SK-001-Building_115_Single_Line.pdf
PDF 228 KB Posted
- Solicitation number
- W911PT26QA095
About this file
This is an electrical system schematic diagram for Building 115, depicting the power distribution infrastructure across multiple floors and zones. The drawing illustrates a complex electrical network serving Floor 1 and Floor 2 South areas, the Mezzanine, and specialized spaces including a Computer Room, Pump Room, and Extreme Pressure Lab.
The system includes dual 2000 kVA transformers operating at 13.2 kV/480 V, a 250 kW generator for backup power, and a 45 kVA transformer providing 480V/120V conversion. Power distribution is managed through multiple panels and bus ducts, with amperage ratings ranging from 45A to 3200A depending on the circuit. Key distribution points include the B115 Distribution Switchboard, Computer Room Panel, and various floor-level bus ducts (South East, South West, South Center, and High Center) serving different building zones. The system employs tie configurations for load balancing and redundancy across Floor 1 and Floor 2 South bus ducts, Floor 1 South Center and East/West ducts, and the Mezzanine 480V and 208/120V bus ducts. The schematic references Loop #1 and Loop #2 connections to other substations (1A2 and 2A1/2A2) and includes an Uninterruptible Power Supply (UPS) for critical systems. The document is marked "DO NOT SCALE THIS DRAWING" and is designated as Sheet SK-01.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING 115 WALL
SUBSTATION 1A2
SPAR
E
SPAR
E
BU
S D
U C
T BLD
G
BLD
G
3200A 800A 1600A 1600A 1600A 1600A 1600A
BLD
G
LOOP #1
TO 1A3
LOOP #1
TO 1A1MH-11
N S
800A
FLOOR 1 SOUTH EAST BUS DUCT
480V/120V 225kVA
M
EC
H
AN
IC
AL R
O O
M
FLOOR 1 SOUTH WEST BUS DUCT
FLOOR 1 SOUTH CENTER BUS DUCT
ELEVATO
R
FLOOR 2 SOUTH BUS DUCT
225A 225A 225A
300A
225A800A 400A
FLOOR 2 SOUTH BUS DUCT
400A
FLOOR 1 SOUTH BUS DUCT
600A
B115 DISTRIBUTION
SWITCHBOARD
U
PS
PO
W
ER
PAN
EL
125A125A
400A
60A
480 PAN
EL W
ITH
AC
U N
ITS
200A
480V/120V 45kVA LIG
H
TIN
G
PAN
EL
13.2kV/480V
2000KVA
13.2kV/480V
2000KVA
3200A3200A 1000A800A 3200A
TIE
MM
100A 100A
100E100E
COMPUTER ROOM PANEL
0A
0A
0A
0A
TI
E
TI
E
0A TI
E40
0A TI
E40
0A TI
E40
0A TI
E
FLOOR 1 SOUTH CENTER BUS DUCT 40
0A
FLOOR 1 SOUTH EAST BUS DUCT
FLOOR 1 SOUTH WEST BUS DUCT
FLOOR 2 SOUTH BUS DUCT
0A
0A
0A
FLOOR 2 SOUTH BUS DUCT
FLOOR 1 SOUTH BUS DUCT
2A1
MH-41A
LOOP #2 LOOP #2
TO 2A2
480V/208V 225kVA
400AEXTREME PRESSURE LAB
PUMP ROOM 400A
480V 1200A
EN
L
AUTOMATIC
TRANSFER
SWITCH
G 250kVA
GENERATOR
1000A
C O
M
PU
TER
R
O O
M
NO
NO
NO
NO
NC
NC
TI
E
FLOOR 1 HIGH CENTER BUS DUCT
NO
M
EZZAN
IN
E BU
S D U
C T 208/120V
M
EZZAN
IN
E BU
S D U
C T 480V
1A2
SPAR
E
NO
NC
NC NC NC NC NC NC
NC
NC
NC
NC
NC
NC
NONO
NO
SHEET OF
D A
T E
D A
T E
PR
O
JE
C
T N
U M
B E
R
D R
A W
N B
Y
A
PP
R O
V E
D B
Y
SC
A
L E
R E
V D
E
SC
R
IP
T
IO
N B
Y
DO NOT SCALE THIS DRAWING
AutoCAD SHX Text WATERVLIET ARSENAL PUBLIC WORKS DIVISION 1 BUFFINGTON ST. WATERVLIET, N. Y. 12189
AutoCAD SHX Text THIS DOCUMENT IS THE PROPERTY OF THE IMP-F AND NEITHER THIS DOCUMENT NOR ANY INFORMATION CONTAINED HEREIN MAY BE RELEASED OR TRANSFERRED WITHOUT THE WRITTEN CONSENT OF THE WATERVLIET ARSENAL, PUBLIC WORKS DIVISION, TAWV-IMP-F. IF IN THE COURSE OF CONSTRUCTION A CONDITION EXISTS WHICH DISAGREES WITH THAT AS INDICATED ON THIS PLAN, THE CONTRACTOR SHALL STOP WORK AND NOTIFY THE ARCHITECT & ENGINEER OR ASSUME ALL RESPONSIBILITY AND LIABILITY ARISING THEREFROM.
AutoCAD SHX Text
WATERVLIET ARSENAL
AutoCAD SHX Text
ELECTRICAL SITE PLAN
AutoCAD SHX Text
M. CHASE
AutoCAD SHX Text
28NOV2022
AutoCAD SHX Text
D. FISCHER
AutoCAD SHX Text
28NOV2022
AutoCAD SHX Text
NONE
AutoCAD SHX Text
SK-01
AutoCAD SHX Text
AutoCAD SHX Text
| Sheets and Views |
| Layout1 |
File details come from the government source that posted it. Updated .