SOLICITATION is added without the draft - HVAC 18 Aug 2020.pdf

PDF 732 KB Posted

Attached to
Replace HVAC System Federal contract opportunity
Solicitation number
W9124M-20-B-0015
Issued by
Department of the Army Materiel Command Mission and Installation Contracting Command

About this file

This solicitation is for the replacement of the HVAC system at Building 865 located at Hunter Army Airfield in Georgia. The project involves demolishing the existing HVAC system and installing a new system including a new chiller, chilled water piping and pumps, six new air handling units, thirty-four VAV units, hot water piping to each VAV coil, and new controls. The NAICS code is 238220 for plumbing, heating, and air conditioning contractors with a small business size standard of $16.5 million. The requirement is set aside as 100% for women-owned small businesses. Questions are due by August 25th and bids are due by September 15th at 2:00pm. The award will be a firm-fixed-price contract.

The Army Materiel Command Mission and Installation Contracting Command at Fort Stewart is the contracting agency. The project is to be completed within 180 days of award.

View the file

Other files for this federal contract opportunity

Other files attached to Replace HVAC System, newest first.
File Type Posted
ABSTRACT of Offers - 20-B-0015-Replace HVAC System.pdf PDF
ENCL 5 CDC DIY-cloth-face-covering-instructions.pdf PDF
2040-25 E-6 FIRE ALARM PLAN Rev-1.pdf PDF
AMENDMENT 01.pdf PDF
ENCL 4 200405_DoD Guidance on the Use of Cloth Face Coverings.pdf PDF
Asbestos Report -H bldg 865 UPDATED 6 JAN 2020.pdf PDF
IMG_1085.jpg JPG image
IMG_1087.jpg JPG image
Drawings-Full page photo.pdf PDF
Lead Based Paint Inspection.pdf PDF
IMG_1086.jpg JPG image
Drawings -revised.pdf PDF
DRAWINGS -HAAF-2040.pdf PDF
SOLICITATION1 - HVAC 17 Aug 2020.pdf PDF
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

0011511835-0001

PROJECT NO : Q5B-26-8J

PROJECT LOCATION : HUNTER ARMY AIRFIELD, GA

SET ASIDE : 100% Women ow ned small business

NAICS CODE : 238220 SIZE STANDARD: 16,500,000.00

MAGNITUDE OF CONSTRUCTION PROJECT : Betw een $ 1,000,000 and $ 5,000,000

All w ork shall be completed per Scope of Work, Terms and Conditions, Provisions, Clauses, Draw ings and Specif ications.

BONDS: Bid Bonds, Payment Bonds, and Performance Bonds w ill be required.

ENVIRONMENTAL REPORT: WIll be posted separatly.

SITE VISIT: Thursday, 20 August 2020 at 9:00 a.m.

DUE DATE FOR ALL QUESTIONS: Tuesday, 25 August 2020 @ 2:00p.m.

BID OPENING : Tuesday, 15 September, 2020 @ 2:00 p.m. at the Parking lot of Paul R.. Smith Education Center , 100 Know ledge Drive, Fort Stew art, GA 31314

X

TATJANA M. FISHER 912-767-3747

NOTE: In sealed bid solicitations "offer" and "offeror" mean "bid" and "bidder".

10. THE GOVERNMENT REQUIRES PERFORMANCE OF THE WORK DESCRIBED IN THESE DOCUMENTS

NEGOTIATED

12-Aug-2020

(RFP)

(IFB)

CALL:

Replace HVAC System

B. TELEPHONE NO. (Include area code) (NO COLLECT CALLS)

See Item 7

2. TYPE OF SOLICITATION

SEALED BID

3. DATE ISSUED

9. FOR INFORMATION A. NAME

SOLICITATION

NSN 7540-01-155-3212 1442-101 STANDARD FORM 1442 (REV. 4-85)

Prescribed by GSA FAR (48 CFR) 53.236-1(e)

11. The Contractor shall begin performance w ithin _______10 calendar days and complete it w ithin ________180 calendar days after receiving aw ard, X notice to proceed. This performance period is X mandatory, negotiable. (See _________________________52.211-10

12 A. THE CONTRACTOR MUST FURNISH ANY REQUIRED PERFORMANCE AND PAYMENT BONDS?

(If "YES," indicate within how many calendar days after award in Item 12B.)

X YES NO

13. ADDITIONAL SOLICITATION REQUIREMENTS:

A. Sealed offers in original and __________1 copies to perform the w ork required are due at the place specif ied in Item 8 by ___________ local time ______________15 Sep 2020 (date). If this is a sealed bid solicitation, offers must be publicly opened at that time.

shall be marked to show the offeror's name and address, the solicitation number, and the date and time of fers are due.

B. An offer guarantee X is, is not required.

C. All offers are subject to the (1) w ork requirements, and (2) other provisions and clauses incorporated in the solicitation in full text or by reference.

D. Offers providing less than _______60 calendar days for Government acceptance after the date offers are due w ill not be considered and w ill be rejected.

SOLICITATION, OFFER,

AND AWARD

(Construction, Alteration, or Repair)

1. SOLICITATION NO.

IMPORTANT - The "offer" section on the reverse must be fully completed by offeror.

4. CONTRACT NO.

7. ISSUED BY CODE

MICC - FORT STEWART

976 WILLIAM H. WILSON AVE SUITE 100

FORT STEWART GA 31314

W9124M

PAGE OF PAGES

1 OF

CODE

(Title, identifying no., date):

12B. CALENDAR DAYS

02:00 PM (hour) Sealed envelopes containing offers

5. REQUISITION/PURCHASE REQUEST NO. 6. PROJECT NO.

Q5B-26-8J

8. ADDRESS OFFER TO (If Other Than Item 7)

FAX:TEL: (912)767-8420 TEL: FAX:

W9124M20B0015 134

20B. SIGNATURE

(REV. 4-85)STANDARD FORM 1442 BACK

TO SIGN

NSN 7540-01-155-3212

SOLICITATION, OFFER, AND AWARD (Continued) (Construction, Alteration, or Repair)

CODE FACILITY CODE

17. The offeror agrees to perform the w ork required at the prices specif ied below in strict accordance w ith the terms of this solicitation, if this offer is accepted by the Government in w riting w ithin ________ calendar days after the date offers are due.

the minimum requirements stated in Item 13D. Failure to insert any number means the offeror accepts the minimum in Item 13D.)

AMOUNTS SEE SCHEDULE OF PRICES

18. The offeror agrees to furnish any required performance and payment bonds.

19. ACKNOWLEDGMENT OF AMENDMENTS

(The offeror acknowledges receipt of amendments to the solicitation -- give number and date of each)

AMENDMENT NO.

DATE

20A. NAME AND TITLE OF PERSON AUTHORIZED TO SIGN

OFFER (Type or print)

AWARD (To be completed by Government)

21. ITEMS ACCEPTED:

22. AMOUNT 23. ACCOUNTING AND APPROPRIATION DATA

24. SUBMIT INVOICES TO ADDRESS SHOWN IN ITEM

(4 copies unless otherwise specified)

CODE

(Insert any number equal to or greater than

20C. OFFER DATE

25. OTHER THAN FULL AND OPEN COMPETITION PURSUANT TO

10 U.S.C. 2304(c) 41 U.S.C. 253(c)

CODE27. PAYMENT WILL BE MADE BY:26. ADMINISTERED BY

(Include ZIP Code)14. NAME AND ADDRESS OF OFFEROR 15. TELEPHONE NO. (Include area code)

See Item 14

(Include only if different than Item 14)16. REMITTANCE ADDRESS

30B. SIGNATURE

29. AWARD (Contractor is not required to sign this document.)

document and return _______ copies to issuing office.) Contractor agrees Your of f er on this solicitation, is hereby accepted as to the items listed. This award con-to f urnish and deliv er all items or perf orm all work, requisitions identif ied summates the contract, which consists of (a) the Gov ernment solicitation and on this f orm and any continuation sheets f or the consideration stated in this y our of f er, and (b) this contract award. No f urther contractual document is contract. The rights and obligations of the parties to this contract shall be necessary .

gov erned by (a) this contract award, (b) the solicitation, and (c) the clauses, representations, certif ications, and specif ications or incorporated by ref er-ence in or attached to this contract.

30A. NAME AND TITLE OF CONTRACTOR OR PERSON AUTHORIZED 31A. NAME OF CONTRACTING OFFICER (Type or print)

30C. DATE

(Type or print)

TEL: EMAIL:

31B. UNITED STATES OF AMERICA 31C. AWARD DATE

BY

CONTRACTING OFFICER WILL COMPLETE ITEM 28 OR 29 AS APPLICABLE

(Contractor is required to sign this28. NEGOTIATED AGREEMENT

(M ust be fully completed by offeror)OFFER

W9124M20B0015

Section A - Solicitation/Contract Form

TABLE OF CONTENTS

PART I – THE SCHEDULE

• SECTION A – Solicitation/Contract Form

• SECTION B – Supplies or Services and Prices/Costs

• SECTION C – Descriptions/Specifications/Statement of Work

• SECTION D – N/A

• SECTION E – Inspection and Acceptance

• SECTION F – Description and Performance

• SECTION G – Contract Administration Data

• SECTION H – Special Contract Requirements

PART II – CONTRACT CLAUSES

SECTION I – Contract Clauses

PART III – LIST OF DOCUMENTS, EXIBITS AND OTHER ATTACHMENTS

SECTION J – List of Exhibits, Attachments, and Appendices

PART IV – REPRESENTATIONS AND INSTRUCTIONS

SECTION K – Representations, Certifications and Other Statements of Offerors or

Respondents SECTION L – Solicitation Provisions SECTION M – Evaluation Factors for Award

Section B - Supplies or Services and Prices

ITEM NO SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

0001 1 Job Replace HVAC Systems Bldg. 865, HAAF

FFP

Replace HVAC Systems Bldg. 865, HAAF FOB: Destination

PURCHASE REQUEST NUMBER: 0011511835-0001

PSC CD: Z2NB

NET AMT

BID PRICE

ITEM

NO.

DESCRIPTION

BID AMOUNT

0001 REPLACE HVAC SYSTEMS

AT BUILDING 865 AT HAAF

TOTAL

Section C - Descriptions and Specifications

TECHNICAL PROVISIONS GENERAL

Technical Provision General

REPLACE HEATING, VENTILATION & AIR

CONDITIONING (HVAC) SYSTEMS AT BUILDING 865 AT

HAAF

IJO NO. Q5B-26-8J

1. DESCRIPTION OF WORK:

The work covered by this (IJO) Individual Job Order consists of furnishing all plant, labor, materials and performing all operations required in connection with providing design/build services for “REPLACE HVAC SYSTEMS AT BUILDING 865 AT HAAF” complete in strict accordance with following requirements.

1.1 We estimate 6 months construction time.

The work includes, but is not necessarily restricted to, the following items.

1.1.1. SITE / CIVIL

1.1.2 STRUCTURAL

1.1.3 GENERAL CONSTRUCTION

The entire HVAC system will be demolished. The only items we will save and re-use is the boiler and its circulating pump. Return the temporary flexible Chilled Water (CW) piping running across the walkway at the rear of the building and through the Mechanical Room doors to DPW. The three existing fresh air roof intake hoods will remain & be re-used. Return both the Hot Water (HW) pump and the Chilled Water Pump (CW) pump over to DPW. All ductwork, grills and diffusers, chiller, air handling units, hot water and chilled water piping, controls and circuits will be removed and disposed of in accordance with the hunter army airfield policies.

At 7 feet off the corridor wall in each office, the ceiling, and the wood blocking and a row of ceiling mounted lighting will be removed in each office for the new bulkhead and dropped ceiling. Openings will have to be cut in the block walls for the medium pressure supply duct and for the Hot Water Supply (HWS) and Hot Water Return (HWR) lines between each office. Existing return air grills will be removed and the openings infilled with 8” Concrete Masonry Unit (CMU).

All of the corridor ceilings will be removed in order to access the existing ductwork above the ceilings. The corridor lighting and exit signs will be demolished. After new ductwork & piping is installed, new ceiling, lighting and exit/egress lighting will be installed.

Ceiling mounted electrical busway duct will be removed from the rear wing of the buildings. This existing busway is an old 400 Mega Hertz system that is no longer used and only the busway duct remains. Demolish the busway duct turn and it over to the government. Two existing rooftop fresh air intakes and their associated ductwork will be removed and the openings sealed (see architectural plans for details). These intakes are located at the end of the back corridor and at the left end of the front corridor (when facing the building). The (2) existing fresh air intakes (located above each mechanical room) will remain and be re-used.

ASBESTOS REMEDIATION

Attachment B is the environmental report. To our knowledge, there is existing asbestos insulation on limited piping & tanks in the mechanical room. This insulation is clearly marked. Much of the asbestos insulation has been removed however some places it was left in place (probably because it was difficult to access). All of the asbestos insulation will be removed (see the architectural plans for details). The report also mentions that there is a trace of asbestos material in the sheetrock mud.

Where this is disturbed, it must be remediated (see the architectural plans for details).

1.1.4 FIRE PROTECTION

The existing fire alarm/mass notification system will be re-used with new devices added as required.

1.1.5 PLUMBING

1.1.7 MECHANICAL

The HVAC system at building # 865 is outdated and has failed. The building is now provided with temporary HVAC using two temporary package HVAC systems with flex duct connections into the building blowing conditioned air into the corridors.

The original system was designed in the 1950’s and was updated in the 1970’s. It consists of a temporary chiller installed on a pad at the rear of the building with temporary flex chilled water supply and return lines installed on the ground and through openings cut into the mechanical room doors routed to the existing chilled water piping. This Chiller has failed and the AHU units have physically deteriorated.

We have been tasked to install a new HVAC chilled water system with a Variable Air Volume (VAV) unit in each office with DDC (direct digital controls). Each office will have a zone controller (thermostat) for individual control of that room.

The existing system has overhead in-line pumps on the supply & return chilled water lines and they supplied (3) air handler units, one of each wing of the building. The three thermostats measured the return air temperature at the return grills, giving an average temperature reading at each return grill and no zone controls (thermostat) in any of the rooms. It was an old design with low pressure supply air installed above the ceiling in the corridors, then ducted through the block walls into the offices, terminating in a wall mounted supply grill in two locations into the offices. The return duct system had a wall mounted return grill mounted in the corridor wall nearest to the air handler unit and pulled the return air through the room doors and through the corridors. This system does not meet the current Fire Codes as the corridors are now protected egress corridors and the Fire Codes no longer allow this return in the egress corridors except in smaller residential applications. The building also has limited space above the ceilings of about 25”at the beam locations.

The new system design consists of a new chiller, all new chilled water piping and pumps and devices, six new air handling units and thirty four VAV units (one for each office and one for each of the three corridors). The new system will be controlled with a new Direct Digital Control (DDC) system that has a Building Automatic Control (BACNET) interface.

The new return air system will be installed in the corridor ceilings and will duct through the block walls into the offices using the old supply openings. From that duct, they will be connected with flex duct to the ceiling lay-in return grills (2 per office).

The new medium pressure supply ducts will be routed above dropped ceilings in each office. This medium pressure duct will supply a VAV box in each classroom.

The VAV box has an air valve that will modulate the volume of conditioned air to satisfy each zone controller depending on the set-points. A hot water coil will be provided in each VAV box for heat/reheat. We will install a partition wall above the ceiling at 7’ into each classroom from the corridor. We will then install a 2’ x 2’ acoustic dropped ceiling in each classroom. This is being done to create additional ceiling cavity for the supply duct, the VAV box and for the hot water supply & return lines, lighting and supply and return diffusers. Where the medium pressure supply duct goes from office to office, openings will have to be cut in the existing block wall for the medium pressure supply duct and also for the hot water supply & return lines.

This will occur above the ceiling between each office on all wings of the building.

1.1.8 ELECTRICAL

Electrical upgrades include replacing the panel in the mechanical room including new circuits from this new panel to each AHU, HW & CW pumps, water heater, exhaust fans, controls and new lighting & receptacle circuits.

1.6 WORK BY OTHERS:

1.6.1 The Contractor shall afford the Government and separate contractor’s reasonable opportunity for the introduction and storage of their materials and equipment and the execution of their work, and shall connect and coordinate his work with theirs as required by the Contract Documents.

2. FACTORS AFFECTING PERFORMANCE UNDER THIS CONTRACT:

2.1 The Contractor shall coordinate use of the site for access, staging, and parking with the Contracting Officer.

2.2 Contractor shall be responsible for limiting access of it’s employees and subcontractors to the area of work defined in the Contract.

Contractor shall not have access to restrooms and amenities such as vending machines unless granted permission by the Contracting Officer Representative.

2.3 Contractor shall maintain haul routes to and from the job sites and the borrow pits, to include the borrow pit. In addition it is the contractor’s responsibility to meet all Local, State and Federal regulations for the operation of a borrow pit. Contractor shall control runoff and erosion on all excavation and backfilling operations.

2.4 For Environmental Requirements see Attachment B.

3. AS-BUILT RECORD DRAWINGS:

3.1 The Contractor shall be responsible for maintaining one set of master/record construction drawing prints on the job site on which he shall keep a neat and accurate record of all deviations from the original contract documents as the work progresses. The contractor is responsible for noting all changes and correction on these master/record construction drawing prints promptly as the changes occur in red ink(redline prints) and note date when these changes occurred, but in no case less often than on a weekly basis. The master/record construction drawing prints which are maintained in red ink shall indicate all the changes and modifications incorporated into the work as well as the following:

3.1.1 Actual locations of all subsurface and concealed utility lines, type of materials used, sizes, etc. In order that the location of these lines and appurtenances may be determined in the event the surface openings or indicators become covered or obscured, the master/record construction drawings shall show by offset dimensions to two permanently fixed surface features. Valves, splices boxes and similar appurtenances shall be located by dimensions along the utility run from a reference point.

The average depth below the surface of each run shall also be recorded.

3.1.2 Any shop drawings that constitute part of the design shall be included with the record drawings.

3.2 The master/record (redline construction drawings) prints with corrections, such as field changes and contract modifications, shall be certified by the Contractor as to their correctness and submitted to the Contracting Officer’s Representative (COR) for approval. Once these provisional master/record (redline construction drawing) prints have been approved by the COR, the COR will obtain a compact disc (CD) of computer generated construction drawings from the DPW Engineering Service Division, Building 1114 at Ft. Stewart or Building 1021 at Hunter AAF, as applicable. The contractor shall then transfer all corrections from redline construction drawing prints to the compact disc (CD) of computer generated construction drawings. Corrections done shall be in microStation “.dgn” format. The Contractor shall note on the computer generated construction drawings the words “AS-BUILT” in the revision block with the next revision number to identify any changes made. Also, revision number identification will be placed where any changes were made. The contractor shall then submit AS-BUILT compact disc (CD) of computer generated drawing and one (1) AS- BUILT hardcopy with contractor’s redline corrections to the COR to insure accuracy that all corrections made were transferred from redline construction drawing prints to AS-BUILT hardcopy prints. Once the COR approves the AS- BUILT hardcopy prints the COR will then turn over to DPW/ ESD/ Drafting section for final approval of AS-BUILT compact disc (CD) of computer generated drawings and at this time the Contractor can receive final payment.

4. SECURITY REQUIREMENTS.

4.1 Attached to the final contract shall be an

Antiterrorism/Operational Security cover sheet provided by the Core of Engineers (COE) with all the appropriate signatures. The cover sheet shall outline all, if any, security training requirements associated with the contract. All A/E employees, construction contractor employees and construction subcontractor employees, requiring access to government installations, facilities and controlled access areas shall complete AT Level I awareness training within 30 calendar days after contract start date or effective date of incorporation of this requirement into the contract, whichever is applicable. The A/E or construction contractor shall submit certificates of completion for each affected Architect/Engineer (A/E) employee, construction contractor employee and construction subcontractor employee to the COR or the Contracting Officer (if a COR has not been designated) within 30 calendar days after completion of training by all employees and subcontractor personnel.

AT level I awareness training is available at the following website:

https://jkodirect.jten.mil/.

All A/E employees, construction contractor employees and construction sub-contractor employees shall be briefed on the local iWATCH program. This training shall be completed within 30 calendar days of contract award and within 30 calendar days of new employees commencing performance with the results reported to the COR NLT 30 calendar days after contract award.

A/E, construction contractor and all associated construction sub-contractor employees shall comply with applicable Installation, facility, and area Commander’s local access and security policies and procedures. If required by this contract, the contractor shall also provide all information for background checks to meet Installation access requirements to be accomplished by installation Provost Marshal Office, Director of Emergency Services or Security Office. All A/E and contractor workforce must comply with all personal identity verification requirements as directed by DOD, HQDA and/or local policy. In addition to the changes otherwise authorized by the changes clause of this contract, should the Force Protection Condition (FPCON) at any individual facility or Installation change, the Government may require changes in A/E and contractor security matters or processes.

------------------------- -END OF TECHNICAL PROVISIONS GENERAL-------------------

COMBINED SPECIFICATIONS

DOCUMENT 00010

TABLE OF CONTENTS

DIVISION 1 - GENERAL REQUIREMENTS

Section 01000 General Requirements

DIVISION 2 - SITE CONSTRUCTION

NOT USED

DIVISION 3 - CONCRETE

Section 03300 Cast-In-Place Concrete

DIVISION 4 - MASONRY

Section 04800 Masonry

DIVISION 5 - METALS

NOT USED

DIVISION 6 - WOOD AND PLASTICS

NOT USED

DIVISION 7 - THERMAL AND MOISTURE PROTECTION

Section 07600 Flashing

DIVISION 8 - DOORS AND WINDOWS

Section 08110 Steel Doors And Frames Section 08710 Door Hardware

DIVISION 9 – FINISHES

DIVISION 10 - SPECIALTIES

NOT USED

DIVISION 11 - EQUIPMENT

NOT USED

DIVISION 12 - FURNISHINGS

NOT USED

DIVISION 13 - SPECIAL CONSTRUCTION

NOT USED

DIVISION 14 - CONVEYING SYSTEMS

NOT USED

DIVISION 15 - MECHANICAL

Section 15050 Basic Mechanical Materials Section 15080 Mechanical Insulation Section 15180 Hydronic Piping Section 15800 Air Distribution Section 15810 Ducts and Duct Accessories Section 15820 Air Distribution

Section 15900 Open EMCS and HVAC Controls Section 15950 Testing, Adjusting, and Balancing

DIVISION 16 - ELECTRICAL

Section 16010 Conductors and Cables Section 16020 Electrical Raceways Section 16030 Wiring Devices Section 16300 Fire Alarm and Mass Notification Section 16510 Luminaries

END OF TABLE OF CONTENTS

SECTION 03300

CAST-IN-PLACE CONCRETE

PART 1 – GENERAL

1.01 SUMMARY

A. Provide cast-in-place concrete for general building construction, including, without limitation:

1. Slabs on grade(Door stoops).

B. Requirements (materials, mixes, finishes) apply to concrete work specified in other sections, such as sidewalk paving and fill for metal pan stair treads.

1.02 SUBMITTALS

A. Mix Design: Submit for approval mix design proposed for use.

B. Concrete strength: Submit 7 and 28 day cylinder tests.

1.03 QUALITY ASSURANCE

A. Comply with governing codes and regulations. Provide products of acceptable manufacturers which have been in satisfactory use in similar service for three years. Use experienced installers. Deliver, handle, and store materials in accordance with manufacturer's instructions.

B. Testing: Employ an independent testing agency acceptable to Government to design concrete mixes and to perform material evaluation tests. Provide 7 and 28 day cylinder tests. Comply with ASTM C 143, C 173, C 31 and C 39.

1. Perform minimum of one test (two cylinders per test) per day for each day concrete is placed and for each 50 cubic yards placed.

C. Standards:

1. ACI 301, Specifications for structural Concrete for Buildings.

2. ACI 318, Building Code Requirements for Reinforced Concrete, and CRSI Manual of Standard Practice.

PART 2 – PRODUCTS

2.01 MATERIALS

A. Concrete Design Mixes, ASTM C 94, 28 Day Compressive Strength:

1. Exterior Site Concrete and Pads Exposed to Weather:

a. Compressive Strength: 4000 psi, Air-Entrained.

B. Formwork: Plywood or metal panel formwork sufficient for structural and visual requirements.

C. Reinforcing Materials:

1. Steel Wire: ASTM A 82.

2. Steel Wire Fabric: ASTM A 497, welded, deformed.

D. Concrete Materials: ASTM C 150, Type I, Portland cement; potable water.

1. Normal weight aggregates, ASTM C 33.

E. Concrete Admixtures: Containing less than 0.1 percent chloride ions.

1. Air-Entraining Admixture: ASTM C 260, for exterior exposed concrete and foundations exposed to freeze-thaw.

2. Water-Reducing Admixture: ASTM C 494, Type A, for placement and workability.

3. High-Range Water-Reducing Admixture, Super Plasticizer: ASTM C 494, Type F or G for placement and workability.

4. Water-Reducing, Accelerating Admixture: ASTM C 494, Type E for placement and workability.

5. Water-Reducing, Retarding Admixture: ASTM C 494, Type D for placement and workability.

F. Concrete Finishes for Monolithic Slabs:

1. Nonslip broom finish for exterior concrete platforms, steps, ramps, door stoops and sloped walks.

PART 3 – EXECUTION

3.01 INSTALLATION

A. Comply with ASTM C 94. Do not change mix design without approval. Calcium chloride admixtures are not permitted.

B. Chamfer exposed edges/corners to provide straight lines.

C. Slab Finishes: Obtain sample approval before beginning work.

1. Broom: After trowel finishing, roughen surface by fine brooming perpendicular to traffic direction for exposed exterior walks, steps, stoops and ramps.

3.02 CURING AND PROTECTION

A. Comply with ACI standards for Hot and Cold Weather Concreting.

B. Concrete shall be protected against loss of moisture and rapid temperature changes for at least 7 days from the beginning of curing operation. All equipment needed for adequate curing and protection of the concrete shall be on hand and ready for use before actual concrete placement begins.

Protection shall be provided as necessary to prevent cracking due to temperature changes during the curing period.

B. CURING: Begin initial curing as soon as free water has disappeared from exposed surfaces. Continue curing by use of moisture-retaining cover or membrane-forming curing compound. Cure formed surfaces by moist curing until forms are removed. Provide protection as required to prevent damage to exposed concrete surfaces.

END OF SECTION

SECTION 04800

MASONRY

A. Provide unit masonry construction:

1. 8” masonry in-fill for removed doors and ventilation grilles.

A. Product Data: Submit manufacturer's product data and installation instructions for each material and product used.

have been in satisfactory use in similar service for three years.

Use experienced installers. Deliver, handle, and store materials in accordance with manufacturer's instructions.

PART 2 – PRODUCTS

2.01 MATERIALS

A. Concrete Masonry Units:

1. Concrete Masonry Units: ASTM C 90, 1500 f'm compressive strength:

a. Normal weight.

2. Size: Face dimension of 7-5/8 inches high by 15-5/8 inches long by 7 5/8”” wide.

3. Special Finish: N/A.

4. Special Shapes: As required by building configuration.

5. Bond Pattern: Running Bond.

B. Mortar and Grout for Concrete Masonry Unit Assemblies:

1. Mortar Mix: ASTM C 270, Type S, for reinforced masonry, masonry below grade and masonry in contact with earth and ASTM C 270, Type N, for abovegrade loadbearing and nonloadbearing walls and parapet walls and for interior loadbearing and nonloadbearing partitions.

2. Mortar Materials: Portland cement, ASTM C 150, Type I or II.

3. Mortar Aggregate: Natural color, ASTM C 144.

4. Grout Aggregate: ASTM C 404.

5. Hydrated Lime: ASTM C 207, Type S.

6. Color: Natural color.

C. Reinforcing Steel:

1. Reinforcing Bars: ASTM A 615, Grade 60.

D. Reinforcing: Welded wire with deformed side rods.

1. Steel Wire: 9 gauge (.1875 inch) galvanized steel.

2. Type: Ladder or truss type.

3.1 INSTALLATION

A. Installation of Masonry Assemblies:

1. Comply with PCA Recommended Practices for Laying Concrete Block, Brick Institute of America BIA Tech Notes, and NCMA TEK Bulletins.

2. Comply with Masonry Industry Council recommendations for Hot and Cold Weather Masonry Construction.

3. Sawcut units when required. Maintain uniform joint width. Provide full bed, head and collar joints.

4. Install lintels and accessories in masonry construction.

5. Coordinate installation of flashings.

6. Comply with applicable codes and regulations for spacing of ties and horizontal reinforcing.

7. Provide expansion and control joints in accordance with BIA and NCMA recommendations.

8. Remove and replace damaged units.

9. Clean concrete masonry by dry brushing, NCMA TEK No. 28.

SECTION 07600

FLASHING

A. Provide flashing at new masonry door opening have been in satisfactory use in similar service for three years. Use experienced installers. Deliver, handle, and store materials in accordance with manufacturer's instructions.

PART 2 – PRODUCTS

2.01 MATERIALS

A. Applications:

1. Exterior wall flashing.

B. Sheet Metal Flashing and Trim:

1. Zinc-Coated Steel: ASTM A 653, G90 hot-dip galvanized, 20 gauge (.0359 inch).

2. Extruded Aluminum: 6063-T52, clear anodized, 0.080 inches for primary legs of extrusion.

C.Fabricated Units: Compliance with SMACNA Sheet Metal Manual.

D. Auxiliary Materials:

1. Solder compatible with metal.

2. Mastic and elastomeric sealantsC

3. Rosin-sized building paper slip sheet.

A. Follow recommendations of SMACNA Sheet Metal Manual. Allow for expansion. Isolate dissimilar materials.

B.Install materials and systems in accordance with manufacturer's instructions and approved submittals. Install materials and systems in proper relation with adjacent construction and with uniform appearance. Coordinate with work of other sections.

B. Restore damaged components and finishes. Clean and protect work from damage.

SECTION 08110

STEEL DOORS AND FRAMES

A. Provide steel doors and frames.

A. Product Data: Submit manufacturer's product data and installation instructions for each material and product used.

B. Shop Drawings: Submit shop drawings indicating material characteristics, details of construction, connections, and relationship with adjacent construction.

A. Comply with governing codes and regulations. Provide products of acceptable manufacturers which have been in satisfactory use in similar service for three years. Use experienced installers. Deliver, handle, and store materials in accordance with manufacturer's instructions.

B. Standards: ANSI/SDI-100, Recommended Specifications for Standard Steel

Doors and Frames.

C. Performance Standards:

1. Thermal-Rated Assemblies at Exterior: ASTM C 236 or ASTM C 976.

PART 2 – PRODUCTS

2.01 MATERIALS

A. Manufacturers: Amweld Building Products, Ceco Door Products, Curries Co., Mesker Door, Steelcraft Manufacturing, or approved equal.

B. Steel Doors:

1. Door Type: Standard steel doors with hollow or composite construction.

3. Exterior Doors: ANSI/SDI-100, Grade II, heavy-duty, minimum 18 gauge (.0358 inch) cold-Rolled galvanized sheet steel, 1-3/4 inches thick.

4. Finish: Factory primed and field painted.

C. Steel Frames:

1. Exterior Frames:

a. Material: Galvanized sheet steel.

b. Corners: Mitered or coped.

c. Type: Welded.

d. Thickness: 16 gauge (.0358 inch).

3. Accessories:

a. Door silencers

b. Aluminum threshold

4. Finish: Factory primed and field painted.

3.01 INSTALLATION

A. Fabricate work to be rigid, neat and free from seams, defects, dents, warp, buckle, and exposed fasteners. Install doors and frames in compliance with SDI-100, NFPA 80, and requirements of authorities having jurisdiction.

B. Provide thermally improved doors with maximum U-value of 0.24 BTU/hr./sq. ft. degree F (ASTM C 236) for all exterior doors and elsewhere as noted.

C. Hardware: Prepare doors and frames to receive hardware on final schedule. Provide for 3 silencers on single door frames; 2 on double door frames.

D. Shop Finish: Clean, treat and prime paint all work with rust-inhibiting primer comparable with finish paint specified in Division 9 section. Provide asphalt emulsion sound deadening coating on concealed frame interiors.

E.Touch-up damaged coatings and leave ready to receive finish painting.

SECTION 08710

DOOR HARDWARE

A. Provide door hardware as indicated on drawings.

A. Product Data: Submit manufacturer's product data and installation instructions for each material and product used.

B. Submit for approval hardware schedule proposed for use based on Government's requirements.

have been in satisfactory use in similar service for three years. Use experienced installers. Deliver, handle, and store materials in accordance with manufacturer's instructions.

B. Materials and Application: ANSI / BHMA A156 series standards.

A. Manufacturers: Corbin Russwin Architectural Hardware, Sargent Manufacturing,Schlage Lock Co., Yale Locks and Hardware, or equal.

B. Door Hardware:

1. Hinges: BHMA A156.1, 4 1/2 by 4 1/2 inches unless otherwise specified. Construct loose pin hinges for exterior doors and reverse-bevel interior doors so that pins will be non removable when door is closed.

Other antifriction bearing hinges may be provided in lieu of ball-bearing hinges.

2. Lock Cylinders: Interchangeable.

3. Cylinders and Cores

a. Provide cylinders and cores for new locks, including locks provided under other sections of this specification. Cylinders and cores shall have [six] [seven] pin tumblers. Cylinders shall be products of one manufacturer, and cores shall be the products of one manufacturer. Rim cylinders, mortise cylinders, and knobs of bored locksets shall have interchangeable cores which are removable by special control keys.

Stamp each interchangeable core with a key control symbol in a concealed place on the core.

4. Keying System:

a. Equipment spaces and mechanical rooms shall be keyed separately from the building systems and shall be keyed alike to the existing key system for these doors. Provide Best / Arrow compatible core, SKD1 key.

5. Keys: Furnish one file key, one duplicate key, and one working key for each key change and for each master [and grand master] keying system]. Furnish one additional working key for each lock of each keyed-alike group. [Furnish two additional keys for each sleeping room.] [Furnish [[_____] great grand master keys,] [[_____] construction master keys,] [and [_____] control keys for removable cores].] [Furnish a quantity of key blanks equal to 20 percent of the total number of file keys.] Stamp each key with appropriate key control symbol and "U.S. property - Do not duplicate." Do not place room number on keys.

6. Lock Trim: Provide lever handles in lieu of knobs unless otherwise noted.

7. Closers: BHMA A156.4, Series C02000, Grade 1, with PT 4C.

8. Door Stops and Silencers: BHMA A156.16. Silencers Type L03011. Provide three silencers for each single door, two for each pair.

9. Thresholds: BHMA A156.21. Use J35100, with vinyl or silicone rubber insert in face of stop, for exterior doors opening out, unless specified otherwise.

10. FINISHES: BHMA A156.18. Hardware shall have BHMA 630 finish (satin stainless steel), unless specified otherwise.

PART 3 – EXECUTION

3.01 INSTALLATION

A Follow guidelines of DHI "Recommended Locations for Builder's Hardware and hardware manufacturers' instructions.

B. Install materials and systems in accordance with manufacturer's instructions and approved submittals. Install materials and systems in proper relation with adjacent construction and with uniform appearance. Coordinate with work of other sections.

C. Adjust operation, clean and protect.

SECTION 09260

GYPSUM BOARD ASSEMBLIES

A. Provide gypsum board assemblies:

1. Interior bulkheads with tape and joint compound finish.

1.02 SUBMITTALS

A. Product Data: Submit manufacturer's product data and installation instructions for each material and

1.02 QUALITY ASSURANCE

have been in satisfactory use in similar service for three years. Use experienced installers. Deliver, handle, and store materials in accordance with manufacturer's instructions.

B. Tolerances: Not more than 1/16 inch difference in true plane at joints between adjacent boards before finishing. After finishing, joints shall be not be visible. Not more than 1/8 inch in 10 feet deviation from true plane, plumb, level and proper relation to adjacent surfaces in finished work.

C. Performance: Fire, structural, and seismic performance meeting requirements of building code and local authorities.

PART 2 – PRODUCTS

2.01 MATERIALS

A. Manufacturers of Gypsum Board: Domtar Gypsum, Georgia-Pacific Corp., National Gypsum Co., United States Gypsum Co., or equal.

B. Manufacturers of Steel Framing and Furring: Dale Incor, Dietrich Industries, Marino Ware, National Gypsum Co., Unimast, or equal.

C. Manufacturers of Grid and Suspension Systems: Armstrong World Industries, Chicago Metallic, USG Interiors, or equal.

D. Gypsum Board:

1. Gypsum Wallboard for Tape and Joint Compound Finish: ASTM C 36, regular, moisture-resistant, mold

- resistant, foil-backed, and fire-rated types as required:

a. Typical Thickness: 5/8 inch.

2. Joint Treatment: ASTM C 475 and ASTM C 840, 3-coat system, paper or fiberglass tape.

E. Trim Accessories:

1. Material: Metal or plastic trim.

2. Types: Cornerbead, edge trim, and control joints.

F. Auxiliary Materials:

1. Gypsum board screws, ASTM C 1002.

2. Gypsum board nails, ASTM C 514.

3. Fastening adhesive.

PART 3 – EXECUTION

A. Install metal framing in compliance with AISI S220. Install with tolerances necessary to produce substrate for gypsum board assemblies with tolerances specified.

B. Install gypsum board for tape and 3-coat joint compound finish in compliance with ASTM C 840 and GA 216, Recommended Specifications for the Application and Finishing of Gypsum Board.

Install gypsum board assemblies’ true, plumb, level and in proper relation to adjacent surfaces.

C. Install boards vertically. Do not allow butt-to-butt joints and joints that do not fall over framing members.

D. Install trim in strict compliance with manufacturer's instructions and recommendations.

E. Repair surface defects. Leave ready for finish painting or wall treatment.

SECTION 09513

ACOUSTICAL TILE CEILINGS

A. Provide acoustical tile ceilings and metal suspension system.

A. Product Data: Submit manufacturer's product data and installation instructions for each material and product used.

B. Samples: Submit two representative samples of each material specified indicating visual characteristics and finish. Include range samples if variation of finish is anticipated.

B. Extra Stock: Submit extra stock equal to 2% of amount installed.

have been in satisfactory use in similar service for three years. Use experienced installers. Deliver, handle, and store materials in accordance with manufacturer's instructions.

B. Performance: Fire, structural, and seismic performance meeting requirements of building code and local authorities. Acoustical performance based on project requirements.

PART 2 – PRODUCTS

2.01 MATERIALS

A. Manufacturers:

1. Acoustical Units: Armstrong World Industries, Celotex, USG Interiors or equal.

2. Metal Suspension Systems: Armstrong World Industries, Celotex, Donn, Chicago Metallic or equal.

2.02 ACOUSTICAL UNITS FOR EXPOSED-GRID

A. Units for Exposed-Grid System

1. Type: III non-asbestos mineral fiber

2. Minimum NRC: 0.75

4. Nominal size: 24 by 24 inches.

5. Edge detail: Square

6. Finish: Factory-applied standard finish

7. Minimum LR coefficient: LR-1, 0.75 or greater

8. Minimum CAC: 40

9. Flame Spread: Class A, 25 or less

2.03 EXPOSED-GRID SUSPENSION SYSTEM

A. Components: Main runners and cross tees, base metal and end detail, fabricated from commercial quality steel complying with ASTM A 366 or A 625. Main runners and cross tees to be double web steel construction with exposed flange design.

1. Type:

a. Standard.

2. Structural Classification: ASTM C 635

a. Intermediate Duty.

3. Flange: 15/16 inch.

4. Finish:

a. Exposed surfaces chemically cleansed, protective coated, capping prefinished steel in baked-on enamel paint.

5. Color: Grid shall be white unless noted otherwise.

B. Suspended ceiling framing system shall have the capability to support the finished ceiling, light fixtures, air diffusers, and accessories, as shown. The suspension system shall have a maximum deflection of 1/360 of span length.

C. Attachment Devices: Size for five times design load indicated in ASTM C 635, Table 1, Direct Hung unless otherwise indicated.

D. Wire for Hangers and Ties: ASTM A 641, Class 1 zinc coating, soft temper, prestretched, with a yield stress load of at least three times design load, but not less than 12 gage (2.05 mm).

E. Edge Moldings and Trim: Steel or aluminum of types and profiles indicated or, if not indicated, manufacturer’s standard moldings for edges and penetrations, including light fixtures, that fit type of edge detail and suspension system indicated. Provide moldings with exposed flange of the same width as exposed main runner.

1. Hold-down clips and impact clips.

PART 3 – EXECUTION

3.01 INSTALLATION

A. Install materials and suspension systems in accordance with manufacturer's instructions and recommendations, and ASTM C 636. Coordinate installation with location of mechanical and electrical work to ensure proper locations.

B. Level ceiling to within 1/8" in 10' in both directions. Scribe and cut panels to fit accurately. Measure and layout to avoid less than half panel units.

D. Adjust, clean, and touch-up all system components.

SECTION 09910

PAINTING

A. Provide the following:

1. Painting and surface preparation for interior unfinished surfaces as indicated on drawings.

2. Painting and surface preparation for new H.C. doors and frames as indicated on drawings.

A. Product Data: Submit manufacturer's product data and installation instructions for each material and

B. Samples: Submit two representative samples of each material specified indicating visual characteristics and finish. Include range samples if variation of finish is anticipated.

1. Include manufacturer's full range of color and finish options if additional selection is required.

C. Extra Stock: Submit 2 unopened gallons of each paint and color used in the project.

1.03 QUALITY ASSURANCE

A. Comply with governing codes and regulations. Provide products of acceptable manufacturers which have been in satisfactory use in similar service for three years. Use experienced Installers. Deliver, handle, and store materials in accordance with manufacturer's instructions.

B. Regulations: Compliance with VOC and environmental regulations.

PART 2 - PRODUCTS

2.01 MATERIALS

A. Manufacturers: ICI Devoe Coatings, Benjamin Moore, Pratt and Lambert, Sherwin Williams or approved equal. Multicolor finishes by Polomyx, Zolatone or approved equal. First-line commercial-quality products for all coating systems.

A. Inspect surfaces, report unsatisfactory conditions in writing; beginning work means acceptance of substrate.

B. Comply with manufacturer's instructions and recommendations for preparation, priming and coating work. Coordinate with work of other sections.

C. Re-coat or remove & replace work which shows loss of adhesion. Clean up, touch up and protect work.

3.02 PAINT SCHEDULE

A. Gypsum Drywall Bulkheads:

1. Gloss:

a. Eg-shell

2. System:

a. 1 coat latex primer

b. 2 coats latex finish B. Galvanized Metal:

1. Gloss:

b. Semi

2. System:

a. 1 coat galvanized metal primer(factory applied). Touch up in field as reruired.

b. 2 coats exterior latex

BASIC MECHANICAL MATERIALS

SECTION 15050

A. Work of this section includes providing basic mechanical materials including, but not limited to, the following:

1. Valves.

2. Pipe expansion joints.

3. Meters and gages.

4. Supports and anchors.

5. Motors.

6. Mechanical identification.

7. Vibration control.

1.02 SUBMITTALS

A. Product Data: Submit manufacturer's product data and installation instructions for each material and product used.

B. Shop Drawings: Submit shop drawings indicating material characteristics, details of construction, connections, and relationship with adjacent construction.

C. Operation and Maintenance Data: Submit manufacturer's operation and maintenance data, including operating instructions, list of spare parts and maintenance schedule.

1.03 QUALITY ASSURANCE

A. Comply with governing codes and regulations. Provide products of acceptable manufacturers which have been in satisfactory use in similar service for three years. Use experienced installers. Deliver, handle, and store materials in accordance with manufacturer's instructions.

