TECHNICAL EXHIBIT AG SPRINKLER SYSTEM INSPECTION CHECKLIST

View the file

Other files

File Type Posted
Amendment_0002.pdf PDF
Site_Visit_Sign_in_Roster.pdf PDF
Conform_Copy_of_W91151-16-R-0013.pdf PDF
Amendment_0001.pdf PDF
TECHNICAL_EXHIBIT_AJ_MASS_NOTIFICATION_SYSTEM_INSPECTION_CHECKLIST.docx DOCX document
TECHNICAL_EXHIBIT_V_WATER_SUPPLY_TANKS_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_Z_ITM_FORT_HOOD_UFC_TABLE_4-26-11.docx DOCX document
TECHNICAL_EXHIBIT_AA_HAZARDOUS_MATERIAL_AUTHORIZATION_REQUEST.xlsm XLSM spreadsheet
TECHNICAL_EXHIBIT_E_BARRACKS_OVER_1000_DEVICES_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_AP_TECHNICAL_EXHIBIT_LISTING.docx DOCX document
TECHNICAL_EXHIBIT_B_BARRACKS_50_TO_150_DEVICES_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_X_REPLACEMENT_ITEMS_PRICE_SCHEDULE.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_AK__STAND_PIPE_SYSTEM_INSPECTION_CHECKLIST.docx DOCX document
TECHNICAL_EXHIBIT_AQ_PERFORMANCE_REQUIREMENTS_SUMMARY.docx DOCX document
TECHNICAL_EXHIBIT_AC_FIRE_DOOR_INSPECTION_CHECKLIST.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_T_CHEMICAL_SYSTEMS_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_AF_CHEMICAL_SYSTEM_INSPECTION_CHECKLIST.docx DOCX document
TECHNICAL_EXHIBIT_AB_INSPECTION_STATUS_TAGS.docx DOCX document
Attachment_2_-_Wage_Determination.docx DOCX document
TECHNICAL_EXHIBIT_S_FIRE_DOORS_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_D_BARRACKS_301_TO_1000_DEVICES_INVENTORY.xlsx XLSX spreadsheet
Attachment_1_-_Past_Performance_Questionnaire.doc DOC document
TECHNICAL_EXHIBIT_R_BACKFLOW_ASSEMBLIES_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_AD_FIRE_PUMP_TEST_CHECKLIST.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_P_FOAM_SYSTEMS_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_AN_CLEAN_AGENT_SYSTEM_INSPECTION_CHECKLIST.docx DOCX document
TECHNICAL_EXHIBIT_W_CLEAN_AGENT_SYSTEMS_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_Y_INSPECTION_ITEMS_PRICE_SCHEDULE.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_A_BARRACKS_UNDER_50_DEVICES_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_H_VEHICLE_MAINTENANCE_FACILITIES_FIRE_ALARM_SYSTEMS_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_J_WET_SPRINKLER_SYSTEMS_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_K_DRY_SPRINKLER_SYSTEMS_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_M_PREACTION_SYSTEMS_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_N_STAND_PIPE_SYSTEMS_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_Q_FIRE_PUMPS_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_L_DELUGE_SYSTEMS_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_C_BARRACKS_151_TO_300_DEVICES_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_U_MASS_NOTIFICATION_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_G_GENERAL_USE_FIRE_ALARM_SYSTEMS_OVER_200,000_SF_INVENTORY.xlsx XLSX spreadsheet
TECHNICAL_EXHIBIT_AH_FIRE_ALARM_SYSTEM_INSPECTION_CHECKLIST.docx DOCX document
TECHNICAL_EXHIBIT_AL__WATER_SUPPLY_TANK_INSPECTION_CHECKLIST.docx DOCX document
TECHNICAL_EXHIBIT_AE_BACKFLOW_ASSEMBLY_TEST_CHECKLIST.docx DOCX document
TECHNICAL_EXHIBIT_AM_SERVICE_CALL_WORK_REPORT.docx DOCX document
TECHNICAL_EXHIBIT_F_GENERAL_USE_FACILITIES_FIRE_ALARM_SYSTEMS_INVENTORY.xlsx XLSX spreadsheet
W91151-16-R-0013.pdf PDF
Show all 45

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TECHNICAL EXHIBIT AG

SPRINKLER SYSTEM INSPECTION CHECKLIST

Building #: Contact Person: Phone#:

Has Contact Person Been Notified of Test: Yes No Time:

Has Ft. Hood Fire Dept Been Notified: Yes No Time:

Testing/Inspection Conducted By: Date:

NICET#:

Manufacturer:

Type of System: Dry Wet Pre-Action Deluge

SYSTEM TESTS AND INSPECTION *

General Information:

Gauges in good condition and showing normal pressure Yes No N/A

Sprinkler wrench with spare sprinklers Yes No N/A

Hydraulic nameplate attached and legible Yes No N/A

Alarm devices free from damage Yes No N/A

Retarding chamber and drains free of leaks Yes No N/A

Does any piping have leaks (if no, identify where in comments) Yes___ No____

Control Valves:

Number Valves Size of Valves

Are all control valves in good condition Yes No N/A

In correct position and identified Yes No N/A

Sealed, locked, or supervised and accessible Yes No N/A

Operate thru full range and return to normal position Yes No N/A

SPRINKLER SYSTEM INSPECTION CHECKLIST

Building #: Contact Person: Phone#:

Pre-action & Deluge Valves:

Number Valves Size of Valves

Are all control valves in good condition Yes No N/A

Trim valves in correct position and free of leaks Yes No N/A

Electrical components in service Yes No N/A

Sprinkler Pressure Regulating Valves:

In open position and not leaking Yes No N/A

Holding proper pressure maintained in system Yes No N/A

Fire Department Connection:

Gaskets in good condition Yes No N/A

Check valve free of leaks Yes No N/A

Automatic drain valve operating properly Yes No N/A

Couplings and swivels in good condition Yes No N/A

Plugs in-place and undamaged Yes No N/A

Interior free of obstruction Yes No N/A

Valve clapper operates over full range Yes No N/A

Sprinklers:

Number of Heads_______ style or type______________

Free of corrosion Yes No N/A

Free of obstruction to spray patterns Yes No N/A

TECHNICAL EXHIBIT AG

SPRINKLER SYSTEM INSPECTION CHECKLIST

Building #: Contact Person: Phone#:

Free of foreign material, including paint Yes No N/A

Free of damage Yes No N/A

No heads need changed due to recalls or age Yes No N/A

Hangers in good condition and not loose Yes No N/A

Sprinkler System Main Drain Test:

Static Pressure psi Residual Pressure psi

Was flow observed Yes No N/A

Is flow comparable to previous tests (After Initial Annual Test) Yes No N/A

Waterflow Alarm Test:

Inspector’s test connections opened Yes No N/A

By-pass connections opened Yes No N/A

Alarms actuated and flow observed Yes No N/A

Dry Pipe and Pre-action Systems:

Priming water level is correct Yes No N/A

Low air pressure signal passed test Yes No N/A

Quick opening devices passed test Yes No N/A

Valve supervisory switches indicate movement Yes No N/A

INSPECTION OF SPRINKLER SYSTEM

Building #: Contact Person: Phone#:

DRY PIPE TRIP TEST

Dry Valve Size: Year: Make: Model: Ser#:

Q.O.D. Year: Make: Model: Ser#:

Time to trip thru test pipe: Min Sec

Water Pressure: psi Air Pressure: psi Trip Point Air Pressure: psi

Time Water Reached Test Outlet: Min Sec

Alarm Operated Yes No

Upon Completion:

Did alarm panel reset properly Yes No N/A

Did alarm panel clear Yes No N/A

System is in service Yes No N/A

Contact Person and Fire Dept notified of System Return to Service Yes No

System Restored to Normal Operation: Date: Time:

Inspectors Signature: NICET#:

Type:

Annual_____ Two Year______ Three Year_____

INSPECTION OF SPRINKLER SYSTEM

Building #: Contact Person: Phone#:

COMMENTS/DEFICIENCIES: