77525_MECH_DWGS.pdf

PDF 8 MB Posted

Attached to
Repair Fire Protection System, Building S-533, Camp Casey(MATOC only)
Solicitation number
W90VN824R0043
Issued by

About this file

This document is a Request for Proposal (RFP) issued by the Department of the Army Materiel Command for the repair of the fire protection system at Building S-533, Camp Casey in Korea. The RFP is limited to existing Area I & II General Construction Multiple Award Indefinite Delivery Indefinite Quantity (MAIDIQ) Contractors with specific contract numbers listed. The key objectives are to repair the fire protection system, including installing a new automatic wet pipe sprinkler system, repairing the plumbing system, repairing the ventilation system, and repairing the heating and cooling system. Relevant details include the required fire protection system design, occupancy hazard classifications, water supply requirements, and sprinkler head types and quantities. The RFP does not include specific pricing terms or award dates.

View the file

Other files

File Type Posted
77525_CIVIL_DWGS.pdf PDF
Solicitation W90VN824R0043.pdf PDF
77525_ELEC_Drawing.pdf PDF
77525_ARCH_Drawing.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KIM, SM

M-1

NTS

77525 o

ACCU AIR COOLED CONDENSING UNIT

ACLD AIR COOLED

ACU AIR CONDITION UNIT (S)

ACV ALARM CHECK VALVE

ADP APPARATUS DEW POINT

AHU AIR HANDLING UNIT

AIR COND AIR CONDITION (-ING,-ED)

AL ALUMINUM

ALT ALTITUDE

AMB AMBIENT

AMP AMPERE(AMP, AMPS)

APPROX APPROXIMATE

AVG AVERAGE

AWG AMERICAN WIRE GAUGE

BARO BAROMETER(-TRIC)

BARO PR PRESSURE, BAROMETRIC

BHP BRAKE HORSEPOWER

BP BOILING POINT

CAP CAPACITY

CCW COUNTER CLOCKWISE

CHW CHILLED WATER

CKT CIRCUIT

CLASS CLASSIFICATION

CLG LOAD COOLING LOAD

COEF COEFFICIENT

CONN CONNECTION

CONT CONTINUE

C

CMH CUBIC METER PER HOUR

CU M CUBIC METER

CENTIGRADE/ CELCIUS

CFCI

CONTRACTOR INSTALLED

CONTRACTOR FURNISHED

CIP CAST IRON PIPE

CWP

CU MM CUBIC MILLIMETER

Cv COEFFICIENT, VALVE FLOW

CW CLOCKWISE OR COLD WATER

CIRCULATING WATER PUMP

DB DECIBEL OR DRY BULB

COMPRESSORCPRSR

DBT DRY BULB TEMPERATURE

DCWS DOMESTIC COLD WATER SUPPLY

DEG or ° DEGREE

DFW DIESEL OIL

DOMESTIC HOT WATER RETURN

DOMESTIC HOT WATER SUPPLY

DHWR

DHWS

DIRECT EXPANSIONDX

DRY PIPE VALVEDPV

DOUBLE POLE DOUBLE THROWDPDT

DEWPOINT TEMPERATUREDPT

DIVISIONDIV

DIFFERENCEDIFF

DIAGRAMDIAG

DIAMETERDIA or

DWG DRAWING

EXPANSION JOINTEXPJT

ENTERING WATER TEMPEWT

EVAPORAT (-E,-ING,-ED,-OR)EVAP

EXTERNAL STATIC PRESSUREESP

EXPLOSION PROOFEP

EQUIPMENTEQPT

ENTERINGENT

EFFICIENCYEFF

EQUIVALENT DIRECT RADIATIONEDR

ECONOMIZERECON

ECCENTRICECC

ENTERING AIR TEMPERATUREEAT

FUEL OILFO

FA FACE AREA OR FRESH AIR

FHC FIRE HOSE CABINET

FHY FIRE HYDRANT

FLA FULL LOAD AMPERES

F FARENHEIT

FLR FLOOR

FEED WATER PUMPFWP

FACE VELOCITYFVEL

FLUSH VALVEFV

FRP

FREQUENCYFREQ

FEMALE PIPE THREADFPT

FIBERGLASS REINFORCED PLASTIC

Ft or ' FEET

FXTR FIXTURE

GALVANIZED STEELGALVS

GAGE OR GAUGEGA

GR GRAMS

GOVERNMENT INSTALLED

GOVERNMENT FURNISHED GFGI

CONTRACTOR INSTALLED

GOVERNMENT FURNISHEDGFCI

GAL GALLONS

GALLONS PER MINUTEGPM

HERTZHZ

HORIZONTALHORIZ

HOT WATER HEATERHWH

HOT WATERHW

HOUR(S)HR

HORSEPOWERHP

MERCURYHG

HEADHD

HB HOSE BIBB

DIAMETER, INSIDEID

ISOMETRICISO

IRON PIPE SIZEIPS

J JOULE

K THERMAL CONDUCTIVITY

K THERMAL CONDUCTIVITY

kG kCAL/HR

KILOGRAM

kG/SQ CM KILOGRAM PER SQ. CENTIMETER kG/SQ CM A

KILOCALORIE PER HOUR

(ABSOLUTE)

KILOGRAM PER SQ. CENTIMETER

kG/SQ CM G

(GAUGE)

KILOGRAM PER SQ. CENTIMETER

kG/SM KILOGRAM PER SQ. METER kG/SM A kG/SM G

(ABSOLUTE)

KILOGRAM PER SQ. METER

KILOGRAM PER SQ. METER (GAGE)

kW KILOWATT kWH KILOWATT HOUR kJ KILOJOULE kPa KILO PASCAL

LAT LEAVING AIR TEMPERATURE

LBS POUNDS

LG LENGTH

LH LATENT HEAT

LWT LEAVING WATER TEMPERATURE

LIQUID LINELL

L LITERS

LPD LITERS PER DAY

LPH LITERS PER HOUR

LPS

LM LINEAR METER

LITERS PER SECOND

LAV LAVATORY

LPM LITERS PER MINUTE

LT LAUNDRY TRAY

NUMBERNO

NORMALLY OPENN.O.

NOT IN CONTRACTNIC

NORMALLY CLOSEDN.C.

NOISE CRITERIANC

NCK

MAX

NOT TO SCALENTS

MIN

MPH

M METERS

MAXIMUM

MINIMUM OR MINUTE

METERS PER HOUR

MPS METERS PER SECOND

MM MILLIMETER

NPT NATIONAL TAPER PIPE (THREAD)

NOT APPLICABLEN/A

NECK

MECH MECHANICAL

OS&Y OUTSIDE SCREW & YOKE

OD

OAIL OUTSIDE AIR INTAKE LOUVER

OA OUTSIDE AIR

OUTSIDE DIAMETER

OPNG OPENING

OXY OXYGEN

PERCENT

PRESSURE REDUCING VALVEPRV

PARTS PER MILLIONPPM

POINT OF CONNECTIONPOC

PLUMBINGPLMB

PHASE (ELECTRIC)PH

PRESSURE GAGEPG

PD

POLEP

PRESSURE DROP OR DIFFERENCE

Pa PASCAL

POL PETROLEUM, OIL AND LUBRICANTS

QUANTITYQTY

QUARTQT

REFRIGERATION TONRT

REVOLUTIONS PER MINUTERPM

RADIATORRDTR

RETURN AIRRA

THERMAL RESISTANCER

REFRIGERANT (134A, 22, ETC)R134A,R22

RH RELATIVE HUMIDITY

SUPPLY AIRSA

SYMBOLSYM

SUCTIONSUCT

STORAGESTOR

STEELSTL

STANDARDSTD

STEAMST

SAYBOLT SECONDS UNIVERSALSSU

STAINLESS STEELSST

SAYBOLT SECONDS FUROLSSF

SQUARESQ

SPECIFICATIONSPEC

SINGLE POLE DOUBLE THROWSPDT

SM

LPH, STANDARD CONDITIONSSLPH

LPS, STANDARD CONDITIONSSLPS

SG

SLPD LPD, STANDARD CONDITIONS

SL SENSIBLE LOAD

SH SENSIBLE HEAT

SPECIFIC GRAVITY

SF SAFETY FACTOR

SEC SECOND

SCH SCHEDULE

STATIC PRESSURE

SQUARE METER

SP

SBM

SAN SANITARY

SUBMERSIBLE

TYPICALTYP

THERMOSTATTSTAT

TONS OF REFRIGERATIONTONS

THICKNESSTHK

THERMOMETERTHERM

TEMPERATURETEMP

TEMPERATURE DIFFERENCETD

UNIT HEATERUH

HEAT TRANSFER COEFFICIENTU

WTRPRF

WT

WSHR

WITHW/

WH

WIDTHWD

WCLD

WC

WBT

WB

WATTW

VP

VOL

VISC

VERTICALVERT

VENTILATIONVENT

VELOCITYVEL

VARIABLE AIR VOLUMEVAV

VAC VACUUM

VLV VALVE

V VOLT

WATERPROOF

WEIGHT

WASHER

WATTHOUR OR WATER HEATER

WATER-COOLED

WATER CLOSET

WET BULB TEMPERATURE

WET BULB

PRESSURE, DYNAMIC(VELOCITY)

