Appendix E.pdf
PDF 1 MB Posted
- Attached to
- HVAC EQUIPMENT REPAIRS AND REPLACEMENT
- Solicitation number
- W9123825QA008
About this file
This document is a comprehensive set of technical drawings and control logic diagrams for an HVAC system installation at the USFS Mirov Lab in Placerville, California. The drawings, prepared by Total Control and dated February 27, 2024, detail the technical specifications for a Johnson Controls Metasys-based building automation and climate control system, including LAN architecture, wiring schematics, control panel configurations, and detailed logic diagrams for various components such as the boiler, air handler, exhaust fans, and VAV (Variable Air Volume) zone controls.
The technical documentation covers multiple interconnected systems, including a 20-ton rooftop package single-zone air handler with hot water heating, a boiler system with a secondary hot water pump, and multiple VAV terminal units serving different lab spaces like the Pathology Lab, Seed Workroom, Tissue Culture, and DNA Workrooms. The system is designed with advanced control features including occupancy-based temperature management, heating and cooling sequence of operations, damper and flow control, and comprehensive monitoring capabilities with multiple alarm and trend tracking functionalities. The system utilizes 208V-3 phase power and includes features like economizer dampers, DX cooling equipment, and integrated temperature and airflow control across different lab zones.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFI Questions and Answers.pdf | ||
| Solicitation - W9123825QA008.pdf | ||
| Appendix B.pdf | ||
| Appendix D.pdf | ||
| Wage detemination.pdf | ||
| PWS.pdf | ||
| Appendix C.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FEB 27, 2024
P E
R F
O R
M A
N C
E
H
A T
IN
G
A N
D A
IR
U
S F
S
M
IR
O V
L A
B
T H
IS
D
O C
U M
E N
T C
O N
T A
IN
S
R
O P
R
IE
T A
R Y
I N
F O
R M
A T
IO
N
W
IC
H
S H
A L
L N
O T
B
P R
O D
U C
E D
T
R A
N S
F E
R R
D
T O
O T
H E
R D
O C
U M
E N
T S
D
IS
C L O
S E
D T
O O
T H
E R
S U
S
F
R M
A N
U F
A C
T U
R
IN
G O
R A
Y
H E
R P
U R
P O
S E
W
IT
H O
U
IO
R
W R
IT
T
E N
P E
R M
IS
S
O M
R S
D /T
O T
A L C
O N
T R
O L
S h e e t T it le
P ro je c t:
C o n tr a c to r:
P L
A C
E R
V
IL
L E
C
A
Sheet:
Job #:
Designed By:
Drawing By:
Date:
813151
JMG
JMG
R e v is io n s
R e v D a te
C h a n g e
C o m m e rc e D ri v e
R o s e v ill e C
A
-7
-5
-7
-5
F a x
Approved By: JMG
Total Control is a factory authorized Johnson Controls Metasys Specialist.
Total Control assures through Training, Project Management, Application Engineering, On-site Start-up Assistance and over 45 years of Metasys experience, the operational conformance and satisfaction of each and every installed system.
TABLE OF CONTENTS
SHEET
INDEX
LAN Architecture
Sequence of Operation
(NC-1) NCE Panel Wiring Schematic
(B-1) Boiler Control Panel Wiring Schematic
(HW-1) Booster Pump Panel Wiring Schematic
VAV Zone Control Wiring Schematic (Typical of 7)
IOM Exhaust Fan Control Wiring Schematic
AC-1 Air Handler Control
TITLE
IN
D
E X
USFS Mirov Lab
E
R F
O R
M A
N
A T
IN
G
A N
D A
IR
U
S F
S
M
IR
O V
L A
B
T H
IS
D
O C
U M
E N
T C
O N
T A
O P
R
IE
T A
R Y
I N
F O
R M
A T
IC
H
S H
A L
L N
O T
P R
O D
U C
E D
T
R A
N S
F E
R R
O T
H E
R D
O C
U M
E N
T S
D
IS
C L O
S E
D T
O O
T H
E R
S U
S
R M
A N
U F
A C
T U
R
IN
G O
R A
H E
R P
U R
P O
S E
W
IT
H O
IO
R
W R
IT
T
E N
P E
R M
IS
S
O M
R S
D /T
O T
A L C
O N
T R
O L
S h e e t T it le
P ro je c t:
C o n tr a c to r:
P L
A C
E R
V
IL
L E
C
A
Sheet:
Job #:
Designed By:
Drawing By:
Date:
813151
JMG
JMG
R e v is io n s
R e v D a te
C h a n g e
C o m m e rc e D ri v e
R o s e v ill e C
A
-7
-5
-7
-5
F authorized Johnson Controls Metasys Specialist.
Total Control assures through Training, Project Management, Application Engineering, On-site Start-up Assistance and over 45 years of Metasys experience, the operational conformance and satisfaction of each and every installed system.
L A
N A rc h it e c tu re
NCE PANEL
TCP-11
HW Control
CUSTOMER LAN
1 LAN Architecture
WORKSTATIONWORKSTATION
VAV-2
ADD: 06
VAV-2
ADD: 06
VAV-03
ADD: 07
VAV-03
ADD: 07
VAV-4
ADD: 08
VAV-4
ADD: 08
VAV-5
ADD: 09
VAV-5
ADD: 09
VAV-6
ADD: 10
VAV-6
ADD: 10
VAV-7
ADD: 11
VAV-7
ADD: 11
IOM-1
ADD: 14
IOM-1
ADD: 14
IOM-2
ADD: 15
IOM-2
ADD: 15
FEC - 1
ADD: 12
FEC - 1
ADD: 12
72° F
72° F
ZN-T
72° F
ZN-T
72° F
72° F
ZN-T
72° F
ZN-T
72° F
72° F
ZN-T
72° F
ZN-T
72° F
72° F
ZN-T
72° F
ZN-T
72° F
72° F
ZN-T
72° F
ZN-T
72° F
72° F
ZN-T
72° F
ZN-T
Architecture
The FC Bus and the SA Bus are both networks of daisy-chained devices.
The maximum allowable length of each bus is determined by the total length and type of cable between each daisy-chained device on the segment. For the FC Bus, the maximum allowable device counts and maximum lengths are based on the number of segments.
The FC Bus can be devided into segments by repeaters (See Below). The SA Bus is only one segment.
Segment 1
5,000 ft (maximum)
50 Nodes (maximum)*
RETSY
EOL Switch ON (Up)
NAE
TT T
T
T
R R
T
= EOL switch set to ONT
R = Repeater odes (max)* 100 Total N
Segment 2
5,000 ft (maximum)
50 Nodes (maximum)*
Segment 3
5,000 ft (maximum)
50 Nodes (maximum)*
Architecture
The FC Bus and the SA Bus are both networks of daisy-chained devices.
The maximum allowable length of each bus is determined by the total length and type of cable between each daisy-chained device on the segment. For the FC Bus, the maximum allowable device counts and maximum lengths are based on the number of segments.
The FC Bus can be devided into segments by repeaters (See Below). The SA Bus is only one segment.
Segment 1
5,000 ft (maximum)
50 Nodes (maximum)*
RETSY
EOL Switch ON (Up)
NAE
TT T
T
T
R R
T
= EOL switch set to ONT
R = Repeater odes (max)* 100 Total N
Segment 2
5,000 ft (maximum)
50 Nodes (maximum)*
Segment 3
5,000 ft (maximum)
50 Nodes (maximum)*
SA BUS
SA BUS
SA BUS
SA BUS
SA BUS
SA BUS
FC BUS
Address Controller Label Description/Location
5 VMA CAV-1 Pathology Lab
6 VMA VAV-2 Seed Workroom
7 VMA VAV-3 Tissue Culture
8 VMA VAV-4 DNA Workroom
9 VMA VAV-5 DNA Workroom
10 VMA VAV-6
11 VMA VAV-7 Microscopy Workroom
12 SPARE
13 FEC BOILER Boiler Skid
14 IOM IOM-1 w/ CAV-1
15 IOM IOM-2 w/ VAV-7
16 McQuay AH-1 Air Handler
Address Table
CAV-1
ADD: 05
CAV-1
ADD: 05
Microtech III
Air Handler Controller
169.254.132.143
Workstation provided by customer.
Dedicated Data Line
(530) 622-7289
E
R F
O R
M A
N
A T
IN
G
A N
D A
IR
U
S F
S
M
IR
O V
L A
B
T H
IS
D
O C
U M
E N
T C
O N
T A
O P
R
IE
T A
R Y
I N
F O
R M
A T
IC
H
S H
A L
L N
O T
P R
O D
U C
E D
T
R A
N S
F E
R R
O T
H E
R D
O C
U M
E N
T S
D
IS
C L O
S E
D T
O O
T H
E R
S U
S
R M
A N
U F
A C
T U
R
IN
G O
R A
H E
R P
U R
P O
S E
W
IT
H O
IO
R
W R
IT
T
E N
P E
R M
IS
S
O M
R S
D /T
O T
A L C
O N
T R
O L
S h e e t T it le
P ro je c t:
C o n tr a c to r:
P L
A C
E R
V
IL
L E
C
A
Sheet:
Job #:
Designed By:
Drawing By:
Date:
813151
JMG
JMG
R e v is io n s
R e v D a te
C h a n g e
C o m m e rc e D ri v e
R o s e v ill e C
A
-7
-5
-7
-5
F authorized Johnson Controls Metasys Specialist.
Total Control assures through Training, Project Management, Application Engineering, On-site Start-up Assistance and over 45 years of Metasys experience, the operational conformance and satisfaction of each and every installed system.
S e q u e n c e o f
O p e ra ti o n
SEQUENCE OF OPERATION
Heating Hot Water System: The boiler shall be enabled whenever AC-1 is operating and the outside air temperature falls below 60°F (user adjustable).
During unoccupied periods, the boiler shall be enabled if the outside air temperature falls below an adjustable low limit setpoint (initially 35°F) to ensure circulation through the heating hot water coils at low outside air temperature.
A flow switch in the heating hot water return piping is factory hardwire interlocked to disable the boiler if there is no flow. The secondary hot water pump (HWP-1) shall be software interlocked to disable the boiler if the pump is not operating. HWP-1 shall run for at least 5 minutes (user adjustable) after the boiler has been disabled due to lack of demand. The boiler shall operate when enabled by the Temperature Control and Facility Management
System (TCFMS) only through its own safeties. The TCFMS shall monitor the status of HWP-1 and report if the status does not match the commanded state.
Secondary hot water pump (HWP-1) VFD shall modulate to maintain the differential pressure at the heating hot water coil serving VAV-3.
Trends:
Boiler Supply Temperature
Heating Water Loop Supply Temperature
Alarms:
High Heating Water Loop Supply Temperature
Low Heating Water Loop Supply Temperature
High Boiler Supply Temperature
Low Boiler Supply Temperature
Boiler Alarm
Boiler Failure
Secondary Heating Water Pump Failure Low Secondary Heating Water Loop Pressure
Building Exhaust Fans: Exhaust fan EF-5 shall be software interlocked to start whenever AC-1 is operating. A current switch on EF-5 shall monitor the fan status and shut down AC-1 in the event of a fan failure.
Exhaust fan EF-4 shall be operable only when AC-1 is operating. EF-4 shall operate from a local start/stop switch.
A current switch shall monitor each fan in the event of a failure.
Trends:
None
Alarms:
Exhaust Fan EF-5 Failure
Exhaust Fan EF-4 Failure
Toilet Exhaust Fans: Toilet Exhaust Fans shall be interlocked (by Div. 16 contractor) to operate with restroom light switch.
Fume Hood: A current switch on EF-3 shall monitor the fan status.
Trends:
None
Alarms:
Exhaust Fan EF-3 Failure
Air Conditioning Unit AC-1: AC-1 shall be controlled and monitored through the Bacnet integration to the TCFMS.
AC-1 shall start whenever the TCFMS indicates occupied mode based on the weekly time schedule or whenever a push-button override switch at a
VAV zone temperature sensor indicates a local temporary override. The
TCFMS shall monitor the status of the fan and refrigeration systems and report if the status does not match the commanded state. The TCFMS shall monitor the status of the supply and return fans, and shut down exhaust fan
EF-5 in the event of a fan failure.
The heating hot water coil control valve, economizer dampers, and DX cooling equipment shall operate in sequence to maintain the supply air temperature setpoint (user adjustable). The DX cooling equipment shall be software locked out if the mixed air temperature is below the low limit setpoint (user adjustable). The outside air and exhaust air dampers shall close when AC-1 is stopped. The heating hot water coil control valve shall remain open during unoccupied periods to ensure flow should the boiler be enabled due to low outside air temperature.
Trends:
Supply Air Temperature
Alarms:
Supply Fan Failure
Return Fan Failure
DX Cooling Failure
Outside Air Temperature Low Limit
Mixed Air Temperature Low Limit
High Supply Air Temperature
Low Supply Air Temperature
Duct Smoke Detector Alarm
Dirty Filter Alarm
High Building Static Pressure Alarm
Low Building Static Pressure Alarm
High Supply Duct Static Pressure Alarm
Low Supply Duct Static Pressure Alarm
CAV Boxes With Reheat: CAV box CAV-1 shall be programmed to control for a constant volume of supply air during occupied periods. The reheat coil control valve shall modulate to maintain zone temperature heating setpoint.
During unoccupied periods, the reheat valve shall remain open to ensure flow should the boiler be activated due to low outside air temperatures.
Trends:
Zone Temperature
Alarms:
High Zone Temperature Alarm
Low Zone Temperature Alarm
VAV Boxes With Reheat: The cooling and heating mode status will be received by each zone VAV terminal. If the cooling mode is enabled, the VAV terminal’s temperature control PID loop will be set to direct acting and the effective setpoint will be set to the box’s cooling setpoint. The box air flow will be modulated between the box’s minimum and maximum flow in order to maintain zone temperature cooling setpoint. If the heating mode is enabled, the VAV terminal’s temperature control PID loop will be set to reverse acting and the effective setpoint will be set to the box’s heating setpoint. The box air flow will be modulated between the box’s minimum and maximum flow, and the reheat coil control valve shall modulate, to maintain zone temperature heating setpoint. During unoccupied periods, the reheat valve shall remain open to ensure flow should the boiler be activated due to low outside air temperatures.
Trends:
Zone Temperature
Alarms:
High Zone Temperature Alarm Low Zone Temperature Alarm
1 Sequence of Operations
E
R F
O R
M A
N
A T
IN
G
A N
D A
IR
U
S F
S
M
IR
O V
L A
B
T H
IS
D
O C
U M
E N
T C
O N
T A
O P
R
IE
T A
R Y
I N
F O
R M
A T
IC
H
S H
A L
L N
O T
P R
O D
U C
E D
T
R A
N S
F E
R R
O T
H E
R D
O C
U M
E N
T S
D
IS
C L O
S E
D T
O O
T H
E R
S U
S
R M
A N
U F
A C
T U
R
IN
G O
R A
H E
R P
U R
P O
S E
W
IT
H O
IO
R
W R
IT
T
E N
P E
R M
IS
S
O M
R S
D /T
O T
A L C
O N
T R
O L
S h e e t T it le
P ro je c t:
C o n tr a c to r:
P L
A C
E R
V
IL
L E
C
A
Sheet:
Job #:
Designed By:
Drawing By:
Date:
813151
JMG
JMG
R e v is io n s
R e v D a te
C h a n g e
C o m m e rc e D ri v e
R o s e v ill e C
A
-7
-5
-7
-5
F authorized Johnson Controls Metasys Specialist.
Total Control assures through Training, Project Management, Application Engineering, On-site Start-up Assistance and over 45 years of Metasys experience, the operational conformance and satisfaction of each and every installed system.
(N C
-1
N C
E P a n e l W ir in g S c h e m a ti c
1 NCE Panel (NC-1) Wiring Schematic 2 NCE Panel (NC-1) Wiring Schematic (Continued)
XF1XF1
L1L1
NN
L1
CB
10A
CB
10A 120V 1Ø
Provided By Electrician
120V 1Ø
Provided By Electrician
ENC
HOTHOT
COMCOM2
V A
C HOT
COM2
V A
C
+15V+15V
IN1IN1
ICOM1ICOM1
IN2IN2
ICOM2ICOM2
+15V+15V
IN3IN3
ICOM3ICOM3
IN4IN4
ICOM4ICOM4
+15V+15V
IN5IN5
ICOM5ICOM5
IN6IN6
ICOM6ICOM6
+15V+15V
IN7IN7
ICOM7ICOM7
IN8IN8
ICOM8ICOM8
+15V+15V
IN9IN9
ICOM9ICOM9
IN10IN10
ICOM
ICOM
IN11IN11
ICOM
ICOM
IN12IN12
ICOM
ICOM
IN13IN13
ICOM
ICOM
IN14IN14
ICOM
ICOM
IN15IN15
ICOM
ICOM
IN16IN16
ICOM
ICOM
IN17IN17
ICOM
ICOM
IN18IN18
ICOM
ICOM
MS-NCE25XX-XX
R
MS-NCE25XX-XX
I1 Exhaust Fan 1 Status
U I2 Exhaust Fan 3 Status
U
I3 SPARE
U
I4 SPARE
U
I5 SPARE
U
I6 SPARE
U
I7 SPARE
U
I8 SPARE
U
I9 SPARE
U I1
SPARE
B I1
SPARE
B I1
SPARE
B I1
SPARE
B I1
SPARE
B I1
SPARE
B I1
SPARE
B I1
SPARE
B I1
SPARE
UNIVERSAL INPUTS
BINARY INPUTS
S A
B U
S
COMCOM
SHLDSHLD
S A
B U
S
COM
SHLD
F C
B U
S
COMCOM
SHLDSHLD
F C
B U
S
COM
SHLD
LAN CONNECTION
SA BUS INPUT
Connects NCE to N2 Bus or FC
Bus segment.
Connects the
NCE field controller to the
SA Bus
Connects to a NS network sensor, a DIS1710 Local
Controller Display, or a
Wireless Commissioning
Converter (MS-BTCVT-0)
CONTINUED
ON NEXT DETAIL
HOT
COM2
V A
C
+15V
IN1
ICOM1
IN2
ICOM2
+15V
IN3
ICOM3
IN4
ICOM4
+15V
IN5
ICOM5
IN6
ICOM6
+15V
IN7
ICOM7
IN8
ICOM8
+15V
IN9
ICOM9
IN10
ICOM
IN11
ICOM
IN12
ICOM
IN13
ICOM
IN14
ICOM
IN15
ICOM
IN16
ICOM
IN17
ICOM
IN18
ICOM
MS-NCE25XX-XX
I1 Exhaust Fan 1 Status
U I2 Exhaust Fan 3 Status
U
I3 SPARE
U
I4 SPARE
U
I5 SPARE
U
I6 SPARE
U
I7 SPARE
U
I8 SPARE
U
I9 SPARE
U I1
SPARE
B I1
SPARE
B I1
SPARE
B I1
SPARE
B I1
SPARE
B I1
SPARE
B I1
SPARE
B I1
SPARE
B I1
SPARE
UNIVERSAL INPUTS
BINARY INPUTS
S A
B U
S
COM
SHLD
F C
B U
S
COM
SHLD
LAN CONNECTION
SA BUS INPUT
Connects NCE to N2 Bus or FC
Bus segment.
Connects the
NCE field controller to the
SA Bus
Connects to a NS network sensor, a DIS1710 Local
Controller Display, or a
Wireless Commissioning
Converter (MS-BTCVT-0)
CONTINUED
ON NEXT DETAIL
OUT1OUT1
OCOM1OCOM1
OUT2OUT2
OCOM2OCOM2
OUT3OUT3
OCOM3OCOM3
OUT4OUT4
OCOM4OCOM4
OUT5OUT5
OCOM5OCOM5
OUT6OUT6
OCOM6OCOM6
OUT7OUT7
OCOM7OCOM7
OUT8OUT8
OCOM8OCOM8
OUT9OUT9
OCOM9OCOM9
OUT10OUT10
OCOM
OCOM
OUT11OUT11
OCOM
OCOM
OUT12OUT12
OCOM
OCOM
OUT13OUT13
OCOM
OCOM
OUT14OUT14
OCOM
OCOM
OUT15OUT15
OCOM
OCOM
BINARY OUTPUTS
BINARY OUTPUT JUMPER POSITIONS
INTERNAL
POWER
EXTERNAL
POWER
CONFIGURABLE
OUTPUTS
ANALOG OUTPUTS
B O
SPARE
B O
SPARE
B O
SPARE
B O
SPARE
B O
SPARE
B O
SPARE
B O
SPARE
C O
SPARE
C O
SPARE
C O
SPARE
C O
SPARE
A O
SPARE
A O
SPARE
A O
SPARE
A O
SPARE
OUT1
JUMPER SETTING
OUT2
JUMPER SETTING
OUT3
JUMPER SETTING
OUT4
JUMPER SETTING
OUT5
JUMPER SETTING
OUT6
JUMPER SETTING
OUT7
JUMPER SETTING
OUT1
OCOM1
OUT2
OCOM2
OUT3
OCOM3
OUT4
OCOM4
OUT5
OCOM5
OUT6
OCOM6
OUT7
OCOM7
OUT8
OCOM8
OUT9
OCOM9
OUT10
OCOM
OUT11
OCOM
OUT12
OCOM
OUT13
OCOM
OUT14
OCOM
OUT15
OCOM
BINARY OUTPUTS
BINARY OUTPUT JUMPER POSITIONS
INTERNAL
POWER
EXTERNAL
POWER
CONFIGURABLE
OUTPUTS
ANALOG OUTPUTS
B O
SPARE
B O
SPARE
B O
SPARE
B O
SPARE
B O
SPARE
B O
SPARE
B O
SPARE
C O
SPARE
C O
SPARE
C O
SPARE
C O
SPARE
A O
SPARE
A O
SPARE
A O
SPARE
A O
SPARE
OUT1
JUMPER SETTING
OUT2
JUMPER SETTING
OUT3
JUMPER SETTING
OUT4
JUMPER SETTING
OUT5
JUMPER SETTING
OUT6
JUMPER SETTING
OUT7
JUMPER SETTING
FC+
FC-
COM
FC BUS CONNECTED TO ALL
CONTROLLERS BY DAISY CHAIN
(SEE LAN ARCHITECTURE PAGE
FOR SPECIFICATIONS)
SHIELD OPTIONAL
FC+
FC-
COM
FC BUS CONNECTED TO ALL
CONTROLLERS BY DAISY CHAIN
(SEE LAN ARCHITECTURE PAGE
FOR SPECIFICATIONS)
SHIELD OPTIONAL
Exhaust Fan 1 Status
24V
Exhaust Fan 1 Status
24V
Exhaust Fan 2 Status
24V
Exhaust Fan 2 Status
24V
TAG QTY DESCRIPTION
ENC 1 HAM SE0301675 Nema 1 20x20x7 Enclosure
XF-1 1 LEC LE15550 75VA 120V/24V Transformer
C-1 1 JC NCE2561-0 33 Points, MSTP, Modem
CB 1 AB 1489A1C100 10A Circuit Breaker
HUB 1 CAB GIG-500-S 5 Port Ethernet Hub
TB1 1 AB 1492-J4-BL Terminal Block, 10-22AWG Black
TB1_1 1 AB 1492-J4-W Terminal Block, 10-22AWG White
TB1_2 1 AB 1492-JG4 Ground Block, 10-22AWG
Panel Components
PART NUMBER
HUB
PWR
HUB
PWR
Ethernet Connection
To Workstation
Ethernet Connection
To Workstation
Ethernet Connection
To Mcquay Air Handler
Ethernet Connection
To Mcquay Air Handler
TB1
E
R F
O R
M A
N
A T
IN
G
A N
D A
IR
U
S F
S
M
IR
O V
L A
B
T H
IS
D
O C
U M
E N
T C
O N
T A
O P
R
IE
T A
R Y
I N
F O
R M
A T
IC
H
S H
A L
L N
O T
P R
O D
U C
E D
T
R A
N S
F E
R R
O T
H E
R D
O C
U M
E N
T S
D
IS
C L O
S E
D T
O O
T H
E R
S U
S
R M
A N
U F
A C
T U
R
IN
G O
R A
H E
R P
U R
P O
S E
W
IT
H O
IO
R
W R
IT
T
E N
P E
R M
IS
S
O M
R S
D /T
O T
A L C
O N
T R
O L
S h e e t T it le
P ro je c t:
C o n tr a c to r:
P L
A C
E R
V
IL
L E
C
A
Sheet:
Job #:
Designed By:
Drawing By:
Date:
813151
JMG
JMG
R e v is io n s
R e v D a te
C h a n g e
C o m m e rc e D ri v e
R o s e v ill e C
A
-7
-5
-7
-5
F authorized Johnson Controls Metasys Specialist.
Total Control assures through Training, Project Management, Application Engineering, On-site Start-up Assistance and over 45 years of Metasys experience, the operational conformance and satisfaction of each and every installed system.
(B -1
B o il e r
C o n tr o l P a n e l W ir in g S c h e m a ti c
1 Boiler Control Panel (B-1) Wiring Schematic
XF1XF1
L1L1
L2L2
L1
N 120V 1Ø120V 1Ø
ENC
O
N
O
N
ON
FC
BUS
ADD
6 8 4 2 1
FC ADD:
+15+15
CC
SS
F C
B U
S
CC
SS
S A
B U
S
HH
CC2
V
RJ RJ
IN1IN1
C1C1
IN2IN2
C2C2
IN8IN8
C8C8
O1O1
OC1OC1
O2O2
OC2OC2
O3O3
OC3OC3
O4O4
OC4OC4
O5O5
OC5OC5
O6O6
OC6OC6
O7O7
OC7OC7
U I1
U I2
Boiler Hot Water
Temperature
HW Diff Pressure
B I8 Boiler Status
INPUTS
OUTPUTS
B O
Boiler Command
B O
2 Hot Water Pump
Command
B O
SPARE
C O
SPARE
C O
SPARE
C O
SPARE
C O
SPARE
FEC2610
EOL
SWITCH
RJ-45 SENSOR INPUT
IN3IN3
C3C3
IN4IN4
C4C4
U I3
U I4
BLDG Hot Water
Return Temperature
BLDG Hot Water
Supply Temperature
IN5IN5
C5C5
IN6IN6
C6C6
U I5
U I6
Hot Water Pump Status
Outside Air
Temperature
+15+15
+15+15
IN7IN7
C7C7B I7 Boiler Alarm
O6O6
OC6OC6
O7O7
OC7OC7
A O
8 Hot Water Pump
Output
A O
SPARE
O
N
ON
FC
BUS
ADD
6 8 4 2 1
FC ADD:
+15
C
S
F C
B U
S
C
S
S A
B U
S
H
C2 V
RJ
IN1
C1
IN2
C2
IN8
C8
O1
OC1
O2
OC2
O3
OC3
O4
OC4
O5
OC5
O6
OC6
O7
OC7
U I1
U I2
Boiler Hot Water
Temperature
HW Diff Pressure
B I8 Boiler Status
INPUTS
OUTPUTS
B O
Boiler Command
B O
2 Hot Water Pump
Command
B O
SPARE
C O
SPARE
C O
SPARE
C O
SPARE
C O
SPARE
FEC2610
EOL
RJ-45 SENSOR INPUT
IN3
C3
IN4
C4
U I3
U I4
BLDG Hot Water
Return Temperature
BLDG Hot Water
Supply Temperature
IN5
C5
IN6
C6
U I5
U I6
Hot Water Pump Status
Outside Air
Temperature
+15
+15
IN7
C7B I7 Boiler Alarm
O6
OC6
O7
OC7
A O
8 Hot Water Pump
Output
A O
SPARE
FC+
FC-
COM
FC BUS CONNECTED TO ALL
CONTROLLERS BY DAISY CHAIN
(SEE LAN ARCHITECTURE PAGE
FOR SPECIFICATIONS)
SHIELD OPTIONAL
FC+
FC-
COM
FC BUS CONNECTED TO ALL
CONTROLLERS BY DAISY CHAIN
(SEE LAN ARCHITECTURE PAGE
FOR SPECIFICATIONS)
SHIELD OPTIONAL
Boiler Hot Water Supply Temperature
Platinum 1k
Boiler Hot Water Supply Temperature
Platinum 1k
HW Diff Pressure
4-20mA, 0-25 PSI
HW Diff Pressure
4-20mA, 0-25 PSI
Building Hot Water Return Temperature
Platinum 1k
Building Hot Water Return Temperature
Platinum 1k
Building Hot Water Supply Temperature
Platinum 1k
Building Hot Water Supply Temperature
Platinum 1k
Hot Water Pump Status
24VAC
(From HW-1 Panel)
Hot Water Pump Status
24VAC
(From HW-1 Panel)
Outside Air Temperature
Nickel 1k
(From HW-1 Panel)
Outside Air Temperature
Nickel 1k
(From HW-1 Panel)
Boiler Alarm
24VAC
Boiler Alarm
24VAC
Boiler Status
24VAC
Boiler Status
24VAC
GG
HH
GG
SHSH
PS1
PS1
LL
NN
LL
NN
1A1A
4A4A
Boiler Command
24VAC
Boiler Command
24VAC
Hot Water Pump Command
24VAC
(To HW-1 Panel)
Hot Water Pump Command
24VAC
(To HW-1 Panel)
Hot Water Pump Command
4-20mA
(To HW-1 Panel)
Hot Water Pump Command
4-20mA
(To HW-1 Panel)
24V
24V
COM
COM
Boiler
Booster Pump Control Panel
(HW-1)
See Page 6
VFD
STATUS
ENABLE
SPEED
STATUS
ENABLE
SPEED
Boiler Hot Water Supply Temperature
(To Boiler Control Panel B-1)
Boiler Hot Water Supply Temperature
(To Boiler Control Panel B-1)
Building Hot Water Return Temperature
(To Boiler Control Panel B-1)
Building Hot Water Return Temperature
(To Boiler Control Panel B-1)
Building Hot Water Supply Temperature
(To Boiler Control Panel B-1)
Building Hot Water Supply Temperature
(To Boiler Control Panel B-1)
Hot Water Pump Status
(To Boiler Control Panel B-1)
Hot Water Pump Status
(To Boiler Control Panel B-1)
Hot Water Pump Command
(From Boiler Control Panel B-1)
Hot Water Pump Command
(From Boiler Control Panel B-1)
Hot Water Pump Output
(From Boiler Control Panel B-1)
Hot Water Pump Output
(From Boiler Control Panel B-1)
DPT-1
OO ++
DPT-1
O +
NO NO
NC
R1R1 Enable
Status
Alarm
Boiler Enable
(From Boiler Control Panel B-1)
Boiler Enable
(From Boiler Control Panel B-1)
Boiler Status
(To Boiler Control Panel B-1)
Boiler Status
(To Boiler Control Panel B-1)
Boiler Alarm
(To Boiler Control Panel B-1)
Boiler Alarm
(To Boiler Control Panel B-1)
TS
TS
2TS
DPT
TAG QTY DESCRIPTION
ENC 1 HOFF C-SD20206 HC 20"x20"x6" NEMA 12 Enclosure
1 HOFF C-P2020 Sub Panel
1 HOFF C-WHK Lock for "Concept" Enclosure
C-1 1 JC FEU2610 FEC Controller, 6UI, 2BI, 3BO, 4CO, 2AO
XF-1 1 CORE T-202 85VA 120V/24V Transformer
PS-1 1 MAMAC PS-200-1-A-1-N PWR SPLY 120AC/24DC 1.5A
FD1 2 KELE M10/16SFL 16mm Fuseholder 24-8AWG 16A
FD1_2 1 BUSS AGC-1 Fuse 1A 250V .25"x1.25"
FD1_2 1 BUSS AGC-4 Fuse 4A 250V .25"x1.25"
FD1_1 2 KELE FEM8S 8mm End Section
LBL1 1 LOCAL LABEL Phenolic 1/2" Wht Ltr on Blk
TB1_A2 3 KELE KEL-M4/6 Terminal Block, 10-22AWG
TB1_A3 1 KELE KEL-M4/6.P Ground Block, 30A (Grn/Yel)
TB1_A1 1 Label Only Label Only
TB2_A1 5 KELE KEL-M4/6 Terminal Block, 10-22AWG
TB2_A2 1 KELE KELM4/6.P Ground Block, 30A (Grn/Yel)
TD1 1 KELE M4/6SNBT Terminal Block 22-10AWG DISC
PANEL COMPONENTS
PART NUMBER TAG QTY DESCRIPTION
DPT-1 1 SETRA 2301-025PD-3V-11 DPT Wet 0-25PSIG 4-20mA BYP AS
R1-R3 3 IDEC RH2B-ULAC24V DPDT 24V Relay w/ LED
3 IDEC SH2B-05 DPDT Relay Socket
TS1-3 3 MAMAC TE-703-D-3-A-3 Immersion Sensor 4" ak Pt 1/2" N4
3 MAMAC A-500-1-A-2 Well 4", SS 3/4" Ext, 1/2" Int
FIELD COMPONENTS
PART NUMBER
TB2
TB1
R2R2
R3R3
E
R F
O R
M A
N
A T
IN
G
A N
D A
IR
U
S F
S
M
IR
O V
L A
B
T H
IS
D
O C
U M
E N
T C
O N
T A
O P
R
IE
T A
R Y
I N
F O
R M
A T
IC
H
S H
A L
L N
O T
P R
O D
U C
E D
T
R A
N S
F E
R R
O T
H E
R D
O C
U M
E N
T S
D
IS
C L O
S E
D T
O O
T H
E R
S U
S
R M
A N
U F
A C
T U
R
IN
G O
R A
H E
R P
U R
P O
S E
W
IT
H O
IO
R
W R
IT
T
E N
P E
R M
IS
S
O M
R S
D /T
O T
A L C
O N
T R
O L
S h e e t T it le
P ro je c t:
C o n tr a c to r:
P L
A C
E R
V
IL
L E
C
A
Sheet:
Job #:
Designed By:
Drawing By:
Date:
813151
JMG
JMG
R e v is io n s
R e v D a te
C h a n g e
C o m m e rc e D ri v e
R o s e v ill e C
A
-7
-5
-7
-5
F authorized Johnson Controls Metasys Specialist.
Total Control assures through Training, Project Management, Application Engineering, On-site Start-up Assistance and over 45 years of Metasys experience, the operational conformance and satisfaction of each and every installed system.
(H W
-1
B o o s te r
P u m p
P a n e l W ir in g S c h e m a ti c
VFD
L1L1
L3L3
L2L2
T1T1
T3T3
T2T2
R
S
T
U
V
W
P1P1
CMCM
V1V1
CMCM
VFD
Enable
VFD Speed
Reference
DiscDisc
15A
15A
F1-F3
DiscDisc
CB1
20A
CB1
20A
C1
C1
X
-1 X
F -1
CB2
2A
CB2
2A
Boiler Power
Off On
Boiler Power
Off On
A1 A2 C1
A1 A2 C1
X1 X2
PL1
X1 X2
PL1
120V
24V
75VA
Boiler Power
On
H
H
C
C
3A3A
3C3CVFD
Status
5 9 R1-1 5 9 R1-1
208V, 3Ø, 10 FLA Provided by others.
A 25A MCCB or 20A J-Type fuses are recommended. Panel provides individual, branch short circuit protection.
208V, 3Ø, 10 FLA Provided by others.
A 25A MCCB or 20A J-Type fuses are recommended. Panel provides individual, branch short circuit protection.
208V 3HP Booster Pump
10 FLA
208V 3HP Booster Pump
10 FLA
120V, 1Ø, 25 FLA Provided by others.
A 60A MCCB or 45A J-Type fuses are recommended. Panel provides individual, branch short circuit protection.
120V, 1Ø, 25 FLA Provided by others.
A 60A MCCB or 45A J-Type fuses are recommended. Panel provides individual, branch short circuit protection.
Boiler Power
120V AC 15A
Boiler Power
120V AC 15A
ThermostatThermostatThermostatThermostat
Fan
1 Booster Pump Panel (HW-1) Wiring Schematic
ENC
T1T1
T2T2
T3T3
Hot Water Pump Command
24VAC
(From B-1 Control Panel)
Hot Water Pump Command
24VAC
(From B-1 Control Panel)
Hot Water Pump Status
24VAC
(To B-1 Control Panel)
Hot Water Pump Status
24VAC
(To B-1 Control Panel)
Hot Water Pump Output
4-20mA
(From B-1 Panel)
Hot Water Pump Output
4-20mA
(From B-1 Panel)
14 13 R1
14 13 R1
L1L1
NN
Panel furnished and installed on boiler skid by manufacturer
E
R F
O R
M A
N
A T
IN
G
A N
D A
IR
U
S F
S
M
IR
O V
L A
B
T H
IS
D
O C
U M
E N
T C
O N
T A
O P
R
IE
T A
R Y
I N
F O
R M
A T
IC
H
S H
A L
L N
O T
P R
O D
U C
E D
T
R A
N S
F E
R R
O T
H E
R D
O C
U M
E N
T S
D
IS
C L O
S E
D T
O O
T H
E R
S U
S
R M
A N
U F
A C
T U
R
IN
G O
R A
H E
R P
U R
P O
S E
W
IT
H O
IO
R
W R
IT
T
E N
P E
R M
IS
S
O M
R S
D /T
O T
A L C
O N
T R
O L
S h e e t T it le
P ro je c t:
C o n tr a c to r:
P L
A C
E R
V
IL
L E
C
A
Sheet:
Job #:
Designed By:
Drawing By:
Date:
813151
JMG
JMG
R e v is io n s
R e v D a te
C h a n g e
C o m m e rc e D ri v e
R o s e v ill e C
A
-7
-5
-7
-5
F authorized Johnson Controls Metasys Specialist.
Total Control assures through Training, Project Management, Application Engineering, On-site Start-up Assistance and over 45 years of Metasys experience, the operational conformance and satisfaction of each and every installed system.
OUT1
OCOM1
OUT2
OCOM2
OUT3
OCOM3
OUT4
OCOM4
OUT5
OCOM5
B
IN
A R
Y C
O N
F
IG
U R
A B
L E
U N
IV
E
R S
A L
+15
IN
ICOM
HOT
COM
SA PWR
COM
SHLD
COM
METASYS
MS-VMA1620-0
OUT2
OCOM2
OUT3
OCOM3
OUT4
OCOM4
OUT5
OCOM5
B
IN
A R
Y C
O N
F
IG
U R
A B
L E
U N
IV
E
R S
A L
+15
IN
ICOM
HOT
COM
SA PWR
COM
SHLD
COM
METASYS
MS-VMA1620-0
LOHIHI
OUT2
OCOM2
OUT3
OCOM3
OUT4
OCOM4
OUT5
OCOM5
B
IN
A R
Y C
O N
F
IG
U R
A B
L E
U N
IV
E
R S
A L
+15
IN
ICOM
HOT
COM
SA PWR
COM
SHLD
COM
METASYS
MS-VMA1620-0
LOHI
SA BUS
OUT2
OCOM2
OUT3
OCOM3
OUT4
OCOM4
OUT5
OCOM5
B
IN
A R
Y C
O N
F
IG
U R
A B
L E
U N
IV
E
R S
A L
+15
IN
ICOM
HOT
COM
SA PWR
COM
SHLD
COM
METASYS
MS-VMA1620-0
LOHI
SA BUS
V A
V Z o n e C o n tr o l W ir in g S c h e m a ti c
T y p ic a l o f
AHU SAAHU SA
NCNC
FLOW
STATION
HIHI LOLO
FLOW
STATION
HI LO
H
C
H
C
22 11
2 1
HWRHWR
HWSHWS
VAV TERMINAL UNIT
NC
NO
C
ZNT
VMA
HWV
ZONE SA
DA
24H
24C
1 VAV Zone Control Wiring Schematic (Typical of 7)
24VAC
From Transformer
24VAC
From Transformer
Discharge Air Temperature
Platinum 1k
Discharge Air Temperature
Platinum 1k
FC+
FC-
COM
FC BUS CONNECTED TO ALL
CONTROLLERS BY DAISY CHAIN
(SEE LAN ARCHITECTURE PAGE
FOR SPECIFICATIONS)
SHIELD OPTIONAL
FC+
FC-
COM
FC BUS CONNECTED TO ALL
CONTROLLERS BY DAISY CHAIN
(SEE LAN ARCHITECTURE PAGE
FOR SPECIFICATIONS)
SHIELD OPTIONAL
SA+
SA-
COM
SA BUS
CONNECTED TO ZONE STAT
AND ALL OTHER SA BUS DEVICES
(SEE LAN ARCHITECTURE PAGE
FOR SPECIFICATIONS)
PWR
SA+
SA-
COM
SA BUS
CONNECTED TO ZONE STAT
AND ALL OTHER SA BUS DEVICES
(SEE LAN ARCHITECTURE PAGE
FOR SPECIFICATIONS)
PWR
SA+
SA-
COM
SA BUS CONNECTION
TO THERMOSTAT
PWR
SA+
SA-
COM
SA BUS CONNECTION
TO THERMOSTAT
PWR
CC
PP
C
P
SA+
SA-
COM
SA BUS CONNECTION
TO THERMOSTAT
PWR
C
P
D is c h a rg e A ir T e m p e ra tu re
(T o
V M
A C o n tr o lle r)
D is c h a rg e A ir T e m p e ra tu re
(T o
V M
A C o n tr o lle r)
TAG QTY DESCRIPTION
ZN-T 6 JC NS-BTB7002 Zone Sensor w/ Setpoint Adj, LCD
VAV-1 7 JC AP-VMA1620-0 VMA Controller 1UI, 3BO, 2CO
HWV 7
DA-T 7 MAMACTE-201-B-3-A Duct Temp Sensor 1k Platinum
FIELD COMPONENTS
PART NUMBER
See Schedule
VALVE
ASSEMBLY
ACUTATOR CALC. ACT.
1 CAV CAV-1 1 HW B210 TR24-3/300 Floating 24 VAC 2 Way Straight 1/2 3/4 Fails Last Position FNPT 2.00 1.00 1.20 2.78 200 B210+TR24-3/300 US+NO+CAV-1
112 VAV VAV-2 1 HW B210 TR24-3/300 Floating 24 VAC 2 Way Straight 1/2 3/4 Fails Last Position FNPT 2.00 1.00 1.20 2.78 200 B210+TR24-3/300 US+NO+VAV-2
98 VAV VAV-3 1 HW B210 TR24-3/300 Floating 24 VAC 2 Way Straight 1/2 3/4 Fails Last Position FNPT 2.00 1.00 1.20 2.78 200 B210+TR24-3/300 US+NO+VAV-3
92 VAV VAV-4 1 HW B210 TR24-3/300 Floating 24 VAC 2 Way Straight 1/2 3/4 Fails Last Position FNPT 2.00 1.00 1.20 2.78 200 B210+TR24-3/300 US+NO+VAV-4
115 VAV VAV-5 1 HW B210 TR24-3/300 Floating 24 VAC 2 Way Straight 1/2 3/4 Fails Last Position FNPT 2.00 1.00 1.20 2.78 200 B210+TR24-3/300 US+NO+VAV-5
116 VAV VAV-6 1 HW B210 TR24-3/300 Floating 24 VAC 2 Way Straight 1/2 3/4 Fails Last Position FNPT 2.00 1.00 1.20 2.78 200 B210+TR24-3/300 US+NO+VAV-6
117 VAV VAV-7 1 HW B210 TR24-3/300 Floating 24 VAC 2 Way Straight 1/2 3/4 Fails Last Position FNPT 2.00 1.00 1.20 2.78 200 B210+TR24-3/300 US+NO+VAV-7
ACT.
PRESS.
DROP
CLOSE
OFF
(PSI)
PIPING
DETAIL
BELIMO ORDER CODE
VLV
SIZE
PIPE
SIZE
VALVE ACTION
CONN.
TYPE
FLOW
GPM
VALVE CV
AUTOMATIC TEMPERATURE CONTROL VALVE SCHEDULE (PRESSURE DROP USED IN CALCULATIONS: 4.0 PSI)
ITEM SYSTEM TAG QTY SERVICE
PART#
CONTOL
TYPE
CONTROL
SIGNAL
VALVE TYPE
MAX MIN
Basement B02A Pathology Lab AC-1 M2.1 CAV-1 VMA-1 AP-VMA1620-0 12 384 1075 1075
Basement Seed Workroom AC-1 M2.1 VAV-2 VMA-2 AP-VMA1620-0 10 314 735 230
Main Level M02A Tissue Culture AC-1 M2.2 VAV-3 VMA-3 AP-VMA1620-0 12 452 960 325 VAV-4, VAV-5 share a zone temp sensor
Main Level M02B DNA Workroom AC-1 M2.2 VAV-4 VMA-4 AP-VMA1620-0 12 452 1155 325
Main Level M02B DNA Workroom AC-1 M2.2 VAV-5 VMA-5 AP-VMA1620-0 12 452 1145 325
Main Level AC-1 M2.2 VAV-6 VMA-6 AP-VMA1620-0 12 452 910 325
INLET
SIZE
INLET
AREA
CFM
COMMENTS
BOX INFORMATIONLOCATION
AIR TERMINAL UNIT SCHEDULE
FLOOR
ROOM
NUMBE
NAME
SYSTEM
NAME
SENSOR
REF
BOX ID
CONTROLLER
ID
CONTROLLER
MODEL
E
R F
O R
M A
N
A T
IN
G
A N
D A
IR
U
S F
S
M
IR
O V
L A
B
T H
IS
D
O C
U M
E N
T C
O N
T A
O P
R
IE
T A
R Y
I N
F O
R M
A T
IC
H
S H
A L
L N
O T
P R
O D
U C
E D
T
R A
N S
F E
R R
O T
H E
R D
O C
U M
E N
T S
D
IS
C L O
S E
D T
O O
T H
E R
S U
S
R M
A N
U F
A C
T U
R
IN
G O
R A
H E
R P
U R
P O
S E
W
IT
H O
IO
R
W R
IT
T
E N
P E
R M
IS
S
O M
R S
D /T
O T
A L C
O N
T R
O L
S h e e t T it le
P ro je c t:
C o n tr a c to r:
P L
A C
E R
V
IL
L E
C
A
Sheet:
Job #:
Designed By:
Drawing By:
Date:
813151
JMG
JMG
R e v is io n s
R e v D a te
C h a n g e
C o m m e rc e D ri v e
R o s e v ill e C
A
-7
-5
-7
-5
F authorized Johnson Controls Metasys Specialist.
Total Control assures through Training, Project Management, Application Engineering, On-site Start-up Assistance and over 45 years of Metasys experience, the operational conformance and satisfaction of each and every installed system.
IO
M
E x h a u s t
F a n
C o n tr o l
W ir in g
S c h e m a ti c
1 Exhaust Fan 5 Wiring Schematic
3 Exhaust Fan 2 and 4 Wiring Schematic
O
N
O
N
ON
FC
BUS
ADD
6 8 4 2 1
FC ADD:
CC
SS
F C
/S A
B U
S
HH
CC2
V
RJ RJ
U I1
U I2
Exhaust Fan 5 (EF-5)
Status
SPARE
INPUTS
IOM2710
EOL
SA/FC PORT BUS
E
L A
Y
R E
L A
Y
Exhaust Fan 5 (EF-5)
Enable
SPARE
OUTPUTS
U O
SPARE
U O
SPARE
+15+15
+5+5
IN1IN1
C1C1
IN2IN2
C2C2
NONO
COMCOM
NCNC
NONO
COMCOM
NCNC
O3O3
OC3OC3
O4O4
OC4OC4
O
N
ON
FC
BUS
ADD
6 8 4 2 1
FC ADD:
C
S
F C
/S A
B U
S
H
C2 V
RJ
U I1
U I2
Exhaust Fan 5 (EF-5)
Status
SPARE
INPUTS
IOM2710
EOL
E
L A
Y
R E
L A
Y
Exhaust Fan 5 (EF-5)
Enable
SPARE
OUTPUTS
U O
SPARE
U O
SPARE
+15
+5
IN1
C1
IN2
C2
NO
COM
NC
NO
COM
NC
O3
OC3
O4
OC4
O
N
O
N
ON
FC
BUS
ADD
6 8 4 2 1
FC ADD:
CC
SS
F C
/S A
B U
S
HH
CC2
V
RJ RJ
U I1
U I2
Exhaust Fan 4 (EF-4)
Status
Exhaust Fan 2 (EF-2)
Status
INPUTS
IOM2710
EOL
E
L A
Y
R E
L A
Y
Exhaust Fan 4 (EF-4)
Enable
SPARE
OUTPUTS
U O
SPARE
U O
SPARE
+15+15
+5+5
IN1IN1
C1C1
IN2IN2
C2C2
NONO
COMCOM
NCNC
NONO
COMCOM
NCNC
O3O3
OC3OC3
O4O4
OC4OC4
O
N
ON
FC
BUS
ADD
6 8 4 2 1
FC ADD:
C
S
F C
/S A
B U
S
H
C2 V
RJ
U I1
U I2
Exhaust Fan 4 (EF-4)
Status
Exhaust Fan 2 (EF-2)
Status
INPUTS
IOM2710
EOL
E
L A
Y
R E
L A
Y
Exhaust Fan 4 (EF-4)
Enable
SPARE
OUTPUTS
U O
SPARE
U O
SPARE
+15
+5
IN1
C1
IN2
C2
NO
COM
NC
NO
COM
NC
O3
OC3
O4
OC4
SA+
SA-
COM
SA BUS CONNECTION TO CAV-1
(SEE LAN ARCHITECTURE SA BUS
NOTES FOR SPECIFICATIONS)
PWR
SA+
SA-
COM
SA BUS CONNECTION TO CAV-1
(SEE LAN ARCHITECTURE SA BUS
NOTES FOR SPECIFICATIONS)
PWR
SA+
SA-
COM
SA BUS CONNECTION TO VAV-7
(SEE LAN ARCHITECTURE SA BUS
NOTES FOR SPECIFICATIONS)
PWR
SA+
SA-
COM
SA BUS CONNECTION TO VAV-7
(SEE LAN ARCHITECTURE SA BUS
NOTES FOR SPECIFICATIONS)
PWR
24VAC
From CAV-1
24VAC
From CAV-1
Exhaust Fan 5 Enable
24V
Exhaust Fan 5 Enable
24V
24VAC
From CAV-1
24VAC
From CAV-1
Exhaust Fan 4 Enable
24V
Exhaust Fan 4 Enable
24V
Exhaust Fan 4 Status
24V
Exhaust Fan 4 Status
24V
Exhaust Fan 2 Status
24V
Exhaust Fan 2 Status
24V
Exhaust Fan 5 Status
24V
Exhaust Fan 5 Status
24V
EAEAEAEA
EF-5EF-5
R1R1
Current
24VAC
Common
Status
R1
Current
24VAC
Common
Status
Yel
Orn
L N
120 VAC
Gry
Gry
Exhaust Fan Enable
24VAC
Exhaust Fan Enable
24VAC
Exhaust Fan Status
24VAC
Exhaust Fan Status
24VAC
1 Exhaust Fan 5 Field Wiring Schematic8
1 Exhaust Fan 5 Field Wiring Schematic
EAEAEAEA
EF-4EF-4
R1R1
Current
24VAC
Common
Status
R1
Current
24VAC
Common
Status
Yel
Orn
L N
120 VAC
Gry
Gry
Exhaust Fan Enable
24VAC
Exhaust Fan Enable
24VAC
Exhaust Fan Status
24VAC
Exhaust Fan Status
24VAC
3 Exhaust Fan 4 Field Wiring Schematic8
3 Exhaust Fan 4 Field Wiring Schematic
EAEAEAEA
EF-2EF-2
L N
120 VAC
Gry
Gry
Exhaust Fan Status
24VAC
Exhaust Fan Status
24VAC
4 Exhaust Fan 2 Field Wiring Schematic8
4 Exhaust Fan 2 Field Wiring Schematic
2 Exhaust Fan 1 and 3 Wiring Schematic (Typical)
EAEAEAEA
EF-2EF-2
L N
120 VAC
Gry
Gry
Exhaust Fan Status
24VAC
(Wired to NCE Panel)
Exhaust Fan Status
24VAC
(Wired to NCE Panel)
2 Exhaust Fan 1 (Typical of EF-3) Field Wiring Schematic8
2 Exhaust Fan 1 (Typical of EF-3) Field Wiring Schematic
TAG QTY DESCRIPTION
C1 1 JC IOM2710 IOM Controller 2UI, 2RO, 2UO
CSR1 1 FUN FUN-RIBXL-CRA Rem Adj Current Sensor Relay
FIELD COMPONENTS
PART NUMBER
CSR
CSR
TAG QTY DESCRIPTION
C1 1 JC IOM2710 IOM Controller 2UI, 2RO, 2UO
CSR1 1 FUN FUN-RIBXL-CRA Rem Adj Current Sensor Relay
CS1 1 VERISE112-708 Current Sensor
FIELD COMPONENTS
PART NUMBER
TAG QTY DESCRIPTION
CS1 2 VERISE112-708 Current Sensor
FIELD COMPONENTS
PART NUMBER
CS
CS
E
R F
O R
M A
N
A T
IN
G
A N
D A
IR
U
S F
S
M
IR
O V
L A
B
T H
IS
D
O C
U M
E N
T C
O N
T A
O P
R
IE
T A
R Y
I N
F O
R M
A T
IC
H
S H
A L
L N
O T
P R
O D
U C
E D
T
R A
N S
F E
R R
O T
H E
R D
O C
U M
E N
T S
D
IS
C L O
S E
D T
O O
T H
E R
S U
S
R M
A N
U F
A C
T U
R
IN
G O
R A
H E
R P
U R
P O
S E
W
IT
H O
IO
R
W R
IT
T
E N
P E
R M
IS
S
O M
R S
D /T
O T
A L C
O N
T R
O L
S h e e t T it le
P ro je c t:
C o n tr a c to r:
P L
A C
E R
V
IL
L E
C
A
Sheet:
Job #:
Designed By:
Drawing By:
Date:
813151
JMG
JMG
R e v is io n s
R e v D a te
C h a n g e
C o m m e rc e D ri v e
R o s e v ill e C
A
-7
-5
-7
-5
F authorized Johnson Controls Metasys Specialist.
Total Control assures through Training, Project Management, Application Engineering, On-site Start-up Assistance and over 45 years of Metasys experience, the operational conformance and satisfaction of each and every installed system.
A C
-1 A ir H a n d le r C o n tr o l
1 AC-1 Air Handler Control
OAOA
OAOA
EAEA
SASA
RARA
SFSF
RFRF
NONO
NCNC
NCNC
NCNC
PRE
FILTER
PRE
FILTER
FINAL
FILTER
FINAL
FILTER
D
X
D
X
D
X
D
X
D
X
D
X
H
W
RF
RF
VFD
DM
DM
DM
1A
DM
1B
HCV
CFM
CFM
OA
T
RA
T
DA
T
DS
DS
11 DF
SHEET NOTES (UNLESS OTHERWISE SPECIFIED):
1. Terminate field devices at manufacturer’s unit control panel
NUMBERED NOTES:
Furnished, installed, wired to manufacturer’s controls, and programmed by AHU manufacturer per 1/M7.1 and manufacturer equipment submittal.
Duct smoke detector furnished, wired for power, and wired to Fire Alarm System by Div. 16 contractor. Installed by Div. 15 contractor. Wired to Mcquay controls for fan shutdown by Yamas.
1378 CFM
1378 CFM
5845 CFM
1.0" E.S.P.
3.0 HP
8600 CFM
2.0" E.S.P.
10 HP
DS
P
+ OUT
SPS1
TO CEILING
SPACE
Item # Value Description Code Description
1 RPS MODEL ROOFTOP PKGD SINGLEZONE
2 020C UNIT SIZE 20 TON
3 S COOLING COIL FACE AREA SMALL FACE AREA
4 W HEAT TYPE HOT WATER
5 Y SPLIT UNIT NONE
6 2 INSULATION & LINERS 2"-1 1/2 LB INSULATION WITH SOLID LINERS
7 EY APPROVAL LISTING ETL(USA)/MEA
8 D MAIN CONTL BOX CONTROL BOX IN DISCHARGE PLENUM
9 12 VOLTAGE 208V-60HZ-3PH
10 AL STARTING OPT ACCROSS THE LINE
11 A2 POWER CONN 1 THRU-THE-DOOR DISCONNECT
12 LE CONTROL MT III DAC - LONmark Certified
13 3 STATIC PRESS SENSORS 1 DUCT SENSOR/1 SPACE SENSOR
14 2 INVERTERS SAF,RAF, WITH ADDED SECTION, BYPASS
15 A INVERTER VENDOR ABB INVETER
16 Y SMOKE DETECTORS NONE
17 YY MISC CONTLS NONE
18 S274 MISC CONTROLS/UNIT LENGTH NONE/AHU LENGTH IN INCHES
19 HY RETURN AIR PLENUM BACK (HORIZONTAL)
Code String Report 847872 010
US FOREST SERVICE MIROV LAB
E847872010 FINAL - RPS020CS
NORMAN WRIGHT MECHANICAL
Placerville, CA 95667
GO Number / Line /
Job Name
Item / Description
ShipTo Customer
ShipTo Address
Serial Number FBOU090500878
Special Text C25 - Similar to AB, except factory mount a magnehelic filter gauge on section door. C39 - Similar to A, except factory mount a magnehelic filter gauge on section door. C50 - Unit to be labeled California EER compliant.
SO Number / Line 152826 / 10
RPS020CSWY2EYD12ALA2LE32AYYYS274HYFE30B3HJY0714AYA
BSCYYS4Z124DYYYYYYYYYYYY20A3LJY1954AW11E3EYYYYYYYY
YYYYYYYYYASYY3AGZ121YYXX1AAY
Complete CodeString
Wednesday, June 03, 2009Shipment Date
20 FE O.A. OPT 0-100% ECON W/ACT & EXH DAMP,
DESIGNFLOW
21 30B3 RETURN FAN 30" AF SW SPRING ISO AND SEISMIC RESTR
22 HJY RETURN FAN MOTOR 3 HP DRIPPROOF PREMIUM EFF
23 0714A RETURN FAN DRIVE FIXED PITCH DRIVE-STD SF
24 Y HEAT WHEEL FROST PROTECTION NONE
25 AB FILTERS 35% ANGULAR
26 S DRAW-THRU BLANK SECT BLANK 40" SECTION
27 CYYS DRAW-THRU COIL SECT COOLING COIL, STAINLESS STEEL DRAIN PAN
28 4Z124D COOLING COIL 4EZ1204 AL FINS
29 YYYYYY NOT RPS, RFS CODE ITEM NONE
30 YYYYYY DRAW-THRU BLANK SECT NONE
31 20A3 SUPPLY FAN 20" AF DW SPRING ISO & SEISMIC RESTR
32 LJY SUPPLY FAN MOTOR 10 HP DRIPPROOF PREMIUM EFF
33 1954A SUPPLY FAN DRIVE FIXED PITCH-STD SF
34 W11E3E HEAT 5WH0901H HW 1.25" 3-WAY VALVE W/ACT
35 YYYY BLOW-THRU COIL SECT NONE
36 YYYYYY COOLING COIL NONE
37 YYYYYY NOT RPS, RFS CODE ITEM NONE
38 Y BLOW-THRU BLANK SECTION NONE
39 A FINAL FILTER SECT 28" SECT-FLAT RACK W/95% CARTRIDGE
40 SY DISCHARGE PLENUM SIDE
41 Y BLANK COMPARTMENT (OUT OF
AIRSTREAM)
NONE
42 3 CAPACITY CONTL 3 STEPS
43 AG CONDENSER OPT ALUM FINS & COIL GUARDS
44 Z COMPRESSOR SCROLL - R22
45 1 COMPRESSOR ISOLATION RESILIENT RUBBER
46 2 PIPING OPT HOT GAS BYPASS CIRCUITS #1 & #2
47 1 LOW AMBIENT OPERATION FANTROL
48 Y IBC SEISMIC/PF CAP NONE
49 Y FAN SECT OPT NONE
50 XX MISC/SPECIAL SPECIAL
51 1 PACKAGING STEEL SKID (BUILT IN)
52 A WARRANTY-PARTS STD 1 YR
53 A COMPRESSOR WARRANTY STD 1 YR
54 Y WARRANTY-HEAT EXCHANGER NONE
SEP 21, 2009
O R M A N W R
IG
H T
M
IR
O V L A B S
T H
IS
D
O C
U M
E N
T C
O N
T A
O P
R
IE
T A
R Y
I N
F O
R M
A T
IC
H
S H
A L
L N
O T
P R
O D
U C
E D
T
R A
N S
F E
R R
O T
H E
R D
O C
U M
E N
T S
D
IS
C L
O S
E D
T O
O T
H E
R S
U
S
R M
A N
U F
A C
T U
R
IN
G O
R A
H E
R P
U R
P O
S E
W
IT
H O
IO
R
W R
IT
T
E N
P E
R M
IS
S
O M
R S
D /T
O T
A L
C O
N T
R O
L
S h e e t T it le
P ro je c t:
C o n tr a c to r:
A N
Y T
O W
N
C A
Sheet:
Job #:
Designed By:
Drawing By:
Date:
813025
RLF
RLF
R e v is io n s
R e v D a te
C h a n g e
C o m m e rc e
D ri v e
R o s e v ill e
C A
-7 -5
-7
-5
F a x B
R
IS
B A
N E
C
A
(4
-7
Approved By: CUST
Total Control is a factory authorized Johnson Controls Metasys Specialist.
Total Control assures through Training, Project Management, Application Engineering, On-site Start-up Assistance and over 45 years of Metasys experience, the operational conformance and satisfaction of each and every installed system.
B o o s te r P u m p C o n tr o l
VFD
L1
L3
L2
T1
T3
T2
R
S
T
U
V
W
VFD
Enable
VFD Speed
Refernce
ON
FC ADDRESS
(SEE SCHEDULE)
FC+
FC-
REF
IN1
IC1
IN2
IC2
RJ
UI IN1 Diff Pressure
UI IN2
UI IN3
BI IN7 VFD Fault
HOT
COM
System Enable
Spare
UI IN6 Spare
UI IN4 Spare
BI IN8 Spare
V A
C F
C B
U S
SHLD
SA+
SA-
COM
RJ
S A
B U
S
PWR
+15V
+15V
IN3
IC3
IN4
IC4
+15V
IN6
IC6
U N
IV
E
R S
A L
I N
P U
T S
IN7
IC7
IN8
IC8B
IN
A R
Y I
N P
U T
S
BO OUT1 VFD Enable
BO OUT2 Spare
O1
OC1
O2
OC2
B
IN
A R
Y O
U T
P U
T S
O3
OC3
BO OUT3 Spare
CO OUT4 Spare
CO OUT5 Spare
O4
OC4
O5
OC5
C O
N F
IG
U
R A
B L
E O
U T
P U
T S
O6
OC6
CO OUT6 Spare
CO OUT7 Spare
AO OUT8 VFD Speed Ref
AO OUT9 Spare
O7
OC7
O8
OC8
O9
OC9A
N
A L
G
T
P U
T S
INT
EXT
SOURCE 24VAC
INT
EXT
SOURCE 24VAC
INT
EXT
SOURCE 24VAC
SETUP: 0-10 VDC
SETUP: Dry Contact Maintained
SETUP:
SETUP:
SETUP:
SETUP:
SETUP:
SETUP:
SETUP:
SETUP: 0-10 VDC
SETUP:
UI IN5 Spare IN5
IC5
SETUP:
SETUP:
SETUP: Dry Contact Maintained
Disc
15A
F1-F3
T1
T2
T3
1 Boiler Booster Pump
Disc
CB1
20A
C1
L1
N
X F -1
CB2
2A
Boiler Power
Off On
A1 A2 C1
X1 X2
PL1
120V
24V
75VA
Boiler Power
On
H
C
H
C
01 VFD
Fault
H
14 13 R1
C
5 9 R1-1
460V, 3Ø, 10 FLA Provided by others.
A 25A MCCB or 20A J-Type fuses are recommended. Panel provides individual, branch short circuit protection.
FEC
FEC
VFD
VFD
460V 3HP Booster Pump
10 FLA
120V, 1Ø, 25 FLA Provided by others.
A 60A MCCB or 45A J-Type fuses are recommended. Panel provides individual, branch short circuit protection.
Boiler Power
120V AC 15A
Differential Pressure
0-10V DC 0-20PSI
System Enable Close To Run Booster System
Thermostat
E
R F
O R
M A
N
A T
IN
G
A N
D A
IR
U
S F
S M
IR
O
V L
A B
T H
IS
D
O C
U M
E
N T
A
O P
R
IE
T A
O
R M
A T
IO
N
W H
IC
A
L L N
O T
P
R O
D U
C E
D
T R
A N
S F
E R
R E
D
H E
R D
O C
U M
E N
T S
D
IS
C
L O
S E
D
H E
R S
U
S E
D F
M
A N
U F
A C
T U
R
IN
G
Y O
T H
E R
P U
R P
O
IT
H O
U T
P R
IT
T E
N P
E R
M
IS
S
O M
R S
D /T
O T
L
N T
R O
L
S h e e t T it le
P ro je c t:
C o n tr a c to r:
P L
A C
E R
V
IL
L E
C
A
Sheet:
Job #:
Designed By:
Drawing By:
Date:
813151
JMG
ZS
R e v is io n s
R e v D a te
C h a n g e
C o m m e rc e D ri v e
R o s e v ill e C
A
-7
-5
-7
-5
F
TABLE OF CONTENTS
SHEET
INDEX
Boiler logic
CAV-1 Logic
VAV-2 Logic
VAV-3 Logic
VAV-4 Logic
VAV-5 Logic
VAV-6 Logic
Application Logic
TITLE
IN
D
E X
USFS Mirov Lab
Control Logic
Total Control is a factory authorized Johnson Controls Metasys Specialist.
Total Control assures through Training, Project Management, Application Engineering, On-site Start-up Assistance and over 45 years of Metasys experience, the operational conformance and satisfaction of each and every installed system.
E
R F
O R
M A
N
A T
IN
G
A N
D A
IR
U
S F
S M
IR
O
V L
A B
T H
IS
D
O C
U M
E
N T
A
O P
R
IE
T A
O
R M
A T
IO
N
W H
A
L L N
O T
P
R O
D U
C E
D
T R
A N
S F
E R
R E
D
H E
R D
O C
U M
E N
T S
D
IS
C
L O
S E
D
H E
R S
U
S E
D F
N
U F
A C
T U
R
IN
G
Y O
T H
E R
P U
R P
O
H O
U T
P R
IT
T E
N P
E R
M
IS
S
O M
R S
D /T
O T
N T
R O
L
S h e e t T it le
P ro je c t:
C o n tr a c to r:
P L
A C
E R
V
IL
L E
C
A
Sheet:
Job #:
Designed By:
Drawing By:
Date:
813151
JMG
ZS
R e v is io n s
R e v D a te
C h a n g e
C o m m e rc e D ri v e
R o s e v ill e C
A
-7
-5
-7
-5
F o il e r lo g ic
RTU Rgunnin
O1
Hot Water Differential Pressure
O1
Hot Water Differential Pressure
O1
Out Door Air Temperature
O1
Hot Water Pump Status
Priority
Priority
Priority
RTU Call
Heat Call
Boiler call
Outside Air Temperature
Outside Air Low Limit
HW DP Pressure
Diff Pressure SP HWP Output
HW DP Control
HW DP Pressure
Diff Pressure SP HWP Output
HW DP Control
Heat Call
HWP Off Delay
Boiler Enable
Plant Enable
I1
Hot Water Pump Output
Priority
I1
Hot Water Pump Output
Priority
HWP Status HWP Enable
I1
Boiler Command
Priority
I1
Boiler Command
Priority
I1
Hot Water Pump Command
Priority
I1
Hot Water Pump Command
Priority
E
R F
O R
M A
N
A T
IN
G
A N
D A
IR
U
S F
S M
IR
O
V L
A B
T H
IS
D
O C
U M
E
N T
A
O P
R
IE
T A
O
R M
A T
IO
N
W H
A
L L N
O T
P
R O
D U
C E
D
T R
A N
S F
E R
R E
D
H E
R D
O C
U M
E N
T S
D
IS
C
L O
S E
D
H E
R S
U
S E
D F
N
U F
A C
T U
R
IN
G
Y O
T H
E R
P U
R P
O
H O
U T
P R
IT
T E
N P
E R
M
IS
S
O M
R S
D /T
O T
N T
R O
L
S h e e t T it le
P ro je c t:
C o n tr a c to r:
P L
A C
E R
V
IL
L E
C
A
Sheet:
Job #:
Designed By:
Drawing By:
Date:
813151
JMG
ZS
R e v is io n s
R e v D a te
C h a n g e
C o m m e rc e D ri v e
R o s e v ill e C
A
-7
-5
-7
-5
F
A
V -1
L o g ic
Uniten-Mode
Flushpos
Heating Available
OA Percent
System Mode
OCC Schedule
O1
Exhaust Fan Status
Priority
O1
Exhaust Fan Status
Priority
O1
Discharge Air Temperature
Priority
O1
Discharge Air Temperature
Priority
O1
DA-VP
Priority
O1
DA-VP
Priority
O1
Zone Temperature
Priority
O1
Zone Temperature
Priority
O1
Zone Setpoint
Priority
O1
Zone Setpoint
Priority
O1
ZN-TOCC
Priority
O1
ZN-TOCC
Priority
Input Present Value
Autocalibrate Now LV
Input Present Value
Autocalibrate Now LV
SAD-ST
Supply Damper Stroke Tim:60.00000
SAD-ST
Supply Damper Stroke Tim:60.00000
Differential Pressure
Supply Air Flow
Supply Flow Calculation
Differential Pressure
Supply Air Flow
Supply Flow Calculation
Input Present Value
Supply Pickup Gain LV
Input Present Value
Supply Pickup Gain LV
Input Present Value
Supply Area LV
Input Present Value
Supply Area LV
Autocalibrate
Pickup Gain
Area Percent dp Offset
Occupancy
Effective Cooling Setpoint
ZN-T Setpoint Determination
Sample Text
Sample Text
Sample Text
Occupancy
Warmup Cooldown
CLG-MINFLOW
Minimum Flow Determination
Process Variable
HTG MINFLOW
OCC Cooling Min Flow
Cooling Max Flow
OCC Heating Min Flow
MINFLOWCO2-PB
MINFLOWCO2-SP
OA Percent
CLGUNOCC-MINFLOW
CLDWN-MINFLOW
HTGUNOCCMINFLOW
WU-MINFLOW
OCC-Level
Min Flow Reset Type
Ventilation Requirement
Optimal Start Status
OCC Cooling Shift
Standby Cooling Shift
UNOCC Cooling Shift
OCC Heating Shift
Standby Heating Shift
UNOCC Heating
Network Setpoint
Hardware Setpoint
OCC Cooling Setpoint
CLGSTBY-SP
UNOCC Cooling Setpoint
OCC HeatingSetpoint
HTGSTBY-SP
UNOCC Heating Setpoint
Remote SetpointMode
Hardware Setpoint
Effective Heating Setpoint
Effective Heating Setpoint
Effective OCC Heating setpoint
EFF Stroke Time 1
Days Between Autocals
Auto-calibration Status
Autocalibration Sequence
EFF Stroke Time 2
Damper Percent Cmd
Auto-calibration Request
EFF Stroke Time 3
Auto-calibrate Now
Flow
State
Flow Test Box
Percent dp Offset
Rated Box Flow
Eff Stroke Time
Damper Percent Cmd
Step Position
Flow
State
Flow Test Box
Percent dp Offset
Rated Box Flow
Eff Stroke Time
Damper Percent Cmd
Step Position
Network Autocal
Balancer Override SD
Auto-calibrate Now
Supply Stroke Time
Occupancy
Supply Flow
Supply Percent
Cooling Max CFM
Cooling Min CFM
SA-Kfactor
SA-Area
Balancer Override
Flow Setpoint Occupancy
Effective Auto-calibrate
Heating Min CFM Flow
Network Autocal
Balancer Override SD
Auto-calibrate Now
Supply Stroke Time
Occupancy
Supply Flow
Supply Percent
Cooling Max CFM
Cooling Min CFM
SA-Kfactor
SA-Area
Balancer Override
Flow Setpoint Occupancy
Effective Auto-calibrate
Heating Min CFM Flow
System Mode
Water Flush
System Mode Determination
Network Mode
PFRESTART-Enable
Uniten-State
Unite Enable Determination
Hardware Mode
Resolution Mode
PFRESTART-TIME
Network Mode
PFRESTART-Enable
Uniten-State
Unite Enable Determination
Hardware Mode
Resolution Mode
PFRESTART-TIME
Input Present Value
Box Heating is Available Pass Through
Input Present Value
Box Heating is Available Pass Through
Occupancy
Supp Heating Control Staus
UNOCC-STATE
Unoccupied Sequencing (VAV)
Heating Priority
UNOCC-SATTIME
Warm up Cool Down
Cooling Setpoint
Zone Temperature
Heating Setpoint
Box Heating Control Status
State
Detailed State
Occupancy
Supp Heating Control Staus
UNOCC-STATE
Unoccupied Sequencing (VAV)
Heating Priority
UNOCC-SATTIME
Warm up Cool Down
Cooling Setpoint
Zone Temperature
Heating Setpoint
Box Heating Control Status
State
Detailed State
Effective Mode
Input Present Value
Water System Flush Pass Through
Input Present Value
Water System Flush Pass Through
Occupancy Schedule
Occupancy Sensor
Effective Occupancy
Occupancy Mode Determination
Occupancy Override
Zone Temperature
Supp Heating Control Status
ZNT-STATE
Zone Sequencing (VAV)
Heating Priority
Setpoint Threshold
Fast Sequence Enable
Box Heating Control Status
Primary Cooling Control Status
Cooling Setpoint
Heating Setpoint
Zone Temperature
Supp Heating Control Status
ZNT-STATE
Zone Sequencing (VAV)
Heating Priority
Setpoint Threshold
Fast Sequence Enable
Box Heating Control Status
Primary Cooling Control Status
Cooling Setpoint
Heating Setpoint
Temporary Occupancy
Temporary OCC Bypass Time
O2
State Selection
I10
O3
O4
O2
State Selection
I10
O3
O4
Input Present Value
Damper Control Status LV
Input Present Value
Damper Control Status LV
Input Present Value
Box Heating LV
Input Present Value
Box Heating LV
Process Variable
Limited Max Value
Control Status
Proportional Box Heating Control
Heating Cooling
Flush Position
Setpoint
Mode
Failsoft Value
Process Units
Percent Cmd
Heating-Out State
Process Variable
Limited Max Value
Control Status
Proportional Box Heating Control
Heating Cooling
Flush Position
Setpoint
Mode
Failsoft Value
Process Units
Percent Cmd
Heating-Out State
Mode
Process Units
Supply Flow Setpoint Control
Failsoft Value
Process Variable
Cooling Setpoint
Heating Setpoint
Heating Min Flow
Cooling Max Flow
Cooling Min Flow Flow Setpoint
Cooling-o
Control Status
Low-Out State
Mode
Process Units
Supply Flow Setpoint Control
Failsoft Value
Process Variable
Cooling Setpoint
Heating Setpoint
Heating Min Flow
Cooling Max Flow
Cooling Min Flow Flow Setpoint
Cooling-o
Control Status
Low-Out State
Mode
Auxiliary Flow 1
Damper Percent Cmd
Supply Damper Control
Auxiliary Stroke Time 1
Flow
Supply Flow Setpoint
Rated Box Flow
Box Flow Test Position
Stroke Time
Auxiliary Flow 2
Auxiliary Stroke Time 2
PD Max Position
Failsoft Value
Minimum Pulse Width
Control Status
SAD-OUTSTATE
Mode
Auxiliary Flow 1
Damper Percent Cmd
Supply Damper Control
Auxiliary Stroke Time 1
Flow
Supply Flow Setpoint
Rated Box Flow
Box Flow Test Position
Stroke Time
Auxiliary Flow 2
Auxiliary Stroke Time 2
PD Max Position
Failsoft Value
Minimum Pulse Width
Control Status
SAD-OUTSTATE
Input Present value
Damper Output LV
Input Present value
Damper Output LV
I1
Exhaust Fan Command
Priority
I1
Exhaust Fan Command
Priority
I1
Param Damper St.
Priority
I1
Param Damper St.
Priority
I1
Damper Position
Priority
I1
Damper Position
Priority
I1
Param Damper Min Pos.
Priority
I1
Param Damper Min Pos.
Priority
I1
Heating Output
Priority
I1
Heating Output
Priority
I1
Occupancy Mode
Priority
I1
Occupancy Mode
Priority
Auto Calibration CommandAuto Calibration Command
1 CAV-1 Logic
E
R F
O R
M A
N
A T
IN
G
A N
D A
IR
U
S F
S M
IR
O
V L
A B
T H
IS
D
O C
U M
E
N T
A
O P
R
IE
T A
O
R M
A T
IO
N
W H
A
L L N
O T
P
R O
D U
C E
D
T R
A N
S F
E R
R E
D
H E
R D
O C
U M
E N
T S
D
IS
C
L O
S E
D
H E
R S
U
S E
D F
N
U F
A C
T U
R
IN
G
Y O
T H
E R
P U
R P
O
H O
U T
P R
IT
T E
N P
E R
M
IS
S
O M
R S
D /T
O T
N T
R O
L
S h e e t T it le
P ro je c t:
C o n tr a c to r:
P L
A C
E R
V
IL
L E
C
A
Sheet:
Job #:
Designed By:
Drawing By:
Date:
813151
JMG
ZS
R e v is io n s
R e v D a te
C h a n g e
C o m m e rc e D ri v e
R o s e v ill e C
A
-7
-5
-7
-5
F
V A
V -2
L o g ic
Uniten-Mode
Flushpos
Heating Available
OA Percent
System Mode
OCC Schedule
O1
Discharge Air Temperature
Priority
O1
Discharge Air Temperature
Priority
O1
DA-VP
Priority
O1
DA-VP
Priority
O1
Zone Temperature
Priority
O1
Zone Temperature
Priority
O1
Zone Setpoint
Priority
O1
Zone Setpoint
Priority
O1
ZN-TOCC
Priority
O1
ZN-TOCC
Priority
Input Present Value
Autocalibrate Now LV
Input Present Value
Autocalibrate Now LV
SAD-ST
Supply Damper Stroke Tim:60.00000
SAD-ST
Supply Damper Stroke Tim:60.00000
Differential Pressure
Supply Air Flow
Supply Flow Calculation
Differential Pressure
Supply Air Flow
Supply Flow Calculation
Input Present Value
Supply Pickup Gain LV
Input Present Value
Supply Pickup Gain LV
Input Present Value
Supply Area LV
Input Present Value
Supply Area LV
Autocalibrate
Pickup Gain
Area Percent dp Offset
Occupancy
Effective Cooling Setpoint
ZN-T Setpoint Determination
Sample Text
Sample Text
Sample Text
Occupancy
Warmup Cooldown
CLG-MINFLOW
Minimum Flow Determination
Process Variable
HTG MINFLOW
OCC Cooling Min Flow
Cooling Max Flow
OCC Heating Min Flow
MINFLOWCO2-PB
MINFLOWCO2-SP
OA Percent
CLGUNOCC-MINFLOW
CLDWN-MINFLOW
HTGUNOCCMINFLOW
WU-MINFLOW
OCC-Level
Min Flow Reset Type
Ventilation Requirement
Optimal Start Status
OCC Cooling Shift
Standby Cooling Shift
UNOCC Cooling Shift
OCC Heating Shift
Standby Heating Shift
UNOCC Heating
Network Setpoint
Hardware Setpoint
OCC Cooling Setpoint
CLGSTBY-SP
UNOCC Cooling Setpoint
OCC HeatingSetpoint
HTGSTBY-SP
UNOCC Heating Setpoint
Remote SetpointMode
Hardware Setpoint
Effective Heating Setpoint
Effective Heating Setpoint
Effective OCC Heating setpoint
EFF Stroke Time 1
Days Between Autocals
Auto-calibration Status
Autocalibration Sequence
EFF Stroke Time 2
Damper Percent Cmd
Auto-calibration Request
EFF Stroke Time 3
Auto-calibrate Now
Flow
State
Flow Test Box
Percent dp Offset
Rated Box Flow
Eff Stroke Time
Damper Percent Cmd
Step Position
Flow
State
Flow Test Box
Percent dp Offset
Rated Box Flow
Eff Stroke Time
Damper Percent Cmd
Step Position
Network Autocal
Balancer Override SD
Auto-calibrate Now
Supply Stroke Time
Occupancy
Supply Flow
Supply Percent
Cooling Max CFM
Cooling Min CFM
SA-Kfactor
SA-Area
Balancer Override
Flow Setpoint Occupancy
Effective Auto-calibrate
Heating Min CFM Flow
Network Autocal
Balancer Override SD
Auto-calibrate Now
Supply Stroke Time
Occupancy
Supply Flow
Supply Percent
Cooling Max CFM
Cooling Min CFM
SA-Kfactor
SA-Area
Balancer Override
Flow Setpoint Occupancy
Effective Auto-calibrate
Heating Min CFM Flow
System Mode
Water Flush
System Mode Determination
Network Mode
PFRESTART-Enable
Uniten-State
Unite Enable Determination
Hardware Mode
Resolution Mode
PFRESTART-TIME
Network Mode
PFRESTART-Enable
Uniten-State
Unite Enable Determination
Hardware Mode
Resolution Mode
PFRESTART-TIME
Input Present Value
Box Heating is Available Pass Through
Input Present Value
Box Heating is Available Pass Through
Occupancy
Supp Heating Control Staus
UNOCC-STATE
Unoccupied Sequencing (VAV)
Heating Priority
UNOCC-SATTIME
Warm up Cool Down
Cooling Setpoint
Zone Temperature
Heating Setpoint
Box Heating Control Status
State
Detailed State
Occupancy
Supp Heating Control Staus
UNOCC-STATE
Unoccupied Sequencing (VAV)
Heating Priority
UNOCC-SATTIME
Warm up Cool Down
Cooling Setpoint
Zone Temperature
Heating Setpoint
Box Heating Control Status
State
Detailed State
Effective Mode
Input Present Value
Water System Flush Pass Through
Input Present Value
Water System Flush Pass Through
Occupancy Schedule
Occupancy Sensor
Effective Occupancy
Occupancy Mode Determination
Occupancy Override
Zone Temperature
Supp Heating Control Status
ZNT-STATE
Zone Sequencing (VAV)
Heating Priority
Setpoint Threshold
Fast Sequence Enable
Box Heating Control Status
Primary Cooling Control Status
Cooling Setpoint
Heating Setpoint
Zone Temperature
Supp Heating Control Status
ZNT-STATE
Zone Sequencing (VAV)
Heating Priority
Setpoint Threshold
Fast Sequence Enable
Box Heating Control Status
Primary Cooling Control Status
Cooling Setpoint
Heating Setpoint
Temporary Occupancy
Temporary OCC Bypass Time
O2
State Selection
I10
O3
O4
O2
State Selection
I10
O3
O4
Input Present Value
Damper Control Status LV
Input Present Value
Damper Control Status LV
Input Present Value
Box Heating LV
Input Present Value
Box Heating LV
Pro…