Tech Exhibit D- As Builts July 2005
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| TECHNICAL_EXHIBIT_C_DRAWINGS-REVISED.pdf | ||
| Amendment_0001__3-14-2019.pdf | ||
| Solicitation_W91151-19-B-0005_Rpl__2Chiller_at_CEP_B_37015.pdf | ||
| Attachment_1-Appendix_A_19-B-0005.pdf | ||
| TECH_EXHIBIT_A_-_SPECIFICATION_19-B-0005.pdf | ||
| TECH_EXHIBIT_B_-_DRAWINGS_19-B-0005.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet reference number:
A
B
C
D
2 3 4 5
US Army Corps of Engineers
Fort Worth District
E-E201
N 0 8’8’ 4’
SCALE: 1 / 8" = 1’- 0"
E101
CHILLER
ROOM
CHAIN HUNG 4’ TURRET INDUSTRIAL
FEATURES
LAMP TYPE: F32T8/75 CRI
PROFILE: 2 LAMP
SHIELDING: WIRE GUARD
GENERAL DESCRIPTION
HOUSING: DIE-FORMED CRS HOUSING WITH ROLLED SYMMETRIC
REFLECTOR/BALLAST COVER
FINISH: WHITE ENAMEL POLYESTER POWDER COAT
BALLAST: ELECTRONIC IN TYPE "D"
ELECTRONIC WITH TYPE "XFI" EMERGENCY BATTERY
PACK UNIT IN TYPE "DE"
FIXTURE DETAIL
NOT TO SCALE
FLUORESCENT TYPE D & DE
NOM. DIMENSIONS 7"H X 14"W X 4’L
WALL PAK LIGHT FIXTURE
PROFILE: 2 LAMP
SHIELDING: PRISMATIC BOROSILICATE
HOUSING: DIE CAST ALUMINUM HOUSING, DOOR ASSEMBLY AND BACKPLATE
MOUNTING: DIE CAST ALUMINUM BACKPLATE WITH CAST-IN KNOCKOUTS FOR
REFLECTORS: SPECULAR ANODIZED ALUMINUM
FINISH: BAKED-ON POLYURETHANE POWDER COAT PAINT
ELECTRICAL: 277 VOLT BALLAST
BALLAST: ELECTRONIC
LAMP TYPE: F26DTT/RS
TYPE T2 FIXTURE DETAIL
GLASS
MOUNTING HOLE ALIGNMENT.
NOM. DIMENSIONS 12 1/4 "L X 9 1/2 "H X 7 1/4 "D
LAMP TYPE: F32T8/RS, F25T8/RS
PROFILE: 1 LAMP
MOUNTING: CONCEALED IN FIXTURE
OTHER: CHARGING INDICATOR
LIGHT; TEST SWITCH
BATTERY: 90 MINUTE OPERATION
HOUSING: 22 GAUGE RED PAINTED STEEL ENCLOSURE
BATTERY: HIGH TEMPERATURE NICKEL CADMIUM
PACK UNIT
TYPE XF1 EMERGENCY BATTERY
NOM. DIMENSIONS 1 1/2 "W X 2 1/2 "H X 9 1/2 "L
REFLECTORS: COLD ROLLED STEEL, PAINTED WHITE, 10% UPLIGHT
APERATURES.
S
S
T2
S
S
T2
T2
T2
T2
S
S
S
S 1
WALL PAK LIGHT FIXTURE
PROFILE: 1 LAMP
SHIELDING: PRISMATIC BOROSILICATE
HOUSING: DIE CAST ALUMINUM HOUSING, DOOR ASSEMBLY AND BACKPLATE
MOUNTING: DIE CAST ALUMINUM BACKPLATE WITH CAST-IN KNOCKOUTS FOR
REFLECTORS: SPECULAR ANODIZED ALUMINUM
FINISH: BAKED-ON POLYURETHANE POWDER COAT PAINT
TYPE S FIXTURE DETAIL
GLASS
MOUNTING HOLE ALIGNMENT.
NOM. DIMENSIONS 12 1/4 "L X 9 1/2 "H X 7 1/4 "D
LAMP TYPE: 175W METAL HALIDE
MECHANICAL YARD
B-1
BALLAST: HIGH POWER FACTOR
PE
B-3
277V, CONDUIT MOUNTED PHOTOCELL WITH
MANUALLY ADJUSTABLE LIGHT LEVEL SLIDE
FACING NORTH.
WEATHERPROOF SWITCH.
WEATHERPROOF SWITCH.
S
GENERAL NOTES:
1. MOUNT TYPE D AND DE FIXTURES AT 14’ AFF.
2. ALL SWITCHES SHOWN ON THIS SHEET SHALL BE RATED 277V.
KEYED NOTES FOR THIS SHEET ONLY:
1. MOUNT TOP OF FIXTURE 2" BELOW TOP OF WALL.
2. MOUNT FIXTURE AT 8’ ABOVE FINISHED GRADE.
3. NOT USED.
4. MOUNT FIXTURE AT 12’ ABOVE FINISHED GRADE.
reference number:
A
B
C
D
2 3 4 5
US Army Corps of Engineers
Fort Worth District
E-E301
N 0 8’8’ 4’
SCALE: 1 / 8" = 1’- 0"
MECHANICAL YARD
E101
CHILLER
ROOM
GF
WP
GF
WP
GF
WP
GF
WP
GF
WP
GF
WP
GF
WP
GF
WP
GF
WP
GF
WP
PAD MOUNTED UNIT SUBSTATION
T
FOR FIRE ALARM PANEL.
M CP-01
1/3
M
3/4
M
EF-01
990A
M
CH-1
A-7
B-20
C-1
J
AIR COMP.
AIR DRYER
5 J
C-5
C-3
1/3
M
M
A-19
CWP-01
1.5
M
B-8
SSF-01
C-2
UH-01
M
B-2
UH-02
B-7
B-2614
VARIABLE FREQ DRIVE.
C-8
C-7,9
C-11,13
METER INTERFACE UNIT
SEE SHEET E-E602.
1. ALL MECHANICAL CONTROL PANELS SHALL HAVE INTEGRAL
SURGE SUPPRESSION AS PER CONTRACT SPECIFICATIONS.
2. SEE GROUNDING DETAILS ON SHEET E-E801.
B-38
CONTROL PUSHBUTTON STATION
FOR DOOR OPENER MTD 4’ AFF.
J
FLOW METER.
FIRE PROTECTION SPRINKLER
PIPING SPACE.
C-15
HEAT TAPE
CT-1
2-25
M
DOOR
OPENER
1 HP
KEYED NOTES FOR THIS SHEET ONLY:
1. TO UNIT SUBSTATION. SEE SHEET E-E602 FOR CONDUIT &
CONDUCTOR SIZE AND CIRCUIT NUMBER.
2. STUB UP AND CAP 4 - 3-1/2" CONDUITS FROM UNIT
SUBSTATION FOR FUTURE CHILLER.
3. ILON AND DDC CONTROL PANEL. SEE MECH DWGS.
4. LEAK DETECTION CONTROL PANEL.
5. TUBE CLEANING SYSTEM CONTROL PANEL.
6. CHILLED WATER TREATMENT PANEL & PUMP.
7. CONDENSOR WATER TREATMENT PUMP.
8. CONDENSOR WATER TRTMNT CONTROL PANEL.
9. 3#10 & 1#10 GND IN 1/2 " C.
10. 3#1/0 & 1#6 GND IN 2" C.
11. 1-2" CONDUIT STUBBED UP 6" AFF AND CAPPED FROM PANEL B
FOR FUTURE COOLING TOWER.
12. 3#3/0 & 1#4 GND IN 2" C,
13. 3#1 & 1#6 GND IN 1-1/2" C.
14. 3#3 & 1#8 GND IN 1-1/4"C.
15. 2ea 1" C. AND 2ea 2"C. UNDERGROUND BETWEEN EACH INDICATED
EXTERIOR EQUIP. PAD AND THE INSIDE WALL OF BUILDING.
16. STUB UP 4 - 3-1/2" CONDUITS FROM UNIT SUBSTATION FOR
CIRCUITS FEEDING CHILLER CH-1. THE CIRCUITS WILL BE RUN
FROM HERE OVERHEAD TO THE CHILLER.
M
CHP-01
A-1
CHP-02
reference number:
A
B
C
D
2 3 4 5
US Army Corps of Engineers
Fort Worth District
MECHANICAL YARD
E101
CHILLER
ROOM
W
2 - 4" CONDUITS STUBBED UP
FOR INCOMING COPPER AND
FIBER CABLES.
ILON PANEL.
SEE MECH DWGS.
METER INTERFACE UNIT
SEE SHEET E-E602.
NOTE: SEE COMMO RISER ON SHEET E-E601.
4’ X 8’ X 3/4 " PLYWOOD TELEPHONE
BACKBOARDWITH 19" WALL MOUNT
TYPE RACK.
E-E401
0 8’8’ 4’
SCALE: 1 / 8" = 1’- 0"
N reference number:
A
B
C
D
2 3 4 5
US Army Corps of Engineers
Fort Worth District
FINISHED FLOOR
SPARE CONDUITS TO BE CAPPED.
6 PAIR
TELEPHONE
CABLE.
PLYWOOD TELEPHONE BACKBOARD
TELEPHONE OUTLET
WITH ONE RJ45 JACK.
(TYPICAL)
N.T.S.
1. THE TELEPHONE SYSTEM INSTALLATION SHALL BE
2. ALL TELEPHONE CABLE SHALL BE #24 AWG,
TWISTED PAIR.
IN ACCORDANCE WITH EIA/TIA 568-B AND 569
CHILLER ROOM
TO MANHOLE
W
COMMUNCATIONS RISER DIAGRAM
STANDARDS FOR CATEGORY 6.
EIA/TIA 568-B CATEGORY 6, UNSHIELDED
6"
4" METALLIC CONDUITS
4’ X 8’ X 3/4 "
METER INTERFACE UNIT.
SEE E-E602.
2-CONDUCTOR AMRS
CABLE IN 1/2 " CONDUIT
1#6 AWG GROUND IN 1/2 " C. SEE SHT. E-E801.
1-12 ST SM F.O. CABLE.
ILON CABINET.
SEE MECH DWGS.
12" X 2" X 1/4 " GROUND BAR.
ONE 25 PAIR
PROTECTOR
MODULE.
19" WALL MOUNTED RACK PANEL.
8 RACK SPACES
RESERVED FOR FUTURE
KEYED NOTES:
1 ea. PAIR OF THE INCOMING 6 PAIR SHALL BE CONNECTED TO EACH
RJ-45 CONNECTORS OF THE 24-PORT CATEGORY 6 MODULAR PATCH PANEL.
ONE 4-PAIR CATEGORY 6 CABLE IN 1" CONDUIT
ONE 4-PAIR CATEGORY 6 CABLE IN 1" CONDUIT
24-PORT CATEGORY 6 MODULAR PATCH PANEL WITH RJ-45 PORTS
24-PORT CATEGORY 6 MODULAR PATCH PANEL WITH RJ-45 PORTS
12-PORT FIBER OPTICS MODULAR PATCH PANEL WITH ST PORTS
E-E601
E-F401
Sheet reference number:
A
B
C
D
2 3 4 5
US Army Corps of Engineers
Fort Worth District
FTR
ADDRESSABLE FIRE
ALARM PANEL
GENERAL NOTES FOR FIRE ALARM SYSTEM:
1.
2.
3.
N.T.S.
FIRE ALARM RISER DIAGRAM
FIRE ALARM
PANELTO FIRE ALARM ANTENNA.
SEE DETAIL ON SHEET E-F301.
ALL INITIATING DEVICES SHALL BE ADDRESSABLE, CONNECTED TO SLC, STYLE 6 CIRCUITS EXCEPT CONVENTIONAL DEVICES
FOR FIRE SPRINKLER SYSTEMS (TAMPER & FLOW SWITCHES) MAY BE USED IF PROVIDED WITH INDIVIDUAL ADDRESSABLE
INITIATING DEVICE MODULE. MANUAL PULL STATIONS SHALL BE FACTORY ADDRESSABLE TYPE.
FIRE ALARM TRANSMITTER SHALL
BE MONACO BT-X OR APPROVED EQUAL.
P
EXTERIOR
SPRINKLER
SYSTEM PIV
2#12 & 1#12 GND IN 1/2"
CONDUIT ON CKT C-11.
TRANSMITTER SHALL TRANSMIT ALARM AND TROUBLE TO FIRE DEPARTMENT AS FOLLOWS.
ZID 1 - ALARM/TROUBLE
ZID 2 - SPRINKLER FLOW ALARM/SUPERVISION SYSTEM
IN THE EVENT OF AN ALARM CONDITION FROM ANY INITIATING DEVICE, ALL NOTIFICATION APPLIANCES
SHALL ALERT AND A SIGNAL SHALL BE TRANSMITTED TO THE FIRE STATION.
F
P
1. AT ALL LOCATIONS WHERE ACCESS TO MECHANICAL EQUIPMRNT, PIPING
AND/OR DUCT WORK IS REQUIRED OR INDICATED, THE CONDUIT SHALL BE
MOUNTED ABOVE, OR SO THAT THERE WILL BE SUFFICIENT ACCESS SPACE
FOR MAINTENANCE AND REPLACEMENT.
GENERAL FIRE ALARM NOTES
RAIN PROOF
ENCLOSURE WEATHER-
HEAD
BUILDING WALL
COAXIAL CABLE
ROOF/PARAPET
CONTRACTOR TO PROVIDE
SILICONE CAULKING AT THE
CONDUIT PENETRATION
LIGHTNING ARRESTER
(MONACO MODEL R-T)
COAXIAL CABLE AS PER
MANUFACTURERS
RECOMMENDATIONS IN
3/4 " CONDUIT TO FIRE
ALARM TRANSMITTER.
#6 GND IN 1/2 " C TO
BLDG SERVICE GROUND.
SEE SHT E-E801.
GROUND ROD 3/4 " X 10’
RAIN PROOF
ENCLOSURE WEATHER-
HEAD
BUILDING WALL
COAXIAL CABLE
ROOF/PARAPET
CONTRACTOR TO PROVIDE
SILICONE CAULKING AT THE
CONDUIT PENETRATION
LIGHTNING ARRESTER
(MONACO MODEL R-T)
COAXIAL CABLE AS PER
MANUFACTURERS
RECOMMENDATIONS IN
3/4 " CONDUIT TO FIRE
ALARM TRANSMITTER.
#6 GND IN 1/2 " C TO
BLDG SERVICE GROUND.
SEE SHT E-E801.
GROUND ROD 3/4 " X 10’
DESCRIPTIONSYMBOL
P
WHICHEVER IS LOWER.
82"
FIRE ALARM CONTROL PANEL
TAMPER SWITCH
FLOW SWITCH
FIRE ALARM TRANSMITTER
H
R AHU SHUTDOWN RELAY
D
F
DUCT DETECTOR
ADDRESSABLE FIXED TEMPERATURE HEAT DETECTOR
M
PRESSURE SWITCH
FSA
FCP
FTR
FIRE ALARM REMOTE ANNUNCIATOR
CEILING, WHICHEVER IS LOWER. WP INDICATES WEATHERPROOF.
WP INDICATES WEATHERPROOF.
WP
WP
ADDRESSABLE SMOKE DETECTOR.
H INDICATES ADDRESSABLE COMBINATION SMOKE/HEAT DETECTOR.
MINIATURE FIRE ALARM HORN WITH ADDRESSABLE CONTROL MODULE.
FIRE ALARM SPEAKER
ADDRESSABLE FIRE ALARM MANUAL STATION. MOUNT 48" ABOVE FLOOR.
FIRE ALARM VISUAL INDICATOR. WALL MOUNT ABOVE
FINISHED FLOOR OR BELOW CEILING, WHICHEVER IS LOWER.
OR BELOW CEILING,
6"
FIRE ALARM BELL. MOUNT 82" AFF OR WITHIN SPACE OF 6" BELOW
6"
F
FIRE ALARM HORN. WALL MOUNT 82" ABOVE FINISHED FLOOR
COMBINATION FIRE ALARM VISUAL INDICATOR AND HORN.
reference number:
A
B
C
D
2 3 4 5
US Army Corps of Engineers
Fort Worth District
G
TYPICAL
BRANCH
CIRCUIT
CONDUIT
N
METALLIC
WATER PIPE
#1/0 CU
BONDING
JUMPER
BUILDING REBAR.
STRUCTURAL
STEEL COLUMN
CLOSEST TO
PANEL.
COMMO
BACKBOARD
G
TYPICAL
BRANCH
CIRCUIT
CONDUIT
N
480V 208Y/120V
NEUTRAL
TYPICAL
DRY-TYPE
TRANSFORMER
NEAREST METALLIC
WATER PIPE
BONDING
JUMPER
PANEL CPANEL B
1#8 GND IN 1/2 " C.
#6 CU GROUND IN 1/2 " C.
CONDUIT TO UNIT SUBSTATION
CONDUIT TO UNIT SUBSTATION
G
TYPICAL
BRANCH
CIRCUIT
CONDUIT
N
PANEL A
#3/0 CU GROUNDING ELECTRODE
CONDUCTOR IN 3/4 " CONDUIT
TO SUBSTATION COUNTERPOISE.
EXOTHERMIC WELD (TYPICAL)
#3/0 CU GROUNDING ELECTRODE
CONDUCTOR IN 3/4 " CONDUIT.
SIZES AS SHOWN
ON POWER RISER
DIAGRAM ON
SHT E-E602.
SIZES AS SHOWN
ON POWER RISER
DIAGRAM ON
SHT E-E602.
#6 CU GROUND IN 1/2 " C
TO FIRE ALARM ANTENNA
LIGHTNING ARRESTOR.
SEE SHEET E-F301. GROUND BAR. SEE SHEET E-E601.
E-E801
E-E101
2. ALL MOTOR STARTERS SHALL BE PROVIDED WITH AN INDICATOR LAMP.
LAMP SHALL BE "ON" WHEN MOTOR IS RUNNING.
3. FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTIONS TO ALL FAN COIL
UNITS IN ACCORDANCE WITH SPEC SECTION 16415, EQUIPMENT CONNECTIONS.
4. A GREEN 600V INSULATED GROUND WIRE SHALL BE PROVIDED IN ALL CONDUITS.
MD
CU
DESCRIPTIONSYMBOL
WALL MOUNTED FLUORESCENT LIGHT FIXTURE. LETTERS SAME AS
ABOVE. CIRCLE IS OUTLET BOX.
WP
LETTER DENOTES SWITCH OPERATES FIXTURE HAVING SAME LETTER.Sa
SAME AS SWITCH ABOVE W/ THE FOLLOWING EXCEPTIONS: 3 DENOTES
3-WAY, 4 DENOTES 4-WAY SWITCH.S S4
MOTOR CONTROLLER.
SAFETY OR DISCONNECT SWITCH, UNFUSED UNLESS OTHERWISE NOTED.
"R" INDICATES RAINTIGHT.
PANELBOARD.
BRANCH CIRCUIT HOMERUN TO PANELBOARD W/ CIRCUIT NUMBERS
SHOWN. NO. OF ARROWS INDICATES NUMBER OF CIRCUITS.A-1,3
JUNCTION BOX.
EXIT LIGHT. CEILING MOUNTED. LETTER DENOTES TYPE IN FIXTURE
BATTERY POWERED EMERGENCY LIGHT SET. TRIANGLES INDICATE
KEYED NOTE REFERENCE.
J
TV
R
KELLEY 1991
SINGLE POLE WALL SWITCH. MOUNT ABOVE FLOOR. SMALL
B,c
C,d
A,b
D,e
B
A
M
CONDUIT & CONDUCTORS. CROSSLINES INDICATE NEUTRAL, HOT, SWITCH
LEG AND GROUND CONDUCTORS RESPECTIVELY FROM LEFT TO RIGHT.
A,b
FLUORESCENT LIGHT FIXTURE WITH EMERGENCY BATTERY PACK UNIT.
SMALL LETTER DENOTES SWITCH W/ SAME LETTER OPERATES THIS
FIXTURE. CIRCLE IS OUTLET BOX.
FLUORESCENT LIGHT FIXTURE. CAPITAL LETTER DENOTES TYPE.
LETTERS SAME AS ABOVE. CIRCLE IS OUTLET BOX.
LIGHT FIXTURE. LETTERS SAME AS ABOVE.
WALL MOUNTED COMPACT FLUORESCENT, INCANDESCENT, OR H.I.D. LIGHT
NEUTRAL, HOT, AND GROUND IF NO CROSSLINES ARE INDICATED.
SCHEDULE. SHADED AREA INDICATES FACE SIDE(S). PROVIDE
DIRECTIONAL ARROWS WHERE INDICATED.
ARROW SAME AS ABOVE.
WALL MOUNTED EXIT LIGHT. LETTER, SHADED AREA, & DIRECTIONAL
TELEPHONE OUTLET. MOUNT
DUAL PORT COMMUNICATION OUTLET. MOUNT
TV OUTLET. MOUNT
HP.MOTOR. NUMERAL INDICATES
UNLESS NOTED OTHERWISE.
W
TELEPHONE OUTLET. MOUNT
SM MANUAL MOTOR CONTROLLER.
ULTRASONIC OCCUPANCY SENSOR CONTROL UNIT.
CEILING MOUNTED ULTRASONIC OCCUPANCY SENSOR.
GENERAL NOTES FOR ALL SHEETS:
C,d ROUND RECESSED LIGHT FIXTURE WITH EMERGENCY BATTERY BACKUP.
ROUND RECESSED LIGHT FIXTURE. LETTERS SAME AS ABOVE.
LETTERS SAME AS ABOVE.
PE CONDUIT MOUNTED PHTOCELL WITH MANUALLY ADJUSTABLE LIGHT
LEVEL SLIDE.
20A, 125V, NEMA 5-20R, DUPLEX RECEPTACLE. GROUNDED TYPE MOUNTED
"GF" INDICATES GROUND FAULT INTERRUPTER.
20A, 125V, NEMA 5-20R, QUADRUPLEX RECEPTACLE. GROUNDED TYPE
"WP" INDICATES WEATHERPROOF. "EP" INDICATES EXPLOSIONPROOF.
1. A DISCONNECT SWITCH, CAPABLE OF BEING INDIVIDUALLY LOCKED IN THE OPEN POSITION, SHALL BE LOCATED WITHIN SIGHT OF THE MOTOR DRIVEN EQUIPMENT AND A DISCONNECT
SWITCH, CAPABLE OF BEING INDIVIDUALLY LOCKED IN THE OPEN POSITION, SHALL BE LOCATED
WITHIN SIGHT OF ANY MOTOR DRIVEN EQUIPMENT’S ASSOCIATED STARTER. THESE DISCONNECTS
SHALL BE IN ADDITION TO ALL OTHER DISCONNECTS PROVIDED ON OR WITH MOTOR DRIVEN
EQUIPMENT. THERE SHALL NEVER BE A STARTER-DISCONNECT-MOTOR SITUATION.
5. EMERGENCY LIGHTING FIXTURES SHALL BE WIRED SO THAT THE LIGHTS WILL TURN
ON AND OFF WITH THE WALL SWITCH AND WHEN THE NORMAL POWER SUPPLYING
THE CIRCUIT HAS FAILED. THE FIXTURE WILL SWITCH TO EMERGENCY BATTERY POWER.
THEY SHALL NOT BE WIRED AS NIGHT LIGHTS EXCEPT WHERE NOTED OTHERWISE.
24" ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED.
42"
24" ABOVE FLOOR UNO.
42" ABOVE FLOOR UNO.
24" ABOVE FLOOR UNO.
NUMBER OF HEADS & DIRECTION OF AIM. MOUNT SET AT 8’ AFF
MOUNTED 24" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE.
S
6. UNO INDICATES UNLESS NOTED OTHERWISE.
GFGI INDICATES GOVERNMENT FURNISHED, GOVERNMENT INSTALLED.
A
SPECIAL PURPOSE RECEPTACLE. MOUNT AT 24" ABOVE FINISHED FLOOR
UNLESS NOTED OTHERWISE.
24" ABOVE FLOOR UNO.
7. AT ALL LOCATIONS WHERE ACCESS TO MECHANICAL EQUIPMRNT, PIPING
AND/OR DUCT WORK IS REQUIRED OR INDICATED, THE CONDUIT SHALL BE
MOUNTED ABOVE, OR SO THAT THERE WILL BE SUFFICIENT ACCESS SPACE
FOR MAINTENANCE AND REPLACEMENT.
MASS NOTIFICATION STROBE, AMBER LENS. WALL MOUNT SHALL BE AT 82" AFF
OR 6" BELOW CEILING WHICHEVER IS LOWER. CEILING MOUNT SHALL BE AS A
PART OF A FLUSH MOUNTED CEILING SPEAKER.
AUDIO DEVICE. SPEAKER, CEILING FLUSH MOUNTED.
DESCRIPTIONSYMBOL
SPEAKER, HORN TYPE, WALL MOUNT. "W" INDICATES WEATHER PROOF.
MOUNT AT 8’ AFF.
LOC MASS NOTIFICATION SYSTEM, LOCAL OPERATOR CONTROL
20A, 125V, NEMA 5-20R, DUPLEX RECEPTACLE. GROUNDED TYPE
FLOOR MOUNTED FLUSH TO FINISHED FLOOR.
DUAL PORT COMMUNICATION OUTLET. MOUNT FLUSH IN FLOOR.
COMMUNICATIONS CABLE TRAY. MOUNT AT 9’6" AFF. UNO
DATA COMMUNICATION OUTLET. MOUNT AT 42" ABOVE FLOOR. UNO
C C
WP INDICATES WEATHERPROOF.
WP
Sheet reference number:
A
B
C
D
2 3 4 5
US Army Corps of Engineers
Fort Worth District reference number:
A
B
C
D
2 3 4 5
US Army Corps of Engineers
Fort Worth District
E-E701
PANEL A
18500 AMPS MINIMUM INTERRUPTING RATING
277/480 Volts 3 Phase 4 Wire 1200A Main Circuit Breaker
CKT TRIP NO.
LOAD SERVED
PHASE LOAD VA
LOAD SERVED
CKT TRIP NO.
NO. AMPSPOLES A B C NO. AMPSPOLE
350 3 125 HP CHP-1 43212 2
43212 125 HP CHP-2 350 3
3 - - - 43212 4 43212 - - -
5 - - - 43212 6 43212 - - -
7 175 3 60 HP CP-1 21329 8
21329 FUTURE 60 HP CP-2 175 3
9 - - - 21329 10 21329 - - -
11 - - - 21329 12 21329 - - -
13 3 14
15 - - - 16
17 - - - 18
19 200 3 75 HP CWP-1 26592 20
26592 200 3
21 - - - 26592 22 26592 - - -
23 - - - 26592 24 26592 - - -
25 200 3 26592 26 21329 175 3
27 - - - 26592 28 21329 - - -
29 - - - 26592 30 21329 - - -
TOTAL
CIRCUIT BREAKER C-8 SHALL BE LOCKABLE AS PER NFPA FOR FIRE ALARM.
PANEL BPANEL B
13933 AMPS MINIMUM INTERRUPTING RATING
277/480 Volts 3 Phase 4 Wire 350A Main Circuit Breaker
CK TRI NO.
LOAD SERVED
PHASE LOAD VA
LOAD SERVED
CK TRI NO.
NO AMP POLES A B C NO AMP POLES
20 1 LIGHTING 1536 2
5266 UH-1 25 3
3 20 1 LIGHTING 1920 4
5266 - - -
5 20 1 SPARE 1000 6
5266 - - -
7 25 3 UH-2 5266 8
721 1.5 HP SSF-1 20 3
9 - - - 5266 10 721 - - -
11 - - - 5266 12 721 - - -
13 20 3 14
721 FUTURE 1.5 HP SSF-3 20 3
15 - - - 16 721 - - -
17 - - - 18 721 - - -
19 20 3 20
388 AIR COMP. AC 20 3
21 - - - 22 388 - - -
23 - - - 24 388 - - -
25 20 3 TRANSFORMER TC 5748 26
18836 COOLING TOWER 1 CT-1 125 3
27 - - - 4364 28 18836 - - -
29 - - - 4048 30 18836 - - -
31 125 3 FUTURE CT-2 18836 32
18836 FUTURE CT-3 125 3
- - - 18836 34 18836 - - -
35 - - - 18836 36 18836 - - -
37 80 3 SPARE 38
499 DOOR OPENER 20 3
39 - - - 40 499 - - -
41 - - - 42 499 - - -
TOTAL
PANEL C
10000 AMPS MINIMUM INTERRUPTING RATING
120/208 Volts 3 Phase 4 Wire 35A Main Circuit Breaker
CK TRI NO.
LOAD SERVED
PHASE LOAD VA
LOAD SERVED
CK TRI NO.
NO AMP POLES A B C NO AMP POLES
20 1 EF1 AND DRYER EF-1 984 2
864 WTR TRTMNT PUMP WTR 20 1
3 20 1 CONTROL PANELS 1000 4
864 FUTURE WTR2 20 1
5 20 1 WATER TREAT WT4 864 6
864 FUTURE WTR3 20 1
7 20 1 DUPLEX RECEPTACLES 900 8
1000 FIRE ALARM 20 1
9 20 1 DUPLEX RECEPTACLES 900 10
500 SPARE 20 1
11 20 1 DUPLEX RECEPTACLES 720 12
500 SPARE 20 1
13 20 1 DUPLEX RECEPTACLES 900 14
500 SPARE 20 1
15 20 1 HEAT TAPE 100 16
500 SPARE 20 1
17 20 1 FUTURE HEAT TAPE 100 18
500 SPARE 20 1
19 20 1 FUTURE HEAT TAPE 100 20
500 SPARE 20 1
21 - 1 SPACE ONLY (20A - 1P) 0 22
500 SPARE 20 1
23 - 1 SPACE ONLY (20A - 1P) 0 24
500 SPARE 20 1
TOTAL 5748 4364 4048
TOTAL CONNECTED LOAD 14.2 KVA
DEMAND AMPS 31.8
TOTAL DEMAND LOAD 11.4 KVA
FUTURE 1.5 HP SSF-2 721
SPARE 15000
15000
15000
DEMAND AMPS 331.4
TOTAL DEMAND LOAD 275.5 KVA
TOTAL CONNECTED LOAD 276.9 KVA
93374 92374 91138
SPARE35
FUTURE 75 HP CWP-3
10000
10000
10000
258187 258187 258187
TOTAL CONNECTED LOAD 804.8 KVA
TOTAL DEMAND LOAD 793.2 KVA
DEMAND AMPS 954
SPARE 125
FUTURE 75 HP CWP-2
FUTURE 60 HP CP-3
D w n b y
D e s ig n e d b y
R e v ie w e d b y
D a te
S u b m it te d b y
D e s c ri p ti o n
D a te
A c ti o n
S o l N o
C o n tr
N o
C o n tr
N o
D E
S
IG
N F
IL
E
R e v reference number:
A
B
C
D
2 3 4 5
C O
R P
S O
F E
N G
IN
E
E R
F O
R T
W O
R T
H T
E X
A
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
C
N
T R
A L
C H
I L
L E
R P
L A
G
IN
E E
R
IN
G
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
D E
S
IG
N B
R A
N C
H
F il e n a m e
P lo t d a te
P lo t s c a le
S y m b o l
US Army Corps of Engineers
Fort Worth District
W
G
-0
-R -0
C H
IE
F
E
L E
C T
R
IC
A L
S E
C T
IO
N
J A
C K
D S
T O
R Y
R
E F
E R
E N
C E
F
IL
E
R
E F
E R
E N
C E
F
IL
E
R E
F E
R E
N C
E F
IL
E
R
E F
E R
E N
C E
F
IL
E
R E
F E
R E
N C
E F
IL
E
R
E F
E R
E N
C E
F
IL
E
R E
F E
R E
N C
E F
IL
E
R
E F
E R
E N
C E
F
IL
E
R
E F
E R
E N
C E
F
IL
E
R
E F
E R
E N
C E
F
IL
E
R
E F
E R
E N
C E
F
IL
E
R
E F
E R
E N
C E
F
IL
E
R
E F
E R
E N
C E
F
IL
E
R E
F E
R E
N C
E F
IL
E
S
R E
F E
R E
N C
E F
IL
E c a d d f il e n a m e ti m e d a te u s e r$
F O
R T
H O
O D
T
E X
A S
E N
L
IS
T E
D B
A R
R A
C K
S V
P N
J U
L Y
T ra c k in g N o
PANEL
C 4#8 & 1#10 G IN 1" C.
15 KVA,
480 TO 120/208V
DRY TYPE XFMR
A WH
DM
V
MAIN/METERING
SECTION INCOMING SECTION
TRANSFORMER
2000 KVA, 3 PHASE
12470-277/480 VOLT
#3/0 CU TO
COUNTERPOISE
#3/0 CU TO
COUNTERPOISE
TIE BREAKER
NEUTRAL BUS
GROUND BUS
K
3P
2500A
3P
2500A
UNIT SUBSTATION
S
A
WH
DM
V
SURGE ARRESTOR - 9KV
CIRCUIT BREAKER
POTENTIAL TRANSFORMER. (480:120V)
VOLTMETER WITH SELECTOR SWITCH
KILOWATT HOUR DEMAND METER
AMMETER WITH SELECTOR SWITCH
SYMBOL DESCRIPTION
LEGEND (THIS SHEET ONLY)
MIU
WTR
GAS
WATER METER
GAS METER
NOTE: MIU cable shall be No. 22 AWG minimum solid copper with 600-volt insulation, twisted and shielded, 3-wire to match MIU hardware. The color code shall be red and black or red and green.
PANEL
A
PANEL
B
M
GROUND FAULT RELAY (1200A, 0.2 SEC)
KEYED NOTE
3P
2000A
TVSS
200kA
S
GF
3P
400A
CHILLER
CH-1
M M
3P
2000A
AWH
DM
V
#3/0 CU TO
COUNTERPOISE
#3/0 CU TO
COUNTERPOISE
3P
2500A S
TVSS
200kA
S
GF
P
GF
TVSS
200kA
200 KA TRANSIENT VOLTAGE
SURGE SUPPRESSION
INCOMING SECTION
TRANSFORMER
2000 KVA, 3 PHASE
12470-277/480 VOLT
MAIN/METERING
SECTION
METER INTERFACE UNIT IN CHILLER ROOM.
SEE SHEET E-E301 AND CONTRACT
SPECIFICATIONS SECTION 13815.
1#8 GND IN 1/2 " C.
3P
2000A
FUTURE
CHILLER
CH-3
FUTURE
CHILLER
CH-2
3#12 & 1#12 GND IN 1/2 " C.
3P
1600A
1200A, 3P, 480V
DISC SWITCH
INTEGRAL WITH
CHILLER
1. SEE GROUNDING DETAILS ON SHEET E-E801.
2. TIE BREAKER SHALL BE NORMALLY OPEN AND SHALL
NOT BE ABLE TO CLOSE UNLESS ONE OF THE MAINS
IS OPENED. THE TWO MAIN BREAKERS SHALL BE
NORMALLY CLOSED.
MIU CABLE IN
1/2 " CONDUIT.
MIU CABLE IN 1/2 " CONDUIT
TO TYPE 110 CONNECTING
BLOCK ON TELEPHONE
BACKBOARD.
MIU CABLE IN
1/2 " CONDUIT.
S
DISTRIBUTION SECTION.
2500A, 277/480V-3 PH
20,000 IAC MIN.
CURRENT TRANSFORMER 2500:5A
600A, 15KV, 3P SWITCH UNLESS NOTED
OTHERWISE.
100A, 600V, 3P
SWITCH
100A, 600V, 3P
SWITCH
N.O.
LOOP FEED
UNDERGROUND PRIMARY.
SEE SITE PLAN E-U301.
E-E602
| 00794890 |
| 00794900 |
| 00794910 |
| 00794920 |
| FIRE ALARM |
| GROUNDING DETAIL |
| INTERIOR LEGEND |
| PANEL SCHEDULE |
| POWER RISER |