SHEET INDEX
DRAWING NUMBER TITLE
WS-25900-2019-G-G1-01 Building 25900 COVER SHEET/INDEX SHEET
WS-25900-2019-O-G1-02 PROPOSED STAGING AREA AT 25900
WS-25900-2019-EP-03 Building 25900 PANEL AND TRANSFORMER LAYOUT
WS-25900-2019-EP-04 Building 25900 ROOM 134 PANEL "A1" WS-25900-2019-EP-05 Building 25900 ROOM 134 PANEL "A2" WS-25900-2019-EP-06 Building 25900 PANEL "P" WS-25900-2019-EP-07 Building 25900 ROOM 129 PANEL "C" AND "K" WS-25900-2019-EP-08 Building 25900 ROOM 123 PANEL "OUTSIDE ROOM 123B" WS-25900-2019-EP-09 Building 25900 ROOM 127 PANEL "F" WS-25900-2019-EP-10 Building 25900 ROOM 123B PANEL "E"
WS-25900-2019-EP-11 BUILDING 25900 ROOM 123B PANEL "RM"
WS-25900-2019-EP-12 BUILDING 25900 ROOM 123C PANEL "123C"
WS-25900-2019-EP-13 BUILDING 25900 ROOM 122 PANEL "R4"
WS-25900-2019-EP-14 BUILDING 25900 ROOM 119 PANEL "R5"
WS-25900-2019-EP-15 BUILDING 25900 ROOMS 105 & 106 PANEL "G"
WS-25900-2019-EP-16 BUILDING 25900 ROOM 133 PANEL "H"
WS-25900-2019-EP-17 BUILDING 25900 ROOM 133 PANEL "D"
WS-25900-2019-EP-18 GENERAL NOTES
WS-25900-2019-EP-19 GENERAL NOTES
DESIGNED
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
ARCH D
DRAWING TITLE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
CESAR M. LIMON
VANESSA CUEVAS
RAFAEL H. ACOSTA
NTS
BUILDING 25900 REPLACE ELECTRICAL PANELS
WS-25900-2019-G-G1-01
COVER SHEET / INDEX SHEET
BUILDING 25900
1 19
CESAR M. LIMON
W H
I T E
S ANDS MIS S I LE
RA
NG
E
B I RTHPLACE
OF
AMERI CA' S MI SSI LE & SPACE
AC
TI
V
IT
Y
CONCURRENCES
Note: Signatures affixed on this sheet indicate official recommendation and approval of all the drawings in this set as indexed on this sheet.
Garrison Safety
Physical Security
Fire Department
DPW Environmental
Anti-Terrorism/Force Protection
Information Management
Operations and Maintenance Division
Customer 1
Date
Date
Date
Date
Date
Date
Date
Date
Customer 2 Date
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
AutoCAD SHX Text
WHITE SANDS MISSILE RANGE, NEW MEXICO
AutoCAD SHX Text
DIRECTORATE OF PUBLIC WORKS
AutoCAD SHX Text
ENGINEERING DIVISION
DESIGNED
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-02
PROPOSED STAGING AREA
AT 25900
RAFAEL ACOSTA
2 19
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
ARCH D
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-3
BUILDING 25900
PANEL AND
TRANSFORMER LAYOUT
BUILDING 25900 LAYOUT
KEY NOTES
RAFAEL ACOSTA
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
5 6
PANELS A1 & A2
208 / 120 V
3 PHASE
PANEL DETAIL: SHEETS 6
WS-25900-2019-EP-6 AND
7 WS-25900-2019-EP-7
3 PANELS RG
208 / 120 V
3 PHASE
PANEL DETAIL: SHEETS 17 WS-25900-2019-EP-17
THERE ARE TWO PANELS.
4 PANEL R2
208 / 120 V
3 PHASE
FED FROM SWITCHBOARD BREAKER #14
SHEET 15 WS-25900-2019-EP-10
PANEL DETAIL: SHEETS 10 WS-25900-2019-EP-10
5 PANEL E
208 / 120 V
3 PHASE
PANEL DETAIL: SHEET 12 WS-25900-2019-EP-12
6 PANEL RM
208 / 120 V
3 PHASE
PANEL DETAIL: SHEET 13 WS-25900-2019-EP-13
7 PANEL 123C
208 / 120 V
3 PHASE
PANEL DETAIL: SHEET 14 WS-25900-2019-EP-14
8 PANEL R4
208 / 120 V
3 PHASE
PANEL DETAIL: SHEET 15 WS-25900-2019-EP-15
9 PANEL R5
208 / 120 V
3 PHASE
PANEL DETAIL: SHEET 16 WS-25900-2019-EP-16
10 PANEL D
208 / 120 V
3 PHASE
PANEL DETAIL: SHEET 19 WS-25900-2019-EP-19
11 PANEL H
480 / 277 V
3 PHASE
PANEL DETAIL: SHEET 18 WS-25900-2019-EP-18
12 PANEL P
480 / 277 V
3 PHASE
PANEL DETAIL: SHEET 8 WS-25900-2019-EP-8
THESE TWO PANELS SHALL BE COMBINED INTO ONE
PANEL.
19 20
14 PANEL C
208 / 120 V
3 PHASE
PANEL DETAIL: SHEET 9
WS-25900-2019-EP-9
DRY TYPE TRANSFORMER, 3 PHASE, 45 KVA
480 / 277 V-208 / 120 V
FED FROM SWITCHBOARD BREAKER #3
IN MECHANICAL ROOM 133
DRY TYPE TRANSFORMER, 3 PHASE, 112.5 KVA
480 / 277 V-208 / 120 V
FED FROM SWITCHBOARD BREAKER #3 IN MECHANICAL
ROOM 133
PANEL F
208 / 120 V
3 PHASE
PANEL DETAIL: SHEET 11 WS-25900-
2019-EP-11
PANEL K
208 / 120 V
3 PHASE
PANEL DETAIL: SHEET 9
WS-25900-2019-EP-9
21 OIL FILLED PADMOUNT TRANSFORMER, 3 PHASE,
1500 KVA
24900 / 14376 V-480 / 277 V
FED FROM SWITCHBOARD BREAKER #3 IN MECHANICAL
ROOM 133
PANELS AND DISCONNECT SWITCHES THAT ARE
SPECIFIED TO BE REPLACED AS FOLLOWS:
THE FOLLOWING ARE DISTRIBUTION TRANSFORMERS
THAT FEED 3 PHASE PANELS 208 / 120 V :
17 FUSE DISCONNECT (FOR PANEL R5)
240 V
3 PHASE
ARCH D
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
AutoCAD SHX Text 178'-1 3/4"
AutoCAD SHX Text 103'-4 1/16"
AutoCAD SHX Text 179'-10 11/16"
AutoCAD SHX Text 41'-3 3/16"
AutoCAD SHX Text 61'-4 15/16"
AutoCAD SHX Text 65'-11 5/8"
AutoCAD SHX Text 48'-2 5/16"
AutoCAD SHX Text 90'-2 1/8"
AutoCAD SHX Text 52'-2 3/16"
AutoCAD SHX Text 43'-9 15/16"
AutoCAD SHX Text 8'-2 3/4"
AutoCAD SHX Text 41'-4 15/16"
AutoCAD SHX Text 24'-5 7/16"
AutoCAD SHX Text N
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SWITCHGEAR
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL ROOM
AutoCAD SHX Text
BOILER ROOM
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 103A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 9'-7 11/16"
AutoCAD SHX Text 16'-7 11/16"
AutoCAD SHX Text 10'-1 5/16"
AutoCAD SHX Text 6'-2 5/16"
AutoCAD SHX Text
AutoCAD SHX Text 123C
AutoCAD SHX Text 123B
AutoCAD SHX Text 123A
AutoCAD SHX Text 1/16"=1'-0"
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-04
BUILDING 25900
ROOM 134
PANEL "A1"
GENERAL NOTES
EXISTING SUB PANEL "A1"
208 / 120 V, 3 PHASE, SURFACE MOUNTED BOTTOM FEED, 4 W 225A MAIN WITH LUGS ONLY
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
1 20 Lights Trasnf. Room 2 1 20 Do
1 20 Do 4 1 20 Do
1 20 Do 6 1 20 Do
1 20 Do 8 1 20 Do
1 20 Do 10 1 20 Do
1 20 Do 12 1 20 Do
1 20 Do 14 1 20 Lights Trasnf. Room
1 20 Do 16 1 20 Do
17 1 20 Do 18 1 20 Do
19 1 20 RECP. HIGH BAY 20 1 20 Do
1 20 RECP. HIGH BAY 22 1 20 Do
1 20 4 EVAP PUMP
MOTORS 24 1 20 Do
3 70 PANEL "L" 26 1 20
Contr. Fltr Room Lights
3 70 " 28 1 20 SPARE
3 70 " 30 1 20 Flood Lights
3 30 3 Phase Recept. 32 3 20 Do
33 3 30 " 34 3 20 Do
35 3 30 " 36 3 20 Do
RAFAEL ACOSTA
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
1) PANEL DIMENSIONS
LENGTH: 47 INCHES
WIDTH: 20 1/2 INCHES
DEPTH: 6 INCHES
ARCH D
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-05
BUILDING 25900
ROOM 134
PANEL "A2"
EXISTING SUB PANEL "A2"
208 / 120 V, 3 PHASE, SURFACE MOUNTED BOTTOM FEED, 4 W 225A MAIN WITH LUGS ONLY
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
1 20 Recept. Transf. Room 2 1 20 Do
1 20 Do 4 1 20 OT Alarm & Freeze
UPL
1 20 Recept. Transf. Room 6 3 20 Cardox Cont.
1 20 Recept. Transf. Room 8 3 20 Xmilt
1 20 Recept. Transf. Room 10 3 20 Fire Contr.
ACUNNITT Rm
1 20 Recept. Transf. Room 12 1 20 Fire Contr. Ex.
Motors
1 20 Recept. Tr Control 14 1 20
Recept. Tr.
Rm./Damper Motor
1 20 Recept. TR Control 16 3 20 Recept. Sw Board
Room
17 1 20 Recept. Ex. Mtr. Rm
122 18 3 20 Recept. Sw Board Room
19 1 20 Outside BR Light 20 3 20 Recept. Sw Board
Room
1 20 Lights Swboard
Room 22 1 20 Driver Rm. Cir
1 20 Lights Swboard Room 24 1 20 Corr. 116 Lights
1 20 Lights Swboard
Room 26 1 20 Recept. Trans. Rm
1 20 Warning System 28 1 20 28 Volt UnReg
1 20 Warning System 30 1 Blank
1 20 Outside Bracketline 32 1 Blank
33 2 20 Heater Wave Guide
HSC 34 3 20 Phase Do
35 2 20 " 36 3 20
37 3 20 Phase Do 38 3 20 "
39 3 20 " 40 3 30 Phase Do
41 3 20 " 42 3 30
44 3 30
RAFAEL ACOSTA
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
1) PANEL DIMENSIONS
LENGTH: 51 INCHES
WIDTH: 20 INCHES
DEPTH: 6 INCHES
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
GENERAL NOTES
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-06
BUILDING 25900
PANEL "P1" AND "P2"
EXISTING PANEL "P1" MECHANICAL
ROOM
480 / 277 V, 3 PHASE, SURFACE MOUNTED BOTTOM FEED, 4 W WITH 150A MAIN BREAKER
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
3 15 SPARE 2 3 15 SHREDOR
3 15 " 4 3 15 "
3 15 " 6 3 15 "
3 30 CONDENSOR UNIT 8 3 30 SPARE
3 30 " 10 3 30 "
3 30 " 12 3 30 "
RAFAEL ACOSTA
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
480 / 277 V, 3 PHASE, SURFACE MOUNTED BOTTOM FEED, 4 W WITH 150A MAIN BREAKER
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
3 40 COAKITE HEATER 2 3 15 HOT WATER PUMP
3 40 " 4 3 15 "
3 40 " 6 3 15 "
3 15 1
2 HP EXH. 8 3 15 1
2 HP EXH.
3 15 " 10 3 15 "
3 15 " 12 3 15 "
3 15 AIR COMPRESSOR 14 BLANK
3 15 " 16 BLANK
3 15 " 18 BLANK
3 15
AIR HANDLING
UNIT TRANS.
ROOM
20 3 15 CHILLED WATER
PUMP
3 15 " 22 3 15 "
3 15 " 24 3 15 "
3 20 EXHANSTER 8 26 3 20 SPARE
3 20 " 28 3 20 SPARE
3 20 " 30 3 20 SPARE
BLANK 32 3 20 SPARE
BLANK 34 3 20 SPARE
BLANK 36 3 20 SPARE
3 30 SPARE 38 BLANK'
3 30 SPARE 40 BLANK
3 30 SPARE 42 BLANK
EXISTING PANEL "P2" MECHANICAL
ROOM
1) PANEL DIMENSIONS
LENGTH: 51 INCHES
WIDTH: 20 1/2 INCHES
DEPTH: 6 INCHES
NOTES:
BOTH PANELS "P1" AND "P2" SHALL BE COMBINED INTO ONE PANEL AND WITH CORRECT SIZE OF BREAKERS
FOR EACH DEVICE WITH A MAIN BREAKER.
1) PANEL DIMENSIONS
LENGTH: 51 INCHES
WIDTH: 20 1/2 INCHES
DEPTH: 6 INCHES
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
NGENERAL NOTES
GENERAL NOTES
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-7
BUILDING 25900
ROOM 129
PANEL "C" AND "K"
7 19
EXISTING SUB PANEL "C"
208 / 120 V, 3 PHASE, SURFACE MOUNTED BOTTOM FEED, 4 W 225A MAIN WITH LUGS ONLY
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
1 20 RECP.
WORKSHOP SHOP 2 1 20 RECP.
WORKSHOP SHOP
1 20 RECP.
WORKSHOP SHOP 4 1 20 RECP. WORKSHOP
SHOP
1 20
Recept. Work Shop (note this has been crossed-out on label with pencil)
6 1 20 RECP. WORKSHOP
SHOP
1 20
EMERGENCY
LIGHTS (note:
breaker in OFF position)
8 1 20 NO Label (note:
breaker in ON
Position)
1 20 HALL LIGHTS 10 1 20 RECEPT. BOILER
ROOM
1 20
BOILER
CONTROL (note: lab el on breaker “Fire Pump Cont”)
12 1 20 SPARE (note: breaker in ON position)
1 20
SPARE (note:
breaker in ON position) 14 1 20
No Label (note:
breaker in ON position)
1 20
SPARE (note:
breaker in ON position) 16 1 20 SPARE (note: breaker in ON position)
17 1
SPARE (note:
breaker in ON position)
18 1 20 ROOM 129 RECPT.
SW
19 1
20 ROOM 129 REC SW 20 1 20 ROOM 129 RECPT.
SW
1 20 ROOM 117 RECEPT.
110 VOLT 22 1 20 ROOM 129 SW
2 20 PUMP (note: label on breaker “Pump Blue”) 24 BLANK
BLANK 26 3 20 208 3 PHASE ROOM
3 50 ELECTRIC WATER
HEATER 28 3 20 "
3 50 " 30 3 20
3 50 208 V 3 PHASE
ROOM 117 32 3 50
Room 129 220-V Computer Power
3 20 " 34 3 50 "
35 3 20 " 36 3 50 "
RAFAEL ACOSTA
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
1) PANEL DIMENSIONS
LENGTH: 47 INCHES
WIDTH: 20 1/2 INCHES
DEPTH: 6 INCHES
EXISTING SUB PANEL "K"
208 / 120 V, 3 PHASE, SURFACE MOUNTED BOTTOM FEED, 4 W 100 A MAIN BREAKER
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
BLANK 2 BLANK
1 20 DISC. #1 4 1 20 DISC. #2
1 BLANK 6 BLANK
1 BLANK 8 BLANK
1 20 DISC. #3 10 1 20 DISC. #4
1 BLANK 12 BLANK
1 BLANK 14 BLANK
1 20 DISC. #5 16 1 20 DISC. #6
17 1
BLANK 18 BLANK
19 1
BLANK 20 BLANK
1 20 DISC. #7 22 BLANK
1) PANEL DIMENSIONS
LENGTH: 34 INCHES
WIDTH: 20 INCHES
DEPTH: 6 INCHES
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
GENERAL NOTES
GENERAL NOTES
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-08
BUILDING 25900
ROOM 123
PANEL "OUTSIDE ROOM
123B"
8 19
EX
IS
TI
N
G S
U B
P A
N
EL
3B
/ 1
V , 3
P H
A
SE
, S U
R
FA
C E
M O
U N
TE
D
B O
TT
O
M F
EE
D
, 4 W
A M
A
IN
W
IT
H L
U G
S O
N
LY
C K
T.
