77525_MECH_DWGS.pdf
PDF 8 MB Posted
- Solicitation number
- W90VN824R0043
About this file
This document is a Request for Proposal (RFP) issued by the Department of the Army Materiel Command for the repair of the fire protection system at Building S-533, Camp Casey in Korea. The RFP is limited to existing Area I & II General Construction Multiple Award Indefinite Delivery Indefinite Quantity (MAIDIQ) Contractors with specific contract numbers listed. The key objectives are to repair the fire protection system, including installing a new automatic wet pipe sprinkler system, repairing the plumbing system, repairing the ventilation system, and repairing the heating and cooling system. Relevant details include the required fire protection system design, occupancy hazard classifications, water supply requirements, and sprinkler head types and quantities. The RFP does not include specific pricing terms or award dates.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 77525_CIVIL_DWGS.pdf | ||
| Solicitation W90VN824R0043.pdf | ||
| 77525_ELEC_Drawing.pdf | ||
| 77525_ARCH_Drawing.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KIM, SM
M-1
NTS
77525 o
ACCU AIR COOLED CONDENSING UNIT
ACLD AIR COOLED
ACU AIR CONDITION UNIT (S)
ACV ALARM CHECK VALVE
ADP APPARATUS DEW POINT
AHU AIR HANDLING UNIT
AIR COND AIR CONDITION (-ING,-ED)
AL ALUMINUM
ALT ALTITUDE
AMB AMBIENT
AMP AMPERE(AMP, AMPS)
APPROX APPROXIMATE
AVG AVERAGE
AWG AMERICAN WIRE GAUGE
BARO BAROMETER(-TRIC)
BARO PR PRESSURE, BAROMETRIC
BHP BRAKE HORSEPOWER
BP BOILING POINT
CAP CAPACITY
CCW COUNTER CLOCKWISE
CHW CHILLED WATER
CKT CIRCUIT
CLASS CLASSIFICATION
CLG LOAD COOLING LOAD
COEF COEFFICIENT
CONN CONNECTION
CONT CONTINUE
C
CMH CUBIC METER PER HOUR
CU M CUBIC METER
CENTIGRADE/ CELCIUS
CFCI
CONTRACTOR INSTALLED
CONTRACTOR FURNISHED
CIP CAST IRON PIPE
CWP
CU MM CUBIC MILLIMETER
Cv COEFFICIENT, VALVE FLOW
CW CLOCKWISE OR COLD WATER
CIRCULATING WATER PUMP
DB DECIBEL OR DRY BULB
COMPRESSORCPRSR
DBT DRY BULB TEMPERATURE
DCWS DOMESTIC COLD WATER SUPPLY
DEG or ° DEGREE
DFW DIESEL OIL
DOMESTIC HOT WATER RETURN
DOMESTIC HOT WATER SUPPLY
DHWR
DHWS
DIRECT EXPANSIONDX
DRY PIPE VALVEDPV
DOUBLE POLE DOUBLE THROWDPDT
DEWPOINT TEMPERATUREDPT
DIVISIONDIV
DIFFERENCEDIFF
DIAGRAMDIAG
DIAMETERDIA or
DWG DRAWING
EXPANSION JOINTEXPJT
ENTERING WATER TEMPEWT
EVAPORAT (-E,-ING,-ED,-OR)EVAP
EXTERNAL STATIC PRESSUREESP
EXPLOSION PROOFEP
EQUIPMENTEQPT
ENTERINGENT
EFFICIENCYEFF
EQUIVALENT DIRECT RADIATIONEDR
ECONOMIZERECON
ECCENTRICECC
ENTERING AIR TEMPERATUREEAT
FUEL OILFO
FA FACE AREA OR FRESH AIR
FHC FIRE HOSE CABINET
FHY FIRE HYDRANT
FLA FULL LOAD AMPERES
F FARENHEIT
FLR FLOOR
FEED WATER PUMPFWP
FACE VELOCITYFVEL
FLUSH VALVEFV
FRP
FREQUENCYFREQ
FEMALE PIPE THREADFPT
FIBERGLASS REINFORCED PLASTIC
Ft or ' FEET
FXTR FIXTURE
GALVANIZED STEELGALVS
GAGE OR GAUGEGA
GR GRAMS
GOVERNMENT INSTALLED
GOVERNMENT FURNISHED GFGI
CONTRACTOR INSTALLED
GOVERNMENT FURNISHEDGFCI
GAL GALLONS
GALLONS PER MINUTEGPM
HERTZHZ
HORIZONTALHORIZ
HOT WATER HEATERHWH
HOT WATERHW
HOUR(S)HR
HORSEPOWERHP
MERCURYHG
HEADHD
HB HOSE BIBB
DIAMETER, INSIDEID
ISOMETRICISO
IRON PIPE SIZEIPS
J JOULE
K THERMAL CONDUCTIVITY
K THERMAL CONDUCTIVITY
kG kCAL/HR
KILOGRAM
kG/SQ CM KILOGRAM PER SQ. CENTIMETER kG/SQ CM A
KILOCALORIE PER HOUR
(ABSOLUTE)
KILOGRAM PER SQ. CENTIMETER
kG/SQ CM G
(GAUGE)
KILOGRAM PER SQ. CENTIMETER
kG/SM KILOGRAM PER SQ. METER kG/SM A kG/SM G
(ABSOLUTE)
KILOGRAM PER SQ. METER
KILOGRAM PER SQ. METER (GAGE)
kW KILOWATT kWH KILOWATT HOUR kJ KILOJOULE kPa KILO PASCAL
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LG LENGTH
LH LATENT HEAT
LWT LEAVING WATER TEMPERATURE
LIQUID LINELL
L LITERS
LPD LITERS PER DAY
LPH LITERS PER HOUR
LPS
LM LINEAR METER
LITERS PER SECOND
LAV LAVATORY
LPM LITERS PER MINUTE
LT LAUNDRY TRAY
NUMBERNO
NORMALLY OPENN.O.
NOT IN CONTRACTNIC
NORMALLY CLOSEDN.C.
NOISE CRITERIANC
NCK
MAX
NOT TO SCALENTS
MIN
MPH
M METERS
MAXIMUM
MINIMUM OR MINUTE
METERS PER HOUR
MPS METERS PER SECOND
MM MILLIMETER
NPT NATIONAL TAPER PIPE (THREAD)
NOT APPLICABLEN/A
NECK
MECH MECHANICAL
OS&Y OUTSIDE SCREW & YOKE
OD
OAIL OUTSIDE AIR INTAKE LOUVER
OA OUTSIDE AIR
OUTSIDE DIAMETER
OPNG OPENING
OXY OXYGEN
PERCENT
PRESSURE REDUCING VALVEPRV
PARTS PER MILLIONPPM
POINT OF CONNECTIONPOC
PLUMBINGPLMB
PHASE (ELECTRIC)PH
PRESSURE GAGEPG
PD
POLEP
PRESSURE DROP OR DIFFERENCE
Pa PASCAL
POL PETROLEUM, OIL AND LUBRICANTS
QUANTITYQTY
QUARTQT
REFRIGERATION TONRT
REVOLUTIONS PER MINUTERPM
RADIATORRDTR
RETURN AIRRA
THERMAL RESISTANCER
REFRIGERANT (134A, 22, ETC)R134A,R22
RH RELATIVE HUMIDITY
SUPPLY AIRSA
SYMBOLSYM
SUCTIONSUCT
STORAGESTOR
STEELSTL
STANDARDSTD
STEAMST
SAYBOLT SECONDS UNIVERSALSSU
STAINLESS STEELSST
SAYBOLT SECONDS FUROLSSF
SQUARESQ
SPECIFICATIONSPEC
SINGLE POLE DOUBLE THROWSPDT
SM
LPH, STANDARD CONDITIONSSLPH
LPS, STANDARD CONDITIONSSLPS
SG
SLPD LPD, STANDARD CONDITIONS
SL SENSIBLE LOAD
SH SENSIBLE HEAT
SPECIFIC GRAVITY
SF SAFETY FACTOR
SEC SECOND
SCH SCHEDULE
STATIC PRESSURE
SQUARE METER
SP
SBM
SAN SANITARY
SUBMERSIBLE
TYPICALTYP
THERMOSTATTSTAT
TONS OF REFRIGERATIONTONS
THICKNESSTHK
THERMOMETERTHERM
TEMPERATURETEMP
TEMPERATURE DIFFERENCETD
UNIT HEATERUH
HEAT TRANSFER COEFFICIENTU
WTRPRF
WT
WSHR
WITHW/
WH
WIDTHWD
WCLD
WC
WBT
WB
WATTW
VP
VOL
VISC
VERTICALVERT
VENTILATIONVENT
VELOCITYVEL
VARIABLE AIR VOLUMEVAV
VAC VACUUM
VLV VALVE
V VOLT
WATERPROOF
WEIGHT
WASHER
WATTHOUR OR WATER HEATER
WATER-COOLED
WATER CLOSET
WET BULB TEMPERATURE
WET BULB
PRESSURE, DYNAMIC(VELOCITY)
VOLUME
VISCOSITY
VTR VENT THRU ROOF
UR URINAL
A B B R E V I A T I O N S
MECHANICAL MATERIAL INDICATIONS AND SYMBOLS
FS
VFM
OFM
AVA
PRESSURE RELIEF
TEMPERATURE
EXPANSION LOOP
EXPANSION JOINT
ANCHOR, INTERMEDIATE
ALIGNMENT GUIDE
AIR VENT, AUTOMATIC
SQUARE HEAD BALANCING COCK
QUICK OPENING
NEEDLE
LOCK SHIELD
FLEXIBLE CONNECTOR
FLOWMETER, ORIFICE
FLOWMETER, VENTURI
FLOW SWITCH
PRESSURE GAUGE AND COCK
STRAINER
THERMOMETER
PRESSURE REDUCING
RELIEF OR SAFETY
SLEEVE
BLOW OFF STRAINER
INLINE PUMP
SAFETY
FLOAT
valves, special duty
S
M
GATE, NORMALLY CLOSED
GLOBE
SOLENOID
3 WAY MANUAL
GATE, NORMALLY OPEN
PLUG
MOTOR OPERATED GATE
MOTOR OPERATED GLOBE
3 WAY ELECMOTOR CONTROL
3 WAY AIR MOTOR CONTROLLER
HOSE GATE
HOSE GLOBE
POST INDICATOR
OS Y
ANGLE GLOBE
ANGLE GATE
SWING GATE CHECK
S
M
P
M
M
ALARM CHECK
DRY PIPE
DELUGE
PREACTION
TAMPER DETECTION SWITCH
QUICK OPENING DEVICE
NON-RISING STEM
DIAPHRAGM
SOLENOID
MOTOR ELECTRIC
valve actuators fittings
TEE, SINGLE SWEEP
UNION, SCREWED
UNION, FLANGED
CONNECTION, TOP
ELBOW, 90°
ELBOW, TURNED UP
ELBOW, TURNED DOWN
TEE, OUTLET UP
TEE, OUTLET DOWN
CONNECTION, BOTTOM
REDUCER, CONCENTRIC
(STRAIGHT, INVERT)
REDUCER, ECCENTRIC
(STRAIGHT, DOWN)
REDUCER, ECCENTRIC
TEE
ELBOW, 45°
LATERAL
SOLVENT CEMENT
BELL AND SPIGOT
SCREWED
FLANGED
WELDED
SOLDERED/BRAZED
M
NS
BUTTERFLY
BALL
DIAPHRAGM
GATE
INDICATING BUTTERFLY
KEY OPERATED
CHECK
SIDEWALL SPRINKLER
UPRIGHT SPRINKLER
DELUGE VALVE
WALL MOUNTED TEST HEADER
FIRE ALARM BELL
HOSE STATION DRY STANDPIPE
MINI HORN
HORN SPEAKER
WALL HYDRANT 2 HOSE OUTLET
SMOKE DETECTOR
PENDENT SPRINKLER DROP NIPPLE
NIPPLED UP UPRIGHT SPRINKLER
OUTSIDE SPRINKLER
CUTTING POINT
CAP
NON-SPRINKLERED SPACE
RISER
(SEE SPRINKLER SCHEDULE)
PENDENT SPRINKLER
CONNECTION (2-WAY SHOWN)
SIAMESE FIRE DEPARTMENT
CONNECTION
SINGLE FIRE DEPARTMENT
valves
POTABLE COLD WATER
POTABLE HOT WATER
POTABLE HOT WATER RETURN
PIPE SLEEVE
BACKFLOW PREVENTER
PITCH OR PIPE, UP(U), DOWN(D)
VENT THRU ROOF
SURFACE CLEANOUT
FLOOR CLEANOUT
FLOOR DRAIN
PIPE SLEEVE WITH FIRE STOPPING
HOSE BIBB
FLOOR SINK (200mm x 200mm)
HOT WATER (60°C)
HOT WATER (82.22°C)
VENT
SANITARY SEWER
COMPRESSED AIR
FUEL OIL SUPPLY
FUEL OIL RETURN
FLOOR DRAIN WITH CLEANOUT
FLOOR DRAIN WITH DEEP TRAP
FLOOR DRAIN WITH NO TRAP
FLOOR DRAIN WITH TRAP TIME
FD
FCO
SCO
200x200
FIRE PROTECTION WATER SUPPLY
MAIN SUPPLY SPRINKLER
WET STANDPIPE
DRY STANDPIPE
COMBINATION STANDPIPE
plumbing sprinkler
DSP
WSP
CSP
S
F
PLAN ELEV
82.22°C
60°C
S
A
FOS
FOR
RD
RS
RL
D
CWS
CWR
LPC
BBD
PC
VPD
MU
FOD
FOV
FOG
FOS
FOR
HWS
M
HCS
HCR
FILL
MU
HWR
LOW PRESSURE CONDENSATE
BOILER BLOW DOWN
PUMPED CONDENSATE
VACUUM PUMP DISCHARGE
MAKE UP WATER
FUEL OIL DRAIN
FUEL OIL TANK VENT
FUEL OIL GAUGE
FUEL OIL SUPPLY
FUEL OIL RETURN
CONTROL AIR MAIN
DUAL TEMPERATURE RETURN
FILL LINE
MAKE UP WATER
DUAL TEMPERATURE SUPPLY
WATER SUPPLY
LOW TEMPERATURE HOT
WATER RETURN
LOW TEMPERATURE HOT
SPLITTER DAMPER
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION
REFRIGERANT LIQUID
DRAIN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
dampers piping heating air conditioning and refrigeration
DU 13mm
47.2
94.4
DG
300x150
500/300L
R
AD
FC
SG
SR
RG
RR
810mm x 400mm
810mm x 400mm
810mm x 400mm
EG
ER
810mm x 400mm
DIRECTION OF FLOW
FLEXIBLE CONNECTION
TRANSITION
(810mm WIDTH x 400mm DEPTH)
DUCT SIZES SHOWN
RISE(R), DOWN(D)
CHANGE OF ELEVATION
VERTICAL OR HORIZONTAL
ACCESS DOOR,
FIRST FIGURE IS ON TOP
POSITIVE PRESS.,
OUTSIDE AIR DUCT SECTION,
FIRST FIGURE IS ON TOP
POSITIVE PRESS.,
SUPPLY AIR DUCT SECTION,
FIRST FIGURE IS ON TOP
SECTION, NEGATIVE PRESS.,
RETURN OR EXHAUST AIR DUCT
SUPPLY OR RETURN
FLEXIBLE AIR DUCT,
TRANSITION
SQUARE TO ROUND
REGISTER, CEILING
EXHAUST AIR GRILLE OR
REGISTER, SIDEWALL
SUPPLY AIR GRILLE OR
REGISTER, CEILING
RETURN AIR GRILLE OR
OR REGISTER, CEILING
SUPPLY AIR MODULAR DIFFUSER
DOOR GRILLE (300mmx150mmH)
(500mmWx300mmH, 94.4 LPS)
LOUVER, DOOR OR WALL
(13mm, 47.2 LPS)
DOOR UNDERCUT
duct works grilles, registers and diffusers
LEGEND & ABBREVIATION
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
CP CASEY
BUILDING S-533
REPAIR FIRE PROTECTION SYSTEM
M-2
NTS
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
GENERAL NOTES & SCOPE OF WORK
A. REPAIR/MAINTENANCE (K-WORK)
SCOPE OF WORK
NOTE :
FIRE PROTECTION AND MECHANICAL GENERAL NOTES
25. SALVAGEABLE MATERIALS SHALL BE RETURNED TO DPW.
AND THE LIKE SHALL BE DONE BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE GOVERNMENT.
24. DISPOSAL OF CONSTRUCTION DEBRIS, WASTE MATERIALS, MATERIALS RESULTING FROM DEMOLITION ACTIVITIES, OFF VALVE WITHIN 1M OF THE UNIT.
23. ALL CONDENSATE DRAINS FROM COOLING UNIT (AS NOTED ON THE DRAWINGS) SHALL BE PROVIDED WITH SHUT-
WATER BEING FLUSHED IS CLEAR AS TAP WATER.
22. PIPING SYSTEM SHALL BE FLUSHED, PURGED & CLEANED PER SPECS REQUIREMENTS AND FLUSHED UNTIL ALL
TYPE FITTINGS AT ALL ROUND DUCT TAKE-OFFS FROM SQUARE OR RECTANGULAR MAINS.
ELBOWS. PROVIDE AIR SPLITTER DAMPERS AT ALL BRANCH TAKE-OFFS FROM THE MAIN DUCT. PROVIDE SPIN-IN
21. PROVIDE TURNING VANES IN ALL ELBOWS THAT CHANGE AIR DIRECTION MORE THAN 30 DEGREES OR USE RADIUS
CONDENSATION, FROM SINK BODIES EXPOSED TO AIR BELOW THE FLOOR.
RECEIVING AIR CONDITIONING CONDENSATE DRAINS, OR ANY OTHER COLD LIQUID WHICH MAY CREATE
20. INSTALL CONDENSATE DRAINS AT A MINIMUM SLOPE OF 1/4 INCH PER 1 FOOT. INSULATE ALL SEWER PIPING
BE MAINTAINED ADEQUATELY. PROVIDE REMOTELY ACTUATED DAMPERS IN AREA WITH CONCEALED CEILINGS.
PANELS FOR TWO VALVES. COORDINATE THE LOCATION OF ACCESS PANELS TO INSURE THAT THE EQUIPMENT CAN
BACKDRAFT DAMPERS AND FOR ANY ITEM INDISE DUCTS REQUIRING SERVICING OR INSPECTION 12"x12" ACCESS
DUCTS AT ALL AUTOMATIC CONTROL DAMPERS, FIRE DAMPERS, FIRE/SMOKE DAMPERS, DUCT SMOKE DETECTOR,
19. PROVIDE ACCESS PANELS TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT. PROVIDE ACCESS DOORS IN
PRESSURE CALSS 500PA AND DUCTWORK SHALL MEET THE REQUIREMENTS OF SEAL CLASS C.
18. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING TO SMACNA STATIC
REPORT SHALL BE SUBMITTED TO THE COR FOR REVIEW AND APPROVAL.
SPECIFICATIONS FOR MISCELLANEOUS PROJECTS, KOREA. THE HVAC TESTING, ADJUSTING AND BALANCING (TAB)
ACCORDANCE WITH APPLICABLE SECTIONS OF DIVISION 22 & 23 - MECHANICAL. O & MA STANDARD TECHNICAL
17. ALL MECHANICAL SYSTEMS SHALL BE TESTED, ADJUSTED AND BALANCED BY THE CONTRACTOR IN STRICT
SUBMITTED TO THE CONTRACTING OFFICER FOR APPROAL.
SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND
16. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT FIELD CONDITIONS. SUCH DETAILS
THE DETAILS SHALL BE UTILIZED WHILE PERFORMING THE MECHANICAL SCOPE OF WORK.
15. FOR O & MA PROJECTS, KOREA, OCTOBER 1, 2003 DEPARTMENT OF THE ARMY FORM AS A PART OF THIS PROJECT.
CONTRACTING OFFICER.
14. THE CONTRACTOR SHALL SUBMIT MANUFACTURERS INSTALLATION SHOP DRAWINGS FOR APPROVAL BY THE
REPAIRED OR REPLACED BY THIS CONTRACTOR AT HIS OWN COST.
DUCT WORK, PIPING ETC. ANY DAMAGED DUE TO THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE
13. CONNECTION TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE ANY EXISTING EQUIPMENT, ROOF, PIPE, DUCT, EQUIPMENT AND ELECTRICAL ITEMS.
NO ADDITIONAL COST TO THE GOVERNMENT, INCLUDING, BUT NOT LIMITED TO ITEMS SUCH AS WALLS, CEILING, NECESSARY TO ALLOW FOR INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE PROTECTION SYSTEM AT
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND REINSTALLATION OF ALL OBSTRUCTIONS AS
BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS AT HIS OWN COST.
11. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO EXISTING AREAS CAUSED
CLEARANCE, EQUIPMENT PAD SIZE, INSTALLATION LOCATIONS, AND ADDITIONAL ITEMS.
10. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE
COMMENCING ANY CONSTRUCTION OR RENOVATION.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITION AND DIMENSIONS PRIOR TO
8. ALL VALVES ON WET PIPE SYSTEM SHALL MEET NFPA 13 REQUIREMENT.
LINE.
7. INSTALL SYSTEM TEST CONNECTION ON WET PIPE SYSTEM AND SHALL BE LOCATED AT THE MOST REMOTE BRANCH
6. SPRINKLERS WITH O-RINGS ARE NOT PERMITTED. PLUG TYPE TAMPER SWITCH SHALL NOT BE USED.
LIMITED TO ALL RISER AND TRIM, SECTIONAL VALVES, INSPECTORS TEST VALVES, AND DRAINS.
5. PROVIDE LABEL TAG INDICATING "NORMALLY OPEN" OR "NORMALLY CLOSED" ON ALL VALVES INCLUDING AND NOT
BRACINGS, FLEXIBLE COUPLINGS, CLEARANCES, AND SEPARATION ASSEMBLIES.
OF PIPING AGAINST DAMAGE WHERE SUBJECT TO EARTHQUAKES". INCLUDING, BUT NOT LIMITED TO, SWAY
4. PROVIDE ALL SEISMIC PROTECTION MEASURES FOR THE FIRE PROTECTION SYSTEM IAW NFPA 13 FOR "PROTECTION
SYSTEM BRANCH LINES AND PIPES LESS THAN 50 MM (2 INCHES) IN NOMINAL.
INDICATING THE TYPE OF FLUID CARRIED AND DIRECTION OF FLOW. LABELS ARE NOT REQUIRED ON SPRINKLER
LABELS CONFORMING TO ASME/ANSI A13. 1-1996, "SCHEME FOR IDENTIFICATION OF PIPING SYSTEMS",
3. MARK ALL EXPOSED INTERIOR PIPING AT 8 METER (26 FT) INTERVALS WITH PLASTIC WRAPAROUND TYPE PIPE
WITH APPROVED FIRE STOPPING MATERIAL IAW SPECIFICATION 07 84 00.
2. THE CLEARANCES AROUND PIPE PENETRATION AT FIRE RATED WALLS AND/OR FLOOR SHALL BE PROPERLY SEALED
PROJECT SPECIFICATION.
EQUIPMENT SHALL BE UL LISTED AND/OR FM APPROVED IN ACCORDANCE WITH NFPA 13, NFPA 20 AND THE
CONTRACTOR SHALL COORDINATE SPRINKLER HEADS LOCATIONS WITH LIGHTING FIXTURES AND HVAC DEVICES. ALL
ACCORDANCE WITH APPLICABLE CODES, MANUFACTURER'S RECOMMENDATIONS, AND EQUIPMENT LISTINGS. THE
1. THE EQUIPMENT SHOWN ON THE PLAN ARE SUGGESTED LOCATIONS. FINAL LAYOUT SHALL BE VERIFIED AND IN
77525
CP CASEY
BUILDING S-533
REPAIR FIRE PROTECTION SYSTEM
TEMPORARY HEATING SYSTEM TO THE ENTIRE BUILDING.
10. IF THE CONTRACTOR IS GOING TO CONSTRUCTION DURING THE HEATING SEASON, THE CONTRACTOR SHALL PROVIDE THE
TRAVEL DISTANCE TO THE NEAREST SHUTOFF SWITCH WILL NOT BE IN EXCESS OF 61 METERS.
ADJACENT TO MANUAL FIRE ALARM PULL BOXES AND WITH AT LEAST ONE SHUTOFF SWITCH PER FLOOR SO THAT THE
AT/FP REQUIREMENTS AND DISABLE THE FAN WHEN ACTIVATED AND CLOSE THE MOTORIZED DAMPER. LOCATION SHALL BE
9. THE BUILDING SHALL HAVE AN EMERGENCY SHUT DOWN SWITCH IN A CLEAR PLASTIC ENCLOSURE WITH LABEL AS PER
OR CERTIFIED INSTALLER.
8. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S SPECIFICATION BY A LICENSED
7. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED PER SPEC.
NECESSARY ACCESSORIES FOR H.V.A.C CONTROLS.
6. THE MECHANICAL/CONTROLS CONTRACTOR SHALL PROVIDE ALL THE WIRINGS, RELAYS, CONTROLLERS, CONDUITS AND ALL
ACTUATED DAMPERS IN AREAS WITH GYPBOARD OR CONCEALED CEILINGS.
5. PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE DRAWINGS OR NOT. PROVIDE REMOTELY
SHALL BE COMPATIBLE WITH THE FIRE WALL OR FLOOR. FIRE DAMPERS SHALL BE UL LISTED.
4. PROVIDE FIRE DAMPERS AT ALL DUCT PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS. FIRE DAMPER RATINGS
DRAWINGS FOR CEILING TYPES.
3. PROVIDE DIFFUSERS AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING TYPES. REFER TO ARCHITECTURAL
OFFICER.
2. THE CONTRACTOR SHALL SUBMIT MECHANICAL SYSTEM INSTALLATION SHOP DRAWINGS FOR APPROVAL BY THE CONTRACTING
INSTALLATION LOCATIONS AND ADDITIONAL ITEMS.
1. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE CLEARANCE, PERFORMED BY THE FPE (FIRE PROTECTION PROFESSIONAL ENGINEER).
6. THE CONTRACTOR SHALL INSPECT AND TEST THE FIRE PROTECTION SYSTEM. THE WORK INSPECTION AND TEST SHALL BE
ON DRAWINGS.
SPARE SPRINKLER HEAD CABINET WITH SPARE SPRINKLER HEAD (6 EA), AND ALL ASSOCIATED ACCESSORIES AS SHOWN
5. REPAIR THE FIRE PROTECTION SYSTEM BY INSTALLING NEW AUTOMATIC WET TYPE FIRE PROTECTION SPRINKLER SYSTEM, HAMMER ARRESTERS, TRAP PRIMER, CONTROL, ACCESS DOORS AND ALL ASSOCIATED ACCESSORIES AS SHOWN ON DRAWINGS.
RE-CIRCULATION PUMP, DOMESTIC HOT WATER CIRCULATION PUMP, BOOSTER PUMP FOR WASHDOWN SYSTEM, VALVES, WATER
PIPES BURIED IN THE WALL), DOMESTIC HOT WATER HEATER, DOMESTIC HOT WATER STORAGE TANK, DOMESTIC HOT WATER
4. REPAIR THE PLUMBING SYSTEM BY INSTALLING NEW DOMESTIC COLD AND HOT WATER PIPING SYSTEM (EXCLUDING BRANCH
VERIFY THAT THE H.V.A.C. SYSTEM WORKS PROPERLY.
3. PERFORM DALT (DUCT AIR LEAKAGE TEST) AND T.A.B (TESTING, ADJUSTING, AND BALANCING) AFTER CONSTRUCTION TO
ASSOCIATED ACCESSORIES FOR VENTILATION SYSTEM AS SHOWN ON DRAWINGS.
CONTROLS, DAMPERS, DIFFUSERS, GRILLES, LOUVERS, DUCTS, INSULATIONS, ACCESS DOORS, EQUIPMENT SUPPORT AND ALL
FANS, IN-LINE EXHAUST FANS, WALL EXHAUST FAN, CONTROLLER, CO2 SENSOR, HVAC EMERGENCY SHUTDOWN SWITCHS,
2. REPAIR THE VENTILATION SYSTEM BY INSTALLING NEW SPLIT TYPE DOAS & VRF HEAT PUMP OUTDOOR UNITS, ROOF EXHAUST
SYSTEM AS SHOWN ON DRAWINGS.
CONTROLS, ACCESS DOORS, EQUIPMENT SUPPORT (CONC. PAD) AND ALL ASSOCIATED ACCESSORIES FOR HEATING AND COOLING
CIRCULATION PUMP, HOT WATER CIRCULATION PUMP, AIR SEPARATORS, PIPES, VALVES, CONTROLLER, INSULATIONS, FINNED TUBE CONVECTOR, AIR CURTAIN, UNIT HEATERS, ELECTRIC UNIT HEATERS, EXPANSION TANKS, CHILLED WATER
UNITS, VARIABLE AIR VOLUME & DAMPER UNITS, SPLIT AIR CONDITIONING INDOOR & OUTDOOR UNIT, FAN COIL UNIT,
1. REPAIR THE HEATING AND COOLING SYSTEM BY INSTALLING NEW HOT WATER BOILER W/ MAGNETIC FILTER, AIR HANDLING
M-3
NTS
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
QTY D E S C R I P T I O NITEM D E S C R I P T I O NQTYITEM QTYITEM D E S C R I P T I O NQTY D E S C R I P T I O NITEM D E S C R I P T I O NQTYITEM QTYITEM D E S C R I P T I O N
E Q U I P M E N T S C H E D U L E S - 1
EQUIPMENT SCHEDULES - 1
AHU
CENTRAL AIR HANDLING UNIT
VOLT/PH/HZ
MOTOR
HP
5 460/3/605,500 1.5"
ESP
COIL
COOLING
ROW
FACE AREA
6.86 SF
11.5 SF
FLOW RATE
6.6 GPM
38 GPM
COOLING CONDITION
SH (BTUH)
146,554 284,600
TH (BTUH) BULB
DRY
WET
EAT
81.5°F
69.5°F
LAT
55.0°F
53.3°F
HEATING CONDITION
66,400
EAT LAT
69°F 80°F
HEATING
HEATING & COOLING COIL CONDITION
S.A (CFM)
AHU
VOLT/PH/HZ
MOTOR
HP
3 460/3/604,000 2.0"
ESP
COIL
COOLING
ROW
FACE AREA
5.83 SF
7.78 SF
FLOW RATE
5.7 GPM
COOLING CONDITION
SH (BTUH)
119,881 216,000
TH (BTUH) BULB
DRY
WET
EAT
81.4°F
69.5°F
LAT
54.0°F
53.8°F
HEATING CONDITION
57,377
EAT LAT
77°F
HEATING
HEATING & COOLING COIL CONDITION
S.A (CFM)
28.8 GPM
61.5°F
CAP (BTUH)
CAP (BTUH)
AHU
CENTRAL AIR HANDLING UNIT
VOLT/PH/HZ
MOTOR
HP
3 460/3/603,500
ESP
COIL
COOLING
ROW
FACE AREA
7.78 SF
FLOW RATE
1.7 GPM
COOLING CONDITION
SH (BTUH)
157,000
TH (BTUH) BULB
DRY
WET
EAT
79.7°F
68.0°F
LAT
55.0°F
53.6°F
HEATING CONDITION
17,000
EAT LAT
65°F
HEATING
HEATING & COOLING COIL CONDITION
S.A (CFM)
AHU
VOLT/PH/HZ
MOTOR
HP
3 460/3/603,500 2.0"
ESP
COIL
COOLING
ROW
FACE AREA FLOW RATE
1.5 GPM
COOLING CONDITION
SH (BTUH)
147,900
TH (BTUH) BULB
DRY
WET
EAT
79.6°F
67.6°F
LAT
55.8°f
54.0°f
HEATING CONDITION
15,371
HEATING
HEATING & COOLING COIL CONDITION
S.A (CFM)
19.7 GPM
CAP (BTUH)
CAP (BTUH)
2.0"
7.0 SF
20.9 GPM
68,862 69.4°F
EAT LAT
65°F 69.0°F
7.0 SF
7.78 SF
70,092
AHU
VOLT/PH/HZ
MOTOR
HP
5 460/3/606,500
ESP
COIL
COOLING
ROW
FACE AREA
11.5 SF
FLOW RATE
5.95 GPM
COOLING CONDITION
SH (BTUH)
263,300
TH (BTUH) BULB
DRY
WET
EAT
80.2°F
67.2°F
LAT
56.0°F
54.2°F
HEATING CONDITION
59,580
EAT LAT
64°F
HEATING
HEATING & COOLING COIL CONDITION
S.A (CFM)
CAP (BTUH)
2.0"
35.1 GPM
72.5°F
CENTRAL STATION VARIABLE AIR VOLUME AIR HANDLING UNIT
13.0 SF
119,881
VAV
VARIABLE AIR VOLUME & DAMPER UNIT
3 YEARS WARRANTY.
ACCESSORIES, AND ALL NECESSARY SAFETIES & OPERATING ACCESSORIES.
ACESS PANEL, EQUIPPED WITH ELECTRIC ACTUATOR STANDARD CONTROL
FACTORY ASSEMBLED, INSULATED PLENUM WITH AIR INLET COLLAR, REMOVABLE
CFM RANGE MIN. P.D. (WG) REMARKS
800 - 2,000 0.28"
VAV
400 - 1,200 0.26"
UH UNIT HEATER
AND ALL NECESSARY ACCESSORIES.
EQUIPPED WITH ADJUSTABLE CONE DIFFUSER, THERMAL OVERLOAD PROTECTION,
SUSPENDED, VERTICAL AIR DISCHARGE, DIRECT-DRIVEN PROPOLLER FAN TYPE,
VOLT/PH/HZ
115/1/60
HP
1/4
GPM
11.6
(BTUH)
HEATING CAP.
E.W.T
196°F
P.D
1.04
RPM
1,070
CFM
3,200116,300
FAN MOTOR SIZE
77525
CP CASEY
BUILDING S-533
REPAIR FIRE PROTECTION SYSTEM
NOTE : NOTE :
THE CONTRACT DOCUMENT REQUIRMENTS.
SHALL BE RESPONSIBLE FOR VERIFYING ACTUAL QUANTITIES BASED ON
QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY, THE CONTRACTOR
FCU
VOLT/PH/HZ
115/1/60
ESP
0.2"
FAN COIL UNIT
SAFETIES & OPERATING ACCESSORIES. 3 YEARS WARRANTY.
FILTER, WITH INSULATED DRAIN PAN W/ DRIP LIP, AND ALL NECESSARY
ALUMINUM FINS WATER COIL AND AIR VENT 1" THK CLEANABLE TYPE AIR
INSULATED CABINET W/ RETURN AIR PLENUM, ELEC BOX COPPER TUBES AND
CEILING HUNG, FORWARD CURVED CENTRIFUGAL FAN, 3-SPEED FAN MOTOR,
W
COOLING HEATING
SENS. TOTAL
4,121 7,490
GPM
0.99 3,746
GPM
0.4
S.A (CFM)
FAN MOTOR
TOTAL
CIRCULATION PUMP
VOLT/PH/HZ
460/3/60
TDH
50'118
HP
P
(GPM)
CAPACITY
REMARKSRPM
MOTOR RATING
1,750 3 CHILLED WATER CIRC. PUMP
460/3/6058' 1,750 389 HOT WATER CIRC. PUMP
CIRCULATING PUMP
OPERATING ACCESSORIES.
QUIET OPERATING RING MOUNTED MOTOR, AND ALL NECESSARY SAFETIES &
PUMP BODY, STAINLESS STEEL IMPELLER, STANDARD MECHANICAL SEAL AND
IN-LINE, CLOSED COUPLED, SINGLE STAGE, STAINLESS STEEL SHAFT, BRONZE
VOLT/PH/HZ
460/3/60
TDH
30'
HP
P
P
(GPM)
CAPACITY
REMARKSRPM
MOTOR RATING
1,750
460/3/6033' 1,7506
P 115/1/601,75010
6'
3/4
1/2
1/12
BOOSTER PUMP
FOR WASHDOWN SYSTEM
DOMESTIC HW. CIRC. PUMP
D.H.W RECIRC. PUMP
P
OPERATING ACCESSORIES. PUMP IS SUITABLE FOR 125 PSI WORKING PRESSURE.
SUCTION AND DISCHARGE CONNECTION, AND ALL NECESSARY SAFETIES &
TEMPERATURE UP TO 250°F, HEAVY CAST IRON CONSTRUCTION CASE & FLANGED
ENCLOSED TYPE BRONZE IMPELLER, MECHANICAL SEAL ARE SUITABLE FOR WATER
STRUCTURAL STEEL BASE, VARIABLE FREQUENCY DRIVE W/VIBRATION ISOLATOR,
END-SUCTION, BASE MOUNTED HORIZONTAL INSTALLATION TYPE, HEAVY
OAU
2,000 1.5"
ESPS.A (CFM)
HPO VARIABLE REFRIGERANT FLOW HEAT PUMP (OUTDOOR UNIT)
SAFETIES & OPERATING ACCESSORIES. ETL LISTED. 3 YEARS WARRANTY.
SENSOR FOR A SAFE AND TROUBLE FREE OPERATION AND ALL NECESSARY
AT LOW AMBIENT CONDITIONS, MULTI CONNECTION PIPING KIT, ALL NECESSARY
ADVANCED PROPORTIONAL INTEGRAL DERIVATIVE (PID) CONTROL TO OPERATES
REFRIGERANT SHUTOFF VALVES, VIBRATION ISOLATORS, SOLENOID VALVES,
OVERLOAD PROTECTION, OVER CURRENT RELAY, R-410A REFRIGERANT CHARGE,
WITH ELECTRONIC EXPANSION VALVES, HIGH PRESSURE SWITCHES, INVERTER
& HEATING REQUIREMENTS, WEATHER-PROOF, INVERTER COMPRESSOR, COMPLETE
CAPABLE OF CHANGING SPEED LINEARY TO FOLLOW THE VARIATION IN COOLING
HEATING EVEN DURING DEFROST OPERATIONS,ELECTRONICALLY CONTROLLED AND
VARIABLE REFRIGERANT FLOW HEAT PUMP OUTDOOR UNIT CAPABLE OF CONTINOUS
VOLT/PH/HZ
460/3/60
(BTUH)
HEATING CAP.
MCA
324,000
ELECTRICAL RATING
MOP(BTUH)
COOLING CAP.
COMPRESSOR
B HOT WATER BOILER
EFFICIENCY
ELEC. POWER
WORKING PRESSURE
SUPPLY WATER TEMP.
GAS INPUT
GROSS OUTPUT
10 YEARS WARRANTY.
SAFETIES & OPERATING ACCESSORIES. CSA CERTIFIED, ASME CERTIFIED.
SENSOR WITH CABLE, MAGNETIC BOILER FILTER, AND ALL NECESSARY
DUAL VENTURI SYSTEM, CONDENSATE NEUTRALIZER, OUTDOOR TEMPERATURE
DUAL STAINLESS STEEL HEAT EXCHANGERS FOR HEATING, MANIFOLD SYSTEM,
GAS FIRED TYPE, CASCADE SYSTEM, CONDENSING TANKLESS COMBI-BOILERS,
MFR. NAVIEN MODEL NO. NFB200H x 4EA OR APPROVED EQUAL.
: 95 %
: 14 FLA, 120 V, 1 PH, 60Hz
: 41.3 - 551.6 kPa
: 80°C
: 18.28 CMH
: 213.2 KW
DC SCROLL
3 / INVERTER
7552.1
REMARK
288,000
3 YEARS WARRANTY.
KIT, AND ALL NECESSARY SAFETIES & OPERATING ACCESSORIES.
COMBINATION MIXING BOX W/ FILTER, VIBRATION ISOLATOR, COMMUNICATIONS
ALUMINUM FIN TYPE CHILLED WATER COOLING & HOT WATER HEATING COILS,
FAN SECTION AND ZONING DAMPER SECTION, STAGGERED COPPER TUBE AND
BLOW-THRU, MULTI-ZONE UNIT COMPONENT MODULES, VERTICAL AIR FLOW TYPE,
SPLIT COMPACT DOAS (DEDICATED OUTDOOR AIR SYSTEM)
FACTORY MOUNTED DISCHARGE AIR TEMPERATURE SENSOR,
SAFETIES & OPERATING ACCESSRIES. 3 YEARS WARRANTY.
SHUTOFF VALVES, VIBRATION ISOLATION, CONTROL PANEL AND ALL NECESSARY
FIN COILS, COMMUNICATIONS KIT, AIR FILTERS, R-410A REFRIGERANT,
PREPAINTED GALVANIZED STEEL DOUBLE SKIN CABINET, ROUND TUBE PLATE
FACTORY ASSEMBLED,
VOLT/PH/HZ
208/1/60
MCA
ELECTRICAL RATING
MOP
157.3
(BTUH)
HEATING CAP.
(BTUH)
COOLING CAP.
143,10059,900
(BTUH)
REHEAT COIL
30,000
PIPE SIZE
VAPOR LIQUID DRAIN
12.7 mm28.58 mm 25 mm
NECESSARY SAFETIES & OPERATING ACCESSORIES. 3 YEARS WARRANTY.
MIXING BOX W/ FILTER, COMMUNICATIONS KIT, VIBRATION ISOLATOR AND ALL
CHILLED WATER COOLING COIL AND HOT WATER HEATING COIL & COMBINATION
TYPE, FAN SECTION, STAGGERED COPPER TUBE AND ALUMINUM FIN TYPE
BLOW-THRU, SINGLE-ZONE UNIT COMPONENT MODULES, VERTICAL AIR FLOW
ACCESSORIES. 3 YEARS WARRANTY.
ISOLATOR, COMMUNICATIONS KIT, AND ALL NECESSARY SAFETIES & OPERATING
CHAIN, VARIABLE SPEED BELT AND STANDARD CONTROL COMPONENT, VIBRATION
MIXING BOX W/ FILTER, ADJUSTABLE PULLEY/BELT, GEAR MOTOR/SPROCKET
CHILLED WATER COOLING COIL AND HOT WATER HEATING COIL & COMBINATION
TYPE, FAN SECTION, STAGGERED COPPER TUBE AND ALUMINUM FIN TYPE
BLOW-THRU, SINGLE-ZONE UNIT COMPONENT MODULES, VERTICAL AIR FLOW
M-4
NTS
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
QTY D E S C R I P T I O NITEM D E S C R I P T I O NQTYITEMQTY D E S C R I P T I O NITEM D E S C R I P T I O NQTYITEM
EQUIPMENT SCHEDULES - 2
E Q U I P M E N T S C H E D U L E S - 2
D E S C R I P T I O NQTYITEM D E S C R I P T I O NQTYITEM
ET
AND ALL NECESSARY SAFETIES & OPERATING ACCESSORIES.
RUBBER DIAPHRAGM AND PIPING CONNECTIONS, 120 PSI WORKING PRESSURE,
CONFORMING TO ASME CODE REQUIREMENTS COMPLETE WITH HEAVY DUTY BUTYL
CLOSED, ROUND HORIZONTAL TYPE, ALL WELDED STEEL CONSTRUCTION,
TANK SIZE
CAPACITY
: 14" DIA x 64-3/4" LG
: 40 GAL'S
ROOF VENTILATOR
ACCESSORIES. UL-LISTED.
DISCONNECT SWITCH, ROOF CURBS, AND ALL NECESSARY SAFETIES & OPERATING
EQUIPPED WITH VIBRATION ISOLATOR, BIRD-SCREEN, BACK-DRAFT DAMPER AND
DESIGN MOTOR, WEATHER-PROOF ALUMINUM FAN HOUSING, SPARK RESISTANT,
ROOF MOUNTED CENTRIFUGAL DIRECT DRIVE, NON-OVERLOADING STANDARD NEMA
VOLT/PH/HZ
1/4"
HP
RF
RF
(CFM)
CAPACITY
REMARKSRPM
MOTOR RATING
1,140
1/8" 1,725
RF
115/1/601,140
1/2
1/4
1/6
RF
115/1/601/12 TOILET IN KITCHEN
RF
115/1/601,550 1/15
RF
115/1/601,550 1/25
115/1/60
115/1/60
SP
1/8"
1/4"
1/8"
1/8"200
850/425
1,100/550
2,500/1,250 DISHWASHING AREA
MECH. ROOM
ELEC. ROOM
FOR COFFEE URN HOOD
FOR UTENSIL SK. HOOD
TYPE
T
T
T
S
S
S
S = SINGLE SPEED TYPE
TYPE : T = TWO SPEED TYPE
ACCESSORIES. UL-LISTED.
DISCONNECT SWITCH, ROOF CURBS, AND ALL NECESSARY SAFETIES & OPERATING
EQUIPPED WITH VIBRATION ISOLATOR, BIRD-SCREEN, BACK-DRAFT DAMPER AND
DESIGN MOTOR, WEATHER-PROOF ALUMINUM FAN HOUSING, SPARK RESISTANT,
WALL MOUNTED CENTRIFUGAL DIRECT DRIVE, NON-OVERLOADING STANDARD NEMA
VOLT/PH/HZ
1/8"
HP
WF
(CFM)
CAPACITY
REMARKSRPM
MOTOR RATING
1,550 1/25 115/1/60
SP
FOR DRY STORAGE200
WALL VENTILATOR
FC
FC
REMARKS
FC
FINNED TUBE CONVECTOR
NO.
ROOM
ROOM NAME
W. TOILET
M. TOILET
W. TOILET
M. TOILET
LOCKER ROOM
NO
ROW
LENGTH
2'-6"
2'-6"
3'-6"
GIVEN (BTUH)
HEATING CAP
1,814
1,780
2,594
2,338
2,419
2-ROW/FOOT ............ 1,270 BTUH
ENCLOSURE CABINET): 1-ROW/FOOT ............ 770 BTUH
RATING FOR FIN TUBE CONVECTIR BASED (AVG, WATER TEMP = 170°F AND
NECESSARY SAFETIES & OPERATING ACCESSORIES.
CABINET, INCLUDE NON-ELECTRIC THERMOSTATIC CONTROL VALVE, AND ALL
FOOT, SLOPING TOP 18 GA. COATED WITH PAINT SHEET METAL ENCLOSURE
1-1/4" I.P.S STEEL TUBE WITH 4-1/4" x 4-1/4" STEEL FINS, 32 FINS
CENTRIFUGAL IN-LINE FAN
ACCESSORIES. UL-LISTED.
WITH DISCONNECT SWITCH, AND ALL NECESSARY SAFETIES & OPERATING
SPRING OR NEOPRENE TYPE VIBRATION ISOLATOR, CENTRIFUGAL FAN, EQUIPPED
HEAVY GAUGE GALVINIZED STEEL CONSTRUCTION, INSULATED FAN HOUSING,
VOLT/PH/HZ
1.2"
HP
IF
IF
REMARKSRPM
MOTOR RATING
IF
IF
115/1/601/4
IF
115/1/601,050 1/4
460/3/60
SP
TYPE
B
B
B
B
D
IF
115/1/601,140 1/6550 D
IF
115/1/601,200 1/4380 B
5,370
4,010
2,880
0.75"
0.75"
0.62"940
0.62"
0.37"
0.75"
1,300
460/3/60
460/3/60
(CFM)
CAP
E.A FOR GAME ROOM
E.A FOR TOILET IN ADMIN
E.A FOR BAR/DANCE (R.W)
E.A FOR BAR/DANCE (L.W)
R.A FOR AHU-5
R.A FOR AHU-1 (L.W)
R.A FOR AHU-2 (R.W)
D = DIRECT DRIVE
TYPE : B = BELT DRIVE
AC AIR CURTAIN
CONTROL VALVE, AND ALL NECESSARY SAFETIES & OPERATING ACCESSORIES.
WHEELS AND FAN HOUSING, ADJUSTABLE LOUVERS AND AIR DIRECTIONAL
MOTOR, DIRECT-DRIVE DOUBLE WITH AND DOUBLE INLET SQUIRREL CAGE BLOWER
POLYCARBONATE CABINET, INCORPORATED WITH A DOUBLE EXTENDED SHAFT
MOTOR RATING
MAX. FPM/CFM NOZZLE
COVERAGE AREA
1,750 RPM
: 1/2 HP, 115 V, 1 PH, 60 Hz
: 2,550 / 2,550
: 4'W x 8'H
ET
AND ALL NECESSARY SAFETIES & OPERATING ACCESSORIES.
RUBBER DIAPHRAGM AND PIPING CONNECTIONS, 120 PSI WORKING PRESSURE,
CONFORMING TO ASME CODE REQUIREMENTS COMPLETE WITH HEAVY DUTY BUTYL
CLOSED, ROUND HORIZONTAL TYPE, ALL WELDED STEEL CONSTRUCTION,
TANK SIZE
CAPACITY
: 13" DIA x 51" LG
: 24 GAL'S
AC SPLIT AIR CONDITIONING OUTDOOR & INDOOR UNIT
NECESSARY SAFETIES & OPERATING ACCESSORIES. 3 YEARS WARRANTY.
FILTER, CLEANABLE FILTERS, WIRELESS REMOTE CONTROLLER AND ALL
REFRIGERATION COMPONENTS, DRAIN PUMP, CONTROL SYSTEM, TOTAL VIRUS
INDOOR UNIT, CONSISTING OF DC INVERTER COMPRESSOR, AIR-COOLED COIL,
VARIABLE REFRIGERANT FLOW HEAT PUMP OUTDOOR UNIT WITH WALL MOUNTED
ELECTRICAL RATING
COMPRESSOR
COOLING CAPACITY
: 15 Amps, 208 V, 1 PH, 60 Hz
: MAX. 282 CFM
: 3,600 W (12,280 BTU/HR)
MFR. LG MODEL NO. SW09BAKWAS OR APPROVED EQUAL.
DWH DOMESTIC HOT WATER HEATER
10 YEARS WARRANTY.
SAFETIES & OPERATING ACCESSORIES. CSA CERTIFIED, ASME CERTIFIED.
SENSOR WITH CABLE, MAGNETIC BOILER FILTER, AND ALL NECESSARY
DUAL VENTURI SYSTEM, CONDENSATE NEUTRALIZER, OUTDOOR TEMPERATURE
DUAL STAINLESS STEEL HEAT EXCHANGERS FOR HEATING, MANIFOLD SYSTEM,
GAS FIRED TYPE, CASCADE SYSTEM, CONDENSING WATER HEATER,
EFFICIENCY
ELEC. POWER
TEMP. RISE
SUPPLY WATER TEMP.
GAS INPUT
HEAT RECOVERY
GROSS OUTPUT
ELECTRIC UNIT HEATER
AND ALL NECESSARY ACCESSORIES. UL LISTED.
HEATING ELEMENT, COMPLETE WITH BUILT-IN CONTROL REMOTE THERMOSTAT
HEAVY 18 GAUGE STEEL CASING, DIRECT DRIVE PROPELLER FAN, ELECTRIC
CEILING HUNG, HORIZONTAL DISCHARGE, ADJUSTABLE LOUVER, COMPLETE WITH
ELEC. RATING
MOTOR
HEATING CAPACITY
FAN CAPACITY
: 3.0 kW, 208 V, 1 Ph, 60 Hz
: 1/50 HP, 240 V, 1 Ph, 60 Hz
: 3.0 kW
: 146 LPS
MFR. CHROMALOX MODEL NO. LUH-04-21-34 OR APPROVED EQUAL.
EUH
NOTE : NOTE :
THE CONTRACT DOCUMENT REQUIRMENTS.
SHALL BE RESPONSIBLE FOR VERIFYING ACTUAL QUANTITIES BASED ON
QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY, THE CONTRACTOR
MFR. NAVIEN MODEL NO. NPE-240S2 x 4EA OR APPROVED EQUAL.
: 97 %
: 3 FLA, 120 V, 1 PH, 60Hz
: 16.7 °C
: 60.0 °C
: 18.28 CMH
: 191.6 LPM
: 223.2 KW
DT DOMESTIC HOT WATER STORAGE TANK
ACCESSORIES.
AND TANK SUPPORTING LEGS AND ALL NECESSARY SAFETIES AND OPERATING
MOUNTED TYPE. CATHODIC PROTECTION, EQUIPPED WITH INSPECTION MANHOLE
150 PSI ASME STAMPED, GLASS-LINED STEEL TANK, CYLINDRICAL VERTICAL
TANK SIZE
CAPACITY
: 1,200mmD x 2,750mmL
: 800 GALLONS
EXPANSION TANK FOR COOLING SYSTEM
EXPANSION TANK FOR HEATING SYSTEM
AS AIR SEPARATOR
ALL NECESSARY SAFETIES & OPERATING ACCESSORIES.
CONNECTION, 3" FLANGED CONNECTION, 125 PSI WORKING PRESSURE, AND
REQUIREMENTS COMPLETE WITH REMOVABLE GALV. STRAINER & PIPING
CYLINDRICAL TYPE, STEEL CONSTRUCTION, CONFORMED TO ASME CODE
CAPACITY : 118 GPM
M-5
NTS
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
CP CASEY
BUILDING S-533
REPAIR FIRE PROTECTION SYSTEM
77525
1SEE
SECTOR "B"
1SEE
SECTOR "D"
M10
1SEE
SECTOR "C"
1SEE
SECTOR "A"
NOT TO SCALE
NEW HVAC & HVAC PIPING COMPOSITE PLAN
CHS
HWR
HWS
CHR
CHS
HWR
HWS
CHR
CHS
HWR
HWS
CHR
T
CWS
CWR
H W
S H
W S
HWS
H W
S
C H
S H
W S
C H
R
CHS
HWS
CHR
C H
S H
W S
C H
R
CHS
HWS
CHR
CHS
HWS
CHR
C W
S
C W
R
H W
R
H W
R
HWRHWR
HWR
H W
R H
W R
H W
R
HWR
60°C
43.3°C
COMPOSITE PLAN
NEW HVAC & HVAC PIPING
T
T T T
T
T
M5
M7
M8
M9
M-6 1:50
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
CP CASEY
BUILDING S-533
REPAIR FIRE PROTECTION SYSTEM
77525
SCALE = 1:50
CHS
HWR
HWS
CHR
CHS
HWR
HWS
CHR
CHS
HWR
HWS
CHR
GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
BELLOWS TYPE (TYP OF 4)
NEW EXPANSION JOINTNEW PIPE GUIDE (TYP.)
(TYPICAL)
NEW PIPE ANCHOR
AHU
W/ CONC. PAD
AIR HANDLING UNIT
AHU
W/ CONC. PAD
AIR HANDLING UNIT
AHU
W/ CONC. PAD
AIR HANDLING UNIT
AHU
W/ CONC. PAD
AIR HANDLING UNIT
AHU
W/ CONC. PAD
AIR HANDLING UNIT
AHU
x x x x x x x x x x x x x x x x x x
S.A S.A S.A S.A S.A S.A S.A S.AS.AS.AR.AR.AR.AR.AR.AR.A E.A E.A
UH
UNIT HEATER
UH
UNIT HEATER
AHU
W/ CONC. PAD
AIR HANDLING UNIT
UH
UNIT HEATER
UH
UNIT HEATER
IF
IN-LINE FAN
CENTRIFUGAL
IF
IN-LINE FAN
CENTRIFUGAL
AHU
AHU
AHU
M I
N
O
C F
M
M A
X
M
L O
U V
E R
W
B I
R D
S C
R E
E N x
L I
A
M
M
M A
M
L O
U V
R D
S C
R E
E N x
L I
M
M A
M
L O
U V
R D
S C
R E
E N x
L I
M
M A
M
L O
U V
R D
S C
R E
E N x
L I
M
M A
M
L O
U V
R D
S C
R E
E N x
L I
IF
IF
IN-LINE FAN
CENTRIFUGAL
AHU
W/ CONC. PAD
AIR HANDLING UNIT
AHU
W/ CONC. PAD
AIR HANDLING UNIT
65,65,100,10050,50,80,8050,50,80,8040,40,65,6532,32,50,50
(TYP OF 2)
DAMPER
BACK-DRAFT
AUTOMATIC
HVAC & HVAC PIPING ENLARGED PLAN (ATTIC SPACE)
PIPE RISER FROM/TO FIRST FLOOR
100mm CWS/CWR, 65mm HWS/HWR
350x750
450x800 R.A
S.A
350x650
300x500
OUTLET CONTINUATION
CONDENSATE DRAIN
SCALE = 1:50
SECTION FOR AHU-1
1,000x2,600
M6
M6
& SECTION FOR AHU-1 (ATTIC SPACE)
HVAC & HVAC PIPING ENLARGED PLAN
DUCT LINING (TYP.)
M-7 1:50
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
SCALE = 1:50
GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
KEY PLAN
A B
C D
CP CASEY
BUILDING S-533
REPAIR FIRE PROTECTION SYSTEM
77525
B
ASECTOR "A"
SECTOR "B"
C
A SECTOR "A"
SECTOR "C"
NEW H.V.A.C ENLARGED PARTIAL PLAN (SECTOR "A")
150/LFx5=750CFM138/LFx5=690CFM
(SECTOR "A")
NEW H.V.A.C ENLARGED PARTIAL PLAN
200 200
150x100150x100
450x250
500x250
600x250 x x x
650x100
350x250
300 450 500
550x350
650x350 x x x x
550x300 x
750x400
500x200
650x300 x x x x
550x250
550x300 x
800x450
300x200 400x200 400x250
200x150
250x200
200x150
200x150 200x100
200x100
200x150
250x150 250x150
300x200300x200 x
200x150
300 375375 425 450
150x100 x x x x
200x100
200x100
400x250 400x200 350x150 250x150 x
350250 400 450
450 400
450300 x x
350x250
500x350
500x300 x
550x400 x
T
36CFM/LFx5'LGx1EA, 180CFM
40CFM/LFx5'LGx4EA, 800CFM
LINEAR DUCT, 200 CONN.,
40CFM/LFx4'LGx2EA, 320CFM
37.5CFM/LFx4'LGx2EA, 300CFM
LINEAR DUCT, 200 CONN.,
55CFM/LFx4'LGx3EA, 660CFM
52.5CFM/LFx4'LGx1EA, 210CFM
LINEAR DUCT, 200 CONN.,
40CFM/LFx5'LGx1EA, 200CFM
LINEAR DUCT, 200 CONN.,
72CFM/LFx5'LGx2EA, 720CFM
LINEAR DUCT, 250 CONN.,
68CFM/LFx5'LGx2EA, 680CFM
LINEAR DUCT, 250 CONN.,
50CFM/LFx5'LGx1EA, 250CFM
48CFM/LFx5'LGx1EA, 240CFM
LINEAR DUCT, 250 CONN.,
138CFM/LFx5'LGx1EA, 690CFM
150CFM/LFx5'LGx3EA, 2,250CFM
LINEAR DUCT, 300 CONN.,
T.D
138CFM/LFx5'LGx1EA, 690CFM
150CFM/LFx5'LGx1EA, 750CFM
LINEAR DUCT, 300 CONN.,
99CFM/LFx5'LGx1EA, 495CFM
98CFM/LFx5'LGx1EA, 490CFM
LINEAR DUCT, 250 CONN.,
50CFM/LFx3'LGx2EA, 300CFM
LINEAR DUCT, 200 CONN.,
50CFM/LFx5'LGx3EA, 750CFM
LINEAR DUCT, 200 CONN.,
117CFM/LFx3'LGx1EA, 350CFM
90CFM/LFx5'LGx3EA, 1,350CFM
LINEAR DUCT, 250 CONN.,
90CFM/LFx4'LGx1EA, 360CFM
LINEAR DUCT, 250 CONN.,
42CFM/LFx5'LGx1EA, 210CFM
50CFM/LFx5'LGx4EA, 1,000CFM
LINEAR DUCT, 200 CONN.,
125CFM/LFx4'LGx2EA, 500CFM
LINEAR DUCT, 250 CONN.,
130 CFM
225x225 CD
375 CFM
250x300 EG
375 CFM
250x300 EG
(TYP OF 2)
2-WAY THROW
50 CFM
100x200 CD
130 CFM
225x225 CD