PART 2 - PRODUCTS

2.01 PRODUCTS

A. Provide components and equipment that are "standard products" of a manufacturer regularly engaged in the manufacturing of products that are of a similar material, design and workmanship. "Standard products" is defined as being in satisfactory commercial or industrial use for 2 years before bid opening, including applications of components and equipment under similar circumstances and of similar size, satisfactorily completed by a product that is sold on the commercial market through advertisements, manufacturers' catalogs, or brochures. Products having less than a 2-year field service record are acceptable if a certified record of satisfactory field operation, for not less than 6000 hours exclusive of the manufacturer's factory tests, can be shown. Provide equipment items that are supported by a service organization. Where applicable, provide equipment that is an ENERGY STAR Qualified product or a Federal Energy Management Program (FEMP) designated product.

C. Pipe, Fittings, and Specialties: Refer to individual piping systems specifications for materials and installation requirements.

D. Supports and Anchors: Hangers and Support Components: MSS SP-58, pipe and equipment hangers and supports including clamps, hanger-rod attachments, saddles and shields, spring hangers, pipe alignment guides, and anchors.

D. Valves: General duty valves cast iron, bronze, and brass, fabricated to comply with Manufacturers Standardization Society (MSS) classification listed. Gate, globe, ball,butterfly, and plug valves for shutoff duty; globe, ball, and plug valves for throttling duty.

1. Gate Valves, 2-Inch and Smaller for Condenser Water, Chilled Water, Domestic Hot and Cold Water:

MSS SP-80, Class 125 or 150 based on system pressure, cast bronze, threaded or solder ends based on service.

2. Gate Valves, 2-Inch and Smaller for Heating Hot Water and Low-Pressure Steam: MSS SP-80, Class 150, cast bronze, threaded or solder ends based on service.

3. Gate Valves, 2-1/2-Inch and Larger: MSS SP-70, Class 125, iron body, flanged ends.

4. Ball Valves, 1 Inch and Smaller: Rated for 150 psi saturated steam pressure, 400 psi WOG pressure, 2 piece construction, bronze body, threaded or solder ends based on service.

5. Ball Valves, 1-1/4-Inch to 2-Inch: Rated for 150 psi saturated steam pressure, 400 psi WOG pressure, 3 piece construction, bronze body, threaded or solder ends based on service.

6. Plug Valves, 2-Inch and Smaller: Rated at 150 psi WOG, bronze body, threaded ends.

7. Plug Valves, 2-1/2-Inchand Larger: MSS SP-78, rated at 175 psi WOG, semi-steel body, flanged ends.

8. Globe Valves, 2-Inch and Smaller: MSS SP-80, Class 125 or 150 based on system pressure, cast bronze, threaded or solder ends based on service.

9. Globe Valves, 2-1/2-Inch and Larger: MSS SP-85, Class 125, iron body, flanged ends.

10. Butterfly Valves: 2-1/2-Inch and Larger: MSS SP-67, rated at 200 psi, cast iron body, field replaceable sleeve, stainless steel stem, lug or wafer type based on service.

11. Swing Check Valves, 2-Inch and Smaller: MSS SP-80, Class 125 or 150 based on system pressure, cast-iron body and cap, threaded or solder ends based on service.

12. Swing Check Valves, 2-1/2 Inch and Larger: MSS SP-71, Class 125 or Class 175 FM for fire protection piping systems), cast iron body and cap, flanged ends.

13. Wafer Check Valves: Class 250, cast-iron body, to open with one foot differential pressure.

14. Lift Check Valves, 2-Inch and Smaller: Class 125, cast-bronze body and cap, threaded ends.

E. Expansion Joints for Piping Systems: Joints shall provide 200 percent absorption capacity of piping expansion between anchors.

1. Packless expansion joints.

2. Slip joints.

3. Flexible ball pipe joints.

4. Mechanical grooved fittings.

5. Fabricated expansion loops.

F. Meters and Gages: Temperature and indicator ranges for services required. Accuracy of thermometers: plus or minus 1 percent.

1. Mercury-In-Glass Thermometers: Die-cast, aluminum finished, glass front, mercury filled tube with magnifying lens.

2. Direct-Mount Filled-System Dial Thermometers: Vapor actuated, universal angle, drawn steel or cast aluminum case with glass lens.

3. Remote-Reading Filled-System Dial Thermometers: Vapor actuated, drawn steel or cast aluminum case with glass lens.

4. Bimetal Dial Thermometers: Direct mounted, bimetal, universal angle type with stainless steel case, glass lens.

5. Dial-Type Insertion Thermometers: Bimetal, stainless steel case and stem.

6. Thermometer Wells: Brass or stainless steel, pressure rated to match piping system design pressure.

7. Pressure Gages: General use, ASME B40.1, Grade A, phosphor bronze bourdon-tube type, drawn steel or brass case, glass lens.

8. Pressure Gauge Accessories: Brass tubing straight coil syphon; brass snubber with disc suitable for fluid served and rated pressure.

9. Wafer Orifice-Type Flood Elements: Differential-pressure type, cast-iron body, brass valves with integral check valves and caps.

10. Venturi-Type Flow Elements: Differential-pressure type, for installation in piping, bronze or cadmium-plated steel with brass fittings.

11. Pitot Tube-Type Flow Elements: Differential-pressure pitot tube-type design with probed, stainless steel probe.

12. Window-Type Flow Meters: Designed for installation on hydronic piping, measure flow directly in gpm, bronze body and impact tube, integral self-closing valve with indicator valve, plus or minus 5 percent accuracy.

13. BTU Meters: Turbine wheel flow meter, temperature sensors, calculator with integral battery back, bronze housing, plus or minus 1 percent accuracy.

14. Test Plugs: Nickel-plated brass body, self-sealing valve-type core inserts.

G. Supports and Anchors: Hangers and Support Components: MSS SP-58, pipe and equipment hangers and supports including clamps, hanger-rod attachments, saddles and shields, spring hangers, pipe alignment guides, and anchors.

H. Motors: NEMA MG 1 motors with phase, frequency rating, voltage rating, and capacity suitable for use.

I. Mechanical Identification: ASME A13.1 as applicable, color coded, of the following types:

Standard stencils, snap-on plastic pipe markers, pressure-sensitive pipe markers, plastic duct markers, plastic tape, valve tags, valve tag fasteners, access panel markers, valve schedule frames, engraved plastic laminate signs, plastic equipment markers, plasticized tags suitable for use.

J.