N
O
PO
LE
S
TR
IP
(A
M
PS
SE
R V
IC
ES
A B
C
Su pe rv is or
's Pl ay A
Su pe rv is or 's
D is pl ay
A
T ap e
Er as er
Sp ar e
A
Eq ui pm en t A
D
A
A
R
IT
A U
X
PC
T w o
Tr ig . D is t.
M ai n
R
IT
PC
O ne
T rig
D is t.
U til
R
TI
T rig
R
TI
O ne M ai n
R
TI
Sp ar e
Sp ar e
Sp ar e
A
Sp ar e
Sp ar e
Te ch ni ca l A re a
Te ch ni ca l A re a
B uf fe r
Sp ar e
Sp ar e
Sp ar e
Sp ar e
Sp ar e
RAFAEL ACOSTA
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
1) PANEL DIMENSIONS
LENGTH: 79 INCHES
WIDTH: 12 INCHES
DEPTH: 6 INCHES
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-09
BUILDING 25900
ROOM 127
PANEL "F"
09 19
EXISTING SUB PANEL "F"
208 / 120 V, 3 PHASE, SURFACE MOUNTED BOTTOM FEED, 4 W 225 A MAIN BREAKER
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
1 20 LIGHTS 2 3 20 GRINDER 208 V
1 20 " 4 3 20 "
1 20
RECEPT. W. WALL
(110 VOLT) 6 3 20 "
1 20
RECEPT. W. WALL
(110 VOLT) 8 1 20 RECEPT.
1 20
RECEPT. W. WALL
(110 VOLT) 10 1 20 RECEPT. (110 V)
1 20 RECEP. WALL M.
TABLE 12 1 20
RECEP. W. WALL
(110 V)
1 20
RECEP. N. WALL
(110 V) 14 1 20
RECEP. E. WALL
(110 V)
1 20
RECEP. N. WALL
(110 V) 16 1 20
RECEP. E. WALL
(110 V)
17 1
RECEP. S. WALL
(110 V) 18 1 20
RECEP. E. WALL
(110 V)
19 1
RECEP. E. WALL
(110 V) 20 1 20
RECEP. E. WALL
(110 V)
1 20 SAW AND
GRINDER 22 1 20 MONO RAIL
1 20 MONO RAIL 24 1 20 SPARE
1 20 SPARE 26 1 20 RCVR. RACK
1 20 EXH. FAN 28 2 20
SPARE
3 20 3 PHASE MILLING
MACHINE 30 2 20 SPARE
3 20 " 32 3 20
MILLING
MACHINE 3 PHASE
208 V
33 3 20 " 34 3 20 "
35 3
LATHE (208 V 3
PHASE) &
GRINDER
36 3 20
37 3 40 " 38
39 3 40 "
RAFAEL ACOSTA
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
1) PANEL DIMENSIONS
LENGTH: 34 INCHES
WIDTH: 20 1/2 INCHES
DEPTH: 6 INCHES
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-10
BUILDING 25900
ROOM 123B
PANEL "E"
10 19
EXISTING SUB PANEL "E"
208 / 120 V, 3 PHASE, SURFACE MOUNTED TOP FEED, 4 W 200A
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
1 20 Lights Room 122 2 1 20 Lights Room 121
1 20 Lights Room 122 4 1 20 Lights Corridor and &
1 20 Lights Room 122 6 1 20 Lights Rm 127
1 20
Adjustable Spotlight Rm 119, Ping Pong 8 1 20 Adjust Spot Rm. 123, 3rd Row VTR
1 20
Adjustable Spotlight Rm 119, Ping Pong 10 1 20 Adjust Spot Rm. 123, 2nd Row
1 20 Adjustable Spotlight
Rm 123, 6th Row 12 1 20 Adjust Spot Rm. 123, 1st Row
1 20 Adjustable Spotlight
Rm 123, 5th Row 14 1 20 Back of Servo Rack
1 20 Adjustable Spotlight
Rm 123, 4th Row 16 1 20 Recepts., Rm 119 &
17 1 20 Wall Coolers, Rm 119
North Wall 18 1 20 Recepts., Rm 119
19 1 20 Wall Coolers, Rm 119
North Wall 20 1 20 Recepts., Rm 119
1 20 Recept. Rm 123
South Wall 22 1 20 Recepts., Rm 123 West Wall
1 20 Recept. Rm 123 East Wall 24 1 20 Recepts., Rm 122
1 20 Recept. Rm 121 &
122 26 1 20 Wall Coolers #1 (123)
West Wall & East Wall (Servo)
1 20 Wall Coolers East
Wall Rm 123 28 2 20 Wall Coolers Rm 122 & 123 (Photo, SDS, and Control Rm)
1 20
Emergency Lights Relay Contacts 30 2 20 Lights, Rm 118
1 20 Lights Rm 119 32 1 20 Lights, Rm 117
33 1 20 Lights Rm 119 34 1 20 Lights, Rm 123, 3rd
Row
35 1 20 Lights Rm 123, 6th
Row 36 1 20 Lights, Rm 123, 2nd
Row (Computer)
37 1
Lights Rm 123, 5th Row (SP) 38 1 20
Lights Rm 123, 1st Row (Computer)
39 1 20 Lights Rm 123 7th
Row 40 1 20 Lights, Rm 123, 7th Row
41 1 20 Wall Coolers Rm 122
& 123, Eastwall 42 1 20 NO LABEL
RAFAEL ACOSTA
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
1) PANEL DIMENSIONS
LENGTH: 63 1/2 INCHES
WIDTH: 20 INCHES
DEPTH: 6 INCHES
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2018-EP-11
BUILDING 25900
ROOM 123B
PANEL "RM"
Cesar Limon
Cesar Limon
Vanessa Cuevas
Rafael Acosta
02/06/17
11 19
EXISTING SUB PANEL "RM"
208 / 120 V, 3 PHASE, SURFACE MOUNTED TOP FEED, 4 W 500A Main Breaker
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
3 100 R1 Panel 2 3 100 Computer Rm
3 100 " 4 3 100 "
3 100 " 6 3 100 "
3 175 R2 & R3 Panel 8 3 150 R5 Panel
3 175 " 10 3 150 "
3 175 " 12 3 150 "
3 60 Outside Switch 14 3 125 R6 Panel
3 60 " 16 3 125 "
17 3 60 " 18 3 125 "
1) PANEL DIMENSIONS
LENGTH: 48 INCHES
WIDTH: 38 INCHES
DEPTH: 11 INCHES
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-12
BUILDING 25900
ROOM 123C
PANEL "123C"
12 19
EXISTING SUB PANEL "123C"
208 / 120 V, 3 PHASE, SURFACE MOUNTED TOP FEED, 4 W 125A Main Breaker Bottom Feed
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
1 15 Spare 2 1 15 Strobe Lights
1 15 Lights on Work Table 4 1 15 Spare
1 15 Outlets on Work Table 6 3 15 Spare
1 15 ON S. Side Work
Table 8 3 15 Spare
3 30 220 V Outlet Bench 10 3 15 Spare
3 30 " 12 1 30 Spare
3 30 " 14 1 Blank
1 30 Spare 16 3 30 Spare
17 1 30 Spare 18 3 30 Spare
19 1 30 Spare 20 3 30 Spare
1 15 Spare 22 1 Blank
1 15 Spare 24 1 20 Blank
1 30 Spare 26 1 30 Spare
1 20 Spare 28 1 30 Spare
1 15 Spare 30 1 Blank
1 Blank 32 1 30 Spare
33 1 Blank 34 3 30 Spare
35 1 Blank 36 3 30
37 1 Blank 38 3 30
39 2 Blank 40 2 Blank
41 2 Blank 42 2 Blank
RAFAEL ACOSTA
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
1) PANEL DIMENSIONS
LENGTH: 81 INCHES
WIDTH: 16 INCHES
DEPTH: 6 INCHES
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-13
BUILDING 25900
ROOM 122
PANEL "R4"
13 19
EXISTING SUB PANEL "ROOM 122"
208 / 120 V, 3 PHASE, SURFACE MOUNTED TOP FEED, 4 W 125A MAIN BREAKER
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
1 30 Spare 2 3 30 Spares
1 30 Spare 4 3 30 Spares
1 30 Spare 6 3 30 Spares
3 20 Spare 8 3 30 Spares
3 20 Spare 10 3 30 Spares
3 20 Spare 12 3 30 Spares
2 15 Spare 14 2 15 Spares
2 15 Spare 16 2 15 Spares
17 2 20 Spare 18 1 20
Rm 119 (CSCMI Floor)
19 2 20 Spare 20 1 20
Rm 119 (CSCMI Console PWR)
1 20 Rm 119 (CSMI Floor) 22 1 20
Rm 119 (CSCMI Floor) UPS PWR (15
A UPS)
1 20 Spare 24 1 20 Rm 119 (CSCMI
Floor)
1 20 Spare 26 1 20
Rm 119 (CSCMI Floor) UPS PWR
(20A)
1 30 Spare 28 1
Blank
1 Blank 30 1 Blank
RAFAEL ACOSTA
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
1) PANEL DIMENSIONS
LENGTH: 38 1/2 INCHES
WIDTH: 16 1/2 INCHES
DEPTH: 5 INCHES
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-14
BUILDING 25900
ROOM 119
PANEL "R5"
14 19
EXISTING SUB PANEL "R5"
208 / 120 V, 3 PHASE, SURFACE MOUNTED TOP FEED, 4 W 225A MAIN LUGS
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
1 20 Outlet 2 VA 2 1 20 CSCMI Table Lights
2 20 FTRS-Far Corner and Side Outlets 4 1 20 CSCMI Table Recept.
South Side
2 20 " 6 2 30 CSCMI Table Recept.
1 20 North Table Recept 8 2 30 "
1 20 East Side Recept. 10 1 20 CSCMI Table Recept.
1 30 Spare 12 1 30 FTRS Lights
1 15 Outlet 30 A 14 1 Blanks
Blanks 16 1 Blanks
Blanks 18 1 Blanks
Blanks 20 1 Blanks
Blanks 22 1 Blanks
3 20 3 Phase Recept. (Not
Operational) 24 3 70
FTRS
OPO/Astrellalca Chiller
3 20 " 26 3 70 "
3 30 " 28 3 70
RAFAEL ACOSTA
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
1) PANEL DIMENSIONS
LENGTH: 52 INCHES
WIDTH: 24 INCHES
DEPTH: 6 INCHES
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-15
BUILDING 25900
ROOMS 105 & 106
PANEL "RG"
15 19
EXISTING SUB PANEL "RG" Right Side
(ROOM 105)
208 / 120 V, 3 PHASE, FLUSH MOUNTED TOP FEED, 4 W 225A Main Lugs
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
1 20 Lights Rm 114 2 1 20 Lights Rm 113
1 20 Lights Rm 115 4 1 20 Lights Rm 112
1 20 Lights Rm 117 6 1 20 Lights Rm 111
1 20 Lights Rm 109 8 1 20 Lights Rm 110
3 20 Lights Rm 108 10 1 20 Corridor Lights
3 20 Lights Rm 107 12 1 20 Lights Rm. 124, 125, & 126
3 20 Spare 14 1 20 Emergency Lights
1 20 Spare 16 1 20 Lights Rm 102
17 1 20 Lights Rm 101 & 103 18 1 20 Lights Rm 131
19 1 20 Lights Rm 105 20 1 20
North Outside Floodlight
1 20 Lights Rm 106 22 1 20
East, Outside Floodlight Added note on panel door “1 Light on NE corner of roof, above front door, pointed at parking area”
1 20
N. Outside Floodlight Note on circuit breakers “Flood
Lights Switches 23, 24, LEA
VE ON”
24 1 20
E. Outside Floodlight Note on circuit breakers “Flood
Lights Switches 23, 24, LEA
VE ON”
1 20
W. Outside Flood Light 26 1 30 Recept. RM 109 &
1 20 Recept. RM 104 &
105 28 1 20 Recept. RM 108 &
1 20 Recept. Rm 103 &
104 30 1 20 Recept. RM 107 &
1 20 Recept. Rm 106 &
128 32 1 20 Recept. RM 101 &
RAFAEL ACOSTA
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
1) PANEL DIMENSIONS
LENGTH: 41 1/2 INCHES
WIDTH: 21 INCHES
DEPTH: 5 INCHES
208 / 120 V, 3 PHASE, FLUSH MOUNTED TOP FEED, 4 W 225A Main Lugs
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
1 20
Recept. Room 109, (note: label is crossed-out)
34 1 20
Not legible (note1:
label is crossed-out)
(note2: breaker in ON position)
1 20 Recept. Room 112, 113 36 1 20 Door Controls Rm
1 20 Recept. Room 111, 112 38 1 20
Recept. Rm 114 & 11 5 (note: added label “Receptacle 113 (1 wall socket)”)
1 20
Recept. Room 110 and Xerox
(note: original label shows Recept Room
110)
40 1 20
Recept. Rm 114 (note:
both added label and label on circuit breaker show “TELETYPE
ONLY”)
1 20
Recept. Room 126 (note: added label “Refrigerator, Ki tchen”)
42 1 30
Recept. by Coke Machine
(note: added label “Room 115 Rece
pt. - Xerox, Coke”)
1 20
Recept. Room 126 (note: added label “Kitchen - Coffe e Pot”)
44 1 20 Recept. By Coke Machine
1 20 Recept. Room 125 &
126 46 1 20 Recept. By Coke
Machine (note: added label “Coke Machine”)
1 20
Recept. Room 117 (note: added label “Recept. 117, Da rk Room”)
48 1 20
Ex. Fan Rm 117 (note: added label “Exhaust Fan 117”)
49 1
Recept. Room 117 (note: label on circuit breaker “Dye Lab Outlets”)
50 1 20 Water Cooler
51 1 20 Recept. Room 131 52 1 20 Ex. Fan Rm 124, 125, and 126
1 20
Spare (note: breaker in ON position) 54 1 20
Spare (note: breaker in ON position)
1 20 Spare
(note: breaker in ON position)
56 1 20 Spare (note: breaker in ON position)
1 20 Spare
(note: breaker in ON position)
58 1 20
Spare (note1: label on breaker “Fire Alarm Circuit; Mass
Notification Circuit”) (note2: breaker locked in ON position)
1 20
Spare (note: breaker in ON position) 60 1 20 Mass Notification
Circuit
1 20 Sing. Phase Outlet
Rm. 117 62 3 Phase Outlet
1 20 Sing. Phase Outlet
Rm. 117 64 2 50 "
66 2 50
Xerox 2400 (note: label on breaker “Coke
Machine”)
68 2 50 "
EXISTING SUB PANEL "RG" Left Side
(ROOM 106)
1) PANEL DIMENSIONS
LENGTH: 41 1/2 INCHES
WIDTH: 21 INCHES
DEPTH: 5 INCHES
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
GENERAL NOTES
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-16
BUILDING 25900
ROOM 133
PANEL "H"
16 19
EXISTING SUB PANEL "H"
480 / 277 V, 3 PHASE, SURFACE MOUNTED TOP FEED, 3 W 600 A MAIN LUGS
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
3 15 Boiler Control 2 3 15 Control Circuit
Transformer
3 15 " 4 3 15 "
3 15 " 6 3 15 "
3 15 #2 Boiler Feeder
Pump #52 8 3 30 #1 Boiler Feeder Pump #52
3 15 " 10 3 30 "
3 15 " 12 3 30 "
3 20 Chilled Water Pump
#55 14 3 30 7" Compressor Brown
3 20 " 16 3 30 "
17 3 20 " 18 3 30 "
19 3 40 Cooling tower #54 20 3 70 Air Handler East Unit
3 40 " 22 3 70 "
3 40 " 24 3 70 "
3 70
Air Handler North Heating 26
3 70 " 28
3 70 " 30
3 400 Chiller 32
3 400 " 34
3 400 " 36
1 15 Spare
RAFAEL ACOSTA
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
1) PANEL DIMENSIONS
LENGTH: 57 INCHES
WIDTH: 38 INCHES
DEPTH: 10 12" INCHES
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-17
BUILDING 25900
ROOM 133
PANEL "D"
17 19
EXISTING SUB PANEL "D"
208 / 120 V, 3 PHASE, SURFACE MOUNTED TOP FEED, 3 W 225 A MAIN LUGS
CKT. NO. POLES TRIP (AMPS) SERVICES A B C CKT. NO. POLES TRIP (AMPS) SERVICES
1 20 No Label 2 1 20 No Label
1 20 No Label 4 1 20 No Label
1 20 No Label 6 1 20 No Label
1 20
No Label (note: note on wall next to panel “Air Conditioning”)
8 1 20 No Label
1 20 Green Compressor 10 1 20 No Label
1 20
No Label (note: note on wall next to panel “Mach Shop Supply”)
12 1 20 No Label
2 30 Air Compressor 14 1 20 No Label
2 30 " 16 1 20 No Label
17 1 20 No Label 18 1 20 No Label
19 1 20 No Label 20 1 20 No Label
1 20 No Label 22 1 20 No Label
3 40 No Label 24 1 20 No Label
3 40 " 26 1 20 No Label
3 40 " 28 1 20 No Label
RAFAEL ACOSTA
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
1) PANEL DIMENSIONS
LENGTH: 43 INCHES
WIDTH: 6 1/2 INCHES
DEPTH: 20 12" INCHES
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-18
RAFAEL ACOSTA
18 19
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
GENERAL NOTES
INSTALLATION:
