Amend_0001_McAllen_Specs_Appendix-B_part-2.pdf
PDF 14 MB Posted
- Attached to
- McAllen CPC RENOVATION Federal contract opportunity
- Solicitation number
- W9126G-15-B-0029
About this file
AMENDMENT 0001 - APPENDIX B - PART 2
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| C1_BID_ABSTRACT_W9126G-15-B-0029.pdf | ||
| B3_AMENDMENT_0005.pdf | ||
| B3_AMENDMENT_0004.pdf | ||
| B3_AMENDMENT__0003.pdf | ||
| B3_Amendment_0002_.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-B_part-1.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-C_thru_G.pdf | ||
| Amendment_0001_B_CLIN_Changes.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-B_part-5.pdf | ||
| Amendment_0001.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-B_part-3.pdf | ||
| Amend_0001_McAllen_Specs_Appendix-B_part-4.pdf | ||
| McAllen_22K_CPC_Warehouse_FINAL_design_Drawings.pdf | ||
| W9126G-15-B-0029-Specs.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CEILING
CASSETTE
“Accessories” on page 84 “Factory Supplied Parts & Materials” on page 85 “1-Way Ceiling Cassette Units” on page 87 “2-Way Ceiling Cassette Units” on page 113 “4-Way Ceiling Cassette Units” on page 133
Due to our policy of continuous product innovation, some specifications may change without notification.84 | CEILING CASSETTES
M U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
Accessory Model Number
1-Way Ceiling Cassette Grille Kit (Required) PT-HJC1
2-Way Ceiling Cassette Grille Kit (Required) PT-HLC1
4-Way Ceiling Cassette Grille Kit (Required)
PT-UQC (5-18 MBh) PT-UMC (24-48 MBh)
Ventilation Kit1 PTVK410 + PTVK420
Ventilation Kit2 PTVK430
Auto Elevation Kit1 PTEGM0
Cassette Decorative Cover3 PTDCM (5-18 MBh) PTDCQ (24-48 MBh)
ACCESSORIES
1For use with TP, TN and TM chassis 4-Way ceiling cassettes.
2For use with TR, TQ, TP, TN and TM chassis 4-Way ceiling cassettes.
3For use with 4-way ceiling cassettes.
All accessories are sold separately.
Due to our policy of continuous product innovation, some specifications may change without notification. CEILING CASSETTES | 85
C eiling C assettes
Part Quantity Image
Clamp (Tie Wrap)
Bolt 4
Screw1 3
Conduit Mounting Plate2 1
FACTORY SUPPLIED PARTS & MATERIALS
Part Quantity Image
Clamp Metal
Drain Hose
Fitting Insulation 1 Set
Hanging Bracket Washer 8
For 1-Way ceiling cassettes, the screws for fixing panels are attached to the decorative panel.
Factory Supplied Materials
• Paper pattern for installation
• Owner’s Manual
• Installation Manual
Factory Supplied Parts
Gas
Liquid
1Supplied with 1-Way ceiling cassettes.
2Supplied with 1-Way and 4-Way ceiling cassettes.
Due to our policy of continuous product innovation, some specifications may change without notification.86 | CEILING CASSETTES
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
4-WAY CEILING
CASSETTE
“Mechanical Specifications” on page 134 “General Data” on page 136 “Dimensions” on page 142 “Performance Data” on page 147 “Electrical & Acoustic Data” on page 161 “Piping Diagrams” on page 165 “Wiring Diagrams” on page 166 “Installation & Best Layout Practices” on page 170 “Air Velocity & Temperature Distribution” on page 177 “Fresh Air Ventilation” on page 201
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.134 | 4-WAY CEILING CASSETTES
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l Casing The case is designed to mount recessed in the ceiling and has a surface-mounted concentric grille on the bottom of the unit. The unit case is manufactured with coated metal. Cold surfaces are covered with a coated polystyrene insulating material. The case is provided with metal ears designed to support the unit weight on four corners.
Ears have pre-punched holes designed to accept field-supplied all-thread rod hangers.
Ventilation Air TQ, TR Chassis The case has a factory designated cutout for the connection of a field-supplied outside air duct. An optional flange kit is available from LG. The outside air can supply only one ceiling cassette indoor unit.
TM, TN, TP Chassis The case has a factory designated cutout for the connection of a field-supplied outside air duct. LG offers two flange kits. The outside air can supply only one ceiling cassette indoor unit.
Supply Air Branch Duct Connections Factory designated cutouts are marked on the unit case. Branch ducts provide the designer with the ability to duct up to ½ the unit airflow capacity to adjacent spaces. The adjacent space must be in the room where the ceiling cassette is installed. It cannot be branched to another room.
TQ, TR Chassis Connections can be made on up to any two of the three available connection points.
TM, TN, TP Chassis Connections can be made on up to any two of four available connection points.
Architectural Filter/Grille The ceiling cassette assembly is provided with an off-white ABS polymeric resin architectural grille equipped with a tapered trim edge and a hinged, spring clip (screwless) return air filter-grille door.
TM, TN, TP Chassis The unit case allows access to hanger rods and the inspection of piping through corner access panels on the architectural grille. The optional auto-elevating grille kit is designed to provide motorized ascent/descent of the return air grille/pre-filter assembly a distance of up to 14-3/4 feet allowing easy access to remove and clean the filter.
The kit consists of two lifting mechanisms comprised of an electric motor driven winch with braided steel lifting cables. The winch kit is mounted behind the grille and is not visible during normal unit operation. The auto-elevating return air grille appearance and finish matches that of the architectural grille on similar indoor unit models equipped with the standard hinged filter grilles. The auto-elevating grille control algorithm accepts up, down, and stop control commands from either a wall-mounted or the lift remote controller.
The algorithm does not permit the lowering of the grille while the indoor unit fan is operating. The pair of winch controllers work in unison to keep the return air grille level during lift and descent operations and will automatically stop the descent of the return air grille/filter if contact is made with any obstacle.
Fan Assembly and Control The indoor unit has a single, direct-drive, turbo fan. The fan wheel is made of high strength ABS HT-700 polymeric resin. The fan motor is a Brushless Digitally-Controlled (BLDC) design with permanently lubricated and sealed ball bearings. The fan/motor assembly is mounted on vibration attenuating rubber grommets. The fan speed is controlled using a microprocessor-based, direct digital control algorithm that provides a minimum of four pre-programmed fan speeds in the Heating and Fan Only modes and five speeds in the Cooling mode. Fan settings are super high, high, medium, and low.
Each setting can be field adjusted from the factory speed setting (RPM/ESP) to compensate for a limited amount of additional resistance to airflow caused by field connected ductwork or other airflow restricting devices. The fifth speed in the Cooling mode is a fan power cooling cycle that runs for 30 minutes at high fan speed. A chaos setting provides a random change in fan speed. The fan speed algorithm provides a field selectable, fixed-speed or auto-speed setting that adjusts the fan speed based on the difference between the controller set-point and space temperature.
Air Filter Return air is filtered with a removable, washable filter. The unit is also equipped with a plasma filter.
Airflow Guide Vanes The architectural grille has four-directional slot diffusers each equipped with independent oscillating motorized guide vanes designed to change the angle airflow is discharged. Discharge range
MECHANICAL SPECIFICATIONS
4-Way Ceiling Cassettes TQ, TR, TM, TN, TP Chassis
2’ x 2’ Chassis 3’ x 3’ Chassis
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. 4-WAY CEILING CASSETTES | 135
4-W ay C eiling C assettes
MECHANICAL SPECIFICATIONS
of motion is 40° in an up/down direction. The unit has a guide vane control algorithm designed to sequentially change the predominant discharge airfl ow direction in a counterclockwise pattern. The control algorithm also provides the capability of locking each guide vane independently in a fi eld adjusted fi xed position. Guide vanes provide airfl ow in all directions. The ends of each vane are tapered to provide airflow to the space in the direction of the four corners of the architectural grille.
Microprocessor Controls The unit is provided with an integrated microprocessor controller capable of performing functions necessary to operate the system without the use of a wall-mounted controller. A temperature thermistor is factory-mounted in the return air stream. All unit operation parameters, excluding the unit operating schedule, are stored in non-volatile memory resident on the unit microprocessor.
Operating schedules are stored in select models of the optional, wall-mounted, local, or central controller. The field-supplied communication cable between the indoor unit(s) and outdoor unit is to be a minimum of 18 AWG, 2 conductor, stranded, and shielded cable (RS485), terminated via screw terminals on the control boards.
The microprocessor control algorithms provide the following functions: self-diagnostics, auto restart following power restoration, test run, and will operate the indoor unit using one of five operating modes:
1. Auto Changeover (Heat Recovery only)
2. Heating
3. Cooling
4. Dry
5. Fan Only For Heat Recovery systems the Auto Changeover setting automatically switches control of the indoor unit between cooling and heating modes based on space temperature conditions.
For Heat Pump systems, heated or cooled air delivery is dependant upon outdoor unit operating mode.
In Heating mode, the microprocessor control will activate indoor unit operation when the indoor room temperature falls below setpoint temperature. At which point, a signal is sent to the outdoor unit to begin the heating cycle. The indoor unit fan operation is delayed until coil pipe temperature reaches 76ºF. Significant airflow is generated when pipe temperature reaches 80°F. The unit is equipped with an infrared receiver designed to communicate with an LG hand-held remote controller. In lieu of wireless remote or factory return air thermistor, pluggable connection sockets on the microprocessor circuit board accommodate various models of wall-mounted local controllers and/or a wall-mounted remote temperature sensor. The unit microprocessor is capable of accepting space temperature readings concurrently or individually from either:
1. Wall-mounted wired controller(s)
2. Factory mounted return air thermistor or the optional wall-mounted wired remote temperature sensor .
A single indoor unit has the capability of being controlled by up to
Standard Features
• Limited Warranty with LG Certified Installation
• Two Year Functional Parts Warranty
Controls Features
• Auto changeover (Heat Recovery only)
• Auto operation
• Auto restart
• Child lock
• Dual themistor control
• Forced operation
• Group control
• High ceiling
• Hot start
• Self diagnostics
• Sleep mode
• Timer (on/off)
• Weekly schedule
• Soft dry (dehumidification)
• Auto direction/swing (up/down)
• Fan speed control
• Chaos wind (random fan speed)
• Swirl wind (alternating vanes)
• Jet cool (fast cooling) two local wired controllers. The microprocessor controls space temperature using the value provided by the temperature sensor sensing a space temperature that is farthest away from the temperature set-point. The microprocessor control provides a cooling mode test cycle that operates the unit for 18 minutes without regard to the space temperature. If the system is provided with an optional wall-mounted, local, or central controller, displayed diagnostic codes are specifi c, alpha numeric, and provide the service technician with the reason for the code displayed.
Condensate Lift/Pump The indoor unit is provided with a factory installed and wired condensate lift/pump capable of providing a minimum 27.5 inch lift from the bottom surface of the unit. The lift pump comes with a safety switch that shuts off the indoor unit if condensate rises too high in the drain pan.
4-Way Ceiling Cassettes TQ, TR, TM, TN, TP Chassis
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.136 | 4-WAY CEILING CASSETTES
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
Type 4-Way Ceiling Cassette
ARNU053TRC2 ARNU073TRC2 ARNU093TRC2
Cooling Mode Performance Capacity (Btu/h) 5,500 7,500 9,600 Power Input1 (W) 30 30 30
Heating Mode Performance Capacity (Btu/h) 6,100 8,500 10,900 Power Input1 (W) 30 30 30
Entering Mixed Air Cooling Max (°F WB) 76 76 76 Heating Min (°F DB) 59 59 59
Unit Data Refrigerant Type2 R410A R410A R410A Refrigerant Control EEV EEV EEV Sound Pressure3 dB(A) (H/M/L) 29/27/26 29/27/26 30/29/27 Net Unit Weight (lbs) 29 29 32 Shipping Weight (lbs) 36 36 36 Grille Weight (lbs) 7 7 7 Grille Shipping Weight (lbs) 11 11 11 Communication Cable4
(No. x AWG) 2 x 18 2 x 18 2 x 18
Fan Type Turbo Turbo Turbo Quantity 1 1 1
Motor/Drive Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Airflow Rate H/M/L (CFM) 265/247/212 265/247/212 283/265/251 Piping Liquid Line (in, OD) 1/4 Flare 1/4 Flare 1/4 Flare Vapor Line (in, OD) 1/2 Flare 1/2 Flare 1/2 Flare Condensate Line (in, ID) 1 1 1
Table 62: 4-Way Ceiling Cassette Unit General Data
ARNU053TRC2, ARNU073TRC2, ARNU093TRC2
GENERAL DATA
4-Way Ceiling Cassette Unit Specifi cations
EEV: Electronic Expansion Valve Power wiring is fi eld supplied and must comply with the applicable local and national codes.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1Power Input is rated at high speed.
2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must comply with applicable and national code.
Power Supply (V/Hz/Ø): 208-230/60/1
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. 4-WAY CEILING CASSETTES | 137 ay C eiling C assettes
ARNU123TRC2, ARNU153TQC2, ARNU183TQC2
GENERAL DATA
Type 4-Way Ceiling Cassette
ARNU123TRC2 ARNU153TQC2 ARNU183TQC2
Cooling Mode Performance Capacity (Btu/h) 12,300 15,400 19,100 Power Input1 (W) 30 30 30
Heating Mode Performance Capacity (Btu/h) 13,600 17,100 21,500 Power Input1 (W) 30 30 30
Entering Mixed Air Cooling Max (°F WB) 76 76 76 Heating Min (°F DB) 59 59 59
Unit Data Refrigerant Type2 R410A R410A R410A Refrigerant Control EEV EEV EEV Sound Pressure3 dB(A) (H/M/L) 32/30/27 36/34/32 37/35/34 Net Unit Weight (lbs) 32 35 35 Shipping Weight (lbs) 36 42 42 Grille Weight (lbs) 7 7 7 Grille Shipping Weight (lbs) 11 11 11 Communication Cable4
(No. x AWG) 2 x 18 2 x 18 2 x 18
Fan Type Turbo Turbo Turbo Quantity 1 1 1
Motor/Drive Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Airflow Rate H/M/L (CFM) 307/283/247 388/353/328 396/388/353 Piping Liquid Line (in, OD) 1/4 Flare 1/4 Flare 1/4 Flare Vapor Line (in, OD) 1/2 Flare 1/2 Flare 1/2 Flare Condensate Line (in, ID) 1 1 1
Table 63: 4-Way Ceiling Cassette Unit General Data
4-Way Ceiling Cassette Unit Specifi cations
EEV: Electronic Expansion Valve Power wiring is fi eld supplied and must comply with the applicable local and national codes.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1Power Input is rated at high speed.
2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.138 | 4-WAY CEILING CASSETTES
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
Type 4-Way Ceiling Cassette
ARNU093TNC2 ARNU123TNC2 ARNU153TNC2
Cooling Mode Performance Capacity (Btu/h) 9,600 12,300 15,400 Power Input1 (W) 144 144 144
Heating Mode Performance Capacity (Btu/h) 10,900 13,600 17,100 Power Input1 (W) 144 144 144
Entering Mixed Air Cooling Max (°F WB) 76 76 76 Heating Min (°F DB) 59 59 59
Unit Data Refrigerant Type2 R410A R410A R410A Refrigerant Control EEV EEV EEV Sound Pressure3 dB(A) (H/M/L) 30/26/22 30/26/22 35/32/29 Net Unit Weight (lbs) 52 52 52 Shipping Weight (lbs) 59 59 59 Grille Weight (lbs) 13 13 13 Grille Shipping Weight (lbs) 20 20 20 Communication Cable4 (No. x AWG) 2 x 18 2 x 18 2 x 18
Fan Type Turbo Turbo Turbo Quantity 1 1 1
Motor/Drive Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Airflow Rate H/M/L (CFM) 484/424/364 484/424/364 600/530/470 Piping Liquid Line (in, OD) 3/8 Flare 3/8 Flare 3/8 Flare Vapor Line (in, OD) 5/8 Flare 5/8 Flare 5/8 Flare Condensate Line (in, ID) 1 1 1
Table 64: 4-Way Ceiling Cassette Unit General Data
ARNU093TNC2, ARNU123TNC2, ARNU153TNC2
GENERAL DATA
4-Way Ceiling Cassette Unit Specifi cations
EEV: Electronic Expansion Valve Power wiring is fi eld supplied and must comply with the applicable local and national codes.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1Power Input is rated at high speed.
2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. 4-WAY CEILING CASSETTES | 139 ay C eiling C assettes
Type 4-Way Ceiling Cassette
ARNU183TMC2 ARNU243TMC2 ARNU243TPC2
Cooling Mode Performance Capacity (Btu/h) 19,100 24,200 24,200 Power Input1 (W) 144 144 33
Heating Mode Performance Capacity (Btu/h) 21,500 27,300 27,300 Power Input1 (W) 144 144 33
Entering Mixed Air Cooling Max (°F WB) 76 76 76 Heating Min (°F DB) 59 59 59
Unit Data Refrigerant Type2 R410A R410A R410A Refrigerant Control EEV EEV EEV Sound Pressure3 dB(A) (H/M/L) 34/30/26 41/39/36 36/34/31 Net Unit Weight (lbs) 57 57 46 Shipping Weight (lbs) 64 64 53 Grille Weight (lbs) 13 13 13 Grille Shipping Weight (lbs) 20 20 20 Communication Cable4
(No. x AWG) 2 x 18 2 x 18 2 x 18
Fan Type Turbo Turbo Turbo Quantity 1 1 1
Motor/Drive Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Brushless Digitally Controlled/ Direct
Airflow Rate H/M/L (CFM) 685/600/530 897/812/742 600/529/459 Piping Liquid Line (in, OD) 3/8 Flare 3/8 Flare 3/8 Flare Vapor Line (in, OD) 5/8 Flare 5/8 Flare 5/8 Flare Condensate Line (in, ID) 1 1 1
Table 65: 4-Way Ceiling Cassette Unit General Data
ARNU183TMC2, ARNU243TMC2, ARNU243TPC2
GENERAL DATA
4-Way Ceiling Cassette Unit Specifi cation
EEV: Electronic Expansion Valve Power wiring is fi eld supplied and must comply with the applicable local and national codes.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1Power Input is rated at high speed.
2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.140 | 4-WAY CEILING CASSETTES
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
Table 66: 4-Way Ceiling Cassette Unit General Data Type 4-Way Ceiling Cassette
ARNU283TPC2 ARNU363TNC2
Cooling Mode Performance Capacity (Btu/h) 28,000 36,200 Power Input1 (W) 33 144
Heating Mode Performance Capacity (Btu/h) 31,500 40,600 Power Input1 (W) 33 144
Entering Mixed Air Cooling Max (°F WB) 76 76 Heating Min (°F DB) 59 59
Unit Data Refrigerant Type2 R410A R410A Refrigerant Control EEV EEV Sound Pressure3 dB(A) (H/M/L) 39/35/33 43/40/37 Net Unit Weight (lbs) 46 52 Shipping Weight (lbs) 53 59 Grille Weight (lbs) 13 13 Grille Shipping Weight (lbs) 20 20 Communication Cable4 (No. x AWG) 2 x 18 2 x 18
Fan Type Turbo Turbo Quantity 1 1 Motor/Drive Brushless Digitally Controlled/Direct Brushless Digitally Controlled/Direct Airflow Rate H/M/L (CFM) 671/565/494 883/742/671
Piping Liquid Line (in, OD) 3/8 Flare 3/8 Flare Vapor Line (in, OD) 5/8 Flare 5/8 Flare Condensate Line (in, ID) 1 1
ARNU283TPC2, ARNU363TNC2
GENERAL DATA
4-Way Ceiling Cassette Unit Specifi cations
EEV: Electronic Expansion Valve Power wiring is fi eld supplied and must comply with the applicable local and national codes.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1Power Input is rated at high speed.
2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. 4-WAY CEILING CASSETTES | 141 ay C eiling C assettes
ARNU423TMC2, ARNU483TMC2
GENERAL DATA
Table 67: 4-Way Ceiling Cassette Unit General Data Type 4-Way Ceiling Cassette
ARNU423TMC2 ARNU483TMC2
Cooling Mode Performance Capacity (Btu/h) 42,000 48,100 Power Input1 (W) 144 144
Heating Mode Performance Capacity (Btu/h) 43,800 51,200 Power Input1 (W) 144 144
Entering Mixed Air Cooling Max (°F WB) 76 76 Heating Min (°F DB) 59 59
Unit Data Refrigerant Type2 R410A R410A Refrigerant Control EEV EEV Sound Pressure3 dB(A) (H/M/L) 44/41/38 46/43/41 Net Unit Weight (lbs) 57 57 Shipping Weight (lbs) 64 64 Grille Weight (lbs) 13 13 Grille Shipping Weight (lbs) 20 20 Communication Cable4 (No. x AWG) 2 x 18 2 x 18
Fan Type Turbo Turbo Quantity 1 1 Motor/Drive Brushless Digitally Controlled/Direct Brushless Digitally Controlled/Direct Airflow Rate H/M/L (CFM) 1,059/954/848 1,095/1,024/954
Piping Liquid Line (in, OD) 3/8 Flare 3/8 Flare Vapor Line (in, OD) 5/8 Flare 5/8 Flare Condensate Line (in, ID) 1 1
4-Way Ceiling Cassette Unit Specifi cations
EEV: Electronic Expansion Valve Power wiring is fi eld supplied and must comply with the applicable local and national codes.
This unit comes with a dry nitrogen charge.
This data is rated 0 ft above sea level, with 25 ft of refrigerant line per indoor unit and a 0 ft level difference between outdoor and indoor units. All capacities are net with a combination ratio between 95-105%.
Cooling capacity rating obtained with air entering the indoor coil at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
1Power Input is rated at high speed.
2Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
3Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4All communication cable to be minimum 18 AWG, 2-conductor, stranded, shielded and must
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.142 | 4-WAY CEILING CASSETTES
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
TR Chassis
DIMENSIONS
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. 4-WAY CEILING CASSETTES | 143 ay C eiling C assettes
TQ Chassis
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.144 | 4-WAY CEILING CASSETTES
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
TP Chassis
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. 4-WAY CEILING CASSETTES | 145 ay C eiling C assettes
TN Chassis
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.146 | 4-WAY CEILING CASSETTES
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
TM Chassis
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. 4-WAY CEILING CASSETTES | 147 ay C eiling C assettes
Cooling Capacity
PERFORMANCE DATA
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.8 9.7 5.7 25 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.8 9.7 5.7 30 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.8 9.7 5.7 35 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.8 9.7 5.7 40 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.8 9.7 5.7 45 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.8 9.7 5.7 50 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.8 9.7 5.7 55 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.8 9.7 5.7 60 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.8 9.6 5.7 65 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.8 9.5 5.6 70 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.8 9.3 5.5 75 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.9 5.8 9.1 5.4 80 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.4 5.8 8.7 5.7 8.9 5.4 85 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.3 5.7 8.4 5.5 8.6 5.2 90 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.2 5.6 8.3 5.4 8.4 5.1 95 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 8.0 5.6 8.2 5.3 8.3 5.1
100 5.0 4.1 6.0 4.8 6.8 5.1 7.5 5.4 7.9 5.5 8.0 5.3 8.2 5.0 105 5.0 4.1 5.7 4.5 6.5 4.9 7.2 5.2 7.4 5.2 7.7 5.1 7.9 4.9 110 4.8 4.0 5.4 4.3 6.0 4.5 6.8 4.9 6.9 4.9 7.4 4.9 7.7 4.8
Table 68: ARNU053TRC2 Cooling Capacities Outdoor
Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.2 4.1 6.5 4.1 7.1 4.1 25 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.2 4.1 6.5 4.1 7.1 4.1 30 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.2 4.1 6.5 4.1 7.1 4.1 35 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.2 4.1 6.5 4.1 7.1 4.1 40 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.2 4.1 6.5 4.1 7.1 4.1 45 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.2 4.1 6.5 4.1 7.1 4.1 50 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.2 4.1 6.5 4.1 7.1 4.1 55 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.2 4.1 6.5 4.1 7.1 4.1 60 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.2 4.1 6.5 4.1 7.0 4.1 65 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.2 4.1 6.5 4.1 6.9 4.0 70 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.2 4.1 6.5 4.1 6.8 3.9 75 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.2 4.1 6.5 4.1 6.7 3.9 80 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.2 4.1 6.4 4.1 6.5 3.8 85 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.1 4.1 6.2 3.9 6.3 3.7 90 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 6.0 4.0 6.1 3.8 6.2 3.6 95 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 5.9 4.0 6.0 3.8 6.1 3.6
100 3.6 3.0 4.4 3.4 5.0 3.6 5.5 3.9 5.8 3.9 5.9 3.8 6.0 3.6 105 3.6 3.0 4.2 3.2 4.7 3.5 5.3 3.7 5.4 3.7 5.7 3.6 5.8 3.5 110 3.5 2.9 4.0 3.1 4.4 3.2 5.0 3.5 5.1 3.5 5.4 3.5 5.6 3.4
Table 69: ARNU073TRC2 Cooling Capacities
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
ARNU053TRC2, ARNU073TRC2
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.148 | 4-WAY CEILING CASSETTES
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.6 9.4 15.9 9.4 25 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.6 9.4 15.9 9.4 30 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.6 9.4 15.9 9.4 35 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.6 9.4 15.9 9.4 40 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.6 9.4 15.9 9.4 45 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.6 9.4 15.9 9.4 50 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.6 9.4 15.9 9.4 55 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.6 9.4 15.9 9.4 60 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.6 9.4 15.7 9.4 65 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.6 9.4 15.5 9.2 70 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.6 9.4 15.3 9.1 75 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.6 9.4 14.9 8.9 80 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.8 9.5 14.3 9.4 14.5 8.8 85 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.7 9.4 13.8 9.0 14.0 8.5 90 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.4 9.3 13.5 8.8 13.8 8.4 95 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 13.2 9.2 13.4 8.8 13.7 8.3 100 8.1 6.8 9.8 7.8 11.1 8.3 12.3 8.9 12.9 9.1 13.2 8.7 13.4 8.2 105 8.1 6.8 9.3 7.4 10.6 8.0 11.8 8.5 12.1 8.5 12.7 8.4 12.9 8.0 110 7.9 6.6 8.9 7.0 9.8 7.4 11.1 8.0 11.3 8.0 12.1 8.0 12.5 7.8
Table 70: ARNU093TRC2 Cooling Capacities Outdoor
Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.4 12.4 7.3 25 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.4 12.4 7.3 30 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.4 12.4 7.3 35 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.4 12.4 7.3 40 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.4 12.4 7.3 45 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.4 12.4 7.3 50 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.4 12.4 7.3 55 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.4 12.4 7.4 60 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.4 12.3 7.3 65 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.4 12.1 7.2 70 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.4 11.9 7.1 75 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.4 7.4 11.6 6.9 80 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.8 7.4 11.1 7.3 11.3 6.9 85 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.7 7.4 10.8 7.0 10.9 6.6 90 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.5 7.2 10.6 6.9 10.8 6.5 95 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.3 7.2 10.5 6.8 10.7 6.5 100 6.3 5.3 7.7 6.1 8.6 6.5 9.6 6.9 10.1 7.1 10.3 6.8 10.5 6.4 105 6.3 5.3 7.3 5.8 8.3 6.2 9.2 6.6 9.4 6.6 9.9 6.5 10.1 6.3 110 6.1 5.1 6.9 5.5 7.7 5.8 8.6 6.2 8.8 6.2 9.4 6.2 9.8 6.1
Table 71: ARNU123TRC2 Cooling Capacities
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Cooling Capacity
PERFORMANCE DATA
ARNU093TRC2, ARNU123TRC2
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. 4-WAY CEILING CASSETTES | 149 ay C eiling C assettes
PERFORMANCE DATA
Cooling Capacity
ARNU153TQC2, ARNU183TQC2
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 21.4 14.8 22.7 14.6 24.6 14.6 25 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 21.4 14.8 22.7 14.6 24.6 14.6 30 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 21.4 14.8 22.7 14.6 24.6 14.6 35 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 21.4 14.8 22.7 14.6 24.6 14.6 40 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 21.4 14.8 22.7 14.6 24.6 14.6 45 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 21.4 14.8 22.7 14.6 24.6 14.6 50 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 21.4 14.8 22.7 14.6 24.6 14.6 55 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 21.4 14.8 22.7 14.6 24.6 14.6 60 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 21.4 14.8 22.7 14.6 24.4 14.5 65 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 21.4 14.8 22.7 14.6 24.1 14.3 70 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 21.4 14.8 22.7 14.6 23.7 14.1 75 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 21.4 14.8 22.7 14.6 23.1 13.8 80 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 21.4 14.8 22.2 14.6 22.5 13.7 85 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 21.2 14.6 21.4 13.9 21.8 13.2 90 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 20.8 14.4 21.0 13.7 21.4 13.0 95 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 20.4 14.3 20.8 13.6 21.2 12.9
100 12.6 10.6 15.3 12.1 17.2 13.0 19.1 13.8 20.1 14.1 20.4 13.5 20.8 12.8 105 12.6 10.6 14.5 11.5 16.4 12.4 18.3 13.2 18.7 13.2 19.7 13.0 20.1 12.5 110 12.2 10.2 13.8 10.9 15.3 11.5 17.2 12.4 17.6 12.4 18.7 12.4 19.5 12.1
Table 72: ARNU153TQC2 Cooling Capacities Outdoor
Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.2 11.9 18.3 11.8 19.9 11.8 25 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.2 11.9 18.3 11.8 19.9 11.8 30 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.2 11.9 18.3 11.8 19.9 11.8 35 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.2 11.9 18.3 11.8 19.9 11.8 40 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.2 11.9 18.3 11.8 19.9 11.8 45 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.2 11.9 18.3 11.8 19.9 11.8 50 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.2 11.9 18.3 11.8 19.9 11.8 55 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.2 11.9 18.3 11.8 19.9 11.8 60 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.2 11.9 18.3 11.8 19.7 11.7 65 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.2 11.9 18.3 11.8 19.4 11.5 70 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.2 11.9 18.3 11.8 19.1 11.4 75 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.2 11.9 18.3 11.8 18.6 11.1 80 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.2 11.9 17.9 11.7 18.2 11.1 85 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 17.1 11.8 17.2 11.2 17.6 10.6 90 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 16.8 11.6 16.9 11.0 17.2 10.5 95 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 16.5 11.5 16.8 11.0 17.1 10.4
100 10.2 8.5 12.3 9.8 13.9 10.4 15.4 11.1 16.2 11.4 16.5 10.9 16.8 10.3 105 10.2 8.5 11.7 9.3 13.2 10.0 14.8 10.6 15.1 10.6 15.9 10.5 16.2 10.0 110 9.9 8.3 11.1 8.8 12.3 9.3 13.9 10.0 14.2 10.0 15.1 10.0 15.7 9.8
Table 73: ARNU183TQC2 Cooling Capacities
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.150 | 4-WAY CEILING CASSETTES
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6 25 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6 30 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6 35 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6 40 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6 45 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6 50 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6 55 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.4 7.6 60 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.3 7.6 65 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 12.1 7.5 70 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 11.9 7.4 75 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.4 7.6 11.6 7.2 80 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.8 7.7 11.1 7.6 11.3 7.2 85 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.6 7.6 10.8 7.3 11.0 6.9 90 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.5 7.5 10.6 7.2 10.8 6.8 95 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.3 7.5 10.5 7.1 10.6 6.7
100 6.3 5.5 7.7 6.4 8.6 6.8 9.6 7.2 10.1 7.4 10.3 7.0 10.5 6.7 105 6.3 5.5 7.3 6.0 8.2 6.5 9.2 6.9 9.4 6.9 9.9 6.8 10.1 6.5 110 6.2 5.3 6.9 5.7 7.7 6.0 8.6 6.5 8.8 6.5 9.4 6.5 9.8 6.3
Table 74: ARNU093TNC2 Cooling Capacities
Table 75: ARNU123TNC2 Cooling Capacities
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Outdoor Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.8 9.9 14.7 9.8 15.9 9.8 25 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.8 9.9 14.7 9.8 15.9 9.8 30 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.8 9.9 14.7 9.8 15.9 9.8 35 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.8 9.9 14.7 9.8 15.9 9.8 40 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.8 9.9 14.7 9.8 15.9 9.8 45 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.8 9.9 14.7 9.8 15.9 9.8 50 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.8 9.9 14.7 9.8 15.9 9.8 55 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.8 9.9 14.7 9.8 15.9 9.8 60 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.8 9.9 14.7 9.8 15.7 9.7 65 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.8 9.9 14.7 9.8 15.5 9.6 70 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.8 9.9 14.7 9.8 15.3 9.4 75 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.8 9.9 14.7 9.8 14.9 9.2 80 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.8 9.9 14.2 9.7 14.5 9.2 85 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.6 9.8 13.8 9.3 14.0 8.8 90 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.4 9.6 13.5 9.2 13.8 8.7 95 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 13.2 9.6 13.4 9.1 13.6 8.6 100 8.1 7.0 9.8 8.1 11.1 8.7 12.3 9.2 12.9 9.4 13.2 9.0 13.4 8.6 105 8.1 7.0 9.3 7.7 10.6 8.3 11.8 8.8 12.0 8.8 12.7 8.7 12.9 8.3 110 7.9 6.8 8.9 7.3 9.8 7.7 11.1 8.3 11.3 8.3 12.0 8.3 12.6 8.1
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Cooling Capacity
ARNU093TNC2, ARNU123TNC2
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. 4-WAY CEILING CASSETTES | 151 ay C eiling C assettes
PERFORMANCE DATA
Cooling Capacity
ARNU153TNC2, ARNU183TMC2
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Table 76: ARNU153TNC2 Cooling Capacities Outdoor
Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 17.3 12.9 18.4 12.8 19.9 12.8 25 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 17.3 12.9 18.4 12.8 19.9 12.8 30 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 17.3 12.9 18.4 12.8 19.9 12.8 35 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 17.3 12.9 18.4 12.8 19.9 12.8 40 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 17.3 12.9 18.4 12.8 19.9 12.8 45 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 17.3 12.9 18.4 12.8 19.9 12.8 50 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 17.3 12.9 18.4 12.8 19.9 12.8 55 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 17.3 12.9 18.4 12.8 19.9 12.8 60 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 17.3 12.9 18.4 12.8 19.7 12.7 65 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 17.3 12.9 18.4 12.8 19.4 12.5 70 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 17.3 12.9 18.4 12.8 19.1 12.3 75 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 17.3 12.9 18.4 12.8 18.6 12.0 80 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 17.3 12.9 17.8 12.7 18.2 11.9 85 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 17.1 12.8 17.3 12.1 17.6 11.5 90 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 16.8 12.6 16.9 11.9 17.3 11.3 95 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 16.5 12.5 16.8 11.9 17.1 11.2 100 10.1 9.2 12.3 10.6 13.9 11.3 15.4 12.0 16.2 12.3 16.5 11.7 16.8 11.1 105 10.1 9.2 11.7 10.1 13.2 10.8 14.8 11.5 15.1 11.5 15.8 11.3 16.2 10.9 110 9.9 8.9 11.1 9.5 12.3 10.1 13.9 10.8 14.2 10.8 15.1 10.8 15.7 10.5
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Table 77: ARNU183TMC2 Cooling Capacities Outdoor
Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 21.4 17.0 22.8 16.8 24.7 16.8 25 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 21.4 17.0 22.8 16.8 24.7 16.8 30 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 21.4 17.0 22.8 16.8 24.7 16.8 35 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 21.4 17.0 22.8 16.8 24.7 16.8 40 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 21.4 17.0 22.8 16.8 24.7 16.8 45 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 21.4 17.0 22.8 16.8 24.7 16.8 50 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 21.4 17.0 22.8 16.8 24.7 16.8 55 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 21.4 17.0 22.8 16.8 24.7 16.8 60 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 21.4 17.0 22.8 16.8 24.4 16.7 65 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 21.4 17.0 22.8 16.8 24.0 16.5 70 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 21.4 17.0 22.8 16.8 23.7 16.2 75 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 21.4 17.0 22.8 16.8 23.1 15.9 80 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 21.4 17.0 22.1 16.7 22.5 15.8 85 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 21.2 16.8 21.4 16.0 21.8 15.1 90 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 20.9 16.6 21.0 15.8 21.4 15.0 95 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 20.5 16.5 20.9 15.7 21.2 14.8 100 12.6 12.1 15.3 14.0 17.2 14.9 19.1 15.9 20.1 16.2 20.5 15.5 20.9 14.7 105 12.6 12.1 14.5 13.3 16.4 14.2 18.3 15.1 18.7 15.1 19.7 15.0 20.1 14.3 110 12.3 11.8 13.8 12.6 15.3 13.3 17.2 14.2 17.6 14.2 18.7 14.2 19.5 13.9
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.152 | 4-WAY CEILING CASSETTES
U
LT
I V
In do or U ni t E ng in ee rin g M an ua l
Table 78: ARNU243TMC2 Cooling Capacities Outdoor
Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 27.1 21.8 28.8 21.6 31.3 21.6 25 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 27.1 21.8 28.8 21.6 31.3 21.6 30 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 27.1 21.8 28.8 21.6 31.3 21.6 35 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 27.1 21.8 28.8 21.6 31.3 21.6 40 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 27.1 21.8 28.8 21.6 31.3 21.6 45 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 27.1 21.8 28.8 21.6 31.3 21.6 50 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 27.1 21.8 28.8 21.6 31.3 21.6 55 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 27.1 21.8 28.8 21.6 31.3 21.6 60 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 27.1 21.8 28.8 21.6 31.0 21.5 65 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 27.1 21.8 28.8 21.6 30.5 21.1 70 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 27.1 21.8 28.8 21.6 30.0 20.8 75 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 27.1 21.8 28.8 21.6 29.2 20.3 80 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 27.1 21.8 28.0 21.5 28.5 20.2 85 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 26.8 21.6 27.1 20.6 27.6 19.4 90 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 26.4 21.2 26.6 20.2 27.1 19.2 95 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 25.9 21.1 26.4 20.1 26.8 19.0 100 15.9 15.5 19.4 17.9 21.8 19.1 24.2 20.3 25.4 20.8 25.9 19.9 26.4 18.8 105 15.9 15.5 18.4 17.0 20.8 18.3 23.2 19.4 23.7 19.4 24.9 19.2 25.4 18.4 110 15.5 15.1 17.4 16.1 19.4 17.0 21.8 18.3 22.3 18.3 23.7 18.3 24.7 17.8
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Table 79: ARNU243TPC2 Cooling Capacities Outdoor
Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 27.1 18.7 28.8 18.6 31.2 18.5 25 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 27.1 18.7 28.8 18.6 31.2 18.5 30 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 27.1 18.7 28.8 18.6 31.2 18.5 35 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 27.1 18.7 28.8 18.6 31.2 18.5 40 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 27.1 18.7 28.8 18.6 31.2 18.5 45 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 27.1 18.7 28.8 18.6 31.2 18.5 50 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 27.1 18.7 28.8 18.6 31.2 18.5 55 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 27.1 18.7 28.8 18.6 31.2 18.5 60 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 27.1 18.7 28.8 18.6 31.0 18.4 65 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 27.1 18.7 28.8 18.6 30.5 18.1 70 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 27.1 18.7 28.8 18.6 30.0 17.9 75 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 27.1 18.7 28.8 18.6 29.3 17.5 80 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 27.1 18.7 28.1 18.4 28.6 17.4 85 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 26.9 18.5 27.1 17.6 27.6 16.7 90 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 26.4 18.2 26.6 17.4 27.1 16.4 95 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 25.9 18.1 26.4 17.2 26.9 16.3
100 16.0 13.4 19.4 15.4 21.8 16.4 24.2 17.4 25.4 17.8 25.9 17.1 26.4 16.2 105 16.0 13.4 18.4 14.6 20.8 15.7 23.2 16.7 23.7 16.7 24.9 16.5 25.4 15.8 110 15.5 13.0 17.4 13.8 19.4 14.6 21.8 15.7 22.3 15.7 23.7 15.7 24.7 15.3
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Cooling Capacity
ARNU243TMC2, ARNU243TPC2
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation. 4-WAY CEILING CASSETTES | 153 ay C eiling C assettes
PERFORMANCE DATA
Cooling Capacity
ARNU283TPC2, ARNU363TNC2
Table 80: ARNU283TPC2 Cooling Capacities Outdoor
Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 31.4 21.6 33.3 21.5 36.1 21.4 25 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 31.4 21.6 33.3 21.5 36.1 21.4 30 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 31.4 21.6 33.3 21.5 36.1 21.4 35 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 31.4 21.6 33.3 21.5 36.1 21.4 40 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 31.4 21.6 33.3 21.5 36.1 21.4 45 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 31.4 21.6 33.3 21.5 36.1 21.4 50 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 31.4 21.6 33.3 21.5 36.1 21.4 55 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 31.4 21.6 33.3 21.5 36.1 21.5 60 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 31.4 21.6 33.3 21.5 35.8 21.3 65 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 31.4 21.6 33.3 21.5 35.3 21.0 70 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 31.4 21.6 33.3 21.5 34.7 20.7 75 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 31.4 21.6 33.3 21.5 33.9 20.2 80 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 31.4 21.6 32.5 21.3 33.0 20.1 85 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 31.1 21.5 31.4 20.4 31.9 19.3 90 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 30.5 21.1 30.8 20.1 31.4 19.0 95 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 30.0 21.0 30.5 20.0 31.1 18.9 100 18.5 15.5 22.4 17.8 25.2 19.0 28.0 20.2 29.4 20.6 30.0 19.8 30.5 18.7 105 18.5 15.5 21.3 16.9 24.1 18.2 26.9 19.4 27.4 19.3 28.8 19.1 29.4 18.3 110 17.9 15.0 20.2 16.0 22.4 16.9 25.2 18.1 25.8 18.2 27.4 18.2 28.6 17.7
TC: Total Capacity (MBh) SHC: Sensible Heat Capacity (MBh)
Table 81: ARNU363TNC2 Cooling Capacities Outdoor
Air Temp.
(°F DB)
Indoor Air Temperature (°F WB) 57 61 64 67 70 73 76
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh MBh
23 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 40.5 28.0 43.1 27.8 46.7 27.7 25 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 40.5 28.0 43.1 27.8 46.7 27.7 30 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 40.5 28.0 43.1 27.8 46.7 27.7 35 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 40.5 28.0 43.1 27.8 46.7 27.7 40 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 40.5 28.0 43.1 27.8 46.7 27.7 45 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 40.5 28.0 43.1 27.8 46.7 27.7 50 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 40.5 28.0 43.1 27.8 46.7 27.7 55 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 40.5 28.0 43.1 27.8 46.7 27.7 60 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 40.5 28.0 43.1 27.8 46.3 27.5 65 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 40.5 28.0 43.1 27.8 45.6 27.1 70 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 40.5 28.0 43.1 27.8 44.9 26.7 75 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 40.5 28.0 43.1 27.8 43.8 26.1 80 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 40.5 28.0 42.0 27.6 42.7 26.0 85 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 40.2 27.7 40.5 26.4 41.3 25.0 90 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 39.5 27.2 39.8 26.0 40.5 24.6 95 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 38.7 27.1 39.5 25.8 40.2 24.4 100 23.9 20.0 29.0 23.0 32.6 24.6 36.2 26.1 38.0 26.7 38.7 25.6 39.5 24.2 105 23.9 20.0 27.5 21.8 31.1 23.5 34.8 25.0 35.5 25.0 37.3 24.7 38.0 23.6 110 23.2 19.4 26.1 20.7 29.0 21.8 32.6 23.5 33.3 23.5 35.5 23.5 36.9 22.9
Due to our policy of continuous product innovation, some specifi cations may change without notifi cation.154 | 4-WAY CEILING…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .