TE 3 IMCOM Standards Storage Tanks 2Mar20.docx
DOCX document 31 KB Posted
- Attached to
- Underground and Above ground tanks Federal contract opportunity
- Solicitation number
- W9124M20R0020
About this file
This technical exhibit outlines requirements for inspections, testing, and repair of underground storage tanks and above-ground storage tanks on Fort Stewart and Hunter Army Airfield in Georgia. The contractor shall perform monthly inspections and annual testing of twenty underground tanks and six above-ground or vaulted tanks, including sensor checks, leak detection tests, and preventative maintenance. The contractor is responsible for minor repairs up to $100 in parts per tank and shall obtain authorization for and propose solutions to any major issues found. The purpose is to maintain compliance with environmental regulations and properly operate fuel storage and dispensing infrastructure for the Department of the Army.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| TE6 Confined Space SOP 15 Jun 16.pdf | ||
| TE1 FS_HAAF Tank Map.pdf | ||
| Storage Tank IDs.xlsx | XLSX spreadsheet | |
| W9124M20R0020 SOLICITATION.pdf | ||
| Questions regarding AST.pdf | ||
| Questions regarding AST.pdf | ||
| PWS Storage Tanks-(rev. 09Mar2020).docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Technical Exhibit 3 - IMCOM Standards.
TECHNICAL EXHIBIT 3
UST/AST INSPECTIONS AND MAINTENANCE
(30 December 2019)
| 1 | General Information. |
| 1.1 | Overview. The Contractor shall provide all personnel, equipment, supplies, facilities, transportation, tools, materials, supervision, and other items and non-personal services necessary to provide inspections, testing, and repair of underground storage tanks (UST) and above-ground storage tanks (AST) on Fort Stewart (FS) and Hunter Army Airfield (HAAF), Georgia as defined in this Performance Work Statement (PWS), except for those items specified as government furnished property and services. The Contractor shall perform in accordance with (IAW) the terms and conditions of the contract and consistently with the established standards in this PWS and contract. |
| 2 | Description of Services. |
| 2.1 | Scope. The Contractor shall perform assessments of UST and AST systems at FS/HAAF and assess compliance in accordance with requirements in 40 CFR 280 (Federal UST regulations) and 40 CFR 112 (Federal regulations applicable to ASTs). The assessments shall include the inspection and testing of leak detection and overfill protection systems in accordance with the American Petroleum Institute (API) and Petroleum Equipment Institute (PEI), Steel Tank Institute (STI), National Fire Protection Association (NFPA) 30 and 30A standards, as well as all manufacturer specifications and protocols. All tasks must be performed in accordance with required standards. The Contractor shall provide repair services in support of the operation and maintenance of said systems. Specific tasks to be performed by the Contractor under this PWS are described herein. |
| 3 | Specific Tasks. |
| 3.1 | Monthly Inspections of UST/AST/Vaulted AST Systems. |
| 3.1.1 | USTs. The Contractor shall perform monthly assessment and inspection activities on the following twelve (12) USTs, located at FS/HAAF: |
FS Bldg. 939 (Marne Shoppette): USTs #276, #277, #278, and #279; FS Bldg. 7736 (Bryan Village Shoppette): USTs #286, #287, and #288; HAAF Bldg. 931 (Hunter Corner Express): USTs #124, #125, and #126 at HAAF Bldg. 419 (Hunter Gas Kiosk): USTs #1A and #2B at HAAF.
3.1.2 Monthly assessment and inspection activities of the systems from the fuel storage tanks up to the shear valve of the associated dispensers will include:
Functional checks via the automatic tank gauging system control panel (Veeder-Root or equivalent) of tank interstitial sensors, tank external overfill alarm, compliance well sensors (if applicable) and piping sump sensors.
a. Check condition of spill containment manholes.
b. Visual inspection of dispenser cabinet, spill buckets and sump for potential leaks where applicable. The contractor shall remove any water that is present in sumps and spill buckets.
c. Manually stick tanks to check for the presence of water.
d. The contractor shall replace up to twelve (12) gaskets on pump sump lids and up to twenty-four (24) seals on spill bucket lids, as needed.
e. Photo document system deficiencies as needed.
3.1.3 Vaulted Below-Grade ASTs. The Contractor shall perform assessment and inspection activities on the following four (4) below-grade vaulted ASTs, located at Fort Stewart:
Bldg. 7806 (Harmon Avenue Shoppette): Tanks #1 and #2 Bldg. 3050 (6th Street Mini-Mall): Tanks #1 and #2 The 6th Street Mini-Mall and Harmon Avenue Shoppettes each have two 15,000 gallon vaulted below-grade ASTs. These are forced ventilation vaults and are classified as controlled environment confined entry which does not require any special permitting or procedures when pertaining to general maintenance, repairs, and inspections. In accordance with 29 CFR 1926.21(b) (6) (i), the contractor shall ensure that all employees that enter into the vaults have received appropriate training for controlled-environment confined entry. Monthly inspections of the vaulted ASTs may include a visual inspection of the entire tank, including monitoring the interstice between the primary steel tank and the secondary concrete containment vault.
3.1.4 Monthly assessment and inspection activities of the systems from the fuel storage tanks up to the shear valve of the associated dispensers will include:
a. Functional checks via the automatic tank gauging system control panel (Veeder-Root or equivalent) of tank interstitial sensors, tank external overfill alarm, compliance well sensors (if applicable) and piping sump sensors.
b. Check condition of spill containment manholes.
c. Visual inspection of dispenser cabinet, spill buckets and sump for potential leaks where applicable. The subcontractor shall remove any water that is present in sumps and spill buckets.
d. Manually stick tanks to check for the presence of water.
e. The contractor shall replace up to four (4) gaskets on sump lids and up to eight (8) seals on spill bucket lids as needed.
f. Photo document system deficiencies as needed.
3.1.5 Above-Grade ASTs. The Contractor shall perform monthly assessment and inspection activities on the following two (2) above-grade ASTs, also located at Fort Stewart:
Bldg. 8040 (Shoppette): Tanks #1 and #2
3.1.6 This is the only fueling station on FS that consists of traditional above-grade ASTs. Inspection support will include trouble-shooting activities:
a. Functional checks via the automatic tank gauging system control panel (Veeder-Root or equivalent) of tank interstitial sensors, tank external overfill alarm, compliance well sensors (if applicable) and piping sump sensors.
b. Checking condition of spill containment manholes.
c. Visual inspection of dispenser cabinet, spill buckets and sump for potential leaks.
d. Removal of water or fuel that is present in sumps and spill buckets.
e. Replacement up to two (2) gaskets on sump lids and up to four (4) seals on spill bucket lids as needed.
| f | Photo document system deficiencies, as needed. |
| 3.2 | Annual Inspection of UST/AST/Vaulted AST Systems. |
| 3.2.1 | USTs. The Contractor shall perform the following annual testing and inspection activities on the following twelve (12) USTs at FS/HAAF: |
FS Bldg. 939 (Marne Shoppette): USTs #276, #277, #278, and #279; FS Bldg. 7736 (Bryan Village Shoppette): USTs #286, #287, and #288; HAAF Bldg. 931 (Hunter Corner Express): USTs #124, #125, and #126 at HAAF Bldg. 419 (Hunter Gas Kiosk): USTs #1A and #2B at HAAF.
a. Clean, test, calibrate and inspect Veeder-Root TLS-450 ATG system or equivalent and associated probes for the facility located inside the building.
b. Perform precision tank and line tightness testing in accordance with 40 CFR 280.
c. Perform inspection of interstitial space(s) in accordance with manufacturer’s specifications. Adjust interstitial brine level to meet manufacturer’s specifications, if the brine level is found to be out of specification.
d. Clean, calibrate and inspect all sensors within the interstitial monitoring system in accordance with manufacturer’s specifications.
e. Clean, calibrate and inspect all sensors within double-walled piping system(s) in accordance with manufacturer’s specifications. Verify that sensors will automatically shut- off or restrict flow of fuel (unleaded gasoline), if a leak is detected.
f. Inspect liquid float sensors in tank sumps.
g. Verify that sump and spill bucket lids are watertight. If not, remove water and reseal lids, as required.
h. Perform operational check of the automatic line leak detectors in accordance with 40 CFR 280 and provide documentation of passing tests.
i. Inspect sensors in pumping sumps and conduct operational check.
j. Replace any corroded caps on tank interstitial sensors.
k. Check for presence of fill port drop tubes and proper operation of auto-limiting valve.
l. Perform required Stage I Vapor Recovery Testing at one site: The Hunter Corner Express. This work is performed every 3 yrs and is next due in 2018.
3.2.2 Vaulted Below-Grade ASTs. The Contractor shall perform the following annual testing and inspection activities on the following four (4) vaulted below-grade ASTs, located at Fort Stewart:
Bldg. 7806 (Harmon Avenue Shoppette): Tanks #1 and #2 Bldg. 3050 (6th Street Mini-Mall): Tanks #1 and #2
a. Clean, test, calibrate and inspect Veeder-Root TLS-450 ATG system or equivalent and associated probes for the facility located inside building.
b. Perform precision tank and line tightness testing in accordance with 40 CFR 280.
c. Perform inspection of interstitial space(s) in accordance with manufacturer’s specifications.
d. Clean, calibrate and inspect all sensors within the interstitial monitoring system in accordance with manufacturer’s specifications.
e. Clean, calibrate and inspect all sensors within double-walled piping system(s) in accordance with manufacturer’s specifications. Verify that sensors will automatically shut-off or restrict flow of fuel (unleaded gasoline), if a leak is detected.
f. Inspect liquid float sensors in tank sumps.
g. Verify that sump and spill bucket lids are watertight. If not, remove water and reseal lids, as required.
h. Perform operational check of the automatic line leak detectors in accordance with 40 CFR 280 and provide documentation of passing tests.
i. Inspect sensors in pumping sumps and conduct operational check.
j. Replace any corroded caps on tank interstitial sensors.
k. Check for presence of fill port drop tubes and proper operation of auto-limiting valve.
| 3.2.3 | Above-Grade ASTs. A formal STI SP001 specifications/STI SP001 inspection will be performed annually on the above-grade AST at FS Building 350 (Winn Army Community Hospital), and at building 8040 (Shoppette) Tanks #1 and #2 in accordance with the guidelines set forth by the Steel Tank Institute. Ultrasonic thickness testing (A-scans) will be performed, as required. If internal corrosion is detected, the Contractor should note the location and extent of the corrosion and provide recommendations for follow-up. |
| 4 | Repairs. |
| 4.1 | In addition to the monthly and annual inspections, repairs shall be performed as needed. In the course of inspections, if a tank system is discovered to be inoperative (e.g. the automatic tank gauging system control panel is not functioning, or a leak is discovered) the Contractor will notify the COR. The Contractor will, to the best of his ability, map out the deficiency and the best course of action for correcting/repairing it. This will include an estimate of both cost and time for repair. After consultation with Environmental Division, the COR will notify the Contractor on the appropriate action to take to rectify the deficiency. |
| 4.1.1 | Minor Deficiencies: Minor deficiencies found during inspections shall be corrected at the time of discovery. Minor deficiencies are those deficiencies that could be corrected on site that would require less than four hours of labor to complete. |
| 4.1.2 | Reimbursable Parts: The Contractor is responsible for and will not be reimbursed for the first $100.00 of parts cost per storage tank associated with any minor repair. The Government shall reimburse the Contractor for the balance of the parts cost that cumulatively exceeds $100.00. This cost shall be based on a per tank/inspection basis. |
| 4.1.3 | In the event minor repairs cannot be made at the time of discovery due to parts availability or other reasons beyond the Contractor’s control, the Contractor shall immediately notify the designated representative. The Contractor shall provide a written deficiency report within 24 hours of discovery of the deficiency. Once issues preventing the repairs have been resolved, the Contractor shall return to the deficient tank and perform needed repairs. Any deficiencies identified shall be reported utilizing the Contractor’s checklist form. |
| 4.2 | In the event a major repair is needed, the Contractor shall provide the COR with a written proposal within 24 hours or 1 normal working day after storage tank system was evaluated. The proposal shall be detailed and itemized, including start date, estimated labor hours required (lead technician and helper technician if required) and parts list including Contractor’s cost of parts and shipping cost. The Contractor’s quotes shall clearly indicate whether all parts are available for immediate purchase by the Contractor or the date of their expected availability. |
| 4.2.1 | Upon request from the Contracting Officer, the Contractor may be requested to provide three price quotes and manufacturers specifications for materials. |
| 4.2.2 | Replacement components shall match the existing components when possible. |
| 4.2.3 | The Government reserves the right to prioritize the needed repairs and will incorporate this workload into the contract accordingly. |
| 4.2.4 | Building occupants/employees are not allowed to authorize any repairs. |
| 4.3 | Only one technician per repair shall be considered and invoiced as the lead technician. Any other personnel required to assist in the repairs shall be considered as helper technicians and invoiced accordingly. |
| 4.4 | Repair work must be initiated, authorized, and approved by either the KO or COR and shall be ordered when the Government determines repair of an existing fuel storage tank is required and cost effective. |
| 4.5 | The Government reserves the right to reject the offer to repair by the Contractor in the event the repairs are deemed excessive based on the cost of a new unit. |
| 4.6 | The Contractor shall not perform any Repair Work that would exceed the approved quote. |
| 4.7 | Upon completion of Repair Work, the Contractor shall test and certify the fuel storage tank system. |
| 4.7.1 | The Contractor’s QC representative shall conduct a 100% inspection and acceptance test of all repair work to ensure proper operations of the work completed prior to opening the system to the public. |
| 4.7.2 | Warranty: The Contractor shall warrant any completed work is free from defects in labor and materials for one (1) year, beginning on the date of acceptance by the Government or invoice date. During the warranty period, any work to correct deficiencies in materials or workmanship shall be performed by the Contractor at no additional cost to the Government, as directed by the Contracting Officer. |
The Contractor will promptly notify the COR of any inability to comply with any of the requirements of this contract.