1) COMPLY WITH NFPA 70 NATIONAL FIRE PROTECTION ASSOCIATION, NATIONAL ELECTRIC CODE
2017 AND IEEE C2 NATIONAL ELECTRICAL SAFETY CODE.
2) AIR HANDLER AND HEAT PUMP TO BE ON CIRCUITS WITH HACR TYPE BREAKERS.
3) ALL CONDUCTOR WIRE SHALL BE THHN, 600 V, STRANDED, AND MADE OF COPPER FOR SPLICING AND
INCLUDES NEUTRALS AND GROUNDS.
INSTALLATION OF ELECTRICAL EQUIPMENT INCLUDES:
1. LEVELING AND GROUTING CHANNEL BASES.
DRILLING HOLES, FURNISHING HARDWARE, AND ASSEMBLING COMPONENTS TO EACH
OTHER.
2. FURNISHING MATERIALS FOR AND MAKING ALL CONNECTIONS CORRECTLY IN
ACCORDANCE WITH PANEL SCHEDULES THAT ARE PROVIDED.
3. LABELING WIRES AND TAGGING WIRES AND CABLES AT EACH END.
GROUT ELECTRICAL EQUIPMENT INSTALLED ON CONCRETE FOUNDATIONS IN PLACE TO
PROVIDE FULL AND EVEN BEARING. REPAIR DAMAGED PAINTED SURFACES OF EQUIPMENT TO
MATCH ORIGINAL FINISH. GOVERNMENT WILL INSPECT EQUIPMENT DURING CONSTRUCTION.
CONDUCTOR MARKERS:
· WHITE
· SELF-LAMINATING VINYL TYPE OR HEAT SHRINK TYPE.
· MARKED WITH CONDUCTOR DESIGNATION.
· COMPUTER GENERATED LETTERING.
(CONTINUED ON SHEET 19)
GENERAL NOTES:
CONTRACTOR SHALL VERIFY AND LABEL EACH CONDUCTOR SHOWN IN DRAWINGS OF THE EXISTING
PANELS PRIOR TO REMOVING. THE EXISTING CONDUCTORS INCLUDING FEEDERS SHALL NOT BE
REMOVED BUT TRANSFERRED TO THE NEW PANEL AND TERMINATED TO THE CORRECT BREAKER SIZE.
EXISTING GROUND WIRES SHALL BE REMOVED FROM EACH OF THE 17-PANELS.
NEW GROUND COPPER WIRE WITH ASSOCIATED GROUNDING HARDWARE SHALL BE INSTALLED AND
TERMINATED TO EXISTING GROUND RODS. EACH PANEL AND SUBPANEL WILL HAVE A MAIN BREAKER
ALONG WITH ALL THE BREAKERS FOR EACH BRANCH CIRCUIT THAT FOLLOWS THE NEC SIZING RULES IN
SECTIONS 210-22 (C), 220-3(A), 220-10(A), AND 384-16(C), BOLT ON BREAKERS, AND COPPER BUS.
IF THE EXISTING CONDUCTOR IS TOO SHORT FOR NEW PANELS, CONTRACTOR SHALL ADD TO THAT
CONDUCTOR BY SPLICING THE SAME SIZE OF CONDUCTOR.
IF THE EXISTING CONDUIT IS TOO SHORT FOR NEW PANELS, CONTRACTOR SHALL ADD GALVANIZED RIGID
CONDUIT LABEL CIRCUITS IN THE NEW PANEL TO THE DEVICE IT GOES TO. ONCE EACH PANEL IS
INSTALLED INDIVIDUALLY THE CONTRACTOR SHALL TEST EACH BREAKER IS
WORKING CORRECTLY. ALL NEW PANELS
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
1 08/28/2019 REVISED GENERAL NOTE4 AS INDICATED IN CLOUD. CML
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-25900-2019-EP-19
GENERAL NOTES
RAFAEL ACOSTA
19 19
CESAR M. LIMON
VANESSA CUEVAS
CESAR M. LIMON
1) IDENTIFICATION OF CONDUCTORS SHALL BE DONE AS STATED IN
NFPA 79 ELECTRICAL STANDARD FOR INDUSTRIAL MACHINERY
SECTION 13.2. OVERCURRENT PROTECTION
SIZING . FEEDER OVERCURRENT DEVICES MUST HAVE A RATING OF
NOT LESS THAN 125 PERCENT OF THE CONTINUOUS LOADS, PLUS 100
PERCENT OF THE NON-CONTINUOUS LOADS.
2) EACH PANEL SHALL HAVE THE PROPER MARKING AND SAFETY SIGNS
AS STATED ON NFPA 79 SECTION 16.2 SAFETY SIGNS FOR ELECTRICAL
ENCLOSURES. PANEL SHALL DISPLACE OUTSIDE LABELS ON THE
DOOR OF THE PANEL WITH THE VOLTAGE 208 / 120 V WYE AND 480 V
DELTA, DANGER, AND IN THE PANEL DOOR TO LIST THE CIRCUIT
DESIGNATIONS.
CONDUIT:
A) FITTINGS REQUIRED TO COMPLETE ELECTRICAL CONDUIT SYSTEMS.
INCLUDES CAPS, CONNECTORS, COUPLINGS (EXCLUDING
EXPANSION AND EXPANSION-DEFLECTION COUPLINGS), NIPPLES,
REDUCERS, ELBOWS, PIPE, PLUGS LOCKNUTS, BOND NUTS,
BUSHINGS, SEALS (EXCLUDING WALL PENETRATION AND ANY
OTHER FITTINGS.)
B) DEVICES REQUIRED TO COMPLETE ELECTRICAL CONDUIT SYSTEMS
AND TO FASTEN, CLAMP, ATTACH, AND SUPPORT EACH CONDUIT IN
PLACE.
1) INCLUDES THREADED JOINT COMPOUND; PROTECTIVE SEALANT;
MATERIALS FOR SEALING ENDS OF CONDUITS TERMINATING AT
OUTDOOR BOXES, PANEL BOARDS OR CABINETS; SUPPORTS AND
CLAMPS.
2) COMPLETE WITH BOLTS, WASHERS, AND NUTS.
A) JUNCTION BOX, JUNCTION BOX EXTENSIONS, AND JUNCTION BOX
COVERS: STEEL, OR ZINC COATED.
B) EXPANSION COUPLINGS:
1) FURNISH FOR LONGITUDINAL MOVEMENT ONLY.
GENERAL NOTES:
I
S
S
U
E
D
T
O
C
O
N
S
T
R
U
C
T
I
O
N
ARCH D
A. EXPANSION-DEFLECTION COUPLINGS:
1. FURNISH FOR MOVEMENT IN ANY DIRECTION.
2. WATERTIGHT.
3. DEFLECTION AND EXPANSION: 3/4-INCH, MINIMUM.
4. ANGULAR MISALIGNMENT: 30 DEGREES, MINIMUM.
F. CONDUIT WALL/FLOOR PENETRATION SEALS:
1. ELASTOMERIC MATERIAL TO PREVENT LIQUID OR LIQUID AND GAS SEEPAGE.
2. DUST TIGHT.
3. FIRE RETARDANT.
H. REMOVE BURRS AND SHARP CORNERS AT ENDS OF METAL CONDUIT.
I. SEAL ENDS OF CONDUITS THAT TERMINATE AT BOXES, OR CABINETS WITH SEALING MATERIAL OR SEALING BUSHINGS TO PREVENT AIR CIRCULATION THROUGH CONDUITS INTO BOXES, CABINETS. INSTALL SEALS
IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
J. TIGHTEN CONDUIT TO ELECTRICAL EQUIPMENT MOUNTED ON TUBULAR METAL STRUCTURES SECURELY AND SUPPORT RIGIDLY IN PLACE BY CONDUIT CLAMPS, HEX HEAD NUTS, AND THREADED 3/8-INCH STUD
FASTENERS DRIVEN BY POWER-ACTUATED TOOLS.
K. INSTALL EXPANSION COUPLINGS WHERE EXPOSED OR EMBEDDED CONDUITS CROSS EXPANSION OR CONTRACTION JOINTS. INSTALL EXPANSION COUPLINGS AND EXPANSION AND EXPANSION-DEFELECTION COUPLINGS
IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
L. DRILL HOLES AS NEEDED IN CONCRETE FOR INSTALLATION OF CONDUIT THRU WALLS, FLOOR, OR CEILING. GROUT
CONDUIT IN PLACE IN ACCORDANCE NO SHRINK GROUT.
CONTRACTOR SHALL SUBMIT APPROVAL DATA (MANUFACTURER'S PRODUCT DATA) AND INSTRUCTIONS
(MANUFACTURER'S SURFACE PREPARATION, MIXING, INSTALLATION, AND
CURING INSTRUCTIONS).
GENERAL NOTES:
CHECK THAT ALL THREE PHASES ARE CORRECT (A, B, AND C). THE METER READING ON THE PHASING
TESTER SHOULD READ ZERO BETWEEN PHASE 1 AND PHASE A. THE CONTRACTOR'S CQC SHALL VERIFY
WITH CONTRACTOR THAT EACH CIRCUIT THAT POWERS THAT PIECE OF EQUIPMENT TURNS ON AND WILL
RUN WITHOUT TRIPPING THE CIRCUIT BREAKER.
REPAIRS FOR WALLS AND SURFACES:
ANY SCRATCHES OR HOLES SHALL BE FILLED AND PAINTED TO MATCH
THE EXISTING WALL OR FLOOR COLOR.
| Sheets and Views |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-COVER SHEET |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Staging Area |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-BUILDING 25900 LAYOUT |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Panel A1 |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Panel A2 |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Panel MECH. ROOM |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Room 129 |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Panel 123B |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Room F |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Panel E |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Panel RM |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Panel 123C |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Panel 122 |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Panel R5 |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Panel RG (Right and Left Sides) |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Panel H |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-Panel D |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-RODENT DROPPING REMEDIATION (3) |
| ARL047479P- PLANS AND DRAWINGS - 28 AUGUST 2019 -final Design Upgrade of Panels for Building 25900 AMRAD-RODENT DROPPING REMEDIATION (4) |