VOLUME

VISCOSITY

VTR VENT THRU ROOF

UR URINAL

A B B R E V I A T I O N S

MECHANICAL MATERIAL INDICATIONS AND SYMBOLS

FS

VFM

OFM

AVA

PRESSURE RELIEF

TEMPERATURE

EXPANSION LOOP

EXPANSION JOINT

ANCHOR, INTERMEDIATE

ALIGNMENT GUIDE

AIR VENT, AUTOMATIC

SQUARE HEAD BALANCING COCK

QUICK OPENING

NEEDLE

LOCK SHIELD

FLEXIBLE CONNECTOR

FLOWMETER, ORIFICE

FLOWMETER, VENTURI

FLOW SWITCH

PRESSURE GAUGE AND COCK

STRAINER

THERMOMETER

PRESSURE REDUCING

RELIEF OR SAFETY

SLEEVE

BLOW OFF STRAINER

INLINE PUMP

SAFETY

FLOAT

valves, special duty

S

M

GATE, NORMALLY CLOSED

GLOBE

SOLENOID

3 WAY MANUAL

GATE, NORMALLY OPEN

PLUG

MOTOR OPERATED GATE

MOTOR OPERATED GLOBE

3 WAY ELECMOTOR CONTROL

3 WAY AIR MOTOR CONTROLLER

HOSE GATE

HOSE GLOBE

POST INDICATOR

OS Y

ANGLE GLOBE

ANGLE GATE

SWING GATE CHECK

S

M

P

M

M

ALARM CHECK

DRY PIPE

DELUGE

PREACTION

TAMPER DETECTION SWITCH

QUICK OPENING DEVICE

NON-RISING STEM

DIAPHRAGM

SOLENOID

MOTOR ELECTRIC

valve actuators fittings

TEE, SINGLE SWEEP

UNION, SCREWED

UNION, FLANGED

CONNECTION, TOP

ELBOW, 90°

ELBOW, TURNED UP

ELBOW, TURNED DOWN

TEE, OUTLET UP

TEE, OUTLET DOWN

CONNECTION, BOTTOM

REDUCER, CONCENTRIC

(STRAIGHT, INVERT)

REDUCER, ECCENTRIC

(STRAIGHT, DOWN)

REDUCER, ECCENTRIC

TEE

ELBOW, 45°

LATERAL

SOLVENT CEMENT

BELL AND SPIGOT

SCREWED

FLANGED

WELDED

SOLDERED/BRAZED

M

NS

BUTTERFLY

BALL

DIAPHRAGM

GATE

INDICATING BUTTERFLY

KEY OPERATED

CHECK

SIDEWALL SPRINKLER

UPRIGHT SPRINKLER

DELUGE VALVE

WALL MOUNTED TEST HEADER

FIRE ALARM BELL

HOSE STATION DRY STANDPIPE

MINI HORN

HORN SPEAKER

WALL HYDRANT 2 HOSE OUTLET

SMOKE DETECTOR

PENDENT SPRINKLER DROP NIPPLE

NIPPLED UP UPRIGHT SPRINKLER

OUTSIDE SPRINKLER

CUTTING POINT

CAP

NON-SPRINKLERED SPACE

RISER

(SEE SPRINKLER SCHEDULE)

PENDENT SPRINKLER

CONNECTION (2-WAY SHOWN)

SIAMESE FIRE DEPARTMENT

CONNECTION

SINGLE FIRE DEPARTMENT

valves

POTABLE COLD WATER

POTABLE HOT WATER

POTABLE HOT WATER RETURN

PIPE SLEEVE

BACKFLOW PREVENTER

PITCH OR PIPE, UP(U), DOWN(D)

VENT THRU ROOF

SURFACE CLEANOUT

FLOOR CLEANOUT

FLOOR DRAIN

PIPE SLEEVE WITH FIRE STOPPING

HOSE BIBB

FLOOR SINK (200mm x 200mm)

HOT WATER (60°C)

HOT WATER (82.22°C)

VENT

SANITARY SEWER

COMPRESSED AIR

FUEL OIL SUPPLY

FUEL OIL RETURN

FLOOR DRAIN WITH CLEANOUT

FLOOR DRAIN WITH DEEP TRAP

FLOOR DRAIN WITH NO TRAP

FLOOR DRAIN WITH TRAP TIME

FD

FCO

SCO

200x200

FIRE PROTECTION WATER SUPPLY

MAIN SUPPLY SPRINKLER

WET STANDPIPE

DRY STANDPIPE

COMBINATION STANDPIPE

plumbing sprinkler

DSP

WSP

CSP

S

F

PLAN ELEV

82.22°C

60°C

S

A

FOS

FOR

RD

RS

RL

D

CWS

CWR

LPC

BBD

PC

VPD

MU

FOD

FOV

FOG

FOS

FOR

HWS

M

HCS

HCR

FILL

MU

HWR

LOW PRESSURE CONDENSATE

BOILER BLOW DOWN

PUMPED CONDENSATE

VACUUM PUMP DISCHARGE

MAKE UP WATER

FUEL OIL DRAIN

FUEL OIL TANK VENT

FUEL OIL GAUGE

FUEL OIL SUPPLY

FUEL OIL RETURN

CONTROL AIR MAIN

DUAL TEMPERATURE RETURN

FILL LINE

MAKE UP WATER

DUAL TEMPERATURE SUPPLY

WATER SUPPLY

LOW TEMPERATURE HOT

WATER RETURN

LOW TEMPERATURE HOT

SPLITTER DAMPER

REFRIGERANT DISCHARGE

REFRIGERANT SUCTION

REFRIGERANT LIQUID

DRAIN

CHILLED WATER SUPPLY

CHILLED WATER RETURN

dampers piping heating air conditioning and refrigeration

DU 13mm

47.2

94.4

DG

300x150

500/300L

R

AD

FC

SG

SR

RG

RR

810mm x 400mm

810mm x 400mm

810mm x 400mm

EG

ER

810mm x 400mm

DIRECTION OF FLOW

FLEXIBLE CONNECTION

TRANSITION

(810mm WIDTH x 400mm DEPTH)

DUCT SIZES SHOWN

RISE(R), DOWN(D)

CHANGE OF ELEVATION

VERTICAL OR HORIZONTAL

ACCESS DOOR,

FIRST FIGURE IS ON TOP

POSITIVE PRESS.,

OUTSIDE AIR DUCT SECTION,

FIRST FIGURE IS ON TOP

POSITIVE PRESS.,

SUPPLY AIR DUCT SECTION,

FIRST FIGURE IS ON TOP

SECTION, NEGATIVE PRESS.,

RETURN OR EXHAUST AIR DUCT

SUPPLY OR RETURN

FLEXIBLE AIR DUCT,

TRANSITION

SQUARE TO ROUND

REGISTER, CEILING

EXHAUST AIR GRILLE OR

REGISTER, SIDEWALL

SUPPLY AIR GRILLE OR

REGISTER, CEILING

RETURN AIR GRILLE OR

OR REGISTER, CEILING

SUPPLY AIR MODULAR DIFFUSER

DOOR GRILLE (300mmx150mmH)

(500mmWx300mmH, 94.4 LPS)

LOUVER, DOOR OR WALL

(13mm, 47.2 LPS)

DOOR UNDERCUT

duct works grilles, registers and diffusers

LEGEND & ABBREVIATION

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

CP CASEY

BUILDING S-533

REPAIR FIRE PROTECTION SYSTEM

M-2

NTS

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

GENERAL NOTES & SCOPE OF WORK

A. REPAIR/MAINTENANCE (K-WORK)

SCOPE OF WORK

NOTE :

FIRE PROTECTION AND MECHANICAL GENERAL NOTES

25. SALVAGEABLE MATERIALS SHALL BE RETURNED TO DPW.

AND THE LIKE SHALL BE DONE BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE GOVERNMENT.

24. DISPOSAL OF CONSTRUCTION DEBRIS, WASTE MATERIALS, MATERIALS RESULTING FROM DEMOLITION ACTIVITIES, OFF VALVE WITHIN 1M OF THE UNIT.

23. ALL CONDENSATE DRAINS FROM COOLING UNIT (AS NOTED ON THE DRAWINGS) SHALL BE PROVIDED WITH SHUT-

WATER BEING FLUSHED IS CLEAR AS TAP WATER.

22. PIPING SYSTEM SHALL BE FLUSHED, PURGED & CLEANED PER SPECS REQUIREMENTS AND FLUSHED UNTIL ALL

TYPE FITTINGS AT ALL ROUND DUCT TAKE-OFFS FROM SQUARE OR RECTANGULAR MAINS.

ELBOWS. PROVIDE AIR SPLITTER DAMPERS AT ALL BRANCH TAKE-OFFS FROM THE MAIN DUCT. PROVIDE SPIN-IN

21. PROVIDE TURNING VANES IN ALL ELBOWS THAT CHANGE AIR DIRECTION MORE THAN 30 DEGREES OR USE RADIUS

CONDENSATION, FROM SINK BODIES EXPOSED TO AIR BELOW THE FLOOR.

RECEIVING AIR CONDITIONING CONDENSATE DRAINS, OR ANY OTHER COLD LIQUID WHICH MAY CREATE

20. INSTALL CONDENSATE DRAINS AT A MINIMUM SLOPE OF 1/4 INCH PER 1 FOOT. INSULATE ALL SEWER PIPING

BE MAINTAINED ADEQUATELY. PROVIDE REMOTELY ACTUATED DAMPERS IN AREA WITH CONCEALED CEILINGS.

PANELS FOR TWO VALVES. COORDINATE THE LOCATION OF ACCESS PANELS TO INSURE THAT THE EQUIPMENT CAN

BACKDRAFT DAMPERS AND FOR ANY ITEM INDISE DUCTS REQUIRING SERVICING OR INSPECTION 12"x12" ACCESS

DUCTS AT ALL AUTOMATIC CONTROL DAMPERS, FIRE DAMPERS, FIRE/SMOKE DAMPERS, DUCT SMOKE DETECTOR,

19. PROVIDE ACCESS PANELS TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT. PROVIDE ACCESS DOORS IN

PRESSURE CALSS 500PA AND DUCTWORK SHALL MEET THE REQUIREMENTS OF SEAL CLASS C.

18. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING TO SMACNA STATIC

REPORT SHALL BE SUBMITTED TO THE COR FOR REVIEW AND APPROVAL.

SPECIFICATIONS FOR MISCELLANEOUS PROJECTS, KOREA. THE HVAC TESTING, ADJUSTING AND BALANCING (TAB)

ACCORDANCE WITH APPLICABLE SECTIONS OF DIVISION 22 & 23 - MECHANICAL. O & MA STANDARD TECHNICAL

17. ALL MECHANICAL SYSTEMS SHALL BE TESTED, ADJUSTED AND BALANCED BY THE CONTRACTOR IN STRICT

SUBMITTED TO THE CONTRACTING OFFICER FOR APPROAL.

SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND

16. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT FIELD CONDITIONS. SUCH DETAILS

THE DETAILS SHALL BE UTILIZED WHILE PERFORMING THE MECHANICAL SCOPE OF WORK.

15. FOR O & MA PROJECTS, KOREA, OCTOBER 1, 2003 DEPARTMENT OF THE ARMY FORM AS A PART OF THIS PROJECT.

CONTRACTING OFFICER.

14. THE CONTRACTOR SHALL SUBMIT MANUFACTURERS INSTALLATION SHOP DRAWINGS FOR APPROVAL BY THE

REPAIRED OR REPLACED BY THIS CONTRACTOR AT HIS OWN COST.

DUCT WORK, PIPING ETC. ANY DAMAGED DUE TO THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE

13. CONNECTION TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE ANY EXISTING EQUIPMENT, ROOF, PIPE, DUCT, EQUIPMENT AND ELECTRICAL ITEMS.

NO ADDITIONAL COST TO THE GOVERNMENT, INCLUDING, BUT NOT LIMITED TO ITEMS SUCH AS WALLS, CEILING, NECESSARY TO ALLOW FOR INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE PROTECTION SYSTEM AT

12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND REINSTALLATION OF ALL OBSTRUCTIONS AS

BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS AT HIS OWN COST.

11. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO EXISTING AREAS CAUSED

CLEARANCE, EQUIPMENT PAD SIZE, INSTALLATION LOCATIONS, AND ADDITIONAL ITEMS.

10. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE

COMMENCING ANY CONSTRUCTION OR RENOVATION.

9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITION AND DIMENSIONS PRIOR TO

8. ALL VALVES ON WET PIPE SYSTEM SHALL MEET NFPA 13 REQUIREMENT.

LINE.

7. INSTALL SYSTEM TEST CONNECTION ON WET PIPE SYSTEM AND SHALL BE LOCATED AT THE MOST REMOTE BRANCH

6. SPRINKLERS WITH O-RINGS ARE NOT PERMITTED. PLUG TYPE TAMPER SWITCH SHALL NOT BE USED.

LIMITED TO ALL RISER AND TRIM, SECTIONAL VALVES, INSPECTORS TEST VALVES, AND DRAINS.

5. PROVIDE LABEL TAG INDICATING "NORMALLY OPEN" OR "NORMALLY CLOSED" ON ALL VALVES INCLUDING AND NOT

BRACINGS, FLEXIBLE COUPLINGS, CLEARANCES, AND SEPARATION ASSEMBLIES.

OF PIPING AGAINST DAMAGE WHERE SUBJECT TO EARTHQUAKES". INCLUDING, BUT NOT LIMITED TO, SWAY

4. PROVIDE ALL SEISMIC PROTECTION MEASURES FOR THE FIRE PROTECTION SYSTEM IAW NFPA 13 FOR "PROTECTION

SYSTEM BRANCH LINES AND PIPES LESS THAN 50 MM (2 INCHES) IN NOMINAL.

INDICATING THE TYPE OF FLUID CARRIED AND DIRECTION OF FLOW. LABELS ARE NOT REQUIRED ON SPRINKLER

LABELS CONFORMING TO ASME/ANSI A13. 1-1996, "SCHEME FOR IDENTIFICATION OF PIPING SYSTEMS",

3. MARK ALL EXPOSED INTERIOR PIPING AT 8 METER (26 FT) INTERVALS WITH PLASTIC WRAPAROUND TYPE PIPE

WITH APPROVED FIRE STOPPING MATERIAL IAW SPECIFICATION 07 84 00.

2. THE CLEARANCES AROUND PIPE PENETRATION AT FIRE RATED WALLS AND/OR FLOOR SHALL BE PROPERLY SEALED

PROJECT SPECIFICATION.

EQUIPMENT SHALL BE UL LISTED AND/OR FM APPROVED IN ACCORDANCE WITH NFPA 13, NFPA 20 AND THE

CONTRACTOR SHALL COORDINATE SPRINKLER HEADS LOCATIONS WITH LIGHTING FIXTURES AND HVAC DEVICES. ALL

ACCORDANCE WITH APPLICABLE CODES, MANUFACTURER'S RECOMMENDATIONS, AND EQUIPMENT LISTINGS. THE

1. THE EQUIPMENT SHOWN ON THE PLAN ARE SUGGESTED LOCATIONS. FINAL LAYOUT SHALL BE VERIFIED AND IN

77525

CP CASEY

BUILDING S-533

REPAIR FIRE PROTECTION SYSTEM

TEMPORARY HEATING SYSTEM TO THE ENTIRE BUILDING.

10. IF THE CONTRACTOR IS GOING TO CONSTRUCTION DURING THE HEATING SEASON, THE CONTRACTOR SHALL PROVIDE THE

TRAVEL DISTANCE TO THE NEAREST SHUTOFF SWITCH WILL NOT BE IN EXCESS OF 61 METERS.

ADJACENT TO MANUAL FIRE ALARM PULL BOXES AND WITH AT LEAST ONE SHUTOFF SWITCH PER FLOOR SO THAT THE

AT/FP REQUIREMENTS AND DISABLE THE FAN WHEN ACTIVATED AND CLOSE THE MOTORIZED DAMPER. LOCATION SHALL BE

9. THE BUILDING SHALL HAVE AN EMERGENCY SHUT DOWN SWITCH IN A CLEAR PLASTIC ENCLOSURE WITH LABEL AS PER

OR CERTIFIED INSTALLER.

8. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S SPECIFICATION BY A LICENSED

7. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED PER SPEC.

NECESSARY ACCESSORIES FOR H.V.A.C CONTROLS.

6. THE MECHANICAL/CONTROLS CONTRACTOR SHALL PROVIDE ALL THE WIRINGS, RELAYS, CONTROLLERS, CONDUITS AND ALL

ACTUATED DAMPERS IN AREAS WITH GYPBOARD OR CONCEALED CEILINGS.

5. PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE DRAWINGS OR NOT. PROVIDE REMOTELY

SHALL BE COMPATIBLE WITH THE FIRE WALL OR FLOOR. FIRE DAMPERS SHALL BE UL LISTED.

4. PROVIDE FIRE DAMPERS AT ALL DUCT PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS. FIRE DAMPER RATINGS

DRAWINGS FOR CEILING TYPES.

3. PROVIDE DIFFUSERS AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING TYPES. REFER TO ARCHITECTURAL

OFFICER.

2. THE CONTRACTOR SHALL SUBMIT MECHANICAL SYSTEM INSTALLATION SHOP DRAWINGS FOR APPROVAL BY THE CONTRACTING

INSTALLATION LOCATIONS AND ADDITIONAL ITEMS.

1. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE CLEARANCE, PERFORMED BY THE FPE (FIRE PROTECTION PROFESSIONAL ENGINEER).

6. THE CONTRACTOR SHALL INSPECT AND TEST THE FIRE PROTECTION SYSTEM. THE WORK INSPECTION AND TEST SHALL BE

ON DRAWINGS.

SPARE SPRINKLER HEAD CABINET WITH SPARE SPRINKLER HEAD (6 EA), AND ALL ASSOCIATED ACCESSORIES AS SHOWN

5. REPAIR THE FIRE PROTECTION SYSTEM BY INSTALLING NEW AUTOMATIC WET TYPE FIRE PROTECTION SPRINKLER SYSTEM, HAMMER ARRESTERS, TRAP PRIMER, CONTROL, ACCESS DOORS AND ALL ASSOCIATED ACCESSORIES AS SHOWN ON DRAWINGS.

RE-CIRCULATION PUMP, DOMESTIC HOT WATER CIRCULATION PUMP, BOOSTER PUMP FOR WASHDOWN SYSTEM, VALVES, WATER

PIPES BURIED IN THE WALL), DOMESTIC HOT WATER HEATER, DOMESTIC HOT WATER STORAGE TANK, DOMESTIC HOT WATER

4. REPAIR THE PLUMBING SYSTEM BY INSTALLING NEW DOMESTIC COLD AND HOT WATER PIPING SYSTEM (EXCLUDING BRANCH

VERIFY THAT THE H.V.A.C. SYSTEM WORKS PROPERLY.

3. PERFORM DALT (DUCT AIR LEAKAGE TEST) AND T.A.B (TESTING, ADJUSTING, AND BALANCING) AFTER CONSTRUCTION TO

ASSOCIATED ACCESSORIES FOR VENTILATION SYSTEM AS SHOWN ON DRAWINGS.

CONTROLS, DAMPERS, DIFFUSERS, GRILLES, LOUVERS, DUCTS, INSULATIONS, ACCESS DOORS, EQUIPMENT SUPPORT AND ALL

FANS, IN-LINE EXHAUST FANS, WALL EXHAUST FAN, CONTROLLER, CO2 SENSOR, HVAC EMERGENCY SHUTDOWN SWITCHS,

2. REPAIR THE VENTILATION SYSTEM BY INSTALLING NEW SPLIT TYPE DOAS & VRF HEAT PUMP OUTDOOR UNITS, ROOF EXHAUST

SYSTEM AS SHOWN ON DRAWINGS.

CONTROLS, ACCESS DOORS, EQUIPMENT SUPPORT (CONC. PAD) AND ALL ASSOCIATED ACCESSORIES FOR HEATING AND COOLING

CIRCULATION PUMP, HOT WATER CIRCULATION PUMP, AIR SEPARATORS, PIPES, VALVES, CONTROLLER, INSULATIONS, FINNED TUBE CONVECTOR, AIR CURTAIN, UNIT HEATERS, ELECTRIC UNIT HEATERS, EXPANSION TANKS, CHILLED WATER

UNITS, VARIABLE AIR VOLUME & DAMPER UNITS, SPLIT AIR CONDITIONING INDOOR & OUTDOOR UNIT, FAN COIL UNIT,

1. REPAIR THE HEATING AND COOLING SYSTEM BY INSTALLING NEW HOT WATER BOILER W/ MAGNETIC FILTER, AIR HANDLING

M-3

NTS

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

QTY D E S C R I P T I O NITEM D E S C R I P T I O NQTYITEM QTYITEM D E S C R I P T I O NQTY D E S C R I P T I O NITEM D E S C R I P T I O NQTYITEM QTYITEM D E S C R I P T I O N

E Q U I P M E N T S C H E D U L E S - 1

EQUIPMENT SCHEDULES - 1

AHU

CENTRAL AIR HANDLING UNIT

VOLT/PH/HZ

MOTOR

HP

5 460/3/605,500 1.5"

ESP

COIL

COOLING

ROW

FACE AREA

6.86 SF

11.5 SF

FLOW RATE

6.6 GPM

38 GPM

COOLING CONDITION

SH (BTUH)

146,554 284,600

TH (BTUH) BULB

DRY

WET

EAT

81.5°F

69.5°F

LAT

55.0°F

53.3°F

HEATING CONDITION

66,400

EAT LAT

69°F 80°F

HEATING

HEATING & COOLING COIL CONDITION

S.A (CFM)

AHU

VOLT/PH/HZ

MOTOR

HP

3 460/3/604,000 2.0"

ESP

COIL

COOLING

ROW

FACE AREA

5.83 SF

7.78 SF

FLOW RATE

5.7 GPM

COOLING CONDITION

SH (BTUH)

119,881 216,000

TH (BTUH) BULB

DRY

WET

EAT

81.4°F

69.5°F

LAT

54.0°F

53.8°F

HEATING CONDITION

57,377

EAT LAT

77°F

HEATING

HEATING & COOLING COIL CONDITION

S.A (CFM)

28.8 GPM

61.5°F

CAP (BTUH)

CAP (BTUH)

AHU

CENTRAL AIR HANDLING UNIT

VOLT/PH/HZ

MOTOR

HP

3 460/3/603,500

ESP

COIL

COOLING

ROW

FACE AREA

7.78 SF

FLOW RATE

1.7 GPM

COOLING CONDITION

SH (BTUH)

157,000

TH (BTUH) BULB

DRY

WET

EAT

79.7°F

68.0°F

LAT

55.0°F

53.6°F

HEATING CONDITION

17,000

EAT LAT

65°F

HEATING

HEATING & COOLING COIL CONDITION

S.A (CFM)

AHU

VOLT/PH/HZ

MOTOR

HP

3 460/3/603,500 2.0"

ESP

COIL

COOLING

ROW

FACE AREA FLOW RATE

1.5 GPM

COOLING CONDITION

SH (BTUH)

147,900

TH (BTUH) BULB

DRY

WET

EAT

79.6°F

67.6°F

LAT

55.8°f

54.0°f

HEATING CONDITION

15,371

HEATING

HEATING & COOLING COIL CONDITION

S.A (CFM)

19.7 GPM

CAP (BTUH)

CAP (BTUH)

2.0"

7.0 SF

20.9 GPM

68,862 69.4°F

EAT LAT

65°F 69.0°F

7.0 SF

7.78 SF

70,092

AHU

VOLT/PH/HZ

MOTOR

HP

5 460/3/606,500

ESP

COIL

COOLING

ROW

FACE AREA

11.5 SF

FLOW RATE

5.95 GPM

COOLING CONDITION

SH (BTUH)

263,300

TH (BTUH) BULB

DRY

WET

EAT

80.2°F

67.2°F

LAT

56.0°F

54.2°F

HEATING CONDITION

59,580

EAT LAT

64°F

HEATING

HEATING & COOLING COIL CONDITION

S.A (CFM)

CAP (BTUH)

2.0"

35.1 GPM

72.5°F

CENTRAL STATION VARIABLE AIR VOLUME AIR HANDLING UNIT

13.0 SF

119,881

VAV

VARIABLE AIR VOLUME & DAMPER UNIT

3 YEARS WARRANTY.

ACCESSORIES, AND ALL NECESSARY SAFETIES & OPERATING ACCESSORIES.

ACESS PANEL, EQUIPPED WITH ELECTRIC ACTUATOR STANDARD CONTROL

FACTORY ASSEMBLED, INSULATED PLENUM WITH AIR INLET COLLAR, REMOVABLE

CFM RANGE MIN. P.D. (WG) REMARKS

800 - 2,000 0.28"

VAV

400 - 1,200 0.26"

UH UNIT HEATER

AND ALL NECESSARY ACCESSORIES.

EQUIPPED WITH ADJUSTABLE CONE DIFFUSER, THERMAL OVERLOAD PROTECTION,

SUSPENDED, VERTICAL AIR DISCHARGE, DIRECT-DRIVEN PROPOLLER FAN TYPE,

VOLT/PH/HZ

115/1/60

HP

1/4

GPM

11.6

(BTUH)

HEATING CAP.

E.W.T

196°F

P.D

1.04

RPM

1,070

CFM

3,200116,300

FAN MOTOR SIZE

77525

CP CASEY

BUILDING S-533

REPAIR FIRE PROTECTION SYSTEM

NOTE : NOTE :

THE CONTRACT DOCUMENT REQUIRMENTS.

SHALL BE RESPONSIBLE FOR VERIFYING ACTUAL QUANTITIES BASED ON

QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY, THE CONTRACTOR

FCU

VOLT/PH/HZ

115/1/60

ESP

0.2"

FAN COIL UNIT

SAFETIES & OPERATING ACCESSORIES. 3 YEARS WARRANTY.

FILTER, WITH INSULATED DRAIN PAN W/ DRIP LIP, AND ALL NECESSARY

ALUMINUM FINS WATER COIL AND AIR VENT 1" THK CLEANABLE TYPE AIR

INSULATED CABINET W/ RETURN AIR PLENUM, ELEC BOX COPPER TUBES AND

CEILING HUNG, FORWARD CURVED CENTRIFUGAL FAN, 3-SPEED FAN MOTOR,

W

COOLING HEATING

SENS. TOTAL

4,121 7,490

GPM

0.99 3,746

GPM

0.4

S.A (CFM)

FAN MOTOR

TOTAL

CIRCULATION PUMP

VOLT/PH/HZ

460/3/60

TDH

50'118

HP

P

(GPM)

CAPACITY

REMARKSRPM

MOTOR RATING

1,750 3 CHILLED WATER CIRC. PUMP

460/3/6058' 1,750 389 HOT WATER CIRC. PUMP

CIRCULATING PUMP

OPERATING ACCESSORIES.

QUIET OPERATING RING MOUNTED MOTOR, AND ALL NECESSARY SAFETIES &

PUMP BODY, STAINLESS STEEL IMPELLER, STANDARD MECHANICAL SEAL AND

IN-LINE, CLOSED COUPLED, SINGLE STAGE, STAINLESS STEEL SHAFT, BRONZE

VOLT/PH/HZ

460/3/60

TDH

30'

HP

P

P

(GPM)

CAPACITY

REMARKSRPM

MOTOR RATING

1,750

460/3/6033' 1,7506

P 115/1/601,75010

6'

3/4

1/2

1/12

BOOSTER PUMP

FOR WASHDOWN SYSTEM

DOMESTIC HW. CIRC. PUMP

D.H.W RECIRC. PUMP

P

OPERATING ACCESSORIES. PUMP IS SUITABLE FOR 125 PSI WORKING PRESSURE.

SUCTION AND DISCHARGE CONNECTION, AND ALL NECESSARY SAFETIES &

TEMPERATURE UP TO 250°F, HEAVY CAST IRON CONSTRUCTION CASE & FLANGED

ENCLOSED TYPE BRONZE IMPELLER, MECHANICAL SEAL ARE SUITABLE FOR WATER

STRUCTURAL STEEL BASE, VARIABLE FREQUENCY DRIVE W/VIBRATION ISOLATOR,

END-SUCTION, BASE MOUNTED HORIZONTAL INSTALLATION TYPE, HEAVY

OAU

2,000 1.5"

ESPS.A (CFM)

HPO VARIABLE REFRIGERANT FLOW HEAT PUMP (OUTDOOR UNIT)

SAFETIES & OPERATING ACCESSORIES. ETL LISTED. 3 YEARS WARRANTY.

SENSOR FOR A SAFE AND TROUBLE FREE OPERATION AND ALL NECESSARY

AT LOW AMBIENT CONDITIONS, MULTI CONNECTION PIPING KIT, ALL NECESSARY

ADVANCED PROPORTIONAL INTEGRAL DERIVATIVE (PID) CONTROL TO OPERATES

REFRIGERANT SHUTOFF VALVES, VIBRATION ISOLATORS, SOLENOID VALVES,

OVERLOAD PROTECTION, OVER CURRENT RELAY, R-410A REFRIGERANT CHARGE,

WITH ELECTRONIC EXPANSION VALVES, HIGH PRESSURE SWITCHES, INVERTER

& HEATING REQUIREMENTS, WEATHER-PROOF, INVERTER COMPRESSOR, COMPLETE

CAPABLE OF CHANGING SPEED LINEARY TO FOLLOW THE VARIATION IN COOLING

HEATING EVEN DURING DEFROST OPERATIONS,ELECTRONICALLY CONTROLLED AND

VARIABLE REFRIGERANT FLOW HEAT PUMP OUTDOOR UNIT CAPABLE OF CONTINOUS

VOLT/PH/HZ

460/3/60

(BTUH)

HEATING CAP.

MCA

324,000

ELECTRICAL RATING

MOP(BTUH)

COOLING CAP.

COMPRESSOR

B HOT WATER BOILER

EFFICIENCY

ELEC. POWER

WORKING PRESSURE

SUPPLY WATER TEMP.

GAS INPUT

GROSS OUTPUT

10 YEARS WARRANTY.

SAFETIES & OPERATING ACCESSORIES. CSA CERTIFIED, ASME CERTIFIED.

SENSOR WITH CABLE, MAGNETIC BOILER FILTER, AND ALL NECESSARY

DUAL VENTURI SYSTEM, CONDENSATE NEUTRALIZER, OUTDOOR TEMPERATURE

DUAL STAINLESS STEEL HEAT EXCHANGERS FOR HEATING, MANIFOLD SYSTEM,

GAS FIRED TYPE, CASCADE SYSTEM, CONDENSING TANKLESS COMBI-BOILERS,

MFR. NAVIEN MODEL NO. NFB200H x 4EA OR APPROVED EQUAL.

: 95 %

: 14 FLA, 120 V, 1 PH, 60Hz

: 41.3 - 551.6 kPa

: 80°C

: 18.28 CMH

: 213.2 KW

DC SCROLL

3 / INVERTER

7552.1

REMARK

288,000

3 YEARS WARRANTY.

KIT, AND ALL NECESSARY SAFETIES & OPERATING ACCESSORIES.

COMBINATION MIXING BOX W/ FILTER, VIBRATION ISOLATOR, COMMUNICATIONS

ALUMINUM FIN TYPE CHILLED WATER COOLING & HOT WATER HEATING COILS,

FAN SECTION AND ZONING DAMPER SECTION, STAGGERED COPPER TUBE AND

BLOW-THRU, MULTI-ZONE UNIT COMPONENT MODULES, VERTICAL AIR FLOW TYPE,

SPLIT COMPACT DOAS (DEDICATED OUTDOOR AIR SYSTEM)

FACTORY MOUNTED DISCHARGE AIR TEMPERATURE SENSOR,

SAFETIES & OPERATING ACCESSRIES. 3 YEARS WARRANTY.

SHUTOFF VALVES, VIBRATION ISOLATION, CONTROL PANEL AND ALL NECESSARY

FIN COILS, COMMUNICATIONS KIT, AIR FILTERS, R-410A REFRIGERANT,

PREPAINTED GALVANIZED STEEL DOUBLE SKIN CABINET, ROUND TUBE PLATE

FACTORY ASSEMBLED,

VOLT/PH/HZ

208/1/60

MCA

ELECTRICAL RATING

MOP

157.3

(BTUH)

HEATING CAP.

(BTUH)

COOLING CAP.

143,10059,900

(BTUH)

REHEAT COIL

30,000

PIPE SIZE

VAPOR LIQUID DRAIN

12.7 mm28.58 mm 25 mm

NECESSARY SAFETIES & OPERATING ACCESSORIES. 3 YEARS WARRANTY.

MIXING BOX W/ FILTER, COMMUNICATIONS KIT, VIBRATION ISOLATOR AND ALL

CHILLED WATER COOLING COIL AND HOT WATER HEATING COIL & COMBINATION

TYPE, FAN SECTION, STAGGERED COPPER TUBE AND ALUMINUM FIN TYPE

BLOW-THRU, SINGLE-ZONE UNIT COMPONENT MODULES, VERTICAL AIR FLOW

ACCESSORIES. 3 YEARS WARRANTY.

ISOLATOR, COMMUNICATIONS KIT, AND ALL NECESSARY SAFETIES & OPERATING

CHAIN, VARIABLE SPEED BELT AND STANDARD CONTROL COMPONENT, VIBRATION

MIXING BOX W/ FILTER, ADJUSTABLE PULLEY/BELT, GEAR MOTOR/SPROCKET

CHILLED WATER COOLING COIL AND HOT WATER HEATING COIL & COMBINATION

TYPE, FAN SECTION, STAGGERED COPPER TUBE AND ALUMINUM FIN TYPE

BLOW-THRU, SINGLE-ZONE UNIT COMPONENT MODULES, VERTICAL AIR FLOW

M-4

NTS

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

QTY D E S C R I P T I O NITEM D E S C R I P T I O NQTYITEMQTY D E S C R I P T I O NITEM D E S C R I P T I O NQTYITEM

EQUIPMENT SCHEDULES - 2

E Q U I P M E N T S C H E D U L E S - 2

D E S C R I P T I O NQTYITEM D E S C R I P T I O NQTYITEM

ET

AND ALL NECESSARY SAFETIES & OPERATING ACCESSORIES.

RUBBER DIAPHRAGM AND PIPING CONNECTIONS, 120 PSI WORKING PRESSURE,

CONFORMING TO ASME CODE REQUIREMENTS COMPLETE WITH HEAVY DUTY BUTYL

CLOSED, ROUND HORIZONTAL TYPE, ALL WELDED STEEL CONSTRUCTION,

TANK SIZE

CAPACITY

: 14" DIA x 64-3/4" LG

: 40 GAL'S

ROOF VENTILATOR

ACCESSORIES. UL-LISTED.

DISCONNECT SWITCH, ROOF CURBS, AND ALL NECESSARY SAFETIES & OPERATING

EQUIPPED WITH VIBRATION ISOLATOR, BIRD-SCREEN, BACK-DRAFT DAMPER AND

DESIGN MOTOR, WEATHER-PROOF ALUMINUM FAN HOUSING, SPARK RESISTANT,

ROOF MOUNTED CENTRIFUGAL DIRECT DRIVE, NON-OVERLOADING STANDARD NEMA

VOLT/PH/HZ

1/4"

HP

RF

RF

(CFM)

CAPACITY

REMARKSRPM

MOTOR RATING

1,140

1/8" 1,725

RF

115/1/601,140

1/2

1/4

1/6

RF

115/1/601/12 TOILET IN KITCHEN

RF

115/1/601,550 1/15

RF

115/1/601,550 1/25

115/1/60

115/1/60

SP

1/8"

1/4"

1/8"

1/8"200

850/425

1,100/550

2,500/1,250 DISHWASHING AREA

MECH. ROOM

ELEC. ROOM

FOR COFFEE URN HOOD

FOR UTENSIL SK. HOOD

TYPE

T

T

T

S

S

S

S = SINGLE SPEED TYPE

TYPE : T = TWO SPEED TYPE

ACCESSORIES. UL-LISTED.

DISCONNECT SWITCH, ROOF CURBS, AND ALL NECESSARY SAFETIES & OPERATING

EQUIPPED WITH VIBRATION ISOLATOR, BIRD-SCREEN, BACK-DRAFT DAMPER AND

DESIGN MOTOR, WEATHER-PROOF ALUMINUM FAN HOUSING, SPARK RESISTANT,

WALL MOUNTED CENTRIFUGAL DIRECT DRIVE, NON-OVERLOADING STANDARD NEMA

VOLT/PH/HZ

1/8"

HP

WF

(CFM)

CAPACITY

REMARKSRPM

MOTOR RATING

1,550 1/25 115/1/60

SP

FOR DRY STORAGE200

WALL VENTILATOR

FC

FC

REMARKS

FC

FINNED TUBE CONVECTOR

NO.

ROOM

ROOM NAME

W. TOILET

M. TOILET

W. TOILET

M. TOILET

LOCKER ROOM

NO

ROW

LENGTH

2'-6"

2'-6"

3'-6"

GIVEN (BTUH)

HEATING CAP

1,814

1,780

2,594

2,338

2,419

2-ROW/FOOT ............ 1,270 BTUH

ENCLOSURE CABINET): 1-ROW/FOOT ............ 770 BTUH

RATING FOR FIN TUBE CONVECTIR BASED (AVG, WATER TEMP = 170°F AND

NECESSARY SAFETIES & OPERATING ACCESSORIES.

CABINET, INCLUDE NON-ELECTRIC THERMOSTATIC CONTROL VALVE, AND ALL

FOOT, SLOPING TOP 18 GA. COATED WITH PAINT SHEET METAL ENCLOSURE

1-1/4" I.P.S STEEL TUBE WITH 4-1/4" x 4-1/4" STEEL FINS, 32 FINS

CENTRIFUGAL IN-LINE FAN

ACCESSORIES. UL-LISTED.

WITH DISCONNECT SWITCH, AND ALL NECESSARY SAFETIES & OPERATING

SPRING OR NEOPRENE TYPE VIBRATION ISOLATOR, CENTRIFUGAL FAN, EQUIPPED

HEAVY GAUGE GALVINIZED STEEL CONSTRUCTION, INSULATED FAN HOUSING,

VOLT/PH/HZ

1.2"

HP

IF

IF

REMARKSRPM

MOTOR RATING

IF

IF

115/1/601/4

IF

115/1/601,050 1/4

460/3/60

SP

TYPE

B

B

B

B

D

IF

115/1/601,140 1/6550 D

IF

115/1/601,200 1/4380 B

5,370

4,010

2,880

0.75"

0.75"

0.62"940

0.62"

0.37"

0.75"

1,300

460/3/60

460/3/60

(CFM)

CAP

E.A FOR GAME ROOM

E.A FOR TOILET IN ADMIN

E.A FOR BAR/DANCE (R.W)

E.A FOR BAR/DANCE (L.W)

R.A FOR AHU-5

R.A FOR AHU-1 (L.W)

R.A FOR AHU-2 (R.W)

D = DIRECT DRIVE

TYPE : B = BELT DRIVE

AC AIR CURTAIN

CONTROL VALVE, AND ALL NECESSARY SAFETIES & OPERATING ACCESSORIES.

WHEELS AND FAN HOUSING, ADJUSTABLE LOUVERS AND AIR DIRECTIONAL

MOTOR, DIRECT-DRIVE DOUBLE WITH AND DOUBLE INLET SQUIRREL CAGE BLOWER

POLYCARBONATE CABINET, INCORPORATED WITH A DOUBLE EXTENDED SHAFT

MOTOR RATING

MAX. FPM/CFM NOZZLE

COVERAGE AREA

1,750 RPM

: 1/2 HP, 115 V, 1 PH, 60 Hz

: 2,550 / 2,550

: 4'W x 8'H

ET

AND ALL NECESSARY SAFETIES & OPERATING ACCESSORIES.

RUBBER DIAPHRAGM AND PIPING CONNECTIONS, 120 PSI WORKING PRESSURE,

CONFORMING TO ASME CODE REQUIREMENTS COMPLETE WITH HEAVY DUTY BUTYL

CLOSED, ROUND HORIZONTAL TYPE, ALL WELDED STEEL CONSTRUCTION,

TANK SIZE

CAPACITY

: 13" DIA x 51" LG

: 24 GAL'S

AC SPLIT AIR CONDITIONING OUTDOOR & INDOOR UNIT

NECESSARY SAFETIES & OPERATING ACCESSORIES. 3 YEARS WARRANTY.

FILTER, CLEANABLE FILTERS, WIRELESS REMOTE CONTROLLER AND ALL

REFRIGERATION COMPONENTS, DRAIN PUMP, CONTROL SYSTEM, TOTAL VIRUS

INDOOR UNIT, CONSISTING OF DC INVERTER COMPRESSOR, AIR-COOLED COIL,

VARIABLE REFRIGERANT FLOW HEAT PUMP OUTDOOR UNIT WITH WALL MOUNTED

ELECTRICAL RATING

COMPRESSOR

COOLING CAPACITY

: 15 Amps, 208 V, 1 PH, 60 Hz

: MAX. 282 CFM

: 3,600 W (12,280 BTU/HR)

MFR. LG MODEL NO. SW09BAKWAS OR APPROVED EQUAL.

DWH DOMESTIC HOT WATER HEATER

10 YEARS WARRANTY.

SAFETIES & OPERATING ACCESSORIES. CSA CERTIFIED, ASME CERTIFIED.

SENSOR WITH CABLE, MAGNETIC BOILER FILTER, AND ALL NECESSARY

DUAL VENTURI SYSTEM, CONDENSATE NEUTRALIZER, OUTDOOR TEMPERATURE

DUAL STAINLESS STEEL HEAT EXCHANGERS FOR HEATING, MANIFOLD SYSTEM,

GAS FIRED TYPE, CASCADE SYSTEM, CONDENSING WATER HEATER,

EFFICIENCY

ELEC. POWER

TEMP. RISE

SUPPLY WATER TEMP.

GAS INPUT

HEAT RECOVERY

GROSS OUTPUT

ELECTRIC UNIT HEATER

AND ALL NECESSARY ACCESSORIES. UL LISTED.

HEATING ELEMENT, COMPLETE WITH BUILT-IN CONTROL REMOTE THERMOSTAT

HEAVY 18 GAUGE STEEL CASING, DIRECT DRIVE PROPELLER FAN, ELECTRIC

CEILING HUNG, HORIZONTAL DISCHARGE, ADJUSTABLE LOUVER, COMPLETE WITH

ELEC. RATING

MOTOR

HEATING CAPACITY

FAN CAPACITY

: 3.0 kW, 208 V, 1 Ph, 60 Hz

: 1/50 HP, 240 V, 1 Ph, 60 Hz

: 3.0 kW

: 146 LPS

MFR. CHROMALOX MODEL NO. LUH-04-21-34 OR APPROVED EQUAL.

EUH

NOTE : NOTE :

THE CONTRACT DOCUMENT REQUIRMENTS.

SHALL BE RESPONSIBLE FOR VERIFYING ACTUAL QUANTITIES BASED ON

QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY, THE CONTRACTOR

MFR. NAVIEN MODEL NO. NPE-240S2 x 4EA OR APPROVED EQUAL.

: 97 %

: 3 FLA, 120 V, 1 PH, 60Hz

: 16.7 °C

: 60.0 °C

: 18.28 CMH

: 191.6 LPM

: 223.2 KW

DT DOMESTIC HOT WATER STORAGE TANK

ACCESSORIES.

AND TANK SUPPORTING LEGS AND ALL NECESSARY SAFETIES AND OPERATING

MOUNTED TYPE. CATHODIC PROTECTION, EQUIPPED WITH INSPECTION MANHOLE

150 PSI ASME STAMPED, GLASS-LINED STEEL TANK, CYLINDRICAL VERTICAL

TANK SIZE

CAPACITY

: 1,200mmD x 2,750mmL

: 800 GALLONS

EXPANSION TANK FOR COOLING SYSTEM

EXPANSION TANK FOR HEATING SYSTEM

AS AIR SEPARATOR

ALL NECESSARY SAFETIES & OPERATING ACCESSORIES.

CONNECTION, 3" FLANGED CONNECTION, 125 PSI WORKING PRESSURE, AND

REQUIREMENTS COMPLETE WITH REMOVABLE GALV. STRAINER & PIPING

CYLINDRICAL TYPE, STEEL CONSTRUCTION, CONFORMED TO ASME CODE

CAPACITY : 118 GPM

M-5

NTS

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

CP CASEY

BUILDING S-533

REPAIR FIRE PROTECTION SYSTEM

77525

1SEE

SECTOR "B"

1SEE

SECTOR "D"

M10

1SEE

SECTOR "C"

1SEE

SECTOR "A"

NOT TO SCALE

NEW HVAC & HVAC PIPING COMPOSITE PLAN

CHS

HWR

HWS

CHR

CHS

HWR

HWS

CHR

CHS

HWR

HWS

CHR

T

CWS

CWR

H W

S H

W S

HWS

H W

S

C H

S H

W S

C H

R

CHS

HWS

CHR

C H

S H

W S

C H

R

CHS

HWS

CHR

CHS

HWS

CHR

C W

S

C W

R

H W

R

H W

R

HWRHWR

HWR

H W

R H

W R

H W

R

HWR

60°C

43.3°C

COMPOSITE PLAN

NEW HVAC & HVAC PIPING

T

T T T

T

T

M5

M7

M8

M9

M-6 1:50

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

CP CASEY

BUILDING S-533

REPAIR FIRE PROTECTION SYSTEM

77525

SCALE = 1:50

CHS

HWR

HWS

CHR

CHS

HWR

HWS

CHR

CHS

HWR

HWS

CHR

GRAPHIC SCALE

SCALE: 1:50

0 1000 2000

BELLOWS TYPE (TYP OF 4)

NEW EXPANSION JOINTNEW PIPE GUIDE (TYP.)

(TYPICAL)

NEW PIPE ANCHOR

AHU

W/ CONC. PAD

AIR HANDLING UNIT

AHU

W/ CONC. PAD

AIR HANDLING UNIT

AHU

W/ CONC. PAD

AIR HANDLING UNIT

AHU

W/ CONC. PAD

AIR HANDLING UNIT

AHU

W/ CONC. PAD

AIR HANDLING UNIT

AHU

x x x x x x x x x x x x x x x x x x

S.A S.A S.A S.A S.A S.A S.A S.AS.AS.AR.AR.AR.AR.AR.AR.A E.A E.A

UH

UNIT HEATER

UH

UNIT HEATER

AHU

W/ CONC. PAD

AIR HANDLING UNIT

UH

UNIT HEATER

UH

UNIT HEATER

IF

IN-LINE FAN

CENTRIFUGAL

IF

IN-LINE FAN

CENTRIFUGAL

AHU

AHU

AHU

M I

N

O

C F

M

M A

X

M

L O

U V

E R

W

B I

R D

S C

R E

E N x

L I

A

M

M

M A

M

L O

U V

R D

S C

R E

E N x

L I

M

M A

M

L O

U V

R D

S C

R E

E N x

L I

M

M A

M

L O

U V

R D

S C

R E

E N x

L I

M

M A

M

L O

U V

R D

S C

R E

E N x

L I

IF

IF

IN-LINE FAN

CENTRIFUGAL

AHU

W/ CONC. PAD

AIR HANDLING UNIT

AHU

W/ CONC. PAD

AIR HANDLING UNIT

65,65,100,10050,50,80,8050,50,80,8040,40,65,6532,32,50,50

(TYP OF 2)

DAMPER

BACK-DRAFT

AUTOMATIC

HVAC & HVAC PIPING ENLARGED PLAN (ATTIC SPACE)

PIPE RISER FROM/TO FIRST FLOOR

100mm CWS/CWR, 65mm HWS/HWR

350x750

450x800 R.A

S.A

350x650

300x500

OUTLET CONTINUATION

CONDENSATE DRAIN

SCALE = 1:50

SECTION FOR AHU-1

1,000x2,600

M6

M6

& SECTION FOR AHU-1 (ATTIC SPACE)

HVAC & HVAC PIPING ENLARGED PLAN

DUCT LINING (TYP.)

M-7 1:50

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

SCALE = 1:50

GRAPHIC SCALE

SCALE: 1:50

0 1000 2000

KEY PLAN

A B

C D

CP CASEY

BUILDING S-533

REPAIR FIRE PROTECTION SYSTEM

77525

B

ASECTOR "A"

SECTOR "B"

C

A SECTOR "A"

SECTOR "C"

NEW H.V.A.C ENLARGED PARTIAL PLAN (SECTOR "A")

150/LFx5=750CFM138/LFx5=690CFM

(SECTOR "A")

NEW H.V.A.C ENLARGED PARTIAL PLAN

200 200

150x100150x100

450x250

500x250

600x250 x x x

650x100

350x250

300 450 500

550x350

650x350 x x x x

550x300 x

750x400

500x200

650x300 x x x x

550x250

550x300 x

800x450

300x200 400x200 400x250

200x150

250x200

200x150

200x150 200x100

200x100

200x150

250x150 250x150

300x200300x200 x

200x150

300 375375 425 450

150x100 x x x x

200x100

200x100

400x250 400x200 350x150 250x150 x

350250 400 450

450 400

450300 x x

350x250

500x350

500x300 x

550x400 x

T

36CFM/LFx5'LGx1EA, 180CFM

40CFM/LFx5'LGx4EA, 800CFM

LINEAR DUCT, 200 CONN.,

40CFM/LFx4'LGx2EA, 320CFM

37.5CFM/LFx4'LGx2EA, 300CFM

LINEAR DUCT, 200 CONN.,

55CFM/LFx4'LGx3EA, 660CFM

52.5CFM/LFx4'LGx1EA, 210CFM

LINEAR DUCT, 200 CONN.,

40CFM/LFx5'LGx1EA, 200CFM

LINEAR DUCT, 200 CONN.,

72CFM/LFx5'LGx2EA, 720CFM

LINEAR DUCT, 250 CONN.,

68CFM/LFx5'LGx2EA, 680CFM

LINEAR DUCT, 250 CONN.,

50CFM/LFx5'LGx1EA, 250CFM

48CFM/LFx5'LGx1EA, 240CFM

LINEAR DUCT, 250 CONN.,

138CFM/LFx5'LGx1EA, 690CFM

150CFM/LFx5'LGx3EA, 2,250CFM

LINEAR DUCT, 300 CONN.,

T.D

138CFM/LFx5'LGx1EA, 690CFM

150CFM/LFx5'LGx1EA, 750CFM

LINEAR DUCT, 300 CONN.,

99CFM/LFx5'LGx1EA, 495CFM

98CFM/LFx5'LGx1EA, 490CFM

LINEAR DUCT, 250 CONN.,

50CFM/LFx3'LGx2EA, 300CFM

LINEAR DUCT, 200 CONN.,

50CFM/LFx5'LGx3EA, 750CFM

LINEAR DUCT, 200 CONN.,

117CFM/LFx3'LGx1EA, 350CFM

90CFM/LFx5'LGx3EA, 1,350CFM

LINEAR DUCT, 250 CONN.,

90CFM/LFx4'LGx1EA, 360CFM

LINEAR DUCT, 250 CONN.,

42CFM/LFx5'LGx1EA, 210CFM

50CFM/LFx5'LGx4EA, 1,000CFM

LINEAR DUCT, 200 CONN.,

125CFM/LFx4'LGx2EA, 500CFM

LINEAR DUCT, 250 CONN.,

130 CFM

225x225 CD

375 CFM

250x300 EG

375 CFM

250x300 EG

(TYP OF 2)

2-WAY THROW

50 CFM

100x200 CD

130 CFM

225x225 CD

130 CFM

225x225 CD

130 CFM

225x225 CD

130 CFM

225x225 CD

105 CFM

150x150 CD

130 CFM

225x225 CD

173 CFM

225x225 EG

173 CFM

225x225 EG

174 CFM

225x225 EG

210 CFM

225x225 EG

120 CFM

225x225 EG

50 CFM

150x100 EG

100 CFM

150x150 EG

100 CFM

150x150 CD

220 CFM

225x225 EG

300 CFM

225x225 EG

T

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD VD

VD VD

VD

VD

VD

VD

VD

VD

VD

VD

IF

IN-LINE FAN

CENTRIFUGAL

WALL CAP

VAV

& DAMPER UNIT

VARIABLE AIR VOLUME

VAV

& DAMPER UNIT

VARIABLE AIR VOLUME

IF

IN-LINE FAN

CENTRIFUGAL

M7

(TYPICAL)

DUCT LINING

M-8 1:50

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

GRAPHIC SCALE

SCALE: 1:50

0 1000 2000

KEY PLAN

A B

C D

CP CASEY

BUILDING S-533

REPAIR FIRE PROTECTION SYSTEM

77525

CA

S E

C T

O R

"A

S E

C T

O R

"C

B

A SECTOR "A"

SECTOR "B"

SCALE = 1:50

NEW H.V.A.C ENLARGED PARTIAL PLAN (SECTOR "B")

(SECTOR "B")

NEW H.V.A.C ENLARGED PARTIAL PLAN

x x

250x150 250x150 x

400x150

350x150

400x200500x250

600x300 x x

350x150350x150

450x200

600x250 450x200650x250650x300 x x

350x200

400x250 x x x

300x200300x200

400x200 250x150

450x250

250200

500x300

600x300

400x200 x

400x200 x

250x150

400x250 x x

700x250 600x250 500x250

750x400

600x300

700x300 x x x

150x100150x100 x x

350 375

200x150250x200

200x150

500x300 450x250 300x200

250x200

250x150250x200

250x200

300x150300x150

350x200 350x200

250x150 x

200x150 x x

200x100

200x100 300x150 x x

200x150250x200

350x200

350x200

300450475550500 x x x x x x

350x250

250 (TYP)

400x250400x200350x150250x150

200 (TYP)

x x x

300 300

250250

800x450 x

600x250

0x

0x

0x

450550600 x

550x250550x300650x350

450 300 x

900x350 x

350x250 500x250

T

140 CFM

225x225 CD

145 CFM

225x225 CD

145 CFM

225x225 CD

145 CFM

225x225 CD

90 CFM

150x150 EG

155 CFM

225x225 EG

150 CFM

225x225 EG

155 CFM

225x225 EG

145 CFM

225x225 CD

260 CFM

225x225 CD

260 CFM

225x225 CD

260 CFM

225x225 CD

260 CFM

225x225 CD

250 CFM

225x225 EG

270 CFM

225x225 CD

250 CFM

225x225 EG

250 CFM

225x225 EG

250 CFM

225x225 EG

250x200

250x200

190 CFM

225x225 EG380 CFM

300x300 EG

50 CFM

100x200 CD

50 CFM

100x200 CD

250 CFM

225x225 CD

250 CFM

225x225 CD

250 CFM

225x225 CD

250 CFM

225x225 CD

250 CFM

225x225 CD

270 CFM

225x225 EG

270 CFM

225x225 EG

270 CFM

225x225 EG

250 CFM

225x225 CD

300 CFM

225x225 CD

270 CFM

225x225 EG

270 CFM

225x225 EG

430 CFM

300x300 EG

430 CFM

300x300 EG

250 CFM

225x225 CD

250 CFM

225x225 CD

250 CFM

225x225 CD

250 CFM

225x225 CD

56CFM/LFx3'LGx5EA, 840CFM

LINEAR DUCT, 200 CONN.,

250 CFM

225x225 CD

266 CFM

225x225 CD

267 CFM

225x225 CD

400 CFM

300x300 EG

300 CFM

300x300 EG

130 CFM

225x225 CD

42CFM/LFx5'LGx1EA, 210CFM

50CFM/LFx5'LGx3EA, 750CFM

LINEAR DUCT, 200 CONN.,

90CFM/LFx4'LGx1EA, 360CFM

LINEAR DUCT, 250 CONN.,

125CFM/LFx4'LGx1EA, 500CFM

LINEAR DUCT, 250 CONN.,

50CFM/LFx3'LGx1EA, 150CFM

50CFM/LFx5'LGx3EA, 750CFM

LINEAR DUCT, 200 CONN.,

98CFM/LFx5'LGx1EA, 490CFM

100CFM/LFx5'LGx3EA, 500CFM

LINEAR DUCT, 250 CONN.,

40CFM/LFx5'LGx1EA, 200CFM

LINEAR DUCT, 200 CONN.,

138CFM/LFx5'LGx1EA, 690CFM

150CFM/LFx5'LGx4EA, 750CFM

LINEAR DUCT, 300 CONN.,

VD VD

VD VD

VD VD

VD

VD VD

VD VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD

VD VD

VDVD

VD

VD

VDVD

VD

VD

IF

IN-LINE FAN

CENTRIFUGAL

WALL CAP

VAV

& DAMPER UNIT

VARIABLE AIR VOLUME

VAV

& DAMPER UNIT

VARIABLE AIR VOLUME

VAV

& DAMPER UNIT

VARIABLE AIR VOLUME

IF

IN-LINE FAN

CENTRIFUGAL

IF

IN-LINE FAN

CENTRIFUGAL

M8

DUCT LINING

M-9 1:50

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

GRAPHIC SCALE

SCALE: 1:50

0 1000 2000

KEY PLAN

A B

C D

CP CASEY

BUILDING S-533

REPAIR FIRE PROTECTION SYSTEM

77525

D

CSECTOR "C"

SECTOR "D"

C

A SECTOR "A"

SECTOR "C"

SCALE = 1:50

NEW H.V.A.C ENLARGED PARTIAL PLAN (SECTOR "C")

(SECTOR "C")

NEW H.V.A.C ENLARGED PARTIAL PLAN

200 200 200

600x200 600x250400x200350x200

X x

350x200350x200

150X100

200x150

200x150

200x150 x

300x200 350x250 450x250 500x250 x x

200x100

200x100 x

350x200 x x x x x x x x x

T

S.A S.A S.A S.A S.A R.AR.AR.A E.A

36CFM/LFx5'LGx1EA, 180CFM

40CFM/LFx5'LGx4EA, 800CFM

LINEAR DUCT, 200 CONN.,

72CFM/LFx5'LGx2EA, 720CFM

LINEAR DUCT, 250 CONN.,

48CFM/LFx5'LGx3EA, 720CFM

LINEAR DUCT, 250 CONN.,

200 CFM

150x150 CD

325 CFM

300x300 CD

325 CFM

300x300 CD

400 CFM

300x300 CD

400 CFM

300x300 CD

400 CFM

300x300 CD

200 CFM

150x150 CD

200 CFM

150x150 CD

50 CFM

100x100 CD

200 CFM

200x200 CD

150 CFM

200x150 EG

100 CFM

150x150 CD

90CFM/LFx5'LGx4EA, 1,800CFM

LINEAR DUCT, 250 CONN.,

75CFM/LFx4'LGx1EA, 300CFM

75CFM/LFx5'LGx2EA, 750CFM

LINEAR DUCT, 250 CONN.,

VD

VD VD

VDVD

VD

VD

FCUNOTE :

DOMESTIC WATER PIPING PRIOR TO PIPING INSTALLATION.

3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC &

2. THE CONTRACTOR SHALL CLEAN THE REMAINED DUCT.

LINE.

KITCHEN HOOD REMAIN AND REPLACE THE FAN & CONTROL

1. THE KITCHEN HOOD AND DUCT THAT CONNECTS TO THE

W/ DUCT TO REMAIN

EXISTING HOOD

RF

ROOF VENTILATOR

RF

ROOF VENTILATOR

400x200(E)

600x250

AC

AIR CURTAIN

WF

WALL VENTILATOR

FCU

FAN COIL UNIT

M9

M-10 1:50

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

GRAPHIC SCALE

SCALE: 1:50

0 1000 2000

KEY PLAN

A B

C D

CP CASEY

BUILDING S-533

REPAIR FIRE PROTECTION SYSTEM

77525

C

ASECTOR "A"

SECTOR "C"

D

C SECTOR "C"

SECTOR "D"

SCALE = 1:50M10

NEW H.V.A.C ENLARGED PARTIAL PLAN (SECTOR "D")

(SECTOR "D")

NEW H.V.A.C ENLARGED PARTIAL PLAN

300x200 x x

450x200

250x150250x150

250x150 x

400x200250x150 600x250 500x250700x250 x x x x x x x x x x x

200X150

800x250

800x250

800x250

800x250

700x250600x250600x250

750x250600x250

500x250

350x200

300x150 x

200x150

150x100150x100

150x100

150x100

T

T T

S.AS.AS.AR.AR.AS.AE.AS.A

250 CFM

225x225 CD

250 CFM

225x225 CD

250 CFM

225x225 CD

250 CFM

225x225 CD

250 CFM

225x225 CD

267 CFM

225x225 CD

300 CFM

225x225 EG

400 CFM

300x300 EG

400 CFM

300x300 EG

(TYP OF 2)

50 CFM

150x100 EG

(TYP OF 2)

100 CFM

150x150 EG

50 CFM

100x100 EG

400 CFM

300x300 CD

325 CFM

300x300 CD

325 CFM

300x300 CD

200 CFM

150x150 CD

100CFM/LFx5'LGx4EA, 2,000CFM

LINEAR DUCT, 250 CONN.,

75CFM/LFx4'LGx2EA, 600CFM

75CFM/LFx5'LGx1EA, 375CFM

LINEAR DUCT, 250 CONN.,

150 CFM

150x150 CD

VD

VD VD

VD VD

VD

VD

VD VD

VD

NOTE :

DOMESTIC WATER PIPING PRIOR TO PIPING INSTALLATION.

3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC &

2. THE CONTRACTOR SHALL CLEAN THE REMAINED DUCT.

LINE.

KITCHEN HOOD REMAIN AND REPLACE THE FAN & CONTROL

1. THE KITCHEN HOOD AND DUCT THAT CONNECTS TO THE

W/ DUCT TO REMAIN

EXISTING HOOD

RF

ROOF VENTILATOR

350x150(E)

IF

IN-LINE FAN

CENTRIFUGAL

OAU

SPLIT COMPACT DOAS

OAU

SPLIT COMPACT DOAS

RF

ROOF VENTILATOR

RF

ROOF VENTILATOR

RF

ROOF VENTILATOR

NOTE :

AND ALL NECESSARY ACCESSORIES TO INSTALL THE CONTROLS SYSTEM.

5. THE CONTROLS CONTRACTOR SHALL PROVIDE ALL THE SWITCHES, RELAYS, WIRING, CONDUITS, MECHANICAL JOINTS. THE VRF SYSTEM SHALL BE PRESSURE TESTED & VACUUM TESTED.

FITTINGS, EXTRUDED FITTINGS, PRESS-CONNECT FITTINGS, FLARE FITTINGS, GROOVE JOINTS &

AND JOINTS THAT ARE PROHIBITED INCLUDE BUT ARE NOT LIMITED TO THE FOLLOWING: PUSH-ON

REQUIREMENTS AND THE MANUFACTURER'S INSTALLATION REQUIREMENTS. THE LIST OF FITTINGS

4. VRF SYSTEMS PIPING/TUBING SHALL HAVE ALL BRAZED CONNECTIONS THAT MEET ASME B31.5

A CERTIFIED INSTALLER.

3. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S SPEC BY

2. REFRIGERANT PIPE SIZE & INSTALLATION SHALL BE AS PER MANUFACTURER'S RECOMMENDATION.

1. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PIPEWORK PRIOR TO PIPEWORK INSTALLATION.

VALVE (TYP.)

ISOLATION

NOTE :

KIM, SM

M-11

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

CP CASEY

BUILDING S-533

REPAIR FIRE PROTECTION SYSTEM

77525

CWS

CWR

H W

S H

W S

HWS

H W

S

C H

S H

W S

C H

R

CHS

HWS

CHR

C H

S H

W S

C H

R

CHS

HWS

CHR

CHS

HWS

CHR

H W

R

H W

R

HWRHWR

HWR

H W

R H

W R

H W

R

HWR

60°C

43.3°C

M11 SCALE = 1:100

GRAPHIC SCALE

SCALE: 1:100

0 2000 4000

EXISTING/NEW H.V.A.C PIPING PLAN

EXISTING/NEW H.V.A.C PIPING PLAN

1:100

AC

OUTDOOR UNIT

SPLIT A/C

FC

(TYP OF 2)

FINNED TUBE CONVECTOR

FC

AC

INDOOR UNIT

SPLIT A/C

ISOLATION VALVES AND WATER HAMMER ARRESTORS.

1. PROVIDE CEILING/WALL ACCESS PANEL FOR

HPO

OUTDOOR UNIT

VRF HEAT PUMP

NEW CONC. PAD

C W

S

C W

R

W/ PIPEWORK TO REMAIN

EXIST. WATER CHILLER P.O.C

FCU

FAN COIL UNIT

FC

(TYP OF 2)

FINNED TUBE CONVECTOR

FC

FC

(TYP OF 2)

FINNED TUBE CONVECTOR

FC

OAU

(TYP OF 2)

SPLIT COMPACT DOAS

OAU

(TYPICAL)

METAL PIPE TRAY

65,65,100,100

PIPE RISER FROM/TO ATTIC SPACE

100mm CWS/CWR, 65mm HWS/HWR

M14

PARTIAL PLAN SEE DWG

MECH. ROOM ENLARGED

SCALE = 1:100M12

NOTE ON INSTALLATION OF PIPE INSULATION :

COMPLETED.

INSTALLATION OF THE PIPE INSULATION IS

ENGINEER FOR QUALITY INSPECTION WHEN THE

4. THE CONTRACTOR SHALL INVITE THE MECHANICAL

ACCORDANCE WITH ASTM E84.

DEVELOPED INDEX OF 50 WHEN TESTED IN

SPREAD INDEX OF 25 AND A MAXIMUM SMOKE

FIRERESISTANT AND SHALL HAVE A MAXIMUM FLAME

3. LAGGING ADHESIVES SHALL BE NONFLAMMABLE AND

AND LISTED IN FM APP GUIDE.

2. INSULATION MATERIALS RECOGNIZED UNDER UL94

ASTM C534/C534M, GRADE 1, TYPE I OR II.

OF OMA SPEC 23 07 00, AND SHALL COMPLY WITH

1. INSULATION MATERIALS SHALL CONFORM TO TABLE1

KIM, SM

M-12

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

CP CASEY

BUILDING S-533

REPAIR FIRE PROTECTION SYSTEM

77525

C

C

C

C

60°C

43.3°C

C

C

43.3°C

60°C

43.3°C

GRAPHIC SCALE

SCALE: 1:100

0 2000 4000

EXISTING/NEW DOMESTIC WATER PIPING PLAN

DOMESTIC WATER PIPING PLAN

EXISTING/NEW

1:100

NOTE :

ISOLATION VALVES AND WATER HAMMER ARRESTORS.

4. PROVIDE CEILING/WALL ACCESS PANEL FOR

PIPING INSTALLATION.

SEWER AND VENT PIPING) PRIOR TO PLUMBING

PLUMBING PIPING (HOT & COLD WATER PIPING,

3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR

RISERS AND MECHANICAL ROOM)

THE CRAWL SPACE. (EXCEPT FOR THE MAIN PIPE

2. THE SOW IS LIMITED TO THE CEILING SPACE AND

1. ALL PIPE LINES SHALL BE COPPER TUBE.

ARRESTER (TYP)

WATER HAMMER A

24 23

13 11

PIPE RISER FROM/TO FIRST FLOOR

15mm DHWR, 25mm HW & 32mm CW

VALVE (TYP.)

ISOLATION

(TYPICAL)

BALANCING VALVE

CRAWL SPACECONTROL CABINET

BALANCING VALVE

A

A

32,15,50

32,15,50

32,20,25,50

32,20,25,50

32,20,25,50

ARRESTER (TYP)

WATER HAMMER A

M14

PARTIAL PLAN SEE DWG

MECH. ROOM ENLARGED

WALL HYDRANT

20mm NON-FREEZE

A

ARRESTER (TYP)

WATER HAMMER

PRIMER

TRAP

KIM, SM

M-13

MECHANICAL

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

A

B C D

E F G H

SHEET OF

CP CASEY

BUILDING S-533

REPAIR FIRE PROTECTION SYSTEM

77525

M13

EXISTING/NEW DOMESTIC WATER PIPING PLAN (CRAWL SPACE)

(CRAWL SPACE)

DOMESTIC WATER PIPING PLAN

EXISTING/NEW

1:100

60°C

PE60°C

P E

C

SCALE = 1:50

EXIST. KITCHEN EQUIP. PIPE CONNECTION SCHEDULE

DESCRIPTION CW HW DITEM NO

15 MM

15 MM 15 MM 32 MM

15 MM 15 MM 32 MM

15 MM 15 MM 32 MM

15 MM

15 MM 15 MM 32 MM

15 MM 15 MM

15 MM 15 MM 40 MM

15 MM

15 MM

15 MM 15 MM 50 MM

15 MM 50 MM

15 MM 15 MM 50 MM

1-HP SINK MOUNTED DISPOSER

BANQUET WATER GLASS FILLER

2-COMPT, CONVECTION STEAMER -

VEGETABLE SINK & DRAIN BOARD

ICE MACHINE - -

SINK

SINK UNIT W/ DIPPER WELL

SINK UNIT W/ DIPPER WELL

SINK

AUTIMATIC TWIN 3 COFFEE URN --

SALAD & DESSERT COUNTER

UNKNOWN

UNKNOWN

DESCRIPTION CW HW DITEM NO

15 MM 15 MM 32 MM

15 MM 15 MM 40 MM

15 MM

15 MM

15 MM

15 MM

20 MM 20 MM 50 MM

50 MM

15 MM 15 MM

15 MM 15 MM 50 MM

50 MM

SINK 15 MM 15 MM 32 MM

UTENSIL SINK & DRAIN BOARD

WALL MOUNTED BUGGYWHIP RINSE

DISHWASHER W/ SCRAPER - 20 MM

3-HP COMMERCIAL DISPOSER - -

ICE BIN W/ 2-COMPARTMENT

ICE MACHINE -

LAVATORY 15 MM 15 MM 50 MM

SINK

WALL MOUNTED POT FILLER - -

- -WALL MOUNTED POT FILLER

WORK TABLE W/ SINK

SINK

60°C

(IN KITCHEN AREA)

CONTROL CABINET

4 5

NOTE :

ISOLATION VALVES AND WATER HAMMER ARRESTORS.

4. PROVIDE CEILING/WALL ACCESS PANEL FOR

PIPING INSTALLATION.

SEWER AND VENT PIPING) PRIOR TO PLUMBING

PLUMBING PIPING (HOT & COLD WATER PIPING,

3. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR

RISERS AND MECHANICAL ROOM)

THE CRAWL SPACE. (EXCEPT FOR THE MAIN PIPE

2. THE SOW IS LIMITED TO THE CEILING SPACE AND

1. ALL PIPE LINES SHALL BE COPPER TUBE.

NOTE ON INSTALLATION OF PIPE INSULATION :

COMPLETED.

INSTALLATION OF THE PIPE INSULATION IS

ENGINEER FOR QUALITY INSPECTION WHEN THE

4. THE CONTRACTOR SHALL INVITE THE MECHANICAL

ACCORDANCE WITH ASTM E84.

DEVELOPED INDEX OF 50 WHEN TESTED IN

SPREAD INDEX OF 25 AND A MAXIMUM SMOKE

FIRERESISTANT AND SHALL HAVE A MAXIMUM FLAME

3. LAGGING ADHESIVES SHALL BE NONFLAMMABLE…