SOW- Service/Repair Phoenix Controls Located On Supreme Air LV Chemical Lab Hoods.

POP Date- 8/10/20-8/9/25

The Contractor shall provide all personnel, management, and any other items and services not government furnished, necessary to service/inspect Phoenix Controls on 75 Supreme Air LV chemical lab hoods with located throughout BLDG#, on the United States Army Garrison (USAGWP), West Point, New York.

Services to include: Update Phoenix controls, download & back-up database, communication verification.

Controller Maintenance to include: power supply verification, communication, analog input- 4ma & 20ma, binary input check- open & closed, analog output check, alarm sequence verification.

Fume Hoods: face velocity verification. Room Temperature Controls: Temperature transmitter calibration, reheat valve operation, set point verification.

Fume Hood Controls: power supply verification, communication verification, sensor connections verification, hood valve positioning verification, set point verification, zero point verification, parameters verification, and display operation verification.

Airflow measuring equipment: Airflow measurement and calibration, velocity pressure and flow rate verification, output and power level verification.

Airflow and Pressure Control Valve: Review set point deviation, review and adjust tuning parameters, review control range. Make necessary repairs as needed.