Amend_0001_McAllen_Specs_Appendix-B_part-3.pdf
PDF 15 MB Posted
- Attached to
- McAllen CPC RENOVATION Federal contract opportunity
- Solicitation number
- W9126G-15-B-0029
About this file
AMENDMENT 0001 - APPENDIX B - PART 3
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| C1_BID_ABSTRACT_W9126G-15-B-0029.pdf | ||
| B3_AMENDMENT_0005.pdf | ||
| B3_AMENDMENT_0004.pdf | ||
| B3_AMENDMENT__0003.pdf | ||
| B3_Amendment_0002_.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-B_part-1.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-B_part-2.pdf | ||
| Amendment_0001_B_CLIN_Changes.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-B_part-5.pdf | ||
| Amendment_0001.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-C_thru_G.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-B_part-4.pdf | ||
| McAllen_22K_CPC_Warehouse_FINAL_design_Drawings.pdf | ||
| W9126G-15-B-0029-Specs.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DUCTED
“Accessories” on page 204 “Factory Supplied Parts & Materials” on page 205 “High Static Units” on page 207 “Low Static Convertible Units” on page 259 “Low Static Bottom Return Units” on page 285 “Vertical/Horizontal Air Handling Units” on page 315
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.204 | DUCTED
M U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
ACCESSORIES
Accessory Model Number
Return Air Grille1 PBSGB30 (B3 Chassis) PBSGB40 (B4 Chassis)
Return Air Canvas1 PBSC30 (B3 Chassis) PBSC40 (B4 Chassis)
1For use with Ducted (Low Static Bottom Return) units.
All accessories are sold separately.
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. DUCTED | 205
D ucted
Part Quantity Image
Hanging Bracket Washer 8
Clamp (Tie Wrap) 4
Conduit Mounting Plate1 1
Part Quantity Image
Clamp Metal 1
Drain Hose 1
Fitting Insulation 1 Set
Factory Supplied Materials
• Owner’s Manual
• Installation Manual
Factory Supplied Parts
Gas
Liquid
FACTORY SUPPLIED PARTS & MATERIALS
1Not included with Ducted (Low Static Bottom Return) units.
No factory supplied parts provided for Vertical/Horizontal Air Handling Units.
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.206 | DUCTED
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
(HIGH STATIC)
“Mechanical Specifications” on page 208 “General Data” on page 210 “Dimensions” on page 215 “Performance Data” on page 219 “External Static Pressure & Air Flow” on page 233 “External Static Pressure Range” on page 234 “Electrical & Acoustic Data” on page 236 “Piping Diagrams” on page 240 “Wiring Diagrams” on page 242 “Installation & Best Layout Practices” on page 250
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.208 | DUCTED (HIGH STATIC)
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l Casing The case is designed to mount concealed above a finished ceiling.
Fan supply air is front horizontal with a dedicated rear horizontal return. The unit is manufactured with coated metal. Cold surfaces are covered with a coated polystyrene insulating material. The cold surface areas of the case are covered externally with sheet insulation made of Ethylene Propylene Diene Monomer (M-Class) (EPDM) conforming to ASTM Standard D-1418. The case is provided with hanger brackets designed to support the unit weight on four corners. Hanger brackets have pre-punched holes designed to accept field supplied, allthread rod hangers.
Fan Assembly and Control The unit has Sirocco fans made of high strength ABS GP-2200 polymeric resin. Fans are directly driven and mounted on a common shaft. The fan motor is a Brushless Digitally-Controlled (BLDC) design with permanently lubricated and sealed ball bearings. The fan/motor assembly is mounted on vibration attenuating rubber grommets. The fan speed is controlled using a microprocessor based, direct digital control algorithm that provides a minimum of three pre-programmed fan speeds. Fan settings are high, medium, and low. Each setting can be field adjusted from the factory setting (RPM/ESP) to compensate for a limited amount of additional resistance to airflow caused by field connected ductwork or other airflow restricting devices.
Air Filter Return air is filtered with a removable, washable filter. MERV 13 filter modules with plenums available.
Microprocessor Controls The unit is provided with an integrated microprocessor-based controller. The controller is capable of performing functions necessary to operate the system without the use of a wall-mounted controller. A temperature thermistor is factory-mounted in the return air stream. All unit operation parameters, excluding the unit operating schedule, are stored in non-volatile memory resident on the unit microprocessor. Operating schedules are stored in select models of the optional, wall-mounted, local, or central controller. The field supplied communication cable between the indoor unit(s) and outdoor unit is to be a minimum of 18 AWG, 2-conductor, stranded, and shielded cable (RS485), terminated via screw terminals on the control boards. The microprocessor control provides the following functions: self-diagnostics, auto restart following power restoration, test run, and will operate the indoor unit using one of five operating modes:
1. Auto Changeover (Heat Recovery only)
2. Heating
3. Cooling
4. Dry
5. Fan Only For Heat Recovery systems the Auto Changeover setting automatically switches control of the indoor unit between cooling and heating modes based on space temperature conditions.
For Heat Pump systems, heated or cooled air delivery is dependant upon outdoor unit operating mode.
In Heating mode, the microprocessor control will activate the indoor unit when indoor room temperature falls below setpoint temperature and signals the outdoor unit to begin heating cycle. The indoor unit fan operation is delayed until coil pipe temperature reaches 76ºF.
Significant airflow is generated when pipe temperature reaches 80°F.
In lieu of factory return air thermistor,pluggable connection sockets on the microprocessor circuit board accommodate various models of wall-mounted local controllers and/or a wall-mounted remote temperature sensor. The unit microprocessor is capable of accepting space temperature readings concurrently or individually from either:
1. Wall-mounted wired controller(s)
2. Factory mounted return air thermistor or the optional wall-mounted wired remote temperature sensor A single indoor unit has the capability of being controlled by up to two local wired controllers. The microprocessor controls space temperature using the value provided by the temperature sensor sensing a space temperature that is farthest away from the temperature set-point. If the system is provided with an optional wall-mounted local or central controller, displayed diagnostic codes are specific, alpha numeric, and provide the service technician with a reason for the code displayed.
Condensate Lift/Pump The indoor unit is provided with a factory installed and wired condensate lift/pump capable of providing a minimum 27.5 inch lift from the bottom exterior surface of the unit casing. The unit drain
MECHANICAL SPECIFICATIONS
Ducted (High Static) BH, BG, BR, B8 Chassis
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. DUCTED (HIGH STATIC) | 209 ucted (H igh Static)
MECHANICAL SPECIFICATIONS
pan is provided with a secondary drain port/plug allowing the pan to be drained for service. The lift pump comes with a safety switch that will shut off indoor unit if condensate rises too high in the drain pan.
Standard Features
• Limited Warranty with LG Certified Installation
• Two Year Functional Parts Warranty
Controls Features
• Auto changeover (Heat Recovery only)
• Auto operation
• Auto restart
• Child lock
• Dual themistor control
• Group control
• E.S.P. control
• Hot start
• Self diagnostics
• Sleep mode
• Timer (on/off)
• Weekly schedule
• Soft dry (dehumidification)
• Fan speed control
• Ventilation (outside air)
Ducted (High Static)
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.210 | DUCTED (HIGH STATIC)
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
Type Ducted (High Static)
ARNU073BHA2 ARNU093BHA2 ARNU123BHA2
Cooling Mode Performance Capacity (Btu/h) 7,500 9,600 12,300 Power Input1 (W) 150 150 150
Heating Mode Performance Capacity (Btu/h) 8,500 10,900 13,600 Power Input1 (W) 150 150 150
Entering Mixed Air Cooling Max (°F WB) 76 76 76 Heating Min (°F DB) 59 59 59
Unit Data Refrigerant Type2 R410A R410A R410A Refrigerant Control EEV EEV EEV Sound Pressure3 dB(A) (H/M/L) 34/33/32 35/34/33 37/35/34 Net Unit Weight (lbs) 58 58 58 Shipping Weight (lbs) 68 68 68 Communication Cable4 (No. x AWG) 2 x 18 2 x 18 2 x 18
Fan Type Sirocco Sirocco Sirocco Motor 1 1 1 Housing 2 2 2
Motor/Drive Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Airflow Rate H/M/L (CFM) High Mode (factory set) 300/265/212 353/300/265 424/353/300
External Static Pressure (in wg) High Mode (factory set) 0.31 0.31 0.31
Airflow Rate H/M/L (CFM) Standard Mode 300/282/265 300/282/265 388/300/265
External Static Pressure (in wg) Standard Mode 0.23 0.23 0.23
Piping Liquid Line (in, OD) 1/4 Flare 1/4 Flare 1/4 Flare Vapor Line (in, OD) 1/2 Flare 1/2 Flare 1/2 Flare Condensate Line (in, ID) 1 1 1
Table 105: Ducted (High Static) Unit General Data
Ducted (High Static) Unit Specifi cations
GENERAL DATA
ARNU073BHA2, ARNU093BHA2, ARNU123BHA2
EEV: Electronic Expansion Valve Power wiring is fi eld supplied and must comply with the applicable local and national codes.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1Power Input is rated at high speed.
2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply with applicable and national code.
Power Supply (V/Hz/Ø): 208-230/60/1
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. DUCTED (HIGH STATIC) | 211 ucted (H igh Static)
Table 106: Ducted (High Static) Unit General Data
ARNU153BHA2, ARNU183BHA2, ARNU243BHA2
GENERAL DATA
Type Ducted (High Static)
ARNU153BHA2 ARNU183BHA2 ARNU243BHA2
Cooling Mode Performance Capacity (Btu/h) 15,400 19,100 24,200 Power Input1 (W) 150 150 150
Heating Mode Performance Capacity (Btu/h) 17,100 21,500 27,300 Power Input1 (W) 150 150 150
Entering Mixed Air Cooling Max (°F WB) 76 76 76 Heating Min (°F DB) 59 59 59
Unit Data Refrigerant Type2 R410A R410A R410A Refrigerant Control EEV EEV EEV Sound Pressure3 dB(A) (H/M/L) 39/37/34 40/38/37 42/40/39 Net Unit Weight (lbs) 58 59 59 Shipping Weight (lbs) 64 64 64 Communication Cable4 (No. x AWG) 2 x 18 2 x 18 2 x 18
Fan Type Sirocco Sirocco Sirocco Motor 1 1 1 Housing 2 2 2
Motor/Drive Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Airflow Rate H/M/L (CFM) High Mode (factory set) 477/424/300 547/477/438 646/597/547
External Static Pressure (in wg) High Mode (factory set) 0.31 0.31 0.31
Airflow Rate H/M/L (CFM) Standard Mode 477/424/388 540/480/364 671/579/512
External Static Pressure (in wg) Standard Mode 0.23 0.23 0.23
Piping Liquid Line (in, OD) 1/4 Flare 1/4 Flare 3/8 Flare Vapor Line (in, OD) 1/2 Flare 1/2 Flare 5/8 Flare Condensate Line (in, ID) 1 1 1
Ducted (High Static) Unit Specifi cations
EEV: Electronic Expansion Valve Power wiring is fi eld supplied and must comply with the applicable local and national codes.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1Power Input is rated at high speed.
2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.212 | DUCTED (HIGH STATIC)
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
Table 107: Ducted (High Static) Unit General Data
ARNU153BGA2, ARNU183BGA2, ARNU243BGA2
GENERAL DATA
Type Ducted (High Static)
ARNU153BGA2 ARNU183BGA2 ARNU243BGA2
Cooling Mode Performance Capacity (Btu/h) 15,400 19,100 24,200 Power Input1 (W) 450 450 450
Heating Mode Performance Capacity (Btu/h) 17,100 21,500 27,300 Power Input1 (W) 450 450 450
Entering Mixed Air Cooling Max (°F WB) 76 76 76 Heating Min (°F DB) 59 59 59
Unit Data Refrigerant Type2 R410A R410A R410A Refrigerant Control EEV EEV EEV Sound Pressure3 dB(A) (H/M/L) 37/36/33 41/39/37 42/39/37 Net Unit Weight (lbs) 84 84 84 Shipping Weight (lbs) 95 95 95 Communication Cable4 (No. x AWG) 2 x 18 2 x 18 2 x 18
Fan Type Sirocco Sirocco Sirocco Motor 2 2 2 Housing 2 2 2
Motor/Drive Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Airflow Rate H/M/L (CFM) High Mode (factory set) 487/417/293 537/487/417 671/537/487
External Static Pressure (in wg) High Mode (factory set) 0.31 0.31 0.31
Airflow Rate H/M/L (CFM) Standard Mode 477/427/318 547/470/427 671/576/547
External Static Pressure (in wg) Standard Mode 0.23 0.23 0.23
Piping Liquid Line (in, OD) 3/8 Flare 3/8 Flare 3/8 Flare Vapor Line (in, OD) 5/8 Flare 5/8 Flare 5/8 Flare Condensate Line (in, ID) 1 1 1
Ducted (High Static) Unit Specifi cations
EEV: Electronic Expansion Valve Power wiring is fi eld supplied and must comply with the applicable local and national codes.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1Power Input is rated at high speed.
2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. DUCTED (HIGH STATIC) | 213 ucted (H igh Static)
Table 108: Ducted (High Static) Unit General Data
ARNU283BGA2, ARNU363BGA2, ARNU423BGA2
GENERAL DATA
Type Ducted (High Static)
ARNU283BGA2 ARNU363BGA2 ARNU423BGA2
Cooling Mode Performance Capacity (Btu/h) 28,000 36,200 42,000 Power Input1 (W) 450 450 450
Heating Mode Performance Capacity (Btu/h) 31,500 40,600 43,800 Power Input1 (W) 450 450 450
Entering Mixed Air Cooling Max (°F WB) 76 76 76 Heating Min (°F DB) 59 59 59
Unit Data Refrigerant Type2 R410A R410A R410A Refrigerant Control EEV EEV EEV Sound Pressure3 dB(A) (H/M/L) 42/41/40 44/43/42 45/44/44 Net Unit Weight (lbs) 84 84 84 Shipping Weight (lbs) 95 95 95 Communication Cable4 (No. x AWG) 2 x 18 2 x 18 2 x 18
Fan Type Sirocco Sirocco Sirocco Motor 2 2 2 Housing 2 2 2
Motor/Drive Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Airflow Rate H/M/L (CFM) High Mode (factory set) 915/851/770 1,141/1,024/894 1,218/1,141/1,084
External Static Pressure (in wg) High Mode (factory set) 0.39 0.39 0.39
Airflow Rate H/M/L (CFM) Standard Mode 893/770/622 1,003/894/770 1,130/1,003/961
External Static Pressure (in wg) Standard Mode 0.31 0.31 0.31
Piping Liquid Line (in, OD) 3/8 Flare 3/8 Flare 3/8 Flare Vapor Line (in, OD) 5/8 Flare 5/8 Flare 5/8 Flare Condensate Line (in, ID) 1 1 1
Ducted (High Static) Unit Specifi cations
EEV: Electronic Expansion Valve Power wiring is fi eld supplied and must comply with the applicable local and national codes.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1Power Input is rated at high speed.
2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.214 | DUCTED (HIGH STATIC)
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
Table 109: Ducted (High Static) Unit General Data
ARNU483BRA2, ARNU763B8A2, ARNU963B8A2
GENERAL DATA
Type Ducted (High Static)
ARNU483BRA2 ARNU763B8A2 ARNU963B8A2
Cooling Mode Performance Capacity (Btu/h) 48,100 76,400 95,900 Power Input1 (W) 450 800 800
Heating Mode Performance Capacity (Btu/h) 51,200 86,000 107,500 Power Input1 (W) 450 800 800
Entering Mixed Air Cooling Max (°F WB) 76 76 76 Heating Min (°F DB) 59 59 59
Unit Data Refrigerant Type2 R410A R410A R410A Refrigerant Control EEV EEV EEV Sound Pressure3 dB(A) (H/M/L) 44/42/41 50/48/48 52/50/50 Net Unit Weight (lbs) 117 192 192 Shipping Weight (lbs) 128 212 212 Communication Cable4 (No. x AWG) 2 x 18 2 x 18 2 x 18
Fan Type Sirocco Sirocco Sirocco Motor 2 2 2 Housing 2 2 2
Motor/Drive Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Airflow Rate H/M/L (CFM) High Mode (factory set) 1,582/1,434/1,176 2,119/1,766/1,766 2,542/2,260/2,260
External Static Pressure (in wg) High Mode (factory set) 0.55 0.86 0.86
Airflow Rate H/M/L (CFM) Standard Mode 1,568/1,395/1,183 2,260/1,766/1,766 2,684/2,260/2,260
External Static Pressure (in wg) Standard Mode 0.39 0.59 0.59
Piping Liquid Line (in, OD) 3/8 Flare 3/8 Flare 3/8 Flare Vapor Line (in, OD) 5/8 Flare 3/4 Flare 7/8 Flare Condensate Line (in, ID) 1 1 1
Ducted (High Static) Unit Specifi cations
EEV: Electronic Expansion Valve Power wiring is fi eld supplied and must comply with the applicable local and national codes.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1Power Input is rated at high speed.
2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. DUCTED (HIGH STATIC) | 215 ucted (H igh Static)
BH Chassis
DIMENSIONS
Supply Air
L9
L7 L8
M5L16 L17
L18
L11 L13 L14
M4 M2
Airflow
R eturn Air
O pening
Supply Air O pening
WDHL1L2L3L4L5L6L7L8L9
L10
L11
L12
L13
L14
L15
L16
L17
L18
L19
L20
L21
L22
L23
L24
L25*
M
M
M
M
M
M
6XYZ
W iring Entry
W iring Entry
1/2" D iam eter O pening
M6
C ondensate
Pum p D rain
Vapor Line
Liquid Line
L1 L2
L3 L4
M
M
X
L23
Y
L10
Z
L19 L20
L21 L22
H Top
Bottom
Top
W
D
Top
G ravity D rain (plugged)
L12
L15
L25
L24
Filter C lips
Airflow
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.216 | DUCTED (HIGH STATIC)
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
DIMENSIONS
BG Chassis
Supply Air
L9
L7 L8
M5L16 L17
L18
L11 L13 L14
M4 M2
Airflow
R eturn Air
O penin g
Supply Air O pening
WDHL1L2L3L4L5L6L7L8L9
L10
L11
L12
L13
L14
L15
L16
L17
L18
L19
L20
L21
L22
L23
L24
L25*
M
M
M
M
M
M
6XYZ
W iring Entry
W iring Entry
1/2" D iam eter O pening
M6
C ondensate
Pum p D rain
Vapor Line
Liquid Line
L1 L2
L3 L4
M
M
X
L23
Y
L10
Z
L19 L20
L21 L22
H Top
Bottom
Top
W
D
Top
G ravity D rain (plugged)
L12
L15
L25
L24
Filter C
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. DUCTED (HIGH STATIC) | 217 ucted (H igh Static)
BR Chassis
DIMENSIONS
Supply Air
L9
L7 L8
M5L16 L17
L18
L11 L13 L14
M4 M2
Airflow
R eturn Air
O pening
Supply Air O pening
WDHL1L2L3L4L5L6L7L8L9
L10
L11
L12
L13
L14
L15
L16
L17
L18
L19
L20
L21
L22
L23
L24
L25*
M
M
M
M
M
M
6XYZ
W iring Entry
W iring Entry
1/2" D iam eter O pening
M6
C ondensate
Pum p D rain
Vapor Line
Liquid Line
L1 L2 L3
L4
M
M
X
L23
Y L10
Z
L19 L20
L21 L22
H
Top
Bottom
Top
W
D
Top
G ravity D rain (plugged)
L12
L15
L25
L24
Filter C
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.218 | DUCTED (HIGH STATIC)
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
DIMENSIONS
B8 Chassis
S upply A ir
L9
L7 L8
M5L16 L17
L18
L11 L13 L14
M4 M2
A irflow
R eturn A ir
O pening
S upply A ir O pening
WDHL1L2L3L4L5L6L7L8L9
L10
L11
L12
L13
L14
L15
L16
L17
L18
L19
L20
L21
L22
L23
L24
L25
M
M
M
M
M
M
6XYZ
W iring E ntry
W iring E ntry
1/2" D iam eter O pening
M6
C ondensate
P um p D rain
V apor Line
Liquid Line
L1 L2
L3 L4
M
M
X
L23
Y
L10
Z
L19 L20
L21 L22
H
Top
B ottom
Top
W
D
Top
G ravity D rain (plugged)
L12
L15
L25
L24
Filter C lips
A irflow
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. DUCTED (HIGH STATIC) | 219 ucted (H igh Static)
Cooling Capacity
PERFORMANCE DATA
ARNU073BHA2, ARNU093BHA2
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 25 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 30 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 35 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 40 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 45 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 50 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 55 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.7 5.8 60 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.6 5.8 65 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.5 5.7 70 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.3 5.6 75 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.9 5.8 9.1 5.5 80 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.4 5.9 8.7 5.8 8.9 5.5 85 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.3 5.8 8.4 5.5 8.6 5.2 90 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.2 5.7 8.3 5.5 8.4 5.2 95 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 8.0 5.7 8.2 5.4 8.3 5.1 100 5.0 4.2 6.0 4.8 6.8 5.2 7.5 5.5 7.9 5.6 8.0 5.4 8.2 5.1 105 5.0 4.2 5.7 4.6 6.5 4.9 7.2 5.3 7.4 5.3 7.7 5.2 7.9 5.0 110 4.8 4.1 5.4 4.3 6.0 4.6 6.8 4.9 6.9 4.9 7.4 4.9 7.7 4.8
Table 110: ARNU073BHA2 Cooling Capacities
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4 25 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4 30 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4 35 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4 40 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4 45 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4 50 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.4 55 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.4 7.5 60 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.3 7.4 65 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 12.1 7.3 70 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 11.9 7.2 75 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.4 7.5 11.6 7.0 80 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.8 7.5 11.1 7.4 11.3 7.0 85 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.7 7.5 10.8 7.1 10.9 6.7 90 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.5 7.3 10.6 7.0 10.8 6.6 95 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.3 7.3 10.5 6.9 10.7 6.6 100 6.3 5.4 7.7 6.2 8.6 6.6 9.6 7.0 10.1 7.2 10.3 6.9 10.5 6.5 105 6.3 5.4 7.3 5.9 8.3 6.3 9.2 6.7 9.4 6.7 9.9 6.6 10.1 6.3 110 6.1 5.2 6.9 5.6 7.7 5.9 8.6 6.3 8.8 6.3 9.4 6.3 9.8 6.2
Table 111: ARNU093BHA2 Cooling Capacities
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.220 | DUCTED (HIGH STATIC)
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
PERFORMANCE DATA
Cooling Capacity
ARNU123BHA2, ARNU153BHA2
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5 25 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5 30 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5 35 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5 40 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5 45 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5 50 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.5 55 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.9 9.6 60 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.7 9.5 65 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.5 9.4 70 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 15.3 9.2 75 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.6 9.6 14.9 9.0 80 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.8 9.6 14.3 9.5 14.5 9.0 85 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.7 9.6 13.8 9.1 14.0 8.6 90 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.4 9.4 13.5 8.9 13.8 8.5 95 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 13.2 9.3 13.4 8.9 13.7 8.4
100 8.1 6.9 9.8 7.9 11.1 8.5 12.3 9.0 12.9 9.2 13.2 8.8 13.4 8.3 105 8.1 6.9 9.3 7.5 10.6 8.1 11.8 8.6 12.1 8.6 12.7 8.5 12.9 8.1 110 7.9 6.7 8.9 7.1 9.8 7.5 11.1 8.1 11.3 8.1 12.1 8.1 12.5 7.9
Table 112: ARNU123BHA2 Cooling Capacities
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 11.9 25 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 11.9 30 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 11.9 35 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 11.9 40 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 11.9 45 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 11.9 50 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 11.9 55 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.9 12.0 60 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.7 11.9 65 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.4 11.7 70 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 19.1 11.5 75 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 18.3 12.0 18.6 11.3 80 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.2 12.1 17.9 11.9 18.2 11.2 85 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 17.1 12.0 17.2 11.4 17.6 10.8 90 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 16.8 11.7 16.9 11.2 17.2 10.6 95 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 16.5 11.7 16.8 11.1 17.1 10.5
100 10.2 8.6 12.3 9.9 13.9 10.6 15.4 11.2 16.2 11.5 16.5 11.0 16.8 10.4 105 10.2 8.6 11.7 9.4 13.2 10.1 14.8 10.8 15.1 10.8 15.9 10.7 16.2 10.2 110 9.9 8.4 11.1 8.9 12.3 9.4 13.9 10.1 14.2 10.1 15.1 10.1 15.7 9.9
Table 113: ARNU153BHA2 Cooling Capacities
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. DUCTED (HIGH STATIC) | 221 ucted (H igh Static)
Cooling Capacity
PERFORMANCE DATA
ARNU183BHA2, ARNU243BHA2
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 21.4 15.0 22.7 14.9 24.6 14.8 25 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 21.4 15.0 22.7 14.9 24.6 14.8 30 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 21.4 15.0 22.7 14.9 24.6 14.8 35 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 21.4 15.0 22.7 14.9 24.6 14.8 40 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 21.4 15.0 22.7 14.9 24.6 14.8 45 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 21.4 15.0 22.7 14.9 24.6 14.8 50 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 21.4 15.0 22.7 14.9 24.6 14.8 55 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 21.4 15.0 22.7 14.9 24.6 14.8 60 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 21.4 15.0 22.7 14.9 24.4 14.7 65 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 21.4 15.0 22.7 14.9 24.1 14.5 70 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 21.4 15.0 22.7 14.9 23.7 14.3 75 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 21.4 15.0 22.7 14.9 23.1 14.0 80 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 21.4 15.0 22.2 14.8 22.5 13.9 85 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 21.2 14.8 21.4 14.1 21.8 13.4 90 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 20.8 14.6 21.0 13.9 21.4 13.2 95 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 20.4 14.5 20.8 13.8 21.2 13.1 100 12.6 10.7 15.3 12.3 17.2 13.1 19.1 13.9 20.1 14.3 20.4 13.7 20.8 12.9 105 12.6 10.7 14.5 11.7 16.4 12.6 18.3 13.4 18.7 13.4 19.7 13.2 20.1 12.6 110 12.2 10.4 13.8 11.1 15.3 11.7 17.2 12.5 17.6 12.6 18.7 12.6 19.5 12.3
Table 114: ARNU183BHA2 Cooling Capacities
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 27.1 19.0 28.8 18.8 31.2 18.8 25 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 27.1 19.0 28.8 18.8 31.2 18.8 30 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 27.1 19.0 28.8 18.8 31.2 18.8 35 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 27.1 19.0 28.8 18.8 31.2 18.8 40 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 27.1 19.0 28.8 18.8 31.2 18.8 45 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 27.1 19.0 28.8 18.8 31.2 18.8 50 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 27.1 19.0 28.8 18.8 31.2 18.8 55 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 27.1 19.0 28.8 18.8 31.2 18.8 60 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 27.1 19.0 28.8 18.8 31.0 18.7 65 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 27.1 19.0 28.8 18.8 30.5 18.4 70 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 27.1 19.0 28.8 18.8 30.0 18.1 75 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 27.1 19.0 28.8 18.8 29.3 17.7 80 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 27.1 19.0 28.1 18.7 28.6 17.6 85 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 26.9 18.8 27.1 17.9 27.6 16.9 90 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 26.4 18.5 26.6 17.6 27.1 16.7 95 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 25.9 18.4 26.4 17.5 26.9 16.6 100 16.0 13.6 19.4 15.6 21.8 16.6 24.2 17.7 25.4 18.1 25.9 17.3 26.4 16.4 105 16.0 13.6 18.4 14.8 20.8 15.9 23.2 17.0 23.7 16.9 24.9 16.7 25.4 16.0 110 15.5 13.2 17.4 14.0 19.4 14.8 21.8 15.9 22.3 15.9 23.7 15.9 24.7 15.5
Table 115: ARNU243BHA2 Cooling Capacities
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.222 | DUCTED (HIGH STATIC)
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6 25 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6 30 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6 35 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6 40 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6 45 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6 50 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6 55 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.9 13.6 60 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.7 13.5 65 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.4 13.3 70 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 19.1 13.1 75 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 18.4 13.6 18.6 12.8 80 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.3 13.7 17.8 13.5 18.2 12.7 85 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 17.1 13.6 17.3 12.9 17.6 12.2 90 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 16.8 13.4 16.9 12.7 17.3 12.1 95 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 16.5 13.3 16.8 12.6 17.1 11.9
100 10.1 9.8 12.3 11.3 13.9 12.0 15.4 12.8 16.2 13.1 16.5 12.5 16.8 11.8 105 10.1 9.8 11.7 10.7 13.2 11.5 14.8 12.2 15.1 12.2 15.8 12.1 16.2 11.6 110 9.9 9.5 11.1 10.1 12.3 10.7 13.9 11.5 14.2 11.5 15.1 11.5 15.7 11.2
Table 116: ARNU153BGA2 Cooling Capacities
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8 25 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8 30 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8 35 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8 40 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8 45 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8 50 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8 55 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.7 15.8 60 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.4 15.7 65 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 24.0 15.5 70 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 23.7 15.2 75 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.8 15.8 23.1 14.9 80 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.4 16.0 22.1 15.7 22.5 14.8 85 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 21.2 15.8 21.4 15.1 21.8 14.2 90 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 20.9 15.6 21.0 14.8 21.4 14.1 95 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 20.5 15.5 20.9 14.7 21.2 13.9
100 12.6 11.4 15.3 13.1 17.2 14.0 19.1 14.9 20.1 15.2 20.5 14.6 20.9 13.8 105 12.6 11.4 14.5 12.5 16.4 13.4 18.3 14.2 18.7 14.2 19.7 14.1 20.1 13.5 110 12.3 11.0 13.8 11.8 15.3 12.5 17.2 13.4 17.6 13.4 18.7 13.4 19.5 13.1
Table 117: ARNU183BGA2 Cooling Capacities
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
PERFORMANCE DATA
Cooling Capacity
ARNU153BGA2, ARNU183BGA2
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. DUCTED (HIGH STATIC) | 223 ucted (H igh Static)
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0 25 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0 30 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0 35 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0 40 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0 45 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0 50 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0 55 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.3 20.0 60 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 31.0 19.9 65 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 30.5 19.6 70 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 30.0 19.3 75 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.8 20.0 29.2 18.9 80 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 27.1 20.3 28.0 19.9 28.5 18.8 85 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 26.8 20.0 27.1 19.1 27.6 18.0 90 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 26.4 19.7 26.6 18.8 27.1 17.8 95 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 25.9 19.6 26.4 18.7 26.8 17.6
100 15.9 14.4 19.4 16.6 21.8 17.7 24.2 18.9 25.4 19.3 25.9 18.5 26.4 17.5 105 15.9 14.4 18.4 15.8 20.8 17.0 23.2 18.0 23.7 18.0 24.9 17.8 25.4 17.1 110 15.5 14.0 17.4 15.0 19.4 15.8 21.8 17.0 22.3 17.0 23.7 17.0 24.7 16.5
Table 118: ARNU243BGA2 Cooling Capacities
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0 25 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0 30 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0 35 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0 40 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0 45 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0 50 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0 55 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 36.1 22.0 60 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 35.8 21.9 65 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 35.3 21.6 70 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 34.7 21.2 75 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 33.3 22.1 33.9 20.8 80 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.4 22.2 32.5 21.9 33.0 20.7 85 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 31.1 22.1 31.4 21.0 31.9 19.9 90 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 30.5 21.7 30.8 20.6 31.4 19.6 95 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 30.0 21.5 30.5 20.5 31.1 19.4 100 18.5 15.9 22.4 18.3 25.2 19.5 28.0 20.7 29.4 21.2 30.0 20.3 30.5 19.2 105 18.5 15.9 21.3 17.4 24.1 18.7 26.9 19.9 27.4 19.9 28.8 19.6 29.4 18.8 110 17.9 15.4 20.2 16.5 22.4 17.4 25.2 18.6 25.8 18.7 27.4 18.7 28.6 18.2
Table 119: ARNU283BGA2 Cooling Capacities
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Cooling Capacity
PERFORMANCE DATA
ARNU243BGA2, ARNU283BGA2
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.224 | DUCTED (HIGH STATIC)
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
PERFORMANCE DATA
Cooling Capacity
ARNU363BGA2, ARNU423BGA2
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5 25 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5 30 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5 35 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5 40 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5 45 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5 50 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5 55 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.7 28.5 60 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 46.3 28.3 65 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 45.6 27.9 70 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 44.9 27.5 75 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 43.1 28.5 43.8 26.8 80 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.5 28.8 42.0 28.4 42.7 26.7 85 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 40.2 28.5 40.5 27.1 41.3 25.7 90 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 39.5 28.0 39.8 26.7 40.5 25.3 95 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 38.7 27.9 39.5 26.5 40.2 25.1 100 23.9 20.6 29.0 23.6 32.6 25.2 36.2 26.8 38.0 27.4 38.7 26.3 39.5 24.9 105 23.9 20.6 27.5 22.5 31.1 24.1 34.8 25.7 35.5 25.7 37.3 25.4 38.0 24.3 110 23.2 19.9 26.1 21.3 29.0 22.4 32.6 24.1 33.3 24.1 35.5 24.1 36.9 23.6
Table 120: ARNU363BGA2 Cooling Capacities
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0 25 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0 30 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0 35 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0 40 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0 45 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0 50 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.0 55 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 54.2 33.1 60 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 53.8 32.9 65 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 52.9 32.4 70 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 52.1 31.9 75 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 50.0 33.1 50.8 31.1 80 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 47.0 33.4 48.7 32.9 49.6 31.0 85 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 46.6 33.1 47.0 31.4 47.9 29.8 90 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 45.8 32.5 46.2 31.0 47.0 29.3 95 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 44.9 32.3 45.8 30.8 46.6 29.1 100 27.7 23.9 33.6 27.4 37.8 29.3 42.0 31.1 44.1 31.8 44.9 30.5 45.8 28.8 105 27.7 23.9 31.9 26.0 36.1 28.0 40.3 29.8 41.2 29.8 43.3 29.4 44.1 28.2 110 26.9 23.1 30.2 24.7 33.6 26.0 37.8 28.0 38.6 28.0 41.2 28.0 42.8 27.4
Table 121: ARNU423BGA2 Cooling Capacities
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. DUCTED (HIGH STATIC) | 225 ucted (H igh Static)
Cooling Capacity
PERFORMANCE DATA
ARNU483BRA2
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.3 25 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.3 30 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.3 35 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.3 40 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.3 45 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.3 50 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.3 55 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 62.0 38.4 60 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 61.6 38.1 65 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 60.6 37.6 70 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 59.6 37.0 75 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 57.2 38.4 58.2 36.1 80 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.9 38.7 55.8 38.2 56.8 36.0 85 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 53.4 38.4 53.9 36.5 54.8 34.6 90 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 52.4 37.7 52.9 35.9 53.9 34.0 95 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 51.5 37.5 52.4 35.7 53.4 33.8
100 31.7 27.7 38.5 31.8 43.3 34.0 48.1 36.1 50.5 36.9 51.5 35.4 52.4 33.5 105 31.7 27.7 36.6 30.2 41.4 32.5 46.2 34.6 47.1 34.6 49.5 34.2 50.5 32.7 110 30.8 26.9 34.6 28.6 38.5 30.2 43.3 32.5 44.3 32.5 47.1 32.5 49.1 31.8
Table 122: ARNU483BRA2 Cooling Capacities
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.226 | DUCTED (HIGH STATIC)
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
PERFORMANCE DATA
Cooling Capacity
ARNU763B8A2, ARNU963B8A2
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.3 25 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.3 30 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.3 35 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.3 40 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.3 45 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.3 50 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.3 55 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 123.7 71.4 60 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 122.8 71.0 65 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 120.8 69.9 70 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 118.9 68.8 75 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 114.1 71.5 116.0 67.2 80 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 107.4 72.1 111.2 71.1 113.2 67.0 85 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 106.4 71.4 107.4 67.9 109.3 64.4 90 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 104.5 70.2 105.5 66.9 107.4 63.3 95 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 102.6 69.8 104.5 66.5 106.4 62.9 100 63.3 51.5 76.7 59.2 86.3 63.3 95.9 67.1 100.7 68.8 102.6 65.9 104.5 62.3 105 63.3 51.5 72.9 56.3 82.5 60.4 92.1 64.4 94.0 64.4 98.8 63.6 100.7 60.8 110 61.4 50.0 69.0 53.3 76.7 56.2 86.3 60.4 88.2 60.5 94.0 60.5 97.8 59.1
Table 123: ARNU763B8A2 Cooling Capacities
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Table 124: ARNU963B8A2 Cooling Capacities
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.8 25 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.8 30 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.8 35 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.8 40 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.8 45 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.8 50 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.8 55 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 98.6 56.9 60 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 97.8 56.5 65 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 96.3 55.7 70 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 94.7 54.8 75 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 90.9 57.0 92.4 53.6 80 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 85.6 57.4 88.6 56.6 90.2 53.3 85 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 84.8 56.9 85.6 54.1 87.1 51.3 90 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 83.3 55.9 84.0 53.3 85.6 50.5 95 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 81.7 55.6 83.3 52.9 84.8 50.1
100 50.4 41.1 61.1 47.2 68.8 50.4 76.4 53.5 80.2 54.8 81.7 52.5 83.3 49.6 105 50.4 41.1 58.1 44.8 65.7 48.1 73.3 51.3 74.9 51.3 78.7 50.7 80.2 48.5 110 48.9 39.8 55.0 42.5 61.1 44.8 68.8 48.1 70.3 48.2 74.9 48.2 77.9 47.1
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. DUCTED (HIGH STATIC) | 227 ucted (H igh Static)
Heating Capacity
PERFORMANCE DATA
ARNU073BHA2, ARNU093BHA2, ARNU123BHA2
Table 125: ARNU073BHA2 Heating Capacities Outdoor Air Temp. (°F) Indoor Air Temperature (°F DB)
59 61 64 67 70 73 76 80
DB WB TC TC TC TC TC TC TC TC
MBh MBh MBh MBh MBh MBh MBh MBh -4 -4.4 5.7 5.7 5.7 5.7 5.6 5.6 5.6 5.6 0 -0.4 5.9 5.9 5.9 5.9 5.9 5.8 5.8 5.8
5.0 4.5 6.6 6.5 6.5 6.5 6.5 6.5 6.5 6.5
10.0 9.0 6.9 6.9 6.9 6.8 6.8 6.8 6.8 6.8
15.0 14.0 7.3 7.3 7.3 7.3 7.3 7.3 7.2 7.1
20.0 19.0 7.7 7.7 7.7 7.7 7.5 7.5 7.4 7.3
25.0 23.0 8.1 8.1 8.1 8.1 8.1 7.9 7.8 7.7
30.0 28.0 8.2 8.2 8.2 8.2 8.2 8.1 7.8 7.6
35.0 32.0 8.5 8.5 8.5 8.5 8.4 8.2 7.8 7.4
40.0 36.0 8.8 8.8 8.8 8.8 8.5 8.2 7.8 7.4
45.0 41.0 9.2 9.2 9.2 8.9 8.5 8.2 7.8 7.4
47.0 43.0 9.5 9.4 9.4 8.9 8.5 8.2 7.8 7.4
50.0 46.0 10.2 9.8 9.4 8.9 8.5 8.2 7.8 7.4
55.0 51.0 10.4 9.9 9.4 8.9 8.5 8.2 7.8 7.4
60.0 56.0 10.4 9.9 9.4 8.9 8.5 8.2 7.8 7.4
Outdoor Air Temp. (°F) Indoor Air Temperature (°F DB) 59 61 64 67 70 73 76 80
DB WB TC TC TC TC TC TC TC TC
MBh MBh MBh MBh MBh MBh MBh MBh
-4 -4.4 7.3 7.3 7.3 7.3 7.2 7.2 7.2 7.2 0 -0.4 7.5 7.5 7.5 7.5 7.5 7.4 7.4 7.4
5.0 4.5 8.5 8.4 8.3 8.3 8.3 8.3 8.3 8.3
10.0 9.0 8.8 8.8 8.8 8.7 8.7 8.7 8.7 8.7
15.0 14.0 9.4 9.4 9.4 9.4 9.4 9.4 9.3 9.2
20.0 19.0 9.9 9.9 9.9 9.9 9.7 9.7 9.5 9.4
25.0 23.0 10.4 10.4 10.4 10.4 10.4 10.1 10.0 9.9
30.0 28.0 10.6 10.6 10.6 10.6 10.6 10.4 10.0 9.7
35.0 32.0 10.9 10.9 10.9 10.9 10.8 10.6 10.0 9.5
40.0 36.0 11.3 11.3 11.3 11.3 10.9 10.6 10.0 9.5
45.0 41.0 11.8 11.8 11.8 11.4…