Tech_Exhibit_D-_AS-BUILTS._07_2005.PDF

PDF 1 MB Posted

Attached to
Replace #2 Chiller at CEP, Bldg 37015 Federal contract opportunity
Solicitation number
W9115119B0005
Issued by
Department of the Army Materiel Command Mission and Installation Contracting Command Fort Hood

About this file

Tech Exhibit D- As Builts July 2005

View the file

Other files for this federal contract opportunity

Other files attached to Replace #2 Chiller at CEP, Bldg 37015, newest first.
File Type Posted
TECHNICAL_EXHIBIT_C_DRAWINGS-REVISED.pdf PDF
Amendment_0001__3-14-2019.pdf PDF
Solicitation_W91151-19-B-0005_Rpl__2Chiller_at_CEP_B_37015.pdf PDF
Attachment_1-Appendix_A_19-B-0005.pdf PDF
TECH_EXHIBIT_A_-_SPECIFICATION_19-B-0005.pdf PDF
TECH_EXHIBIT_B_-_DRAWINGS_19-B-0005.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet reference number:

A

B

C

D

2 3 4 5

US Army Corps of Engineers

Fort Worth District

E-E201

N 0 8’8’ 4’

SCALE: 1 / 8" = 1’- 0"

E101

CHILLER

ROOM

CHAIN HUNG 4’ TURRET INDUSTRIAL

FEATURES

LAMP TYPE: F32T8/75 CRI

PROFILE: 2 LAMP

SHIELDING: WIRE GUARD

GENERAL DESCRIPTION

HOUSING: DIE-FORMED CRS HOUSING WITH ROLLED SYMMETRIC

REFLECTOR/BALLAST COVER

FINISH: WHITE ENAMEL POLYESTER POWDER COAT

BALLAST: ELECTRONIC IN TYPE "D"

ELECTRONIC WITH TYPE "XFI" EMERGENCY BATTERY

PACK UNIT IN TYPE "DE"

FIXTURE DETAIL

NOT TO SCALE

FLUORESCENT TYPE D & DE

NOM. DIMENSIONS 7"H X 14"W X 4’L

WALL PAK LIGHT FIXTURE

PROFILE: 2 LAMP

SHIELDING: PRISMATIC BOROSILICATE

HOUSING: DIE CAST ALUMINUM HOUSING, DOOR ASSEMBLY AND BACKPLATE

MOUNTING: DIE CAST ALUMINUM BACKPLATE WITH CAST-IN KNOCKOUTS FOR

REFLECTORS: SPECULAR ANODIZED ALUMINUM

FINISH: BAKED-ON POLYURETHANE POWDER COAT PAINT

ELECTRICAL: 277 VOLT BALLAST

BALLAST: ELECTRONIC

LAMP TYPE: F26DTT/RS

TYPE T2 FIXTURE DETAIL

GLASS

MOUNTING HOLE ALIGNMENT.

NOM. DIMENSIONS 12 1/4 "L X 9 1/2 "H X 7 1/4 "D

LAMP TYPE: F32T8/RS, F25T8/RS

PROFILE: 1 LAMP

MOUNTING: CONCEALED IN FIXTURE

OTHER: CHARGING INDICATOR

LIGHT; TEST SWITCH

BATTERY: 90 MINUTE OPERATION

HOUSING: 22 GAUGE RED PAINTED STEEL ENCLOSURE

BATTERY: HIGH TEMPERATURE NICKEL CADMIUM

PACK UNIT

TYPE XF1 EMERGENCY BATTERY

NOM. DIMENSIONS 1 1/2 "W X 2 1/2 "H X 9 1/2 "L

REFLECTORS: COLD ROLLED STEEL, PAINTED WHITE, 10% UPLIGHT

APERATURES.

S

S

T2

S

S

T2

T2

T2

T2

S

S

S

S 1

WALL PAK LIGHT FIXTURE

PROFILE: 1 LAMP

SHIELDING: PRISMATIC BOROSILICATE

HOUSING: DIE CAST ALUMINUM HOUSING, DOOR ASSEMBLY AND BACKPLATE

MOUNTING: DIE CAST ALUMINUM BACKPLATE WITH CAST-IN KNOCKOUTS FOR

REFLECTORS: SPECULAR ANODIZED ALUMINUM

FINISH: BAKED-ON POLYURETHANE POWDER COAT PAINT

TYPE S FIXTURE DETAIL

GLASS

MOUNTING HOLE ALIGNMENT.

NOM. DIMENSIONS 12 1/4 "L X 9 1/2 "H X 7 1/4 "D

LAMP TYPE: 175W METAL HALIDE

MECHANICAL YARD

B-1

BALLAST: HIGH POWER FACTOR

PE

B-3

277V, CONDUIT MOUNTED PHOTOCELL WITH

MANUALLY ADJUSTABLE LIGHT LEVEL SLIDE

FACING NORTH.

WEATHERPROOF SWITCH.

WEATHERPROOF SWITCH.

S

GENERAL NOTES:

1. MOUNT TYPE D AND DE FIXTURES AT 14’ AFF.

2. ALL SWITCHES SHOWN ON THIS SHEET SHALL BE RATED 277V.

KEYED NOTES FOR THIS SHEET ONLY:

1. MOUNT TOP OF FIXTURE 2" BELOW TOP OF WALL.

2. MOUNT FIXTURE AT 8’ ABOVE FINISHED GRADE.

3. NOT USED.

4. MOUNT FIXTURE AT 12’ ABOVE FINISHED GRADE.

reference number:

A

B

C

D

2 3 4 5

US Army Corps of Engineers

Fort Worth District

E-E301

N 0 8’8’ 4’

SCALE: 1 / 8" = 1’- 0"

MECHANICAL YARD

E101

CHILLER

ROOM

GF

WP

GF

WP

GF

WP

GF

WP

GF

WP

GF

WP

GF

WP

GF

WP

GF

WP

GF

WP

PAD MOUNTED UNIT SUBSTATION

T

FOR FIRE ALARM PANEL.

M CP-01

1/3

M

3/4

M

EF-01

990A

M

CH-1

A-7

B-20

C-1

J

AIR COMP.

AIR DRYER

5 J

C-5

C-3

1/3

M

M

A-19

CWP-01

1.5

M

B-8

SSF-01

C-2

UH-01

M

B-2

UH-02

B-7

B-2614

VARIABLE FREQ DRIVE.

C-8

C-7,9

C-11,13

METER INTERFACE UNIT

SEE SHEET E-E602.

1. ALL MECHANICAL CONTROL PANELS SHALL HAVE INTEGRAL

SURGE SUPPRESSION AS PER CONTRACT SPECIFICATIONS.

2. SEE GROUNDING DETAILS ON SHEET E-E801.

B-38

CONTROL PUSHBUTTON STATION

FOR DOOR OPENER MTD 4’ AFF.

J

FLOW METER.

FIRE PROTECTION SPRINKLER

PIPING SPACE.

C-15

HEAT TAPE

CT-1

2-25

M

DOOR

OPENER

1 HP

KEYED NOTES FOR THIS SHEET ONLY:

1. TO UNIT SUBSTATION. SEE SHEET E-E602 FOR CONDUIT &

CONDUCTOR SIZE AND CIRCUIT NUMBER.

2. STUB UP AND CAP 4 - 3-1/2" CONDUITS FROM UNIT

SUBSTATION FOR FUTURE CHILLER.

3. ILON AND DDC CONTROL PANEL. SEE MECH DWGS.

4. LEAK DETECTION CONTROL PANEL.

5. TUBE CLEANING SYSTEM CONTROL PANEL.

6. CHILLED WATER TREATMENT PANEL & PUMP.

7. CONDENSOR WATER TREATMENT PUMP.

8. CONDENSOR WATER TRTMNT CONTROL PANEL.

9. 3#10 & 1#10 GND IN 1/2 " C.

10. 3#1/0 & 1#6 GND IN 2" C.

11. 1-2" CONDUIT STUBBED UP 6" AFF AND CAPPED FROM PANEL B

FOR FUTURE COOLING TOWER.

12. 3#3/0 & 1#4 GND IN 2" C,

13. 3#1 & 1#6 GND IN 1-1/2" C.

14. 3#3 & 1#8 GND IN 1-1/4"C.

15. 2ea 1" C. AND 2ea 2"C. UNDERGROUND BETWEEN EACH INDICATED

EXTERIOR EQUIP. PAD AND THE INSIDE WALL OF BUILDING.

16. STUB UP 4 - 3-1/2" CONDUITS FROM UNIT SUBSTATION FOR

CIRCUITS FEEDING CHILLER CH-1. THE CIRCUITS WILL BE RUN

FROM HERE OVERHEAD TO THE CHILLER.

M

CHP-01

A-1

CHP-02

reference number:

A

B

C

D

2 3 4 5

US Army Corps of Engineers

Fort Worth District

MECHANICAL YARD

E101

CHILLER

ROOM

W

2 - 4" CONDUITS STUBBED UP

FOR INCOMING COPPER AND

FIBER CABLES.

ILON PANEL.

SEE MECH DWGS.

METER INTERFACE UNIT

SEE SHEET E-E602.

NOTE: SEE COMMO RISER ON SHEET E-E601.

4’ X 8’ X 3/4 " PLYWOOD TELEPHONE

BACKBOARDWITH 19" WALL MOUNT

TYPE RACK.

E-E401

0 8’8’ 4’

SCALE: 1 / 8" = 1’- 0"

N reference number:

A

B

C

D

2 3 4 5

US Army Corps of Engineers

Fort Worth District

FINISHED FLOOR

SPARE CONDUITS TO BE CAPPED.

6 PAIR

TELEPHONE

CABLE.

PLYWOOD TELEPHONE BACKBOARD

TELEPHONE OUTLET

WITH ONE RJ45 JACK.

(TYPICAL)

N.T.S.

1. THE TELEPHONE SYSTEM INSTALLATION SHALL BE

2. ALL TELEPHONE CABLE SHALL BE #24 AWG,

TWISTED PAIR.

IN ACCORDANCE WITH EIA/TIA 568-B AND 569

CHILLER ROOM

TO MANHOLE

W

COMMUNCATIONS RISER DIAGRAM

STANDARDS FOR CATEGORY 6.

EIA/TIA 568-B CATEGORY 6, UNSHIELDED

6"

4" METALLIC CONDUITS

4’ X 8’ X 3/4 "

METER INTERFACE UNIT.

SEE E-E602.

2-CONDUCTOR AMRS

CABLE IN 1/2 " CONDUIT

1#6 AWG GROUND IN 1/2 " C. SEE SHT. E-E801.

1-12 ST SM F.O. CABLE.

ILON CABINET.

SEE MECH DWGS.

12" X 2" X 1/4 " GROUND BAR.

ONE 25 PAIR

PROTECTOR

MODULE.

19" WALL MOUNTED RACK PANEL.

8 RACK SPACES

RESERVED FOR FUTURE

KEYED NOTES:

1 ea. PAIR OF THE INCOMING 6 PAIR SHALL BE CONNECTED TO EACH

RJ-45 CONNECTORS OF THE 24-PORT CATEGORY 6 MODULAR PATCH PANEL.

ONE 4-PAIR CATEGORY 6 CABLE IN 1" CONDUIT

ONE 4-PAIR CATEGORY 6 CABLE IN 1" CONDUIT

24-PORT CATEGORY 6 MODULAR PATCH PANEL WITH RJ-45 PORTS

24-PORT CATEGORY 6 MODULAR PATCH PANEL WITH RJ-45 PORTS

12-PORT FIBER OPTICS MODULAR PATCH PANEL WITH ST PORTS

E-E601

E-F401

Sheet reference number:

A

B

C

D

2 3 4 5

US Army Corps of Engineers

Fort Worth District

FTR

ADDRESSABLE FIRE

ALARM PANEL

GENERAL NOTES FOR FIRE ALARM SYSTEM:

1.

2.

3.

N.T.S.

FIRE ALARM RISER DIAGRAM

FIRE ALARM

PANELTO FIRE ALARM ANTENNA.

SEE DETAIL ON SHEET E-F301.

ALL INITIATING DEVICES SHALL BE ADDRESSABLE, CONNECTED TO SLC, STYLE 6 CIRCUITS EXCEPT CONVENTIONAL DEVICES

FOR FIRE SPRINKLER SYSTEMS (TAMPER & FLOW SWITCHES) MAY BE USED IF PROVIDED WITH INDIVIDUAL ADDRESSABLE

INITIATING DEVICE MODULE. MANUAL PULL STATIONS SHALL BE FACTORY ADDRESSABLE TYPE.

FIRE ALARM TRANSMITTER SHALL

BE MONACO BT-X OR APPROVED EQUAL.

P

EXTERIOR

SPRINKLER

SYSTEM PIV

2#12 & 1#12 GND IN 1/2"

CONDUIT ON CKT C-11.

TRANSMITTER SHALL TRANSMIT ALARM AND TROUBLE TO FIRE DEPARTMENT AS FOLLOWS.

ZID 1 - ALARM/TROUBLE

ZID 2 - SPRINKLER FLOW ALARM/SUPERVISION SYSTEM

IN THE EVENT OF AN ALARM CONDITION FROM ANY INITIATING DEVICE, ALL NOTIFICATION APPLIANCES

SHALL ALERT AND A SIGNAL SHALL BE TRANSMITTED TO THE FIRE STATION.

F

P

1. AT ALL LOCATIONS WHERE ACCESS TO MECHANICAL EQUIPMRNT, PIPING

AND/OR DUCT WORK IS REQUIRED OR INDICATED, THE CONDUIT SHALL BE

MOUNTED ABOVE, OR SO THAT THERE WILL BE SUFFICIENT ACCESS SPACE

FOR MAINTENANCE AND REPLACEMENT.

GENERAL FIRE ALARM NOTES

RAIN PROOF

ENCLOSURE WEATHER-

HEAD

BUILDING WALL

COAXIAL CABLE

ROOF/PARAPET

CONTRACTOR TO PROVIDE

SILICONE CAULKING AT THE

CONDUIT PENETRATION

LIGHTNING ARRESTER

(MONACO MODEL R-T)

COAXIAL CABLE AS PER

MANUFACTURERS

RECOMMENDATIONS IN

3/4 " CONDUIT TO FIRE

ALARM TRANSMITTER.

#6 GND IN 1/2 " C TO

BLDG SERVICE GROUND.

SEE SHT E-E801.

GROUND ROD 3/4 " X 10’

RAIN PROOF

ENCLOSURE WEATHER-

HEAD

BUILDING WALL

COAXIAL CABLE

ROOF/PARAPET

CONTRACTOR TO PROVIDE

SILICONE CAULKING AT THE

CONDUIT PENETRATION

LIGHTNING ARRESTER

(MONACO MODEL R-T)

COAXIAL CABLE AS PER

MANUFACTURERS

RECOMMENDATIONS IN

3/4 " CONDUIT TO FIRE

ALARM TRANSMITTER.

#6 GND IN 1/2 " C TO

BLDG SERVICE GROUND.

SEE SHT E-E801.

GROUND ROD 3/4 " X 10’

DESCRIPTIONSYMBOL

P

WHICHEVER IS LOWER.

82"

FIRE ALARM CONTROL PANEL

TAMPER SWITCH

FLOW SWITCH

FIRE ALARM TRANSMITTER

H

R AHU SHUTDOWN RELAY

D

F

DUCT DETECTOR

ADDRESSABLE FIXED TEMPERATURE HEAT DETECTOR

M

PRESSURE SWITCH

FSA

FCP

FTR

FIRE ALARM REMOTE ANNUNCIATOR

CEILING, WHICHEVER IS LOWER. WP INDICATES WEATHERPROOF.

WP INDICATES WEATHERPROOF.

WP

WP

ADDRESSABLE SMOKE DETECTOR.

H INDICATES ADDRESSABLE COMBINATION SMOKE/HEAT DETECTOR.

MINIATURE FIRE ALARM HORN WITH ADDRESSABLE CONTROL MODULE.

FIRE ALARM SPEAKER

ADDRESSABLE FIRE ALARM MANUAL STATION. MOUNT 48" ABOVE FLOOR.

FIRE ALARM VISUAL INDICATOR. WALL MOUNT ABOVE

FINISHED FLOOR OR BELOW CEILING, WHICHEVER IS LOWER.

OR BELOW CEILING,

6"

FIRE ALARM BELL. MOUNT 82" AFF OR WITHIN SPACE OF 6" BELOW

6"

F

FIRE ALARM HORN. WALL MOUNT 82" ABOVE FINISHED FLOOR

COMBINATION FIRE ALARM VISUAL INDICATOR AND HORN.

reference number:

A

B

C

D

2 3 4 5

US Army Corps of Engineers

Fort Worth District

G

TYPICAL

BRANCH

CIRCUIT

CONDUIT

N

METALLIC

WATER PIPE

#1/0 CU

BONDING

JUMPER

BUILDING REBAR.

STRUCTURAL

STEEL COLUMN

CLOSEST TO

PANEL.

COMMO

BACKBOARD

G

TYPICAL

BRANCH

CIRCUIT

CONDUIT

N

480V 208Y/120V

NEUTRAL

TYPICAL

DRY-TYPE

TRANSFORMER

NEAREST METALLIC

WATER PIPE

BONDING

JUMPER

PANEL CPANEL B

1#8 GND IN 1/2 " C.

#6 CU GROUND IN 1/2 " C.

CONDUIT TO UNIT SUBSTATION

CONDUIT TO UNIT SUBSTATION

G

TYPICAL

BRANCH

CIRCUIT

CONDUIT

N

PANEL A

#3/0 CU GROUNDING ELECTRODE

CONDUCTOR IN 3/4 " CONDUIT

TO SUBSTATION COUNTERPOISE.

EXOTHERMIC WELD (TYPICAL)

#3/0 CU GROUNDING ELECTRODE

CONDUCTOR IN 3/4 " CONDUIT.

SIZES AS SHOWN

ON POWER RISER

DIAGRAM ON

SHT E-E602.

SIZES AS SHOWN

ON POWER RISER

DIAGRAM ON

SHT E-E602.

#6 CU GROUND IN 1/2 " C

TO FIRE ALARM ANTENNA

LIGHTNING ARRESTOR.

SEE SHEET E-F301. GROUND BAR. SEE SHEET E-E601.

E-E801

E-E101

2. ALL MOTOR STARTERS SHALL BE PROVIDED WITH AN INDICATOR LAMP.

LAMP SHALL BE "ON" WHEN MOTOR IS RUNNING.

3. FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTIONS TO ALL FAN COIL

UNITS IN ACCORDANCE WITH SPEC SECTION 16415, EQUIPMENT CONNECTIONS.

4. A GREEN 600V INSULATED GROUND WIRE SHALL BE PROVIDED IN ALL CONDUITS.

MD

CU

DESCRIPTIONSYMBOL

WALL MOUNTED FLUORESCENT LIGHT FIXTURE. LETTERS SAME AS

ABOVE. CIRCLE IS OUTLET BOX.

WP

LETTER DENOTES SWITCH OPERATES FIXTURE HAVING SAME LETTER.Sa

SAME AS SWITCH ABOVE W/ THE FOLLOWING EXCEPTIONS: 3 DENOTES

3-WAY, 4 DENOTES 4-WAY SWITCH.S S4

MOTOR CONTROLLER.

SAFETY OR DISCONNECT SWITCH, UNFUSED UNLESS OTHERWISE NOTED.

"R" INDICATES RAINTIGHT.

PANELBOARD.

BRANCH CIRCUIT HOMERUN TO PANELBOARD W/ CIRCUIT NUMBERS

SHOWN. NO. OF ARROWS INDICATES NUMBER OF CIRCUITS.A-1,3

JUNCTION BOX.

EXIT LIGHT. CEILING MOUNTED. LETTER DENOTES TYPE IN FIXTURE

BATTERY POWERED EMERGENCY LIGHT SET. TRIANGLES INDICATE

KEYED NOTE REFERENCE.

J

TV

R

KELLEY 1991

SINGLE POLE WALL SWITCH. MOUNT ABOVE FLOOR. SMALL

B,c

C,d

A,b

D,e

B

A

M

CONDUIT & CONDUCTORS. CROSSLINES INDICATE NEUTRAL, HOT, SWITCH

LEG AND GROUND CONDUCTORS RESPECTIVELY FROM LEFT TO RIGHT.

A,b

FLUORESCENT LIGHT FIXTURE WITH EMERGENCY BATTERY PACK UNIT.

SMALL LETTER DENOTES SWITCH W/ SAME LETTER OPERATES THIS

FIXTURE. CIRCLE IS OUTLET BOX.

FLUORESCENT LIGHT FIXTURE. CAPITAL LETTER DENOTES TYPE.

LETTERS SAME AS ABOVE. CIRCLE IS OUTLET BOX.

LIGHT FIXTURE. LETTERS SAME AS ABOVE.

WALL MOUNTED COMPACT FLUORESCENT, INCANDESCENT, OR H.I.D. LIGHT

NEUTRAL, HOT, AND GROUND IF NO CROSSLINES ARE INDICATED.

SCHEDULE. SHADED AREA INDICATES FACE SIDE(S). PROVIDE

DIRECTIONAL ARROWS WHERE INDICATED.

ARROW SAME AS ABOVE.

WALL MOUNTED EXIT LIGHT. LETTER, SHADED AREA, & DIRECTIONAL

TELEPHONE OUTLET. MOUNT

DUAL PORT COMMUNICATION OUTLET. MOUNT

TV OUTLET. MOUNT

HP.MOTOR. NUMERAL INDICATES

UNLESS NOTED OTHERWISE.

W

TELEPHONE OUTLET. MOUNT

SM MANUAL MOTOR CONTROLLER.

ULTRASONIC OCCUPANCY SENSOR CONTROL UNIT.

CEILING MOUNTED ULTRASONIC OCCUPANCY SENSOR.

GENERAL NOTES FOR ALL SHEETS:

C,d ROUND RECESSED LIGHT FIXTURE WITH EMERGENCY BATTERY BACKUP.

ROUND RECESSED LIGHT FIXTURE. LETTERS SAME AS ABOVE.

LETTERS SAME AS ABOVE.

PE CONDUIT MOUNTED PHTOCELL WITH MANUALLY ADJUSTABLE LIGHT

LEVEL SLIDE.

20A, 125V, NEMA 5-20R, DUPLEX RECEPTACLE. GROUNDED TYPE MOUNTED

"GF" INDICATES GROUND FAULT INTERRUPTER.

20A, 125V, NEMA 5-20R, QUADRUPLEX RECEPTACLE. GROUNDED TYPE

"WP" INDICATES WEATHERPROOF. "EP" INDICATES EXPLOSIONPROOF.

1. A DISCONNECT SWITCH, CAPABLE OF BEING INDIVIDUALLY LOCKED IN THE OPEN POSITION, SHALL BE LOCATED WITHIN SIGHT OF THE MOTOR DRIVEN EQUIPMENT AND A DISCONNECT

SWITCH, CAPABLE OF BEING INDIVIDUALLY LOCKED IN THE OPEN POSITION, SHALL BE LOCATED

WITHIN SIGHT OF ANY MOTOR DRIVEN EQUIPMENT’S ASSOCIATED STARTER. THESE DISCONNECTS

SHALL BE IN ADDITION TO ALL OTHER DISCONNECTS PROVIDED ON OR WITH MOTOR DRIVEN

EQUIPMENT. THERE SHALL NEVER BE A STARTER-DISCONNECT-MOTOR SITUATION.

5. EMERGENCY LIGHTING FIXTURES SHALL BE WIRED SO THAT THE LIGHTS WILL TURN

ON AND OFF WITH THE WALL SWITCH AND WHEN THE NORMAL POWER SUPPLYING

THE CIRCUIT HAS FAILED. THE FIXTURE WILL SWITCH TO EMERGENCY BATTERY POWER.

THEY SHALL NOT BE WIRED AS NIGHT LIGHTS EXCEPT WHERE NOTED OTHERWISE.

24" ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED.

42"

24" ABOVE FLOOR UNO.

42" ABOVE FLOOR UNO.

24" ABOVE FLOOR UNO.

NUMBER OF HEADS & DIRECTION OF AIM. MOUNT SET AT 8’ AFF

MOUNTED 24" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE.

S

6. UNO INDICATES UNLESS NOTED OTHERWISE.

GFGI INDICATES GOVERNMENT FURNISHED, GOVERNMENT INSTALLED.

A

SPECIAL PURPOSE RECEPTACLE. MOUNT AT 24" ABOVE FINISHED FLOOR

UNLESS NOTED OTHERWISE.

24" ABOVE FLOOR UNO.

7. AT ALL LOCATIONS WHERE ACCESS TO MECHANICAL EQUIPMRNT, PIPING

AND/OR DUCT WORK IS REQUIRED OR INDICATED, THE CONDUIT SHALL BE

MOUNTED ABOVE, OR SO THAT THERE WILL BE SUFFICIENT ACCESS SPACE

FOR MAINTENANCE AND REPLACEMENT.

MASS NOTIFICATION STROBE, AMBER LENS. WALL MOUNT SHALL BE AT 82" AFF

OR 6" BELOW CEILING WHICHEVER IS LOWER. CEILING MOUNT SHALL BE AS A

PART OF A FLUSH MOUNTED CEILING SPEAKER.

AUDIO DEVICE. SPEAKER, CEILING FLUSH MOUNTED.

DESCRIPTIONSYMBOL

SPEAKER, HORN TYPE, WALL MOUNT. "W" INDICATES WEATHER PROOF.

MOUNT AT 8’ AFF.

LOC MASS NOTIFICATION SYSTEM, LOCAL OPERATOR CONTROL

20A, 125V, NEMA 5-20R, DUPLEX RECEPTACLE. GROUNDED TYPE

FLOOR MOUNTED FLUSH TO FINISHED FLOOR.

DUAL PORT COMMUNICATION OUTLET. MOUNT FLUSH IN FLOOR.

COMMUNICATIONS CABLE TRAY. MOUNT AT 9’6" AFF. UNO

DATA COMMUNICATION OUTLET. MOUNT AT 42" ABOVE FLOOR. UNO

C C

WP INDICATES WEATHERPROOF.

WP

Sheet reference number:

A

B

C

D

2 3 4 5

US Army Corps of Engineers

Fort Worth District reference number:

A

B

C

D

2 3 4 5

US Army Corps of Engineers

Fort Worth District

E-E701

PANEL A

18500 AMPS MINIMUM INTERRUPTING RATING

277/480 Volts 3 Phase 4 Wire 1200A Main Circuit Breaker

CKT TRIP NO.

LOAD SERVED

PHASE LOAD VA

LOAD SERVED

CKT TRIP NO.

NO. AMPSPOLES A B C NO. AMPSPOLE

350 3 125 HP CHP-1 43212 2

43212 125 HP CHP-2 350 3

3 - - - 43212 4 43212 - - -

5 - - - 43212 6 43212 - - -

7 175 3 60 HP CP-1 21329 8

21329 FUTURE 60 HP CP-2 175 3

9 - - - 21329 10 21329 - - -

11 - - - 21329 12 21329 - - -

13 3 14

15 - - - 16

17 - - - 18

19 200 3 75 HP CWP-1 26592 20

26592 200 3

21 - - - 26592 22 26592 - - -

23 - - - 26592 24 26592 - - -

25 200 3 26592 26 21329 175 3

27 - - - 26592 28 21329 - - -

29 - - - 26592 30 21329 - - -

TOTAL

CIRCUIT BREAKER C-8 SHALL BE LOCKABLE AS PER NFPA FOR FIRE ALARM.

PANEL BPANEL B

13933 AMPS MINIMUM INTERRUPTING RATING

277/480 Volts 3 Phase 4 Wire 350A Main Circuit Breaker

CK TRI NO.

LOAD SERVED

PHASE LOAD VA

LOAD SERVED

CK TRI NO.

NO AMP POLES A B C NO AMP POLES

20 1 LIGHTING 1536 2

5266 UH-1 25 3

3 20 1 LIGHTING 1920 4

5266 - - -

5 20 1 SPARE 1000 6

5266 - - -

7 25 3 UH-2 5266 8

721 1.5 HP SSF-1 20 3

9 - - - 5266 10 721 - - -

11 - - - 5266 12 721 - - -

13 20 3 14

721 FUTURE 1.5 HP SSF-3 20 3

15 - - - 16 721 - - -

17 - - - 18 721 - - -

19 20 3 20

388 AIR COMP. AC 20 3

21 - - - 22 388 - - -

23 - - - 24 388 - - -

25 20 3 TRANSFORMER TC 5748 26

18836 COOLING TOWER 1 CT-1 125 3

27 - - - 4364 28 18836 - - -

29 - - - 4048 30 18836 - - -

31 125 3 FUTURE CT-2 18836 32

18836 FUTURE CT-3 125 3

- - - 18836 34 18836 - - -

35 - - - 18836 36 18836 - - -

37 80 3 SPARE 38

499 DOOR OPENER 20 3

39 - - - 40 499 - - -

41 - - - 42 499 - - -

TOTAL

PANEL C

10000 AMPS MINIMUM INTERRUPTING RATING

120/208 Volts 3 Phase 4 Wire 35A Main Circuit Breaker

CK TRI NO.

LOAD SERVED

PHASE LOAD VA

LOAD SERVED

CK TRI NO.

NO AMP POLES A B C NO AMP POLES

20 1 EF1 AND DRYER EF-1 984 2

864 WTR TRTMNT PUMP WTR 20 1

3 20 1 CONTROL PANELS 1000 4

864 FUTURE WTR2 20 1

5 20 1 WATER TREAT WT4 864 6

864 FUTURE WTR3 20 1

7 20 1 DUPLEX RECEPTACLES 900 8

1000 FIRE ALARM 20 1

9 20 1 DUPLEX RECEPTACLES 900 10

500 SPARE 20 1

11 20 1 DUPLEX RECEPTACLES 720 12

500 SPARE 20 1

13 20 1 DUPLEX RECEPTACLES 900 14

500 SPARE 20 1

15 20 1 HEAT TAPE 100 16

500 SPARE 20 1

17 20 1 FUTURE HEAT TAPE 100 18

500 SPARE 20 1

19 20 1 FUTURE HEAT TAPE 100 20

500 SPARE 20 1

21 - 1 SPACE ONLY (20A - 1P) 0 22

500 SPARE 20 1

23 - 1 SPACE ONLY (20A - 1P) 0 24

500 SPARE 20 1

TOTAL 5748 4364 4048

TOTAL CONNECTED LOAD 14.2 KVA

DEMAND AMPS 31.8

TOTAL DEMAND LOAD 11.4 KVA

FUTURE 1.5 HP SSF-2 721

SPARE 15000

15000

15000

DEMAND AMPS 331.4

TOTAL DEMAND LOAD 275.5 KVA

TOTAL CONNECTED LOAD 276.9 KVA

93374 92374 91138

SPARE35

FUTURE 75 HP CWP-3

10000

10000

10000

258187 258187 258187

TOTAL CONNECTED LOAD 804.8 KVA

TOTAL DEMAND LOAD 793.2 KVA

DEMAND AMPS 954

SPARE 125

FUTURE 75 HP CWP-2

FUTURE 60 HP CP-3

D w n b y

D e s ig n e d b y

R e v ie w e d b y

D a te

S u b m it te d b y

D e s c ri p ti o n

D a te

A c ti o n

S o l N o

C o n tr

N o

C o n tr

N o

D E

S

IG

N F

IL

E

R e v reference number:

A

B

C

D

2 3 4 5

C O

R P

S O

F E

N G

IN

E

E R

F O

R T

W O

R T

H T

E X

A

U .S

A

R M

Y E

N G

IN

E

E R

D

IS

T R

IC

C

N

T R

A L

C H

I L

L E

R P

L A

G

IN

E E

R

IN

G

C O

N S

T R

U C

T

IO

N D

IV

IS

IO

N

D E

S

IG

N B

R A

N C

H

F il e n a m e

P lo t d a te

P lo t s c a le

S y m b o l

US Army Corps of Engineers

Fort Worth District

W

G

-0

-R -0

C H

IE

F

E

L E

C T

R

IC

A L

S E

C T

IO

N

J A

C K

D S

T O

R Y

R

E F

E R

E N

C E

F

IL

E

R

E F

E R

E N

C E

F

IL

E

R E

F E

R E

N C

E F

IL

E

R

E F

E R

E N

C E

F

IL

E

R E

F E

R E

N C

E F

IL

E

R

E F

E R

E N

C E

F

IL

E

R E

F E

R E

N C

E F

IL

E

R

E F

E R

E N

C E

F

IL

E

R

E F

E R

E N

C E

F

IL

E

R

E F

E R

E N

C E

F

IL

E

R

E F

E R

E N

C E

F

IL

E

R

E F

E R

E N

C E

F

IL

E

R

E F

E R

E N

C E

F

IL

E

R E

F E

R E

N C

E F

IL

E

S

R E

F E

R E

N C

E F

IL

E c a d d f il e n a m e ti m e d a te u s e r$

F O

R T

H O

O D

T

E X

A S

E N

L

IS

T E

D B

A R

R A

C K

S V

P N

J U

L Y

T ra c k in g N o

PANEL

C 4#8 & 1#10 G IN 1" C.

15 KVA,

480 TO 120/208V

DRY TYPE XFMR

A WH

DM

V

MAIN/METERING

SECTION INCOMING SECTION

TRANSFORMER

2000 KVA, 3 PHASE

12470-277/480 VOLT

#3/0 CU TO

COUNTERPOISE

#3/0 CU TO

COUNTERPOISE

TIE BREAKER

NEUTRAL BUS

GROUND BUS

K

3P

2500A

3P

2500A

UNIT SUBSTATION

S

A

WH

DM

V

SURGE ARRESTOR - 9KV

CIRCUIT BREAKER

POTENTIAL TRANSFORMER. (480:120V)

VOLTMETER WITH SELECTOR SWITCH

KILOWATT HOUR DEMAND METER

AMMETER WITH SELECTOR SWITCH

SYMBOL DESCRIPTION

LEGEND (THIS SHEET ONLY)

MIU

WTR

GAS

WATER METER

GAS METER

NOTE: MIU cable shall be No. 22 AWG minimum solid copper with 600-volt insulation, twisted and shielded, 3-wire to match MIU hardware. The color code shall be red and black or red and green.

PANEL

A

PANEL

B

M

GROUND FAULT RELAY (1200A, 0.2 SEC)

KEYED NOTE

3P

2000A

TVSS

200kA

S

GF

3P

400A

CHILLER

CH-1

M M

3P

2000A

AWH

DM

V

#3/0 CU TO

COUNTERPOISE

#3/0 CU TO

COUNTERPOISE

3P

2500A S

TVSS

200kA

S

GF

P

GF

TVSS

200kA

200 KA TRANSIENT VOLTAGE

SURGE SUPPRESSION

INCOMING SECTION

TRANSFORMER

2000 KVA, 3 PHASE

12470-277/480 VOLT

MAIN/METERING

SECTION

METER INTERFACE UNIT IN CHILLER ROOM.

SEE SHEET E-E301 AND CONTRACT

SPECIFICATIONS SECTION 13815.

1#8 GND IN 1/2 " C.

3P

2000A

FUTURE

CHILLER

CH-3

FUTURE

CHILLER

CH-2

3#12 & 1#12 GND IN 1/2 " C.

3P

1600A

1200A, 3P, 480V

DISC SWITCH

INTEGRAL WITH

CHILLER

1. SEE GROUNDING DETAILS ON SHEET E-E801.

2. TIE BREAKER SHALL BE NORMALLY OPEN AND SHALL

NOT BE ABLE TO CLOSE UNLESS ONE OF THE MAINS

IS OPENED. THE TWO MAIN BREAKERS SHALL BE

NORMALLY CLOSED.

MIU CABLE IN

1/2 " CONDUIT.

MIU CABLE IN 1/2 " CONDUIT

TO TYPE 110 CONNECTING

BLOCK ON TELEPHONE

BACKBOARD.

MIU CABLE IN

1/2 " CONDUIT.

S

DISTRIBUTION SECTION.

2500A, 277/480V-3 PH

20,000 IAC MIN.

CURRENT TRANSFORMER 2500:5A

600A, 15KV, 3P SWITCH UNLESS NOTED

OTHERWISE.

100A, 600V, 3P

SWITCH

100A, 600V, 3P

SWITCH

N.O.

LOOP FEED

UNDERGROUND PRIMARY.

SEE SITE PLAN E-U301.

E-E602

00794890
00794900
00794910
00794920
FIRE ALARM
GROUNDING DETAIL
INTERIOR LEGEND
PANEL SCHEDULE
POWER RISER