130 CFM
225x225 CD
130 CFM
225x225 CD
130 CFM
225x225 CD
105 CFM
150x150 CD
130 CFM
225x225 CD
173 CFM
225x225 EG
173 CFM
225x225 EG
174 CFM
225x225 EG
210 CFM
225x225 EG
120 CFM
225x225 EG
50 CFM
150x100 EG
100 CFM
150x150 EG
100 CFM
150x150 CD
220 CFM
225x225 EG
300 CFM
225x225 EG
T
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD VD
VD VD
VD
VD
VD
VD
VD
VD
VD
VD
IF
IN-LINE FAN
CENTRIFUGAL
WALL CAP
VAV
& DAMPER UNIT
VARIABLE AIR VOLUME
VAV
& DAMPER UNIT
VARIABLE AIR VOLUME
IF
IN-LINE FAN
CENTRIFUGAL
M7
(TYPICAL)
DUCT LINING
M-8 1:50
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
KEY PLAN
A B
C D
CP CASEY
BUILDING S-533
REPAIR FIRE PROTECTION SYSTEM
77525
CA
S E
C T
O R
"A
S E
C T
O R
"C
B
A SECTOR "A"
SECTOR "B"
SCALE = 1:50
NEW H.V.A.C ENLARGED PARTIAL PLAN (SECTOR "B")
(SECTOR "B")
NEW H.V.A.C ENLARGED PARTIAL PLAN
x x
250x150 250x150 x
400x150
350x150
400x200500x250
600x300 x x
350x150350x150
450x200
600x250 450x200650x250650x300 x x
350x200
400x250 x x x
300x200300x200
400x200 250x150
450x250
250200
500x300
600x300
400x200 x
400x200 x
250x150
400x250 x x
700x250 600x250 500x250
750x400
600x300
700x300 x x x
150x100150x100 x x
350 375
200x150250x200
200x150
500x300 450x250 300x200
250x200
250x150250x200
250x200
300x150300x150
350x200 350x200
250x150 x
200x150 x x
200x100
200x100 300x150 x x
200x150250x200
350x200
350x200
300450475550500 x x x x x x
350x250
250 (TYP)
400x250400x200350x150250x150
200 (TYP)
x x x
300 300
250250
800x450 x
600x250
0x
0x
0x
450550600 x
550x250550x300650x350
450 300 x
900x350 x
350x250 500x250
T
140 CFM
225x225 CD
145 CFM
225x225 CD
145 CFM
225x225 CD
145 CFM
225x225 CD
90 CFM
150x150 EG
155 CFM
225x225 EG
150 CFM
225x225 EG
155 CFM
225x225 EG
145 CFM
225x225 CD
260 CFM
225x225 CD
260 CFM
225x225 CD
260 CFM
225x225 CD
260 CFM
225x225 CD
250 CFM
225x225 EG
270 CFM
225x225 CD
250 CFM
225x225 EG
250 CFM
225x225 EG
250 CFM
225x225 EG
250x200
250x200
190 CFM
225x225 EG380 CFM
300x300 EG
50 CFM
100x200 CD
50 CFM
100x200 CD
250 CFM
225x225 CD
250 CFM
225x225 CD
250 CFM
225x225 CD
250 CFM
225x225 CD
250 CFM
225x225 CD
270 CFM
225x225 EG
270 CFM
225x225 EG
270 CFM
225x225 EG
250 CFM
225x225 CD
300 CFM
225x225 CD
270 CFM
225x225 EG
270 CFM
225x225 EG
430 CFM
300x300 EG
430 CFM
300x300 EG
250 CFM
225x225 CD
250 CFM
225x225 CD
250 CFM
225x225 CD
250 CFM
225x225 CD
56CFM/LFx3'LGx5EA, 840CFM
LINEAR DUCT, 200 CONN.,
250 CFM
225x225 CD
266 CFM
225x225 CD
267 CFM
225x225 CD
400 CFM
300x300 EG
300 CFM
300x300 EG
130 CFM
225x225 CD
42CFM/LFx5'LGx1EA, 210CFM
50CFM/LFx5'LGx3EA, 750CFM
LINEAR DUCT, 200 CONN.,
90CFM/LFx4'LGx1EA, 360CFM
LINEAR DUCT, 250 CONN.,
125CFM/LFx4'LGx1EA, 500CFM
LINEAR DUCT, 250 CONN.,
50CFM/LFx3'LGx1EA, 150CFM
50CFM/LFx5'LGx3EA, 750CFM
LINEAR DUCT, 200 CONN.,
98CFM/LFx5'LGx1EA, 490CFM
100CFM/LFx5'LGx3EA, 500CFM
LINEAR DUCT, 250 CONN.,
40CFM/LFx5'LGx1EA, 200CFM
LINEAR DUCT, 200 CONN.,
138CFM/LFx5'LGx1EA, 690CFM
150CFM/LFx5'LGx4EA, 750CFM
LINEAR DUCT, 300 CONN.,
VD VD
VD VD
VD VD
VD
VD VD
VD VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD
VD VD
VDVD
VD
VD
VDVD
VD
VD
IF
IN-LINE FAN
CENTRIFUGAL
WALL CAP
VAV
& DAMPER UNIT
VARIABLE AIR VOLUME
VAV
& DAMPER UNIT
VARIABLE AIR VOLUME
VAV
& DAMPER UNIT
VARIABLE AIR VOLUME
IF
IN-LINE FAN
CENTRIFUGAL
IF
IN-LINE FAN
CENTRIFUGAL
M8
DUCT LINING
M-9 1:50
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
KEY PLAN
A B
C D
CP CASEY
BUILDING S-533
REPAIR FIRE PROTECTION SYSTEM
77525
D
CSECTOR "C"
SECTOR "D"
C
A SECTOR "A"
SECTOR "C"
SCALE = 1:50
NEW H.V.A.C ENLARGED PARTIAL PLAN (SECTOR "C")
(SECTOR "C")
NEW H.V.A.C ENLARGED PARTIAL PLAN
200 200 200
600x200 600x250400x200350x200
X x
350x200350x200
150X100
200x150
200x150
200x150 x
300x200 350x250 450x250 500x250 x x
200x100
200x100 x
350x200 x x x x x x x x x
T
S.A S.A S.A S.A S.A R.AR.AR.A E.A
36CFM/LFx5'LGx1EA, 180CFM
40CFM/LFx5'LGx4EA, 800CFM
LINEAR DUCT, 200 CONN.,
72CFM/LFx5'LGx2EA, 720CFM
LINEAR DUCT, 250 CONN.,
48CFM/LFx5'LGx3EA, 720CFM
LINEAR DUCT, 250 CONN.,
200 CFM
150x150 CD
325 CFM
300x300 CD
325 CFM
300x300 CD
400 CFM
300x300 CD
400 CFM
300x300 CD
400 CFM
300x300 CD
200 CFM
150x150 CD
200 CFM
150x150 CD
50 CFM
100x100 CD
200 CFM
200x200 CD
150 CFM
200x150 EG
100 CFM
150x150 CD
90CFM/LFx5'LGx4EA, 1,800CFM
LINEAR DUCT, 250 CONN.,
75CFM/LFx4'LGx1EA, 300CFM
75CFM/LFx5'LGx2EA, 750CFM
LINEAR DUCT, 250 CONN.,
VD
VD VD
VDVD
VD
VD
FCUNOTE :
DOMESTIC WATER PIPING PRIOR TO PIPING INSTALLATION.
3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC &
2. THE CONTRACTOR SHALL CLEAN THE REMAINED DUCT.
LINE.
KITCHEN HOOD REMAIN AND REPLACE THE FAN & CONTROL
1. THE KITCHEN HOOD AND DUCT THAT CONNECTS TO THE
W/ DUCT TO REMAIN
EXISTING HOOD
RF
ROOF VENTILATOR
RF
ROOF VENTILATOR
400x200(E)
600x250
AC
AIR CURTAIN
WF
WALL VENTILATOR
FCU
FAN COIL UNIT
M9
M-10 1:50
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
KEY PLAN
A B
C D
CP CASEY
BUILDING S-533
REPAIR FIRE PROTECTION SYSTEM
77525
C
ASECTOR "A"
SECTOR "C"
D
C SECTOR "C"
SECTOR "D"
SCALE = 1:50M10
NEW H.V.A.C ENLARGED PARTIAL PLAN (SECTOR "D")
(SECTOR "D")
NEW H.V.A.C ENLARGED PARTIAL PLAN
300x200 x x
450x200
250x150250x150
250x150 x
400x200250x150 600x250 500x250700x250 x x x x x x x x x x x
200X150
800x250
800x250
800x250
800x250
700x250600x250600x250
750x250600x250
500x250
350x200
300x150 x
200x150
150x100150x100
150x100
150x100
T
T T
S.AS.AS.AR.AR.AS.AE.AS.A
250 CFM
225x225 CD
250 CFM
225x225 CD
250 CFM
225x225 CD
250 CFM
225x225 CD
250 CFM
225x225 CD
267 CFM
225x225 CD
300 CFM
225x225 EG
400 CFM
300x300 EG
400 CFM
300x300 EG
(TYP OF 2)
50 CFM
150x100 EG
(TYP OF 2)
100 CFM
150x150 EG
50 CFM
100x100 EG
400 CFM
300x300 CD
325 CFM
300x300 CD
325 CFM
300x300 CD
200 CFM
150x150 CD
100CFM/LFx5'LGx4EA, 2,000CFM
LINEAR DUCT, 250 CONN.,
75CFM/LFx4'LGx2EA, 600CFM
75CFM/LFx5'LGx1EA, 375CFM
LINEAR DUCT, 250 CONN.,
150 CFM
150x150 CD
VD
VD VD
VD VD
VD
VD
VD VD
VD
NOTE :
DOMESTIC WATER PIPING PRIOR TO PIPING INSTALLATION.
3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC &
2. THE CONTRACTOR SHALL CLEAN THE REMAINED DUCT.
LINE.
KITCHEN HOOD REMAIN AND REPLACE THE FAN & CONTROL
1. THE KITCHEN HOOD AND DUCT THAT CONNECTS TO THE
W/ DUCT TO REMAIN
EXISTING HOOD
RF
ROOF VENTILATOR
350x150(E)
IF
IN-LINE FAN
CENTRIFUGAL
OAU
SPLIT COMPACT DOAS
OAU
SPLIT COMPACT DOAS
RF
ROOF VENTILATOR
RF
ROOF VENTILATOR
RF
ROOF VENTILATOR
NOTE :
AND ALL NECESSARY ACCESSORIES TO INSTALL THE CONTROLS SYSTEM.
5. THE CONTROLS CONTRACTOR SHALL PROVIDE ALL THE SWITCHES, RELAYS, WIRING, CONDUITS, MECHANICAL JOINTS. THE VRF SYSTEM SHALL BE PRESSURE TESTED & VACUUM TESTED.
FITTINGS, EXTRUDED FITTINGS, PRESS-CONNECT FITTINGS, FLARE FITTINGS, GROOVE JOINTS &
AND JOINTS THAT ARE PROHIBITED INCLUDE BUT ARE NOT LIMITED TO THE FOLLOWING: PUSH-ON
REQUIREMENTS AND THE MANUFACTURER'S INSTALLATION REQUIREMENTS. THE LIST OF FITTINGS
4. VRF SYSTEMS PIPING/TUBING SHALL HAVE ALL BRAZED CONNECTIONS THAT MEET ASME B31.5
A CERTIFIED INSTALLER.
3. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S SPEC BY
2. REFRIGERANT PIPE SIZE & INSTALLATION SHALL BE AS PER MANUFACTURER'S RECOMMENDATION.
1. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PIPEWORK PRIOR TO PIPEWORK INSTALLATION.
VALVE (TYP.)
ISOLATION
NOTE :
KIM, SM
M-11
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
CP CASEY
BUILDING S-533
REPAIR FIRE PROTECTION SYSTEM
77525
CWS
CWR
H W
S H
W S
HWS
H W
S
C H
S H
W S
C H
R
CHS
HWS
CHR
C H
S H
W S
C H
R
CHS
HWS
CHR
CHS
HWS
CHR
H W
R
H W
R
HWRHWR
HWR
H W
R H
W R
H W
R
HWR
60°C
43.3°C
M11 SCALE = 1:100
GRAPHIC SCALE
SCALE: 1:100
0 2000 4000
EXISTING/NEW H.V.A.C PIPING PLAN
EXISTING/NEW H.V.A.C PIPING PLAN
1:100
AC
OUTDOOR UNIT
SPLIT A/C
FC
(TYP OF 2)
FINNED TUBE CONVECTOR
FC
AC
INDOOR UNIT
SPLIT A/C
ISOLATION VALVES AND WATER HAMMER ARRESTORS.
1. PROVIDE CEILING/WALL ACCESS PANEL FOR
HPO
OUTDOOR UNIT
VRF HEAT PUMP
NEW CONC. PAD
C W
S
C W
R
W/ PIPEWORK TO REMAIN
EXIST. WATER CHILLER P.O.C
FCU
FAN COIL UNIT
FC
(TYP OF 2)
FINNED TUBE CONVECTOR
FC
FC
(TYP OF 2)
FINNED TUBE CONVECTOR
FC
OAU
(TYP OF 2)
SPLIT COMPACT DOAS
OAU
(TYPICAL)
METAL PIPE TRAY
65,65,100,100
PIPE RISER FROM/TO ATTIC SPACE
100mm CWS/CWR, 65mm HWS/HWR
M14
PARTIAL PLAN SEE DWG
MECH. ROOM ENLARGED
SCALE = 1:100M12
NOTE ON INSTALLATION OF PIPE INSULATION :
COMPLETED.
INSTALLATION OF THE PIPE INSULATION IS
ENGINEER FOR QUALITY INSPECTION WHEN THE
4. THE CONTRACTOR SHALL INVITE THE MECHANICAL
ACCORDANCE WITH ASTM E84.
DEVELOPED INDEX OF 50 WHEN TESTED IN
SPREAD INDEX OF 25 AND A MAXIMUM SMOKE
FIRERESISTANT AND SHALL HAVE A MAXIMUM FLAME
3. LAGGING ADHESIVES SHALL BE NONFLAMMABLE AND
AND LISTED IN FM APP GUIDE.
2. INSULATION MATERIALS RECOGNIZED UNDER UL94
ASTM C534/C534M, GRADE 1, TYPE I OR II.
OF OMA SPEC 23 07 00, AND SHALL COMPLY WITH
1. INSULATION MATERIALS SHALL CONFORM TO TABLE1
KIM, SM
M-12
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
CP CASEY
BUILDING S-533
REPAIR FIRE PROTECTION SYSTEM
77525
C
C
C
C
60°C
43.3°C
C
C
43.3°C
60°C
43.3°C
GRAPHIC SCALE
SCALE: 1:100
0 2000 4000
EXISTING/NEW DOMESTIC WATER PIPING PLAN
DOMESTIC WATER PIPING PLAN
EXISTING/NEW
1:100
NOTE :
ISOLATION VALVES AND WATER HAMMER ARRESTORS.
4. PROVIDE CEILING/WALL ACCESS PANEL FOR
PIPING INSTALLATION.
SEWER AND VENT PIPING) PRIOR TO PLUMBING
PLUMBING PIPING (HOT & COLD WATER PIPING,
3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR
RISERS AND MECHANICAL ROOM)
THE CRAWL SPACE. (EXCEPT FOR THE MAIN PIPE
2. THE SOW IS LIMITED TO THE CEILING SPACE AND
1. ALL PIPE LINES SHALL BE COPPER TUBE.
ARRESTER (TYP)
WATER HAMMER A
24 23
13 11
PIPE RISER FROM/TO FIRST FLOOR
15mm DHWR, 25mm HW & 32mm CW
VALVE (TYP.)
ISOLATION
(TYPICAL)
BALANCING VALVE
CRAWL SPACECONTROL CABINET
BALANCING VALVE
A
A
32,15,50
32,15,50
32,20,25,50
32,20,25,50
32,20,25,50
ARRESTER (TYP)
WATER HAMMER A
M14
PARTIAL PLAN SEE DWG
MECH. ROOM ENLARGED
WALL HYDRANT
20mm NON-FREEZE
A
ARRESTER (TYP)
WATER HAMMER
PRIMER
TRAP
KIM, SM
M-13
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
CP CASEY
BUILDING S-533
REPAIR FIRE PROTECTION SYSTEM
77525
M13
EXISTING/NEW DOMESTIC WATER PIPING PLAN (CRAWL SPACE)
(CRAWL SPACE)
DOMESTIC WATER PIPING PLAN
EXISTING/NEW
1:100
60°C
PE60°C
P E
C
SCALE = 1:50
EXIST. KITCHEN EQUIP. PIPE CONNECTION SCHEDULE
DESCRIPTION CW HW DITEM NO
15 MM
15 MM 15 MM 32 MM
15 MM 15 MM 32 MM
15 MM 15 MM 32 MM
15 MM
15 MM 15 MM 32 MM
15 MM 15 MM
15 MM 15 MM 40 MM
15 MM
15 MM
15 MM 15 MM 50 MM
15 MM 50 MM
15 MM 15 MM 50 MM
1-HP SINK MOUNTED DISPOSER
BANQUET WATER GLASS FILLER
2-COMPT, CONVECTION STEAMER -
VEGETABLE SINK & DRAIN BOARD
ICE MACHINE - -
SINK
SINK UNIT W/ DIPPER WELL
SINK UNIT W/ DIPPER WELL
SINK
AUTIMATIC TWIN 3 COFFEE URN --
SALAD & DESSERT COUNTER
UNKNOWN
UNKNOWN
DESCRIPTION CW HW DITEM NO
15 MM 15 MM 32 MM
15 MM 15 MM 40 MM
15 MM
15 MM
15 MM
15 MM
20 MM 20 MM 50 MM
50 MM
15 MM 15 MM
15 MM 15 MM 50 MM
50 MM
SINK 15 MM 15 MM 32 MM
UTENSIL SINK & DRAIN BOARD
WALL MOUNTED BUGGYWHIP RINSE
DISHWASHER W/ SCRAPER - 20 MM
3-HP COMMERCIAL DISPOSER - -
ICE BIN W/ 2-COMPARTMENT
ICE MACHINE -
LAVATORY 15 MM 15 MM 50 MM
SINK
WALL MOUNTED POT FILLER - -
- -WALL MOUNTED POT FILLER
WORK TABLE W/ SINK
SINK
60°C
(IN KITCHEN AREA)
CONTROL CABINET
4 5
NOTE :
ISOLATION VALVES AND WATER HAMMER ARRESTORS.
4. PROVIDE CEILING/WALL ACCESS PANEL FOR
PIPING INSTALLATION.
SEWER AND VENT PIPING) PRIOR TO PLUMBING
PLUMBING PIPING (HOT & COLD WATER PIPING,
3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR
RISERS AND MECHANICAL ROOM)
THE CRAWL SPACE. (EXCEPT FOR THE MAIN PIPE
2. THE SOW IS LIMITED TO THE CEILING SPACE AND
1. ALL PIPE LINES SHALL BE COPPER TUBE.
NOTE ON INSTALLATION OF PIPE INSULATION :
COMPLETED.
INSTALLATION OF THE PIPE INSULATION IS
ENGINEER FOR QUALITY INSPECTION WHEN THE
4. THE CONTRACTOR SHALL INVITE THE MECHANICAL
ACCORDANCE WITH ASTM E84.
DEVELOPED INDEX OF 50 WHEN TESTED IN
SPREAD INDEX OF 25 AND A MAXIMUM SMOKE
FIRERESISTANT AND SHALL HAVE A MAXIMUM FLAME
3. LAGGING ADHESIVES SHALL BE NONFLAMMABLE…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .