Minimum Essential Characteristics Brand Name or Equal
TATRC requests the purchase of UPS batteries to replace existing batteries.
These 108 Batteries shall have the following specs:
1) Voltage: 12V
2) Operating temp: -40F to 160F
3) Maximum Charging Current Limit: C/5 amperes @ 20hr rate
4) Float Charging Volt: 13.65 ± 0.15 VDC average per 12V unit (6.75 to 6.90 per 6V unit)
5) Maximum AC Ripple (Charger): 0.5% RMS or 1.5% P-P of float charge
6) Equalize charge and cycle service voltage: 14.40 to 14.80 voe average per ` 12V unit@ 77 14.40 to 14.80 voe average per 12V unit@ 77 Note:
The UPS is an APC MGE Galaxy 5000. The UPA is located in a separate room from the battery racks. All wiring is in place between the battery racks and the UPS. The rooms are located adajent to each other.
File details come from the government source that posted it.