FOR CONSTRUCTION 05/19/2017

CIRCUIT CONDUIT CONDUCTORS

1 1.25 2 No. 4 and 1 No. 4 (G)

2 1.25 2 No. 4 and 1 No. 4 (G)

3 1 2 No. 6 and 1 No. 6 (G)

4 1.25 2 No. 4 and 1 No. 4 (G)

5 0.75 2 No. 8 and 1 No. 8 (G)

6 0.75 2 No. 8 and 1 No. 8 (G)

7 1 2 No. 6 and 1 No. 6 (G)

8 1 2 No. 6 and 1 No. 6 (G)

9 1.25 2 No. 4 and 1 No. 4 (G)

10 1.25 2 No. 3 and 1 No. 3 (G)

11 1.5 2 No. 2 and 1 No. 2 (G)

12 1 2 No. 6 and 1 No. 6 (G)

FEEDER SCHEDULE

REFER TO THE ELECTRICAL DETAILS, SHEET E‐2 FOR

CONDUIT AND ROUGH‐IN INFORMATION.

CKT# AMPS POLES DESCRIPTION LOAD PH. A PH. B LOAD DESCRIPTION POLES AMPS CKT#

1 50 2 FEEDER 1 4800 9600 4,800 FEEDER 7 2 50 2

3 4800 9600 4,800 4

5 50 2 FEEDER 2 4800 9600 4,800 FEEDER 8 2 50 6

7 4800 9600 4,800 8

9 50 2 FEEDER 3 4800 9600 4,800 FEEDER 9 2 50 10

11 4800 9600 4,800 12

13 50 2 FEEDER 4 4800 9600 4,800 FEEDER 10 2 50 14

15 4800 9600 4,800 16

17 50 2 FEEDER 5 4800 9600 4,800 FEEDER 11 2 50 18

19 4800 9600 4,800 20

21 50 2 FEEDER 6 4800 5750 950 PUMP STATION 2 30 22

23 4800 5750 950 24

25 30 3 SURGE SUPPRESSOR SPACE 2 26

27 28

29 180 180 RECEPTACLE 1 20 30

CONNECTED LOAD/PHASE 53,930 53,750

TOTAL CONNECTED LOAD (VA) 107,680

TOTAL CONNECTED LOAD (AMPERES) 449

PANELBOARD: RV VOLTAGE: 240V PHASE: 1 WIRE: 3 MAIN BREAKER: 300/2 TRIM: SURFACE

BRACING: 10,000 AIC ENCLOSURE: NEMA 3R WITH LOCKING COVER.

DEMAND LOAD PER NFPA 70, TABLE 551.73A (AMPERES)

Signed_Cover
3833-02 C-1 Existing Site Plan
3833-03 C-2 Site Plan
3833-04 C-3 Grading and Drainage Plan
3833-05 C-4 Civil Details
3833-06 C-5 Sewage & Water Plan
3833-07 C-6 Sewage and Water Details
3833-08 ES-1
3833-09 ES-2
3833-10 ES-3
3833-11 E-1 Electrical Site Plan
3833-12 E-2 Electrical Details