The document provided contains a series of Tank Compliance Assessment Checklists for annual and monthly inspections of both aboveground and underground storage tanks. The checklists cover a comprehensive set of criteria to assess the condition and compliance of tank containment, foundations, appurtenances, corrosion control, level and overfill prevention, electrical systems, and overall tank site. The checklists require responses to indicate the presence or absence of various tank components and whether they are in working order.
The related federal contract opportunity is for a Fuel Tank requirement, with a solicitation number of W90VN7-24-R-A005. The Department of the Army is the procuring agency. The Performance Work Statement for this opportunity is attached, but not provided in the given documents.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| TE6 FEI FII Guide Lines.pdf | ||
| TE3 STI-SP001-Monthly-Inspection-Checklist.pdf | ||
| Fuel Tank - Solicitation Amendment W90VN724RA0050002 SF 30.pdf | ||
| TE5 STI-SP001-AST-Record.pdf | ||
| TE1 STAR Tank Inventory.pdf | ||
| TE4 STI-SP001-Annual-Inspection-Checklist.pdf | ||
| Fuel Tank PWS V.4 (Solicitation Mod).pdf | ||
| TE2 OM Tank Inventory.pdf | ||
| Fuel Tank - QUESTIONS AND ANSWERS.pdf | ||
| Revised Fuel Tank Solicitation - W90VN724RA005.pdf | ||
| Fuel Tank PWS v.4.pdf | ||
| Fuel Tank Solicitation Amendment W90VN724RA0050001 SF 30.pdf | ||
| Fuel Tank PWS V.3.pdf | ||
| Fuel Tank Solicitation - W90VN724RA005.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TANK COMPLIANCE ASSESSMENT CHECKLIST
ANNUAL ORGANIZATIONAL TANK ASSESSMENT
Installation Date:
Real Property ID:
Installation/GSU:
Owner:
Unit/Org: Designation:
Location: Volume (Gallons):
Model: Contents:
Serial #:
Finding Status:
Perform Date: Status:
Assessor: Duty Phone:
Conclusion:
Comments:
For Official Use Only
TANK CONTAINMENT
Are there water accumulations, debris, vegetation, cracks, fire hazards, or holes observed in the tank containment?
Correct Response: NResponse: Yes No N/A
Comments:
Are containment drain valves in working order and closed?
Correct Response: YResponse: Yes No N/A
Comments:
TANK FOUNDATION AND SUPPORTS
Is there evidence of tank settlement, foundation washout, or foundation cracking?
Correct Response: NResponse: Yes No N/A
Comments:
Is there any cracking, spalling, or corrosion of tank supports and/or saddles?
Correct Response: NResponse: Yes No N/A
Comments:
Are ladders, platforms, handrails, and stairs secure with no indication of corrosion and/or damage?
Correct Response: YResponse: Yes No N/A
Comments:
TANK AND APPURTENANCES
Is the normal vent clear and free of obstructions?
Correct Response: YResponse: Yes No N/A
Comments:
Is vent located five feet or more from adjacent buildings?
Correct Response: YResponse: Yes No N/A
Comments:
For class I fuels (ie MOGAS, AVGAS), are normal vents located at least 12 feet above grade?
Correct Response: YResponse: Yes No N/A
Comments:
For Official Use Only
TANK AND APPURTENANCES (continued)
Are there emergency vents for the primary tank?
Correct Response: YResponse: Yes No N/A
Comments:
If the primary tank is equipped or designed with an emergency vent, is it operable (vent cover can be lifted by hand)?
Correct Response: YResponse: Yes No N/A
Comments:
If a secondary tank is present and equipped or designed with an emergency vent, is it operable (vent cover can be lifted by hand)?
Correct Response: YResponse: Yes No N/A
Comments:
If the primary tank is equipped or designed with a pressure vacuum vent, is it operable?
Correct Response: YResponse: Yes No N/A
Comments:
Are all valves in working order?
Correct Response: YResponse: Yes No N/A
Comments:
Are NFPA-compliant placards present and legible?
Correct Response: YResponse: Yes No N/A
Comments:
CORROSION CONTROL
Is there any evidence of paint coating failure or corrosion of tank and piping surfaces?
Correct Response: NResponse: Yes No N/A
Comments:
Is there evidence of corrosion at pipestand and piping interfaces (undercutting of pipe) including underside of piping?
Correct Response: NResponse: Yes No N/A
Comments:
Is there cathodic protection for underground metallic piping?
Correct Response: YResponse: Yes No N/A
Comments:
Is cathodic protection working and being checked regularly?
Correct Response: YResponse: Yes No N/A
Comments:
LEVEL AND OVERFILL PREVENTION
Has the tank level indicating device been tested and is it in working order?
Correct Response: YResponse: Yes No N/A
Comments:
Is tank level gauge viewable from the filling point?
Correct Response: YResponse: Yes No N/A
Comments:
1550424661A Cross-Out
For Official Use Only
LEVEL AND OVERFILL PREVENTION (continued)
Has the overflow shutoff mechanism (shut off valve or float valve) been tested to determine if it is in good working order?
Correct Response: YResponse: Yes No N/A
Comments:
If a High Level Alarm is present, has it been tested to determine if it is in good working order?
Correct Response: YResponse: Yes No N/A
Comments:
Are anti-siphon valves operable (if present)?
Correct Response: YResponse: Yes No N/A
Comments:
ELECTRICAL WIRING AND EQUIPMENT
Is the tank grounded?
Correct Response: YResponse: Yes No N/A
Comments:
Are grounding straps secure and in good order?
Correct Response: YResponse: Yes No N/A
Comments:
Are wiring, wiring conduit, and junction boxes in good condition?
Correct Response: YResponse: Yes No N/A
Comments:
Are electrical components in classified conduit and enclosures as required?
Correct Response: YResponse: Yes No N/A
Comments:
TANK SITE
Are traffic bollards and/or protection from vehicle traffic in place where required?
Correct Response: YResponse: Yes No N/A
Comments:
ADDITIONAL
Have all other Local, State, or Federal requirements checklist(s) been accomplished, if required, and documents uploaded to this tank record? Provide appropriate reference to record in comments.
Correct Response: YResponse: Yes No N/A
Inspector Signature
MONTHLY ORGANIZATIONAL TANK ASSESSMENT
Installation Date:
Real Property ID:
Installation/GSU:
Owner:
Unit/Org: Designation:
Location: Volume (Gallons):
Model: Contents:
Serial #:
Finding Status:
Perform Date: Status:
Assessor: Duty Phone:
Conclusion:
Comments:
For Official Use Only
TANK CONTAINMENT
Are there water accumulations, debris, vegetation, cracks, fire hazards, or holes observed in the tank containment?
Correct Response: NResponse: Yes No N/A
Comments:
Are containment drain valves in working order and closed?
Correct Response: YResponse: Yes No N/A
Comments:
If the tank is a double wall tank, was there water or fuel in the tank interstitial space?
Correct Response: NResponse: Yes No N/A
Comments:
Are there leaks, broken seals, and/or corrosion of manhole covers?
Correct Response: NResponse: Yes No N/A
Comments:
Are there any indications of leakage, staining, seepage, or corrosion around tank shell or concrete pad?
Correct Response: NResponse: Yes No N/A
Comments:
Are there any indications of leakage, staining, seepage, or corrosion on piping, pipe connections, or pipe stands?
Correct Response: NResponse: Yes No N/A
Comments:
Are there any indications of leakage, staining, seepage, or corrosion on valves?
Correct Response: NResponse: Yes No N/A
Comments:
Are there any indications of leakage, staining, seepage, or corrosion on tank supports/saddles?
Correct Response: NResponse: Yes No N/A
MONTHLY ORGANIZATIONAL TANK ASSESSMENT
For Official Use Only
TANK CONTAINMENT (continued)
Is the tank level gauge working, readable, and can be observed by the operator from the fill position location?
Correct Response: YResponse: Yes No N/A
Comments:
Are ladders, platforms, handrails, and stairs secure with no indication of severe corrosion and/or damage?
Correct Response: YResponse: Yes No N/A
Comments:
Are containment egress (exit) pathways clear?
Correct Response: YResponse: Yes No N/A
Comments:
Are gates/doors operable and in working order?
Correct Response: YResponse: Yes No N/A
Comments:
Are fire extinguishers maintained in a serviceable condition and located in the designated area?
Correct Response: YResponse: Yes No N/A
Comments:
Has an AF Form 332 been completed for any deficiencies observed?
Correct Response: YResponse: Yes No N/A
Comments:
Are NFPA-compliant placards present and legible?
Correct Response: YResponse: Yes No N/A
Comments:
ADDITIONAL
Have all other Local, State, or Federal requirements checklist(s) been accomplished, if required, and documents uploaded to this tank record? Provide appropriate reference to record in comments.
Correct Response: YResponse: Yes No N/A
ANNUAL UST INSPECTION
Installation Date:
Real Property ID:
Installation/GSU:
Designation:
Location:
Volume (Gallons):
Contents:Model:
Finding Status:
Perform Date: Status:
Assessor: Duty Phone:
Conclusion:
Comments:
For Official Use Only
SECONDARY CONTAINMENT SUMPS (SUBMERSIBLE TURBINE PUMP, DISPENSER, TRANSITION)
Are containment sumps free of damage?
Correct Response: YResponse: Yes No N/A
Comments:
Are containment sumps free of leaks to the containment area and without indication of a release to the environment?
Correct Response: YResponse: Yes No N/A
Comments:
Are containment sumps free of water, product and debris? Liquid and debris must be removed and disposed of properly.
Correct Response: YResponse: Yes No N/A
Comments:
HAND-HELD RELEASE DETECTION EQUIPMENT
Do hand-held release detection equipment (e.g. groundwater bailers and tank gauge sticks) accurately measure liquid depth?
Correct Response: YResponse: Yes No N/A
Comments:
DISPENSERS
Are dispenser hoses, nozzles and breakaways free of loose fittings, deterioration, signs of leakage, or improper functionality?
Correct Response: YResponse: Yes No N/A
Comments:
EQUIPMENT TESTING
Is annual piping testing complete with passing results? (Ref: 40 CFR 280.41)
Correct Response: YResponse: Yes No N/A
Comments:
Is triennial spill bucket and containment sump testing complete with passing results? (Ref: 40 CFR 280.35)
Correct Response: YResponse: Yes No N/A
Comments:
Unit/Org:
Serial #:
ANNUAL UST INSPECTION
For Official Use Only
EQUIPMENT TESTING (continued)
Is triennial overfill equipment (Automatic Shutoff Device and Alarm) verification, inspection, and testing complete with passing results?
(Ref: 40 CFR 280.35)
Correct Response: YResponse: Yes No N/A
Comments:
Is annual electronic monitoring system (Automatic Tank Gauging - ATG and liquid sensors) inspection and testing complete with passing results? (Ref: 40 CFR 280.40)
Correct Response: YResponse: Yes No N/A
Comments:
Is annual line leak detector testing complete with passing results? (Ref: 40 CFR 280.40, 280.44)
Correct Response: YResponse: Yes No N/A
Comments:
ADDITIONAL
Have all other Local, State, or Federal requirements checklist(s) been accomplished, if required, and documents uploaded to this tank record? Provide appropriate reference to record in comments.
Correct Response: YResponse: Yes No N/A
MONTHLY UST INSPECTION
Installation Date:
Real Property ID:
Installation/GSU:
Designation:
Location: Volume (Gallons):
Model: Contents:
Serial #:
Finding Status:
Perform Date: Status:
Assessor: Duty Phone:
Conclusion:
Comments:
For Official Use Only
SPILL PREVENTION EQUIPMENT
Is spill prevention equipment (e.g. spill buckets) in good working condition and capable of containing spills?
Correct Response: YResponse: Yes No N/A
Comments:
Is spill prevention equipment free of corrosion?
Correct Response: YResponse: Yes No N/A
Comments:
Is spill prevention equipment free of water, product, or debris? Liquid and debris must be removed and disposed of properly.
Correct Response: YResponse: Yes No N/A
Comments:
Is fill pipe free of obstructions (i.e. gauging stick segments, trash, debris etc.)? Any obstructions must been removed.
Correct Response: YResponse: Yes No N/A
Comments:
Is the fill cap in good condition and equipped with an intact gasket?
Correct Response: YResponse: Yes No N/A
Comments:
Does the fill cap and its assembly fit securely on the fill pipe before, during, and after deliveries?
Correct Response: YResponse: Yes No N/A
Comments:
Is double-walled spill prevention equipment interstitial area free from leaks? (Applicable only to double-walled spill prevention equipment)
Correct Response: YResponse: Yes No N/A
Comments:
RELEASE DETECTION EQUIPMENT
If the tank is equipped with release detection, is the equipment operating properly to determine usual operating conditions (i.e., faulty alarms, monitoring discrepancies, readings, etc.)?
Correct Response: YResponse: Yes No N/A
Comments:
Owner:
Unit/Org:
MONTHLY UST INSPECTION
For Official Use Only
RELEASE DETECTION EQUIPMENT (continued)
If the piping is equipped with release detection, is the equipment operating properly to determine usual operating conditions (i.e., faulty alarms, monitoring discrepancies, readings, etc.)?
Correct Response: YResponse: Yes No N/A
Comments:
Have copies of release detection reports been obtained, for each tank system, to meet record keeping requirements?
Correct Response: YResponse: Yes No N/A
Comments:
Has the Impressed Current Rectifier Check been conducted and results documented within the last 60 days?
Correct Response: YResponse: Yes No N/A
Comments:
ADDITIONAL
Have all other Local, State, or Federal requirements checklist(s) been accomplished, if required, and documents uploaded to this tank record? Provide appropriate reference to record in comments.
Correct Response: YResponse: Yes No N/A
| AST_ANNUAL_STAR_Chklst |
| AST_MONTHLY_STAR_Chklst |
| UST_ANNUAL_STAR_Chklst |
| UST_MONTHLY_STAR_Chklst |
| Response_1: Yes |
| Response_4: Yes_4 |
| Response_5: Yes_5 |
| Response_6: Yes_6 |
| Response_7: Yes_7 |
| Response_8: Yes_8 |
| Text11: |
| 0: KUNSAN AB |
| 2: 8 CES |
| 3: XXXX |
| 5: BLDG# XXXX |
| 7: |
| 8: |
| 11: |
| 12: YYYY/MM/DD |
| 13: SSgt. |
| 15: No Finding |
| 17: |
| text22: |
| 0: |
| 2: |
| 4: |
| 5: xxxxx |
| 7: Deisel |
| 12: Complete/In-Work |
| 14: 782-XXXX |
| comments1: |
| 0: |
| 1: |
| 0: |
| 6: |
| 11: |
| 15: |
| 22: |
| comments5555: |
| comments6666: |
| Response_2: Yes_2 |
| Response_3: Yes_3 |
| Response_9: Yes_9 |
| Response_10: Yes_10 |
| Response_11: Yes_11 |
| Response_12: Yes_12 |
| Response_13: Yes_13 |
| Response_14: Yes_14 |
| Response_15: Yes_15 |
| Response_16: Yes_16 |
| Response_17: Yes_17 |
| Response_18: Yes_18 |
| Response_19: Yes_19 |
| Response_20: Yes_20 |
| tank ID: AST-XXXX |
| comments1111: |
| 0: |
| 5: |
| 9: |
| 14: |
| 18: |
| comments222222: |
| 0: |
| 7: |
| 11: |
| 16: |
| 18: |
| 19: |
| comments88: |
| Response_21: Yes_21 |
| Response_22: Yes_22 |
| Response_23: Yes_23 |
| Response_24: Yes_24 |
| Response_25: Yes_25 |
| Response_26: Yes_26 |
| Response_27: Yes_27 |
| Response_28: Yes_28 |
| Response_29: NA_29 |
| comments333: |
| comments33333: |
| 0: |
| 5: |
| 9: |
| 16: |
| comments44: |
| 0: |
| 5: |
| 9: |
| comment: |
| Response: No |
| Text4: |
| 0: KUNSAN AB |
| 1: 8 CES |
| 3: XXXX |
| 4: BLDG# XXXX |
| 6: |
| 7: |
| 0: |
| 1: |
| 3: YYYY/MM/DD |
| 4: SSgt |
| 6: NO FINDINGS |
| 7: |
| Text5: |
| 0: |
| 2: |
| 3: HFR - Aboveground |
| 4: XXXX |
| 6: DEISEL |
| STATUS: COMPLETE/ IN-WORK |
| DUTY PHONE: 782-XXXX |
| Text7: |
| 0: |
| 4: |
| 7: |
| 11: |
| 15: |
| 19: |
| 22: |
| 26: |
| TANK ID: AST# 0000 |
| COMMENTS111: |
| 0: |
| 4: |
| 8: |
| 11: |
| 15: |
| 19: |
| 22: |
| 24: |
| Status: |
| Comments: |
| Serial: |
| conclusion: No Finding |
| installation date: |
| duty phone: 782-xxxx |
| contents: Gasoline |
| Perform Date: KUNSAN AB |
| Unit/Org: AAFES |
| Location: BLDG# |
| Model: |
| comment111: |
| comment 112: |
| COMMENT1: |
| COMMENT2: |
| COMMENT3: |
| comments 11: |
| COMMENT4: |
| comments 12: |
| comments 13: |
| comment 14: |
| Tank ID: UST xxxxx |
| comment 15: |
| installation/GSU: |
| 0: KUNSAN AB |
| owner: AAFES |
| unit: FILLING STATION |
| location: BLDG# 1108 |
| model: |
| serial: |
| installatindate: |
| real property id: |
| designation: |
| volume: |
| contnts: Gasoline |
| finding status: |
| Perform date: YYYY/MM/DD |
| Assessor: Mr. |
| status: complete/ in-work |
| duty phoen: 782-xxxx |
| Conclustion: No Finding |
| comments: |
| Qcomments: |
| 0: |
| 4: |
| 8: |
| 11: |
| 12: |
| 0: |
| 4: |
| 8: |
| 11: |
| 13: |
| 0: |
| 4: |
| 7: |
| 8: |
File details come from the government source that posted it. Updated .