This is a Questions and Answers document addressing contractor inquiries regarding a vertical lift system installation project. The Government has clarified critical specifications and requirements for bidding purposes.

Unit dimensions must strictly conform to the specification of 133.07" (+/-2") wide by 120.98" (+/-2") deep; larger units such as the Modula MXD model (138.46" x 124.61") are unacceptable due to forklift traffic constraints. Tray compartment sizes, partitions, and dividers are detailed in the Statement of Work and cannot be priced without this information. A site visit has been conducted to verify floor load ratings and ceiling clearance. The Government confirms no known hazardous materials are present in existing systems scheduled for demolition. Contractors are responsible for ensuring systems connect to current electrical outlets and are fully operational; work hours are restricted to 0800-1500. Training must accommodate 5-10 personnel per unit. An accelerated construction schedule is acceptable provided all requirements are met, though the baseline expectation is 112-126 days. All shop drawings, specifications, and installation plans must be included with the quote for Government review. The five-year warranty covers only on-call corrective maintenance support; preventative maintenance is excluded from the base price. Contractors must provide final documentation demonstrating system hookup and operational capability.

View the file

Other files for this federal contract opportunity

Other files attached to Fort Riley Vertical Lifts, newest first.
File Type Posted
Amendment 2 Statement of Work.pdf PDF
W911RX26QA014P00002 Amendment to Fort Riley Vertical Lift.pdf PDF
Site visit roster.pdf PDF
W911RX26QA014P00001 Amendment to Fort Riley Vertical Lift.pdf PDF
Statement of Work.pdf PDF
Fort Riley Vertical Lifts CSS.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Unit size spec is 133.07” (+/-2”) wide by 120.98” (+/-2”) deep. Closest size Modula is an model #MXD at 138.46”wide x 124.61”deep

(3) Question: Will they accept these different dimensions?

Answer: No, any larger size would impede with forklift traffic.

There is no spec on tray compartment size so partitions & dividers cannot be priced.

(4) Question: Will the Government provide description of required partitions and dividers?

Answer: Tray size and capacity is listed in statement of work.

Can the Government confirm whether there are any known hazardous materials (e.g., asbestos, lead paint) associated with the existing vertical lift systems scheduled for demolition?

Answer: No known hazards.

Will the Government provide floor load ratings and ceiling clearance confirmations at the installation location, or should contractors independently verify these during the site visit?

Answer: Site visit was conducted to facilitate these answers.

Beyond the stated 15-foot electrical run and final hookups performed by the end user, are there any additional power, conduit, or disconnect modifications anticipated that contractors should account for?

Answer: Contractor will ensure that systems are able to use current electrical outlets and is responsible to ensure system is hooked up and operational.

Please confirm the expected number of personnel to be trained per unit and whether training must be conducted on-site, during normal duty hours, or over multiple sessions.

Answer:5-10 personnel

During the five-year warranty period, is preventative maintenance expected to be included in the base price, or is the requirement limited to on-call corrective maintenance support?

Answer: Preventative maintenance is NOT expected to be included in the base price; only the five-year warranty

Are there any restrictions on work hours, escort requirements, or badging timelines that may impact installation duration or labor planning?

Answer: Work hours are 0800-1500

Is the stated construction duration of 112–126 days a firm requirement, or is an accelerated schedule acceptable if proposed?

Answer: Accelerated schedule is acceptable as long as all requirements are met

Are shop drawings, installation plans, or commissioning documentation required for Government approval prior to installation and final acceptance?

Answer: Any drawings, specifications, or plans should be included with quote.