spring isolators.
� An electronic, isochronous governor delivers precise frequency regulation.
� Multiple circuit breaker configurations.
Tier 3 EPA-Certified for Stationary Emergency Applications
G5-354 (400REOZJ) 5/12e
Generator Set Ratings
150�C Rise Standby Rating
130�C Rise Standby Rating
125�C Rise Prime Rating
105�C Rise Prime Rating
Alternator Voltage Ph Hz kW/kVA Amps kW/kVA Amps kW/kVA Amps kW/kVA Amps
4M4021
120/208 3 60 400/500 1388 380/475 1318 365/456 1266 345/432 1197 127/220 3 60 400/500 1312 390/488 1279 365/456 1197 355/444 1165 139/240 3 60 400/500 1203 400/500 1203 365/456 1098 365/456 1098 220/380 3 60 315/394 598 315/394 598 285/356 541 285/356 541 240/416 3 60 400/500 694 380/475 659 365/456 633 345/431 599 277/480 3 60 400/500 601 400/500 601 365/456 549 365/456 549
5M4027
120/208 3 60 400/500 1388 400/500 1388 365/456 1266 365/456 1266 127/220 3 60 400/500 1312 400/500 1312 365/456 1197 365/456 1197 139/240 3 60 400/500 1203 400/500 1203 365/456 1098 365/456 1098 220/380 3 60 400/500 760 400/500 760 365/456 693 365/456 693 240/416 3 60 400/500 694 400/500 694 365/456 633 365/456 633 277/480 3 60 400/500 601 400/500 601 365/456 549 365/456 549
5M4028
120/208 3 60 400/500 1388 400/500 1388 365/456 1266 365/456 1266 127/220 3 60 400/500 1312 400/500 1312 365/456 1197 365/456 1197 139/240 3 60 400/500 1203 400/500 1203 365/456 1098 365/456 1089 220/380 3 60 400/500 760 400/500 760 365/456 693 365/456 693 240/416 3 60 400/500 694 400/500 694 365/456 633 365/456 633 277/480 3 60 400/500 601 400/500 601 365/456 549 365/456 549
4M4266 347/600 3 60 400/500 481 400/500 481 365/456 439 365/456 439 5M4272 347/600 3 60 400/500 481 400/500 481 365/456 439 365/456 439 RATINGS: All three-phase units are rated at 0.8 power factor. Standby Ratings: The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Prime Power Ratings: At varying load, the number of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO-8528-1 and ISO-3046-1. For limited running time and continuous ratings, consult the factory. Obtain technical information bulletin (TIB-101) for ratings guidelines, complete ratings definitions, and site condition derates. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever.
G5-354 (400REOZJ) 5/12e
Alternator Specifications
Specifications Alternator
Type 4-Pole, Rotating-Field
Exciter type Brushless, Permanent- Magnet, Pilot Exciter
Leads: quantity, type 12, Reconnectable
Voltage regulator Solid State, Volts/Hz
Insulation: NEMA MG1
Material Class H, Synthetic, Nonhygroscopic
Temperature rise 130�C, 150�C Standby
Bearing: quantity, type 1, Sealed
Coupling Flexible Disc
Amortisseur windings Full
Rotor balancing 125%
Voltage regulation, no-load to full-load Controller Dependent
One-step load acceptance 100% of Rating
Unbalanced load capability 100% of Rated Standby Current
Peak motor starting kVA: (35% dip for voltages below) 480 V 4M4021 (12 lead) 1350 480 V 5M4027 (12 lead) 1550 480 V 5M4028 (12 lead) 1800 600 V 4M4266 (4 lead) 1300 600 V 5M4272 (4 lead) 1750
� NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting.
� Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds.
� Sustained short-circuit current enabling downstream circuit breakers to trip without collapsing the alternator field.
� Self-ventilated and dripproof construction.
� Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
� Brushless alternator with brushless pilot exciter for excellent load response.
Application Data Engine
Engine Specifications
Engine manufacturer John Deere
Engine model 6135HF485
Engine type 4-Cycle, Turbocharged, Charge Air-Cooled
Cylinder arrangement 6, Inline
Displacement, L (cu. in.) 13.5 (824)
Bore and stroke, mm (in.) 132 x 165 (5.2 x 6.5)
Compression ratio 16.0:1
Piston speed, m/min. (ft./min.) 594 (1950)
Main bearings: quantity, type 7, Replaceable Insert
Rated rpm 1800
Max. power at rated rpm, kWm (BHP) 460 (617)
Crankshaft material Forged Steel
Valve material
Intake/Exhaust Nickel-Chromium Head
Chromium-Silicone Stem
Governor: type, make/model JDEC Electronic L15
Frequency regulation, no-load to full-load Isochronous
Frequency regulation, steady state ±0.25%
Frequency Fixed
Air cleaner type, all models Dry
Exhaust
Exhaust System
Exhaust manifold type Dry
Exhaust flow at rated kW, m3/min. (cfm) 81 (2860)
Exhaust temperature at rated kW, dry exhaust, �C (�F) 471 (880)
Maximum allowable back pressure, kPa (in. Hg)
Min. 4 (1.2) Max. 10 (3.0)
Engine exhaust outlet size, mm (in.) See ADV drawing
Engine Electrical
Engine Electrical System
Battery charging alternator:
Ground (negative/positive) Negative
Volts (DC) 24
Ampere rating 60
Starter motor rated voltage (DC) 24
Battery, recommended cold cranking amps (CCA):
Qty., CCA rating each Two, 950
Battery voltage (DC) 12
Fuel
Fuel System
Fuel supply line, min. ID, mm (in.) 13 (0.50)
Fuel return line, min. ID, mm (in.) 10 (0.38)
Max. lift, fuel pump: type, m (ft.) Electronic 2.1 (6.8)
Max. fuel flow, Lph (gph) 196.5 (51.9)
Max. return line restriction, kPa (in. Hg) 35 (10.3)
Fuel prime pump Electronic
Fuel filter
Secondary 2 Microns @ 98% Efficiency
Primary 10 Microns
Water Separator Yes
Recommended fuel #2 Diesel
Lubrication
Lubricating System
Type Full Pressure
Oil pan capacity, L (qt.) 40.0 (42.3)
Oil pan capacity with filter, L (qt.) 42.0 (44.4)
Oil filter: quantity, type 1, Cartridge
Oil cooler Water-Cooled
G5-354 (400REOZJ) 5/12e
Application Data
Cooling
Radiator System
Ambient temperature, �C (�F)* 50 (122)
Engine jacket water capacity, L (gal.) 18 (4.8)
Radiator system capacity, including engine, L (gal.) 67.2 (17.8)
Engine jacket water flow, Lpm (gpm) 469 (124)
Heat rejected to cooling water at rated kW, dry exhaust, kW (Btu/min.) 231 (13148)
Heat rejected to air charge cooler at rated kW, dry exhaust, kW (Btu/min.) 122 (6944)
Water pump type Centrifugal
Fan diameter, including blades, mm (in.) 965 (38)
Fan, kWm (HP) 18 (24)
Max. restriction of cooling air, intake and discharge side of radiator, kPa (in. H2O) 0.125 (0.5)
* Enclosure with internal silencer reduces ambient temperature capability by 5�C (9�F).
Operation Requirements
Air Requirements
Radiator-cooled cooling air, m3/min. (scfm)� 651 (23000)
Cooling air required for generator set when equipped with city water cooling or remote radiator, based on 14�C (25�F) rise, m3/min. (cfm)� 312 (11004)
Combustion air, m3/min. (cfm) 34 (1201)
Heat rejected to ambient air:
Engine, kW (Btu/min.) 87 (4952)
Alternator, kW (Btu/min.) 40 (2277)
� Air density = 1.20 kg/m3 (0.075 lbm/ft3)
Fuel Consumption
Diesel, Lph (gph) at % load Standby Rating
100% 115.7 (30.6)
75% 83.8 (22.1)
50% 57.9 (15.3)
25% 31.9 (8.4)
Diesel, Lph (gph) at % load Prime Rating
100% 101.3 (26.8)
75% 75.1 (19.8)
50% 52.1 (13.8)
25% 29.6 (7.8)
Controllers
Decision-Maker� 3000 Controller Provides advanced control, system monitoring, and system diagnostics for optimum performance and compatibility.
� Digital display and menu control provide easy local data access � Measurements are selectable in metric or English units � Remote communication thru a PC via network or serial configuration � Controller supports Modbus� protocol � Integrated hybrid voltage regulator with ±0.5% regulation � Built-in alternator thermal overload protection � NFPA 110 Level 1 capability Refer to G6-100 for additional controller features and accessories.
Decision-Maker� 550 Controller Provides advanced control, system monitoring, and system diagnostics with remote monitoring capabilities.
� Digital display and keypad provide easy local data access � Measurements are selectable in metric or English units � Remote communication thru a PC via network or modem configuration � Controller supports Modbus� protocol � Integrated voltage regulator with ±0.25% regulation � Built-in alternator thermal overload protection � NFPA 110 Level 1 capability Refer to G6-46 for additional controller features and accessories.
Decision-Maker� 6000 Paralleling Controller Provides advanced control, system monitoring, and system diagnostics with remote monitoring capabilities for paralleling multiple generator sets.
� Paralleling capability with first-on logic, synchronizer, kW and kVAR load sharing, and protective relays � Digital display and keypad provide easy local data access � Measurements are selectable in metric or English units � Remote communication thru a PC via network or modem configuration � Controller supports Modbus� protocol � Integrated voltage regulator with ±0.25% regulation � Built-in alternator thermal overload protection � NFPA 110 Level 1 capability Refer to G6-107 for additional controller features and accessories.
� 2010, 2011, 2012 by Kohler Co. All rights reserved.
DISTRIBUTED BY:
Dimensions and Weights
NOTE: This drawing is provided for reference only and should not be used for planning installation. Contact your local distributor for more detailed information.
H
W L
Overall Size, L x W x H, max., mm (in.): 3630 x 1725 x 1993 (142.9 x 67.9 x 78.5)
Weight (radiator model), wet, max., kg (lb.): 3901 (8600)
G5-354 (400REOZJ) 5/12e
Standard Features � Alternator Protection
� Battery Rack and Cables
� Customer Connection (standard with Decision-Maker� 6000 controller only)
� Local Emergency Stop Switch
� Oil Drain Extension
� Operation and Installation Literature
Available Options Approvals and Listings
� California OSHPD Approval
� CSA Approval
� IBC Seismic Certification
� UL 2200 Listing
Enclosed Unit
� Sound Enclosure Level 1 and Subbase Fuel Tank Packages
� Sound Enclosure Level 2 and Subbase Fuel Tank Packages
� Weather Enclosure and Subbase Fuel Tank Packages
Open Unit
� Exhaust Silencer, Critical (kit: PA-354880)
� Flexible Exhaust Connector, Stainless Steel
Fuel System
� Flexible Fuel Lines (Select rubber or stainless steel)
Controller
� Common Failure Relay (Decision-Maker� 550 and 6000 controllers only)
� Communication Products and PC Software
� Customer Connection (Decision-Maker� 550 controller only)
� Decision-Maker� Paralleling System (DPS) (Decision-Maker� 6000 controller only)
� Dry Contact (isolated alarm) (Decision-Maker� 550 and 6000 controllers only)
� Input/Output Module (Decision-Maker� 3000 controller only)
� Remote Audiovisual Alarm Panel (Decision-Maker� 550 controller only)
� Remote Emergency Stop
� Remote Serial Annunciator Panel
� Run Relay
Cooling System
� Block Heater, 2500 W, 90--120 V, 1 Ph
� Block Heater, 2500 W, 190--208 V, 1 Ph
� Block Heater, 2500 W, 210--240 V, 1 Ph
� Block Heater, 2500 W, 380--480 V, 1 Ph [recommended for ambient temperatures below 0°C (32°F)]
� Radiator Duct Flange
Electrical System
� Alternator Strip Heater
� Battery
� Battery Charger, Equalize/Float Type
� Battery Heater
� Line Circuit Breaker (NEMA type 1 enclosure)
� Line Circuit Breaker with Shunt Trip (NEMA type 1 enclosure)
Paralleling System
� Manual Speed Adjust
� Voltage Sensing
Miscellaneous
� Air Cleaner, Heavy Duty
� Air Cleaner Restriction Indicator
� Crankcase Emissions Canister
� Engine Fluids Added
� Rated Power Factor Testing
Literature
� General Maintenance
� NFPA 110
� Overhaul
� Production
Warranty
� 2-Year Basic
� 5-Year Basic
� 5-Year Comprehensive
Other Options
KOHLER CO., Kohler, Wisconsin 53044 USA Phone 920-457-4441, Fax 920-459-1646 For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 KohlerPower.com
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455
Unmatched performance for critical power needs
Eaton’s automatic transfer switch is designed to provide unmatched performance, reliability and versatility for critical standby power applications. The switches can be equipped with the ATC-300+ or ATC-900 controllers to match your application needs. A bypass isolation transfer switch may be used to provide emergency power to life safety and other critical loads where maintenance of the main transfer switch, without interruption of power to the load, is either desirable or required.
Electrical ratings
• Operating temperature –20° to +70°C (–4° to +158°F)
• Ratings 100, 150, 200, 225, 260, 400, 600, 800, 1000, 1200 and 1600A
• Two-, three- or four-pole (fourth pole is fully rated)
• Up to 600 Vac, 50/60 Hz
• NEMA® 1, 3R, 12, 4X
• UL® 1008 Listed
• CSA� C22.2 No. 178 Certified
Industrial design highlights
• Standard front access on all ratings
• Entry:
• Top, bottom or both
• Isolated compartments
• Field-selectable multi-tap transformer panel permits operation on a wide range of system voltages
• Improved safety:
• Isolated compartments with barriers
• Single motion rack-out with doors closed
• Ability to test power-switching elements during drawout process
• Dual ATS capability—bypass contactor can be controlled by the ATS controller in the bypass mode of operation
• Installation flexibility:
• Field entry/exit locations can be modified in the field
• Interchangeable drawout contactors
Standard features
• Source available contacts
• S1/S2 present 2NO and 2NC
• Switch position contacts
• S1/S2 position 1NO and 1NC
• Source sensing S1 and S2
• Undervoltage/ underfrequency
• Overvoltage/overfrequency
• Three-phase rotation protection
• Three-phase voltage unbalance
• Pretransfer signal contacts
1NO/1NC
• Go to Source 2 (emergency)
• Field-programmable time delays
• Time delay engine start
• Time delay normal to emergency
• Time delay emergency to normal
• Time delay engine cool-down
• Time delay emergency fail
• LCD display for programming, system diagnostics and Help menu display
• Mimic diagram with source available, connected, and status LED indication
• Time-stamped history log
• System TEST pushbutton
• Programmable plant exerciser—off, daily, 7, 14, 28-day, selectable runtime, 0–600 minutes no load / load with fail safe
Optional features
• Available UL 1448 Third Edition surge protection device (SPD)
• Eaton IQ and Power Xpert� multifunction power quality metering
• Automatic transfer mode with selectable non-automatic/ automatic retransfer mode
• Modbus� RTU via RS-485
• Remote annunciation with control
• Open in-phase transition, time delay neutral or in-phase with a default to time delay neutral transfer
• ATC-900 Controller
• Includes Modbus RTU via RS-485
• Includes four programmable inputs/outputs
• Includes two plant exercisers
• Includes LCD color display with easy navigation tools to settings and event logs
• Expandable I/O (up to 20 I/O total)
• Optional integrated load metering
• Optional EtherNet TCP/IP communications
Drawout Bypass Isolation
Automatic transfer switches Contactor-based switches Dual drawout bypass isolation Open/closed transition
Bypass isolation switch features
Front access
Front access is a standard fea-ture. Source 1 (NORMAL) and Load connections are set up as standard top entry and Source 2 (EMERGENCY) connections as bottom entry. These connections are located in their own separate compartments. These connections can be relocated in the field if necessary.
Multi-tap transformer
The industry-exclusive multi-tap system voltage selector allows the transfer switch to be applied on most system voltages by proper insertion of the selector plug.
Dual drawout ATS and bypass contactor
The ATS and the bypass drawout power contactor designs are identical and interchangeable.
This standard feature allows the user the ability to withdraw, maintain or swap contactor assemblies, providing redundancy of ATS and bypass functions from one contactor assembly to the other of a similar frame size.
Improved safety
The unique Eaton design includes separation between control and power components.
The ATS and bypass isolation contactors are mounted in separate compartments with protective barriers between them. This design prevents the possibility of contact with the rear-mounted power connections to the contactors.
In addition, the top and bottom entries have separate compartment doors.
Ease of maintenance
Transfer to the bypass power contactor is easily initiated and controlled via door-mounted controls. After the transfer to the bypass contactor is complete, the ATS contactor is easily racked out with the compartment door closed.
The ATS contactor may then be tested in the racked-out position.
Ease of transfer
The Eaton design allows the operator to make a quick and simple transfer from the ATS power contactor to the bypass contactor by initiating the electrically operated transfer via a two-position switch.
Door-mounted indicating lights confirm that a successful transfer has taken place.
Dual ATS capability
The controller on conventional bypass isolation switches only controls the ATS contactor. The Eaton design allows the switch controller to remain active in both the ATS and the bypass modes, thus providing control to either contactor.
This ability of the controller to remain active and control the bypass isolation contactor provides ”N+1” redundancy of a second fully functioning ATS, a feature unique to Eaton.
Drawout ATS Contactor
Drawout Bypass Contactor Compartment
400A Dual Drawout
Source 1 (NORMAL), Source 2 (EMERGENCY) and Load Connection Located in Top Compartment Behind Removable Electrical Panel
Electrical Panels can be Removed for Installation for Top or Bottom Entry
Drawout ATS Contactor Completely Removed
Separate ATS Compartment and Door
Drawout Bypass Contactor with Separate Compartment Door—Shown Racked Out
Source 1
(NORMAL)
Connections
Load Connections
Source 2
(EMERGENCY)
Connections
Front Access for Top or Bottom Entry; Terminals Can be Relocated in the Field
Separate Doors for ATS and Bypass Compartments
Drawout Bypass Contactor
Multi-Tap Transformer with Quick Connect Plug
Drawout ATS Contactor Completely Removed
1200A Dual Drawout
2 EATON Automatic transfer switches
CG
Load Power Cable Connections
Normal Power Cable Connections
Emergency Power Cable Connections Neutral Cable Connections
B
A
C
Front View Side View (With Right Side Removed)
600–1600A 480V or 225–1200A 600V Dual Drawout Bypass NEMA 1
Bypass
ATS
Side View (With Left Side Removed)
Front View
100–400A 480V or 100–200A 600V Dual Drawout Bypass NEMA 1
BC
A
Emergency Power Cable Connections
Load Cable Connections
Normal Power Cable Connections
Electrical Panel Not Shown for Clarity otee:N Source 1 Normal and Load connections are top and Source 2 is bottom. These connections can be relocated in the field.
Contactor-Based Transfer Switch 100–1600A—NEMA 1 in Inches (mm) and Approximate Shipping Weight
Switch Rating Amperes/Volts B
Enclosure Seismic A Standard Terminals
A B C Normal, Emergency and Load Neutral
Metric Conversion (mm2) C
Weight Lbs (kg)
100–200A 480V D 100–200A 600V D
78.07 (1983.0)
78.07 (1983.0)
30.00 (762.0)
30.00 (762.0)
29.30 (744.2)
29.30 (744.2)
(1) #6–350 Cu/Al
(1) #6–350 Cu/Al
(3) #6–350 Cu/Al
(3) #6–350 Cu/Al
13–177 mm2 Cu/Al 13–177 mm2 Cu/Al
625 (283.8) 625 (283.8)
225–400A 480V D 225–400A 600V E
78.07 (1983.0)
90.00 (2286.0)
30.00 (762.0)
40.00 (1016.0)
29.30 (744.2)
28.97 (735.8)
(1) 3/0–600 Cu/Al
(2) 3/0–750 Cu/Al
(3) 3/0–600 Cu/Al
(6) 3/0–750 Cu/Al
85–304 mm2 Cu/Al 85–380 mm2 Cu/Al
625 (283.8) 1750 (794.5)
600A 480V E 600A 600V E
90.00 (2286.0)
90.00 (2286.0)
40.00 (1016.0)
40.00 (1016.0)
28.97 (735.8)
28.97 (735.8)
(2) 3/0–750 Cu/Al
(2) 3/0–750 Cu/Al
(6) 3/0–750 Cu/Al
(6) 3/0–750 Cu/Al
85–380 mm2 Cu/Al 85–380 mm2 Cu/Al
1750 (794.5) 1750 (794.5)
800–1200A 480V E 800–1200A 600V E
90.00 (2286.0)
90.00 (2286.0)
40.00 (1016.0)
40.00 (1016.0)
28.97 (735.8)
28.97 (735.8)
(4) 3/0–750 Cu/Al
(4) 3/0–750 Cu/Al
(12) 3/0–750 Cu/Al
(12) 3/0–750 Cu/Al
85–380 mm2 Cu/Al 85–380 mm2 Cu/Al
1850 (839.9) 1850 (839.9)
1600A 480V E 90.00 (2286.0) 40.00 (1016.0) 40.00 (1016.0) (5) 1/0–750 Cu/Al (16) 1/0–750 Cu/Al 85–380 mm2 Cu/Al 2200 (997.9)
A For seismic applications, it is necessary to use 5–13 UNC Grade or better hex head bolts and washers torqued to 50 lbs-ft.
B NEMA 12 and 4X dimensions are 90.00 inches H x 46.00 inches W x 38.00 inches D (2286.0 mm H x 1168.4 mm W x 965.2 mm D). NEMA 4X enclosures are 304SS standard with an optional upgrade to 316SS.
C Same number of terminals per phase will be supplied.
D For NEMA 3R dimensions, add 18.29 inches (464.6 mm).
E For NEMA 3R dimensions, add 18.59 inches (472.2 mm).
3EATON Automatic transfer switches
Eaton is a registered trademark.
All other trademarks are property of their respective owners.
Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com
© 2014 Eaton All Rights Reserved Printed in USA Publication No. PA01602013E / Z14365 February 2014
Automatic Bypass Isolation Contactor-Based Transfer Switch Catalog Numbering System
BI C 3 C3 E 3 1200 W S U
Logic
3 = ATC-300+
9 = ATC-900 Mounting
E = Drawout Number of Poles
2 = Two-pole 3 = Three-pole 4 = Four-pole
Amperes
0100 = 100A 0150 = 150A 0200 = 200A 0224 = 225A 0260 = 260A 0400 = 400A 0600 = 600A 0800 = 800A 1000 = 1000A 1200 = 1200A 1600 = 1600A
Voltage
B = 208V, 60 Hz E = 600V, 60 Hz G = 220V, 50 Hz H = 380V, 50 Hz K = 600V, 50 Hz O = 415V, 50 Hz W = 240V, 60 Hz X = 480V, 60 Hz
Enclosure
S = NEMA 1
R = NEMA 3R
J = NEMA 12
D = NEMA 4X
Certification
U = UL 1008 Listed
Mechanism
C3 = Time delay neutral (TDN) only C5 = In-phase/TDN transfer
Switch
C = Contactor
Type
BI = Bypass isolation open transition CB = Bypass isolation closed transition
ATC Features
Features ATC-300+ ATC-900
Basic transfer control, time delays, programmable set points and plant exerciser
Standard Standard
LCD display Standard Color Time stamped history and event log Standard Standard Transfer control for manual retransfer and Source 2 inhibit
Optional Standard
RS-485 communications Optional Standard Ethernet communication Optional Optional USB port — Standard Diagnostic event summary and details with pre/post event data capture
— Standard
Preferred source — Standard Built-in configurable I/O with optional ability to expand up to 20 I/O
— Standard
Integrated load metering — Optional Load management with selective load shed — Optional Three-source ATS—master/slave control — Optional
UL 1008 Withstand and Close-On Ratings (kA)
UL
Rating (A)
480 Volts 600 Volts Rating When Used with Upstream Fuse
Any Breaker
Specific Breaker
Any Breaker
Specific Breaker Rating
Test Voltage
Fuse Type
Max.
Fuse Amps
100 30 50 22 35 200 600 RK5 600
150 30 50 22 35 200 600 RK5 600
200 30 50 22 35 200 600 RK5 600
225 30 50 42 65 200 600 RK5 600
260 30 50 42 65 200 600 RK5 600
400 30 50 42 65 200 600 RK5 600
600 50 65 42 65 200 600 L 1200 800 50 65 42 65 200 600 L 1200 1000 50 65 42 65 200 600 L 1600 1200 50 65 42 65 200 600 L 1600 1600 50 65 N/A N/A 200 480 — —
Bypass Isolation Diagram
Load
Bypass
ATS
(3) (4)
(1) (2)
Source 1
(NORMAL)
Available
Shown as Normal Operation
Source 2
(EMERGENCY)
Available
Bypass Source 1
(NORMAL)
ATS
Source 1
(NORMAL)
ATS
Source 2
(EMERGENCY)
Bypass Source 2
(EMERGENCY)
ATS
Locked In
Door Open
ATS Isolated (Flashing:
ATS Removed)
Dual Drawout otee:N 1600A is rated for 480V and below.
Square D Low Voltage Switchboards A tradition of distinction, with a mission to innovate solutions for tomorrow
TM
A Tradition of Distinction Square D Low Voltage Custom Switchboards
Square D™ Switchboards set the standard for the system solutions of today and those of tomorrow by delivering on higher expectations and standards! Square D Switchboards have been setting the standards for electrical distribution systems due to their trusted durable construction and continuous innovative progression that keeps Square D one step ahead of all others. This progression includes integrating power metering and communications capabilities providing direct access to energy management at main and feeder level. This allows for flexibility in developing simple or complex monitoring solutions, as well as future expansion. Square D Low Voltage Custom Switchboards are designed to distribute electrical power and provide a reduced footprint without compromising performance or versatility.
Innovative but Familiar The Quick Connect capability allows for a simple and seamless connection when installing. Even though Square D Switchboards continue to become more innovative, the quality and familiarity of the equipment leads the industry.
A Solid Foundation Square D Switchboard ratings offer a robust solution through 5,000 A and 200 kA. Higher feeder ampacities are available with individually mounted branch devices up to 4,000 A.
Network Communications PowerPact™ circuit breakers with higher functionality, such as energy and power quality metering capabilities, are integrated in the more advanced trip units. Combined with quality PowerPact communication accessories, Micrologic™ trip units also enable circuit breakers to be networked and remotely controlled, leading to substantial savings in electrical system operating costs. Square D Switchboards comply with the requirements explained in the 2014 National Electric Code Section 240.87.
Efficient Distribution The I-Line™ distribution section is unique — and popular — for its enhanced safety and ease of installation.
The I-Line offers jaw-type connections which provide a firmer, more secure grip on the bus bar under high-level fault conditions for improved uptime. Distribution sections are available in single or double row construction allowing an increased power density in a compact footprint.
Designed with the Customer in Mind Square D Switchboards allow for custom engineering for each line-up such as Main-Tie-Mains, Automatic Transfers, Commercial Multi-Metering, and reduced height configurations.
Industry Leading Compact Footprint Square D Switchboards were designed with the customer in mind. They provide front accessibility that aids in reducing footprint as well as provides convenient access for maintenance.
2 3
A Mission of Innovative Solutions Accelerated Engineering Standard Switchboards
To better meet our customer’s tight schedules, our Square D Standard Switchboard is available with Accelerated Engineering, which brings together standard designs for the most frequently requested ratings and options. With Accelerated Engineered Switchboards, on-demand approval drawings and an auto release of the equipment will allow you to stay competitive by simplifying the order process and offering a reduction in ship time. This means the customer will receive their switchboard 2 weeks faster. This allows for a quicker project turnaround for all parties involved, providing a competitive advantage in the industry.
Enclosure Options Switchboard enclosures are available as Indoor NEMA Type 1 or Outdoor NEMA Type 3R construction.
On-Demand Robust Solution Accelerated Engineering Standard Switchboards provide expedited manufacturing and delivery time without sacrificing the robustness of the solution needed. The maximum rating for these standard switchboards is through 4000 A and 100 kAIC.
Faster Project Turnaround Accelerated Engineering Standard Switchboards offer a more responsive, faster and more flexible solution.
On-demand factory approval drawings
Auto release of Equipment to manufacturing
Select designs with premier 4-week lead time
24/7 services support
Customer-focused order process
Customizable options available
Unrestricted Branch Mounting The unique design of the I-Line single or double row distribution section allows branch circuit breakers the flexibility to mount a 15 A circuit breaker next to a 1,200 A circuit breaker. This presents the opportunity for more effective use of space.
A screwdriver is the only tool you need to install these breakers, which saves valuable installation time.
Metering Down to 15 Amps PowerPact™ with Micrologic trip units offer the capability to meter energy down to 15 A. Standard trip units provide convenient, local data access through a high visibility front display.
Standard Solution without the Compromise
Surge Protection
Internally mounted Surgelogic™ surge protective devices in mains section or I-Line interior.
Metering Options
PowerLogic™ Power Meters are available to monitor at main or feeder level.
4 5
This section supplements Section 26.24.13 10 — Low Voltage Switchboards, unless otherwise noted.
Comply with requirements as follows:
Standards UL 50 Enclosures for Electrical Equipment
UL 98 Enclosed and Deadfront Switches
UL 489 Molded Case Circuit Breakers
UL 891 Deadfront Switchboards
UL 977 Fused Power Circuit Devices
UL 943 Ground Fault Circuit Interrupters
UL 1053 Ground Fault Sensing and Relaying Equipment
NEC Article 834 Switchboards
NFPA 70 National Electrical Code® (NEC®)
ANSI/IEEE C12.1 Code for Electricity Metering
ANSI C39.1 Electrical Analog Indicating Instruments
ANSI C57.13 Instrument Transformers
NEMA AB 1 Molded Case Circuit Breakers and Molded Case Switches
NEMA PB 2 Switchboards
Switchboard Electrical Ratings:
a. Nominal AC System Voltage: [600 Vac] [480 Vac] [240 Vac] [208 Vac]
b. Maximum Design Voltage: 635 Vac
c. Maximum Short-Circuit Current: 100 kAIR (@ 635 Vac)
Switchboard General Construction:
a. Indoor NEMA 1 Enclosure or Outdoor NEMA 3R Enclosure
b. Fixed or drawout breakers
c. Removable Rear Cover Panels Secured with Captive Screws [Hinged Doors]
Introduce Quality into Your Electrical Room
Whether it is a highly customizable switchboard or an expedited switchboard needed.
Your requirements and expectations will not only be met but exceeded with Square D Low Voltage Switchboards.
Schneider Electric USA
800 Federal Street Andover, MA 01810 Tel: (978) 794-0800 www.schneider-electric.com/us
Document Number 2742BR1401 October 2014
S ch ne id er E le ct ric . A ll R ig ht s R es er ve d.
S ch ne id er E le ct ric , S q ua re D
, P ow er Lo gi c, S ur ge lo gi c, P ow er P ac t w ith M ic ro lo gi c ar e tr ad em ar ks ow ne d by S ch ne id er
E le ct ric
In d us tr ie s
S A
S o r its a ff ili at ed c om p an ie s.
A ll ot he r tr ad em ar ks a re p ro p er ty o f t he ir re sp ec tiv e ow ne rs
For assistance or more information:
Ask your authorized Schneider Electric Distributor
Call at 888-SQUARED (888-778-2733)
Visit www.schneider-electric.com/us
Innovative design, smart bus technology, and simple installation
I-Line Panelboards
I-Line Breakers
Main Lugs: Fixed-mounted main lugs are isolated from the branch breaker section for enhanced safety. Lugs are front-removable for ease of wiring.
Plug-on main lugs mount in the branch circuit area.
Main Breakers: A screwdriver is all that’s required, making installation faster and easier. Main lug interiors may be converted to main breaker interiors by simply back feeding a branch-mounted device.
All I-Line™ circuit breakers are UL® Listed for use as a branch or back feed main device.
Branch Breakers: I-Line breakers mount independently of other breakers on the interior.
This design offers greater flexibility in breaker placement and future scalability. The modular I-Line panelboard permits branches to be mounted anywhere on the bus stack without restriction unlike a conventional panelboard design.
Breaker Connections
I-Line breaker connections are “blow-on” type, similar to medium voltage equipment designs.
The magnetic forces developed from high-level fault conditions force the jaws together, resulting in a firmer, more secure grip on the bus bar for improving uptime. Heavy-duty jaw connectors are plated to ensure good conductivity at the contact.
Breaker Mounting
A screwdriver is all that’s needed to mount 15 A through 1,200 A I-Line circuit breakers.
Breakers ratchet firmly onto the bus stack.
Captive retaining screws secure the circuit breaker to the mounting pan.
Smart: designed for efficient installation
The Square D™ I-Line panelboards are the most versatile and innovative on the market, offering the unique I-Line Plug-In Connection, with efficient installation design and outstanding communication capabilities.
Simple: Efficient Installation Process
Delivery that Works for You I-Line panelboards are available custom assembled at the factory or ready to install from local distributor stock. Either way, you get the same time-proven design in a complete line of boxes, interiors, fronts, breakers, and accessories on hand when you need them.
For even faster service, the LASER Quick Shipment program delivers on-site in three, five, or 10 days
Available with main lugs or main breakers through 1,200 A
Rated 600 Vac and 250 Vdc maximum
UL Listed SCCR, suitable for use on systems up to 200,000 RMS symmetrical amps, when assembled with appropriately rated main or branch breakers
Cabinets
Panelboard boxes are constructed of code gauge steel with wiring gutters in accordance with UL and NEMA® standards. Boxes are made of galvanized steel in varying widths to fit your electrical needs. All box sizes have removable end walls.
I-Line panelboard fronts are finished with gray baked enamel electrodeposited over clean phosphatized steel. Fronts are attached to the box with trim screws.
Solid Neutral The solid neutral assembly mounts at the same end of the interior as the main lugs or main breaker or to the side for panels requiring ground fault. Branch neutral connections are provided for a wide variety of breaker combinations and suitable for copper or aluminum wires. The solid neutral is insulated but can be bonded to the enclosure with a full-capacity bonding strap for service entrance requirements.
Accessories A wide variety of accessories are available for field or factory installation into I-Line panelboards.
Equipment ground bars are available for termination of equipment grounding conductors.
Specifically designed QO™ distribution panels mount in I-Line panelboards the same as branch circuit breakers. This allows less expensive QO 15-through-30-ampere breakers to be installed to feed lighting or receptacle circuits from I-Line panelboards applied on 240 V systems.
UL Listed box extensions provide additional end gutter when additional wire bending space is desired.
Blank fillers and extensions are required to fill unused circuit breaker mounting space in I-Line panelboards and switchboards. Specially engineered blank fillers are used with PowerPact™ with Micrologic™ breakers to ensure easy visibility for metered data on the LCD screen.
Smart: built-in communication capabilities
Interface Modules The top I-Line box extension holds Modbus communication interface modules (IFMs). The IFM is the only accessory required for connecting to the network. It contains the Modbus address and automatically adapts to the Modbus network in which it is installed.
Communications Side Car This 14-inch box extension gives the I-Line panelboard power metering and communications capabilities, when equipped with PowerPact with Micrologic molded case circuit breakers. The front display modules mounted to the front of the side car provide local access to detailed metering information. The solid neutral mounts inside the side car along with communications equipment for ease of customer access. The innovative structure also stores supporting communication accessories including power supplies and insulation modules.
PowerPact with Micrologic I-Line Breakers PowerPact with Micrologic breakers provide a smart, safe, and simple solution to the I-Line HCP, HCP-SU, and HCRU interior configurations. These circuit breakers are available as a main breaker or branch breaker in Standard, Ammeter, and Energy electronic trip options.
While seamlessly integrating into the Schneider Electric™ energy management solutions, PowerPact with Micrologic molded case circuit breakers in I-Line construction provide integrated metering with both local and remote communication options.
With a choice among thermal-magnetic circuit breakers, standard and advanced electronic trip unit circuit breakers, select the PowerPact with Micrologic circuit breakers that are right for the job.
Thermal-magnetic molded case circuit breakers
Most common design; automatically opens circuit when it’s overloaded or short-circuited
Uses bimetals and electromagnetic assemblies to provide protection
Ideal for applications where overload conditions are concern because the instantaneous trip allow it to interrupt with no intentional delay
Standard electronic trip circuit breakers Provide long-time, short-time, and instantaneous trip protection
Current transformers sense current and trip units evaluate current to trip the solenoid to trip the breaker
Allow the user to easily adjust settings of the circuit breaker per specific system requirements
Advanced electronic trip circuit breakers Add communications and power metering and monitoring capabilities
Trip units allow the circuit breaker to communicate with other circuit breakers, gather power information, monitor events, and provide predictive maintenance information, to help reduce electrical operating costs
I-Line circuit breakers — the heart of any panelboard
For more information, contact your authorized distributor, visit www.schneider-electric.com/us, or call 1-888-SQUARED.
Document Number 2100BR1301
Schneider Electric USA, Inc.
1415 S. Roselle Road Palatine, IL 60067 Tel: 847-397-2600 Fax: 847-925-7500 www.schneider-electric.com/us
May 2013
S ch ne id er
E le ct ric
. A ll
R ig ht s
R es er ve d.
S ch ne id er
E le ct ric
, S q ua re
D , I
-L in e, Q
O , P ow er
P ac t, M ic ro lo gi c, a nd T he g lo b al s p ec ia lis t i n en er gy m an ag em en t a re tr ad em ar ks o w ne d by S ch ne id er
E le ct ric
In d us tr ie s
S A
S o r its a ff ili at ed c om p an ie s.
A ll ot he r tr ad em ar ks a re p ro p er ty o f t he ir re sp ec tiv e ow ne rs
. 9
-1
_U S
The Square D brand is an integral part of the Schneider Electric portfolio. As the global specialist in energy management, we deliver proven reliability, expertise, and comprehensive solutions.
Developed with extensive input from electrical contractors, Square D™ NQ and NF Lighting Panelboards cover a wide range of electrical lighting and distribution applications.
Square D NQ (240 Vac) and NF Lighting Panelboards (480Y/277 Vac or 600Y/347 Vac) are available in Type 1 (with standard or hinged trim), 3R, 4, 4X, 5, and 12 enclosures.
Simple to Install Square D Lighting Panelboards are designed for optimum space and labor savings. Semi-assembled, ready-to-install (RTI) kits with simple, clear installation instructions, save time on-site. There is also a broad range of field-installable, RTI kits, to address last-minute changes on-site. NQ panelboards also accept QO™ plug-on and QOB bolt-on circuit breakers.
Available When You Need It Square D Lighting Panelboards are available from distributor stock as RTI or “quick ship” factory assembled by our Laser product delivery program with three-, five- and 10-day service. Both NQ and NF Lighting Panelboards can be fitted with field-installable accessories like sub-feed lugs, feed-through lugs, sub-feed circuit breakers, and 200 percent neutrals.
Built to Last Ranked #1 in brand preference and appreciated by contractors for long-lasting quality.
Square D NQ and NF Lighting Panelboards Simple to install, convenient availability, and built to last
NQ Lighting Panelboards 240 Vac Maximum
Available Interiors
3P4W and 1P3W available
100 A, 225 A, 400 A, and 600 A interiors
18, 30, 42, 54, 72, and 84 circuits
Main breaker or main lugs
10,000 A, 22,000 A, and 65,000 A fully rated branches at 208Y/120 Vac
Series ratings to 200,000 A and 208Y/120 Vac
Available Enclosures
Types
Type 1 (Indoor)
Type 2 (Driphood)
Type 3R (Outdoor, rain and sleet protection)
Type 4/4X (Stainless, corrosion protection)
Type 5 (Settling dust and dripping liquids protection)
Type 12 (Circulating dust and dripping liquids protection)
Trims
Surface and flush non-vented Mono-Flat™ trims for 250 A and below
Surface and flush screwed-to-box vented for 400 A and above
Hinged trim available; meets door-in-door specs
Separate trim not required for Type 3R, 4, 4X, 5, and 12 enclosures
NQ panelboards meet 240 Vac applications and accept both the QO plug-on and QOB bolt-on circuit breakers.
Available Options
Copper bussing, copper lugs, copper neutrals
Copper and aluminum, mechanical and crimp lugs
Rail and dead front extension kits provide space only for future addition of ready-to-install kits (extensions of 6", 12", and 18" available)
Increased side gutters 3", 6", and 12"
Split bus
Contactors
Equipment space
Locks (most common brands)
In-line surge suppression
Sub-feed lugs*
Sub-feed breakers*
Feed-through lugs*
200% neutrals*
* Field-installable
NF Lighting Panelboards 600Y/347 Vac Maximum
Available Interiors
3P4W and 1P3W available
125 A, 250 A, 400 A, 600 A, and 800 A interiors
18, 30, 42, 54, 66, and 84 circuits
Main breaker (600 A) or main lug (800 A)
Fully rated branches:
— 480Y/277 Vac: 18,000 A, 35,000 A, and 65,000 A
— 600Y/347 Vac: 14,000 A, 18,000 A, and 35,000 A
Series Ratings
480Y/277 Vac: 200,000 A maximum
600Y/347 Vac: 200,000 A maximum
Available Enclosures
Types
Type 1 (Indoor)
Type 2 (Driphood)
Type 3R (Outdoor, rain and sleet protection)
Type 4/4X (Stainless, corrosion protection)
Type 5 (Settling dust and dripping liquids protection)
Type 12 (Circulating dust and dripping liquids protection)
Trims
Surface and flush non-vented Mono-Flat trims for 250 A and below
Surface and flush screwed-to-box vented for 400 A and above
Hinged trim available; meets door-in-door specs
Separate trim not required for Type 3R, 4, 4X, 5, and 12 enclosures
NF panelboards offer application flexibility for commercial and industrial electrical systems up to 600Y/347 Vac.
Available Options Copper bussing, copper lugs, copper neutrals
Copper and aluminum, mechanical and crimp lugs
Rail and dead front extension kits provide space only for future addition of ready-to-install kits (extensions of 6", 12", and 18" available)
Increased side gutters 3", 6", and 12"
Split bus
Contactors
Equipment space
Locks (most common brands)
In-line surge suppression
Sub-feed lugs*
Sub-feed breakers*
Feed-through lugs*
200% neutrals*
* Field-installable
S ch ne id er E le ct ric . A ll R ig ht s R es er ve d.
S ch ne id er E le ct ric , M on o-
Fl at
, S qu ar e
D , Q
O , P ow er
P ac t, an d M ic ro lo gi c ar e tr ad em ar ks o w ne d by S ch ne id er
E le ct ric
In du st rie s S
A S o r its a ffi lia te d co m pa ni es
-1
Schneider Electric USA, Inc.
1415 S. Roselle Road Palatine, IL 60067 Tel: 847-397-2600 Fax: 847-925-7500 www.schneider-electric.com/us
Document Number 1670HO0701R04/13
The Square D brand is an integral part of the Schneider Electric portfolio.
As the global specialist in energy management, we deliver proven reliability, expertise, and comprehensive solutions.
Ask your authorized distributor for more information, visit www.schneider-electric.com/us, or call 888-SQUARED.
NQ and NF lighting panelboards support PowerPact™ with Micrologic™ Circuit Breakers in H-Frame, J-Frame, and L-Frame sizes with LI or LSI settings. The standard trip units allow faster and more accurate recognition of faults at the main breaker and sub-feed breaker levels.
The J-Frame and L-Frame breakers can be configured as mission-critical circuit protection for hospitals, data centers, and anywhere continuity of service is desired. PowerPact Mission Critical Circuit Breakers provide D, G, J, and L interrupt ratings up to 480Y/277 Vac.
Full integration of PowerPact with Micrologic Circuit Breakers
• UL 1449 3rd Edition for Type 1 and Type 2 SPD applications
• Innovative Z-Path SystemTM ensures equal current sharing, increased reliability and maximum performance
• Individually fused MOVs provide superior protection and continuous operation
• 200kAIC short circuit current rating allows direct bus connection without the need of an upstream over-current protection device
• Includes UL 1283 standard EMI/RFI filter
• All modes of protection (L-N, L-G, N-G & L-L)
• Standard monitoring includes Form “C” contacts and audible alarm with silence button
• DTS-2 compatible for proactive testing
• Ultra compact steel NEMA 4 enclosure makes installation flexible
• 10-Year standard product warranty
Product SPecificationS
100 CurrentGuardTM kA Rating (Must Choose One)
040 40kA per mode 060 60kA per mode 080 80kA per mode 100 100kA per mode 120 120kA per mode 150 150kA per mode 200 200kA per mode
Voltage (Must Choose One)
220-1G 220V, 1-Phase, 2-Wire + Ground 230-1G 230V, 1-Phase, 2-Wire + Ground 240-1G 240V, 1-Phase, 2-Wire + Ground 120/240-2G 120/240V, 2-Phase, 3-Wire + Ground 120/208-3GY 120/208V, 3-Phase Wye, 4-Wire + Ground 220/380-3GY 220/380V, 3-Phase Wye, 4-Wire + Ground 230/400-3GY 230/400V, 3-Phase Wye, 4-Wire + Ground 277/480-3GY 277/480V, 3-Phase Wye, 4-Wire + Ground 347/600-3GY 347/600V, 3-Phase Wye, 4-Wire + Ground 120/240-3GHD 120/240V, 3-Phase High-Leg Delta, 4-Wire + Ground (B-Phase must be 208V) 240-3DG 240V, 3-Phase Delta, 3-Wire + Ground 380-3DG 380V, 3-Phase Delta, 3-Wire + Ground 480-3DG 480V, 3-Phase Delta, 3-Wire + Ground 600-3DG 600V, 3-Phase Delta, 3-Wire + Ground
Available Option
S Stainless Steel Enclosure Leave blank for Standard Enclosure
Stand-Alone Option (To Be Ordered As Separate Items) DTS DTS-2 Diagnostic Test Set
SyStem featureS
General Specifications Maximum Surge Current Rating 100kA per mode, 200kA per phase Nominal Discharge Surge Current I-n = 20kA Safety Listings Listed by UL to UL 1449 3rd Edition
(2009 Revision) for Type 1 and Type 2 SPD applications, cUL, and UL 1283 / Meets Requirements for UL 96A / Compliant to IEEE C62.41.1-2002, C62.41.2-2002 and C62.45-2002 / NFPA 70 [NEC], Article 285 / RoHS Compliant / CE, IEC 61643-11-2011 / EMC Directive 2004/108/EC / Low Voltage Directive 2006/95/EC
Repetitive Surge Current Rating 4,500 impulses per mode based on actual test data (using ANSI/IEEE C62.41.1-2002 C3 combo wave)
Product Design Hybrid parallel design;
Individually fused MOVs UL 1283 EMI/RFI Filter
Application ANSI/IEEE C62.41.1 Locations C, B & A Ideal for Low Exposure Service Entrance, Distribution Panels, Motor Control Centers and Branch Panels
Standard Monitoring Status indicator lights (one per phase) Service indicator light Form C contacts (NO/NC) Audible alarm with silence button Fault Current (SCCR) 200kAIC – no upstream over-current protection device (breaker or fuse) required Connection Method Parallel Protection Modes All Modes (L-N, L-G, N-G, L-L) Response Time < 0.5 Nanoseconds Operating Frequency 47 – 63 Hz Warranty 10 Year
EMI / RFI Filter Attenuation – Mil Standard 220B Up to 33 dB from 10 KHz to 100 MHz
C G — 1 0 0 — 2 7 7 / 4 8 0 - 3 G Y — S
M od el kA R at in g
Vo lta ge
Op tio n
E.g.: CG-100-277/480-3GY (as shown in above photo) model number Scheme
CG
S u r g e P r O T e C T I O N currentguard 100 Performance data
052714
© 2014, Thomas & Betts Power Solutions, LLC. • Thomas & Betts Power Solutions, LLC., is a wholly owned subsidiary of Thomas & Betts Corporation.
Current Technology® is a registered trademark of Thomas & Betts International, Inc. • Specifications are subject to change without notice. • Visit our website for latest revisions.
Thomas & Betts Power Solutions 5900 Eastport Blvd. • Richmond, VA 23231-4453 USA
Tel: (804) 236-3300 • Toll free: (800) 238-5000 • Fax: (804) 236-4841 tnbpowersolutions.com/current_technology
All CurrentGuardTM systems measured limited voltages are peak values (±10%) measured from the zero reference point and are in compliance with test and evaluation procedures outlined in NEMA LS1-1992 (R2000), paragraphs 2.210 and 3.10.
Specifications subject to change without notice, refer to www.currenttechnology.com for latest revision.
System Voltage 220V 230V 240V
120/240V 120/208V
220/380V 230/400V 277/480V
347/600V 120/240V 240V 380V 480V 600V
Protection Mode L-N L-G N-G L-N L-G L-L N-G L-N L-G L-L N-G L-N L-G L-L N-G L-N H-N L-G H-G L-L H-L N-G L-G L-L L-G L-L L-G L-L
MCOV 320 320 320 150 150 300 150 320 320 640 320 420 420 840 420 150 320 150 320 300 470 150 320 320 550 550 750 750
B3 Ring Wave 6kV, 500A
660 750 720 420 480 610 340 660 750 960 720 715 829 1130 670 420 759 470 640 605 800 320 750 630 1050 860 1245 1060
B3/C1 Combo Wave 6kV, 3kA
910 1068 974 642 690 1010 620 910 1068 1700 974 1250 1340 2300 1230 642 910 690 1068 1010 1400 620 940 1020 1450 1670 1960 2260
C3 Combo Wave 20kV, 10kA
1490 1830 1690 1040 1300 1420 1240 1490 1830 2290 1690 1910 1960 2910 1880 1040 1490 1300 1830 1420 2050 1240 1650 1680 2160 2470 2760 2950
UL1449 3rdEdition 6kV, 3000A
VPR
1200 1200 1200 800 800 1200 800 1200 1200 1800 1200 1500 1500 2500 1500 800 1200 800 1200 1200 1500 800 1200 1200 1800 1800 2500 2500
CG10
0-
0/2
-2
G
CG10
0-
0/2
-3
GY
CG10
0-
0/3
-3
GY
CG10
0-
0-
1G
CG10
0-
0/4
-3
GY
CG10
0-
0-
1G
CG10
0-
7/4
-3
GY
CG10
0-
0-
1G
CG10
0-
7/6
-3
GY
CG10
0-
0/2
-3
GHD
CG10
0-
0-
3G D
CG10
0-
0-
3G D
CG10
0-
0-
3G D
CG10
0-
0-
3G D
Model Number
Enclosure Type Powder coated, impact-resistant steel, weather-proof NEMA 4
Installation Location Indoor or outdoor
Dimensions 14"H x 12.75"W x 6.3"D
Connection Method Hard-wired via internal lugs #10AWG –
#3 AWG
Mounting Method Dual mounting flanges
Operating Environment -40° F to +158° F (-40° C to +70° C) 5% – 95% non-condensing humidity
Weight 40 lbs.
CG100 Inches (mm) H1 14.00 (355.6) H2 14.75 (374.7) H3 15.50 (393.7) W1 12.75 (323.9) W2 10.75 (273.1) D 6.30 (160.0) mechanical SPecificationS dimenSional SPecificationS
GE
Critical Power
Introduction
GE’s Zenith ZBTS Series Bypass-Isolation Transfer Switch consists of two major modules – the automatic transfer and the bypass-isolation switches.
This is the start of the file's text. The full file is on GovTribe.