APPENDIX 9 FINAL_REPORT_STEVENS RFAAP Bioplant.pdf
PDF 2 MB Posted
- Solicitation number
- W519TC-26-R-BIOR
About this file
This document is Appendix 9 to a US Army Contracting Command contract (W15QKN-22-C-0051) containing a comprehensive technical evaluation of the Radford Army Ammunition Plant (RFAAP) Bioplant wastewater treatment system performance.
The evaluation encompasses analysis of the Bioplant's operation at RFAAP, which treats wastewater generated in propellant manufacturing areas using biological treatment processes. Key findings indicate 83% BOD₅ removal with effluent satisfying VPDES daily limits, viable biomass with lower-end sludge volume index values, and significantly higher oxygen uptake in equalization basins than in rotating biological contactors. The study identified high nitroglycerin (NG) concentrations in certain upstream monitoring stations (UMS 1, 3, and 9) that correlate with microbial toxicity, elevated graphite concentrations in equalization basin sludge (up to 8,008 mg/L), and phosphorous deficiency throughout the system. Testing of three commercial bioaugmentation products (MB-2, MB-8, and MicroSolv 118) revealed they achieve only approximately 10% NG degradation primarily through denitration to 1,3-DNG rather than complete degradation, likely due to inadequate operational conditions. The report recommends prioritizing assessment of NG interceptor improvements, increasing phosphorous amendment dosing, and conducting techno-economic analysis for potential major modifications. It notes that any substantial plant modifications face regulatory challenges due to FEMA floodplain location and Virginia DEQ Sewage Collection and Treatment Regulations requirements for equipment placement above the 100-year flood level, potentially necessitating consideration of designing a new state-of-the-art treatment facility.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
US Army Contracting Command Contract No. W15QKN-22-C-0051
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other request for this document shall be referred to Ben Smolinski, Benjamin.L.Smolinski.civ@army.mil
Appendix 9: TASK 9 - Evalua�on of RFAAP Bioplant performance mailto:Benjamin.L.Smolinski.civ@army.mil
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
Execu�ve Summary A thorough analysis of the opera�on of the Bioplant at Radford Army Ammuni�ons Plant was performed. Along a sample round and the characteriza�on of selected streams discharging into the Bioplant and Bioplant opera�onal units, the assessment also included the review of:
• The Toxic Review Evaluation performed by BAE
• DBOC JV/Haskell’s assessment of the wastewater systems at RFAAP
• Bioplant logsheets
• Historical information of flows and available parameters for UMS
The results from the study and recommenda�ons are presented below.
o SVI values fall in the lower end of the recommended range o Biomass appears to be viable o Oxygen uptake much higher in the EQ basins than in the RBCs o 83% BOD5 removal and a BOD5 effluent satisfying VPDES daily limits o TCOD and SCOD data need further analysis o Solvent evaporative processes at the EQ basis might be playing a significant role in
SCOD removal o Microtox toxicity found for a few streams (pH effects, NG and derivatives present in samples) o Bioaugmentation products appear not to enhance NG removal (<10% degradation mostly to 1,3 DNG) although might enhance COD removal. This is most likely due to Bioplant opera�onal condi�ons which are not adequate for promo�ng NG degrada�on o High concentrations of graphite found in the EQ basins sludge o DNT (mix of 2,4 and 2,6 DNT) only detected in UMS-6 sample; 96 ppb
Moreover, is recommended that the operator should assess the feasibility of increasing phosphorous amendment to the Bioplant as the values measured in the active treatment areas were below detection. The analysis of the flow through the Bioplant during 2023 shows a wide variation. The average and median flows were 0.92 and 0.9 mgd, respectively; however, the standard deviation was 0.15 mgd and the maximum and minimum values were 1.4 mgd and 0.53 mgd, respectively. It is possible that those swings also have an impact on the Bioplant level of treatment.
Regarding the recommendations made in the DBOC JV/Haskell, the tiered approach valued around $70M addressing the acid and industrial streams systems is sound and will help improve the current plant operation. As high NG concentrations that correlate well with microbial toxicity
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other were found, it is recommended that the assessment of improvements in the NG interceptors as recommended in the report is prioritized. However, a technoeconomic analysis should be performed as the facility is aging and any major modification to the current plant will require Virginia DEQ approval and might face regulatory challenges. All equipment is subject to Virginia DEQ Sewage Collec�on and Treatment Regula�ons (SCAT), Sec�on 9VAC25-790-450 “Treatment Works Design” Part D, “Flooding” which reads: “All mechanical and electrical equipment that could be damaged or inac�vated by contact with or submergence in water (motors, control equipment, blowers, switch-gear, bearings, etc.) shall be physically located above the 100-year level or otherwise protected against the 100-year flood/wave ac�on damage…”
A review of FEMA maps performed by Haskell shows that the Bioplant is in the Zone AE Floodway and the 100-year flood plain; thus, any major modifica�on likely will require reloca�on of major process units at which �me cost es�ma�ons will likely rise and open the possibility of considering the design of a new, state of the art, wastewater treatment plant able to process the industrial streams and the acid streams (upon neutraliza�on) with the associated reduc�on of nutrient discharges to the New River.
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
Table of Contents Appendix 9: TASK 9 - Evalua�on of RFAAP Bioplant performance
Execu�ve Summary
Introduc�on
Approach
Scope of Work
Deliverables
Work performed
UMS descrip�on (informa�on furnished by BAE in a previous project)
Analysis of the informa�on provided by RFAAP
Analy�cal Methods
Results
Evalua�on of Bioaugmenta�on products (BGPs) for RFAAP Bioplant: oxygen uptake tests
Introduc�on
Results
Evalua�on of Bioaugmenta�on products (BGPs) for RFAAP Bioplant: microbial iden�fica�on using next genera�on sequencing (NGS) technology
Introduc�on
Methodology
Summary, conclusions, and recommenda�ons
References
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
Introduc�on There are three wastewater treatment systems in opera�on at RFAAP: the AB acid waste treatment plant (discharge: ou�all 007), the municipal wastewater treatment plant (trickling filter, discharge ou�all 026), and the Bioplant (RBC) treatment system (discharge through ou�all 029). The focus of this task is the analysis of the Bioplant opera�on.
Wastewater generated in propellant manufacturing areas is treated at the Bioplant. Organics are removed using biological treatment. The wastewater is generally pH neutral. Three branches of the collec�on system combine at the Bioplant. Two branches are forced mains from pump sta�ons. The first is from the 4th rolled powder area and mainly contributes wash-down water and water from sprinkler trips. Storm water from building downspouts is also a significant contribu�on from this area. The second branch carries mainly wastewater generated by New River Energe�cs (NRE) opera�ons. A line also enters following the pump sta�on from the DNT/TNT area. This area is not currently in use. If produc�on were occurring in this area, the wastewater would be pretreated in ac�vated carbon columns located in the TNT area. The ac�vated carbon would remove nitro compounds. NRE wastewater collected in this branch has significant graphite content. The third branch carries most of the propellant produc�on wastewater. This branch enters from the west and is a combina�on of 3 sub-branches. These originate from (1) the horseshoe area – rocket and NG2, (2) NRE and some RFAAP solvent recovery and water dry opera�ons and (3) the remainder of the produc�on area – solvent recovery, water dry, green lines, solvent s�lls, and NG1 (Figure 1).
In February 2019, SIT performed a comprehensive sampling event of all UMS (upstream monitoring sta�ons) following by chemical and toxicological characteriza�ons (using microalgae as target organism) of those wastewaters and found that some of them were toxic or par�ally toxic. Moreover, lately, the Bioplant discharge has not met opera�onal requirements and an assessment of its opera�on is long overdue. This situa�on led to the issue of several Notes of Viola�on (NOVs) for TUa (acute toxicity units) and BOD (average and maximum) during the second half of 2021 and the first quarter of 2022. This inves�ga�on aims to evaluate the current opera�on of the Bioplant and perform a preliminary evalua�on of the possibility of combining Bioplant biological with AB acid waste treatment with the aim to reduce BOD and TRI discharges into the New River.
Approach Historical informa�on was procured from RFAAP regarding the discharge flows at ou�all 029 and flow readings from selected UMSs (Upstream Monitoring Sta�ons 1, 3, 9, and 12). To close data gaps in the historical record of Bioplant opera�onal parameters and the chemical/physical
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other characteriza�on of the streams that make up the Bioplant influent, a sampling program was developed as described in the scope of work (SOW) below.
Figure 1. Bioplant schema�cs.
Scope of Work The work was performed as per following subtasks:
Subtask 9.1: Procure and analyze historical data from RFAAP on discharges from ou�all 029 and flows in UMSs 1, 3, 9, and 12.
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
Subtask 9.2: Arrange with RFAAP a sampling round to be performed in the second quarter of the project. Three gallons samples were collected following the procedures used in February 2019.
Beyond the 10 UMS samples taken in 2019, samples were collected from the li� sta�on, equaliza�on basins EQ1 and EQ2, the RBC’s biomass from opera�ng trains.
Subtask 9.3: Chemical and toxicological characteriza�ons of the obtained samples as follows:
• pH
• TOC, COD, BOD
• Total phosphorous, NH4+, Nitrate, nitrite, sulfate
• NG, NC
• Conduc�vity and TSS
• Metals: Al, Ca, Cr, Cu, Fe, K, Na, Zn, Pb, As, Mn, Ni, and Cd
• Toxicity studies (Scenedesmus obliquus and Microtox)
Deliverables Deliverables for this task include:
• Full characteriza�on of the streams discharging into the Bioplant
• An assessment of the Bioplant opera�on. Iden�fica�on of wastewater streams that might impair the Bioplant opera�on.
Work performed Several telecoms were held with BAE/RFAAP and DEVCOM-AC to discuss prac�cal aspects of the work to be performed and to present the results to the stakeholders. The first priority was the signing of the NDA between BAE/RFAAP and SIT. The NDA agreement was fully executed on 8/10/2022 covering informa�on sharing and sampling events. Arrangements were made to transfer relevant Bioplant opera�onal data, data from UMSs 1, 3, 9, 5, and 7B (the last one suggested by BAE, currently known as UMS10), NOVs (no�ces of viola�on), and historical chemical characteriza�on of the streams fed into the Bioplant from RFAAP to SIT via DEVCOM- AC. Although NOVs occurred during 2021 and first quarter of 2022, changes in the performance of the Bioplant were detected at the beginning of 2019; thus, data from 2018 were requested in order to develop an opera�onal baseline for the Bioplant’s performance. Moreover, originally, we requested flow informa�on for UMS12; however, we were informed that flow data from that UMS was not available.
During the period of performance of this study, we con�nuously monitored RFAAP Bioplant opera�on based on the informa�on supplied by RFAAP. Moreover, we also reviewed the full DBOC JV/Haskell report (2023) along the Toxic Reduc�on Evalua�on performed by BAE Systems Inc, (TRE, 2022). The schema�c of the Bioplant is presented in Figures 1 and 2 along with a descrip�on of the upstream monitoring sta�ons (UMSs), and a schema�c of the Bioplant collec�on system (Figure 3). Data (flow, pH, and TC) from several UMS were also furnished by
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
RFAAP. Samples were collected on February 15, 2023, and brought back to Stevens for characteriza�on. The yellow highlighted samples in Table 1 were delivered to Stevens on 3/16/23.
This report presents the results of the full characteriza�on.
Figure 2. Bioplant schema�c. Observe the discharge lines from the clarifiers, thickener, aerobic digesters, and sludge press to the li� sta�on, EQ basins and RBCs.
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
Figure 3. Bioplant collec�on system
UMS descrip�on (informa�on furnished by BAE in a previous project) Figure 3 presents a more detailed view of the Bioplant collec�on system. Below is the BAE provided descrip�on of the loca�ons and monitoring performed at the different UMSs.
UMS 1: This sta�on is located following pump sta�on 906-8. Wastewater is mainly collected from NRE opera�ons. This sta�on includes monitoring for flow, pH, and TC. The flow meter is of the magne�c in-line type and the sample pump is pneuma�c. UMS 9 is upstream of this sta�on. UMS 1 is located 100 yards east of Bldg. 1658.
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
UMS 2: This sta�on is located following pump sta�on 906-9. This pump sta�on receives wastewater generated in the NG2 area and from some water dry buildings. This sta�on includes monitoring for flow, pH, and TC. The flow meter is of the magne�c in-line type and the sample pump is pneuma�c. UMS 8 is upstream of this sta�on. UMS 2 is located 100 yards northwest of Bldg. 420-2.
UMS 3: This sta�on is located following pump sta�on 906-15. This sta�on receives all wastewater generated in the horseshoe area of the plant. This includes wastewater from the Rocket area and NG2. This sta�on includes monitoring for flow, pH, and TC. The flow meter is of the magne�c in-line type and the sample pump is pneuma�c. UMS 3 is located 100 yards northwest of Bldg. 9410.
UMS 4: This sta�on monitors wastewater generated in the center por�on of the plant. This stream is comprised mainly of NRE wastewater and wastewater from RFAAP water dry and solvent recovery buildings. This sta�on includes monitoring for flow, pH, and TC. The flow meter is of the capacitance probe type and the sample pump is pneuma�c. UMS 5 is located upstream of this sta�on. The UMS 4 monitoring building is located 150 yards southwest of Bldg. 1728.
UMS 5: This sta�on monitors wastewater generated in the NRE opera�ons. This sta�on includes monitoring for flow, pH, and TC. The flow meter is of the capacitance probe type and the sample pump is pneuma�c. The UMS 5 monitoring building is located 200 feet south of Bldg. 1612.
UMS 6: This sta�on monitors wastewater from a variety of opera�ons. This sta�on is unique in that the flow monitoring and TC and pH monitoring are of separate streams. Flow is measured in a stream comprised of wastewater from a series of water dry buildings. The flow meter is of the capacitance probe type and the sample pump is pneuma�c. The sample collected for pH and TC analysis at UMS 6 is taken from the main flow which combines wastewater from several opera�ons (i.e., solvent recovery, green lines, solvent s�lls, water dry, and NG1). The flow for this stream can be calculated by adding the flow from UMSs 2, 6, 7, and 10. UMSs 2, 8, 7, 10 and 11 are upstream of this sta�on (when considering pH and TC). The UMS 6 monitoring building is located 100 yards west of Bldg. 1672.
UMS 7 (Formerly 7A): This sta�on monitors wastewater from a series of solvent recovery buildings. This sta�on includes monitoring for flow, pH, and TC. The flow meter is of the capacitance probe type and the sample pump is pneuma�c. The UMS 7 monitoring building is located 150 yards west of Bldg. 1610.
UMS 8: This sta�on monitors wastewater from the NG1 area. This sta�on includes monitoring for flow, pH, and TC. The flow meter is of the capacitance probe type and the sample pump is pneuma�c. The UMS 8 monitoring building is located 150 feet south of Bldg. 3622.
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
UMS 9: This sta�on monitors wastewater from NRE opera�ons in building 1601. This opera�on produces wastewater high in graphite. This sta�on includes monitoring for flow, pH, and TC. The flow meter is of the capacitance probe type and the sample pump is pneuma�c. The graphite present in the wastewater frequently interferes with monitoring for pH and TC due to fouling and blocking of the sampling line. The UMS 9 monitoring building is located 100 feet east of Bldg.
1604.
UMS 10 (Formerly 7B): This sta�on monitors wastewater form the green lines and solvent s�lls.
This sta�on includes monitoring for flow, pH, and TC. The flow meter is of the capacitance probe type and the sample pump is pneuma�c. UMS 11 is located upstream of this sta�on. The UMS 10 monitoring building is located 30 feet northeast of Bldg. 1999.
UMS 11: This sta�on monitors the botoms from solvent s�ll building 1503. This sta�on includes monitoring for pH and TC. Flow is not measured. The monitoring equipment is located on the 1st floor of building 1503.
UMS 12: This sta�on monitors the wastewater from pump sta�on 906-7. The wastewater is from opera�ons in the 4th Roll Powder area. This sta�on monitors flow only. The magne�c in-line flow meter is located in the pump sta�on discharge line. There is no monitoring building, but the monitoring loca�on is 200 yards north of Bldg. 9334-7.
Analysis of the information provided by RFAAP Two lines of inves�ga�on were followed in the TRE (Toxic Release Evalua�on); Bioplant opera�on and influent source iden�fica�on/reduc�on. The conclusions of the study along with the corrected ac�ons taken during the first quarter of 2022 are summarized as follows:
• No single event or toxicant responsible for failed toxicity tests
• Key reported points and observa�ons o NOVs provided show CODMax, BOD5Max, BOD5ave, and TUa viola�ons for ou�all 007 (last quarter 2021) o TUa exceedances in ou�all 029 and 007 in Q3, 2021 and Q1, 2022 (colder months) o Insufficient amount of phosphates (corrected) o No NG adsorp�on within the Bioplant treatment train o Solid accumula�on in the EQ basins (where most of the biological treatment occurs )
(corrected) o Seeding products: Microsolve 118, Microclear M100, Bioremove COD (oil industry), MB2 (for NG), MB MN.
o Inflow and Infiltra�on resul�ng in hydraulic overloading (corrected)
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other o Solvent peaks (ethanol) (corrected) o Monitor discharges from Northrup Grumman Defense Systems (solvent s�ll recovery process) o No direct correla�on between pulses of NG and failed toxicity tests o Currently NG is not being removed withing the Bioplant system. More NG detected in the clarifier than entering the system. Place of adsorp�on unknown.
o Clean up of the EQ tanks located in the pretreatment system for NG-2 did not decrease
NG loading to the Bioplant o Evidence for toxicity test strongly suggest that NG is not the only toxicant responsible for failed toxicity tests o Graphite coa�ngs can inhibit biofilm atachment and growth (RBCs) and movement of oxygen and nutrients through the biofilm o Methyl centralite (1,3-Dimethyl-1,3-diphenylurea from coa�ng opera�ons) role in
NOVs to be assessed o More stringent upstream controls of solvents and graphite entering the Bioplant implemented early 2022 along with the cleanup of the equaliza�on basins expected to result in a more balanced microbial community and improved treatment. Toxicity evalua�on results from the second and third quarter of 2022 show toxicity values below
1.0 TUa within facility’s VPDES (Virginia Pollution Discharge Elimination System permit) which seems to support expectations. The results, although encouraging, need to be taken cautiously as the monitoring period also coincided with higher ambient temperatures and enhanced microbial activity.
o NOVs coincide with periods of higher con�nuous TC measured at UMS6 although flow through was rela�vely small o Discuss solids recycling within the Bioplant and effect of supernatants from clarifier, thickener and filter press to the EQ and RBCs (chemical amendments). As shown in Figure 1 and more clearly in Figure 2 above, no biomass recycling lines are shown in the Bioplant schema�cs. During conversa�ons with RFAAP personnel it was stated the biomass is recycled to the RBCs and the EQ basins, however, detailed informa�on regarding schedule and amounts of biosolids recycling could not be obtained.
Based on the informa�on available, which includes discussions with DBOC JV (company which made an opera�onal assessment of the Bioplant opera�on), an updated sampling plan which includes DBOC and SIT recommenda�ons was compiled and shown in Table 1.
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
Table 1. Sample recommenda�ons by DBOC JV (Haskell, rows 1-5). Stevens’ recommenda�ons for addi�onal sampling (rows 6-10)
Table 1: Sampling Recommendations by Haskell
No. Process Locations Parameters 1 Notes
Pump Station No.
906-17
(Raw Influent)
Wet Well Liquid and Bottom Sludge
• Graphite concentration
• Graphite particle size analysis
• NG, NC
• TSS, COD, pH, Temp, TP, TKN, Sulfate, Conductivity, ORP
Total 2 sample locations
EQ Tank, East and West
1) Mixed area,
2) Unmixed area in corner, &
3) Sludge at bottom
• Micro-organism identification 2
• Floc identification 2
Total 6 sample
Mixed area
• TSS, COD, pH, Temp, Conductivity, ORP
• Dissolved Oxygen
RBC
Trains No. 1, 2 & 4 (No. 3 is offline)
Influent End & Effluent End
(3 different units)
• Graphite
• NG, NC
• TSS, COD, pH, Temp, TP, TKN, Conductivity, ORP
• Dissolved Oxygen
Basin Middle & RBC Media Scrape (3 different units)
• Micro-organism identification 2
• floc identification 2
Clarifiers, East and West
Influent
(MLSS)
• Graphite
• NG, NC
• Sludge volume index (30 minutes)
• TSS, COD, pH, Temp
Sludge
• Batch settleability curve test (see notes)
• TSS
Measure sludge depth every minute for 40 minutes and plot.
Final Effluent
Near Flume
• Graphite
• NG, NC
• TSS, COD, BOD, pH, Temp, TP, TKN, Sulfate
6 Monitoring Stations UMSs 1,3,9,5, 10 (7B), and 11
• Graphite,
• Solvents
• NC, NG (and daughter products)
• COD, pH, TSS
7 samples total
7 Thickener Effluent wastewater (EQB and/or RBC return lines)
• Graphite
• NG, NC
• TSS, COD, pH
• Al, Cl
1 sample
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
8 Aerobic digesters Effluent wastewater (EQB and/or RBC return lines)
• Graphite,
• Solvents
• NC, NG (and daughter products)
• COD, pH, TSS
2 samples
9 Conditioner tankers/sludge press
Effluent wastewater from sludge press
(EQB and/or RBC return lines)
• Fe, Cl, Al
• TSS, pH, TSS, COD
1 sample
10 Clarifiers (East and West)
Effluent wastewater (EQB and/or RBC return lines)
• Graphite
• NG, NC
• TSS, COD, pH
• Al, Cl
2 samples total. How often recycle occurs?
This is the water discharged into the New
River
1) All grab samples
2) Recommend an experienced biomass analysis expert to perform a microscopic review and consider the unique arrangement of this WWTP and provide conclusions and recommendations for operations adjustments and improvements. For example, Environmental Leverage Inc. It would be beneficial to repeat this analysis in January when the wastewater is coldest.
As several processes were not operational at the time of the sampling, the highlighted samples, rows 7 to 10, were collected by BAE/RFAAP personnel on March 15, 2023, once the sludge processing processes were operational, and delivery to SIT by 3/16/23. Currently, 100% of the sludge collected in the clarifiers is recycled either to the EQ basins or the head of the RBC trains.
The visual inspec�on of the three opera�onal RBCs trains shows a rela�vely small amount of biomass atachment. Scrap samples were taken from each of the 4 stages of the trains 1 and 2 and from stages 2-4 from train 4 and the rotators in stage 1 were not turning at the �me of sampling. Moreover, samples of the bioaugmenta�on products used by BAE/RFAAP were also provided by the facility personnel for a preliminary assessment. These products are:
• MB-2: a highly specialized blend of bacteria which will remove BOD, COD, TOC, phenol, chlorinated hydrocarbons, aromatic and aliphatic hydrocarbons meta and ortho chlorinated phenols, propylene dichloride, styrene, formaldehyde, and alcohols.
• MB MN micronutrients: balanced blend of micronutrients specially formulated for industrial and municipal wastewater treatment (to be shipped at a later time).
• BioRemove™ COD (MB-8) is Novozymes’ most versatile product for industrial wastewater and is effective for highly complex waste streams. It has a diverse set of microorganisms that target a wide range of organics found in a variety of industries. BioRemove™ COD has the broadest range of biological activity and helps keep plants in compliance and in control.
• MicroSolvTM 118: a high potency, bacteria-laden, powdered formulation, for use in degrading many types of waste. MicroSolv™ 118 contains a specially formulated blend of microorganisms, micro/macronutrients, fungi, and surface tension
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other suppressants/penetrants, developed for use in bioaugmentation. Because of the diversity of microorganisms this bioaugmentation product is excellent for pulp & paper wastewater applications where there are heavy influxes of cellulosic fibrous organic solids. The enzyme activity enhances cellulosic reduction by converting the fibrous solids into carbon dioxide and water.
• MicrocleanR 100: a proprietary formulation of micronutrients designed to enhance the performance of biological systems. It enhances biological growth, shortens lag time, increases biological activity, and provides the critical building blocks necessary to maintain a healthy floc-forming population. The formulation consists of micronutrients, trace minerals, amino acids, and vitamins. There are sixteen trace minerals, including calcium, iron, magnesium, manganese, and zinc. The formulation also includes twenty amino acids, such as glycine, and thirteen vitamins, including folic acid.
Table 2. Sample IDs and sampling loca�ons from sampling event at RFAAP. S=Sludge, L=liquid.
Sample ID Sample Location Matrix 906-17 #1 pump station No.906-17 S 906-17 #2 pump station No.906-17 L EQ E_MA EQ tank, east, mixed area L EQ W_MA EQ tank, west, mixed area L EQ E_UA EQ tank, east, unmixed area L EQ W_UA EQ tank, west, unmixed area L
EQ E_S EQ tank, east, sludge S EQ W_S EQ tank, west, sludge S
RBC1_Inf RBC Train1, Influent L RBC1_Eff RBC Train1, Effluent L RBC1_BM RBC Train1, Basin media S RBC1_MS RBC Train1, Scrape media S RBC2_Inf RBC Train2, Influent L RBC2_Eff RBC Train2, Effluent L RBC2_BM RBC Train2, Basin media S RBC2_MS RBC Train2, Scrape media S RBC4_Inf RBC Train4, Influent L RBC4_Eff RBC Train4, Effluent L RBC4_MS RBC Train4, Scrape media S
C-East Clarifier East L C-West Clarifier West L Effluent Final effluent near flume L UMS-1 monitoring station 1 L UMS-3 monitoring station 3 L UMS-5 monitoring station 5 L
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
The parameters selected for the ini�al characteriza�on are as follow:
• pH
• Biosolids concentration (TSS, VSS)
• Biological Oxygen Demand at 5 days (BOD5)
• Total organic carbon (TOC)
• Chemical Oxygen Demand (COD)
• Sludge volume Index (SVI)
• Inorganic nitrogen concentrations (nitrate, nitrite, ammonia)
• Selected energetic compounds (NG, DNT)
• Graphite
• Total Phosphorous
• Selected heavy metals
It should be noted that not all parameters were measured for all samples, but targeted analyses were applied to selected samples in accordance with significance and pre-established characteriza�ons objec�ves. Characteriza�on is ongoing at the �me of releasing this report;
however, preliminary results of analysis are included in the Results sec�on.
Analytical Methods A brief descrip�on of analy�cal methodologies u�lized during the sample’s characteriza�on process is presented in this sec�on. Other analy�cal procedures will be made available in future reports as addi�onal parameters are characterized.
• Total suspended solids (TSS) and volatile suspended solids (VSS) analysis are conducted according to procedure described in the standard methods 2540D and 2540E. The solids procedure involves a measured volume of samples (i.e., 5-20 mL) passed through a prepared, pre-weighed ceramic crucibles provided with dedicated glass fibers filters (0.45µm, 934-AH, Whatman, Fisher scientific). After filtration, the filter and any collected particles are dried in an oven at 104 ± 1°C for two hours. After drying, the filter is reweighed and the TSS is calculated by the difference in weight respect to the sample volume filtered. Following determination of the TSS, the same samples are then placed in a furnace at 550 °C for at least 30 min, for VSS determination. A modification of this process, as per BAE information, will be utilized to determine graphite content of selected samples as described in Table 26.
UMS-6 monitoring station 6 L UMS-9 monitoring station 9 L
UMS-7B monitoring station 7B L
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
• The pH measurements are carried out by using glass probe with standard BNC connection and bench pH meter Thermo Orion Stara1110 Star A111 (Thermo Scientific) calibrated with standard buffer solutions of 4.0, 7.0 and 10.0 value.
• Chemical Oxygen Demand (COD), total and soluble. Total Chemical Oxygen Demand (COD) is measured using HACH COD TNT plus vial kits (Kit number 822, testing range 20- 1500 mg/L). The kits procedure follows the reference method 8000 which is USEPA approved for wastewater analysis under 40 CFR 136.3 and based on standard method 5220D. The total COD (TCOD) is measured using sampled mixed liquor while the soluble COD (SCOD) refers to the soluble portion found in the collected effluent after separation of any suspended solids through sample filtration using disposable syringe filters (pore size 0.45 µm).
• Sludge volume Index (SVI) is determined according to the Standard Method 2710D.
Briefly, the SVI is the volume in ml occupied by 1 g of a sludge suspension after 30 minutes settling time; it is typically used to monitor the settling characteristics of activated sludge.
In general, a good quality sludge has an SVI in the range of 50-150 mL/g.
• Nitrate (NO3−), nitrite (NO2−) and ammonia (NH4+). Nitrite and nitrate concentrations are analyzed by using IC (Dionex Asap Series) with a AS18 column (2 mm×250 mm, Dionex) as stationary phase and DI water with 26 mM KOH as mobile phase. The flow rate was fixed to 0.25 ml/min. For the conditions described the nitrite and nitrate had a retention time of 5.58 and 8.50 min, respectively. Ammonia concentrations were measured using IC with IonPac ®AS16 column (4 mm×250 mm, DIONEX), equipped with a guard column (IonPac®AG16 (4 mm×50 mm) DIONEX). The eluent was given by a solution of 26 mM of methanesulfonic acid (0.1 M MilliporeSigma, Supelco 555171L) while the flow rate was fixed to 1.0 ml/min. At such conditions, the retention time of ammonia was 9.1 min.
• Biodegradable Oxygen Demand at 5 days (BOD5) analysis is conducted following the procedure described in the standard method 5210B. Briefly, the method consists of filling with diluted and seeded sample an airtight bottle with a ground-glass stopper and a flared mouth of specified size (300 mL) and incubating it at 20 °C for 5 days. Dissolved oxygen is measured at the beginning and at the end of the incubation period; the BOD is then computed from the difference between initial and final DO by considering sample and seed volume. BOD seed inoculum was added through use of Polyseed capsule (HACH);
each capsule is dispersed directly into the dilution water and mixed for an hour to allow seed revival. Afterwards, the solution is settled for 15 minutes, and decanted supernatant is used as seed source; standard procedure requires the addition of 4 mL of seed to each BOD bottle. Each capsule supplied about 500 mL of seed solution; the solution was prepared fresh for each batch of BOD tests. For each selected sample, the BOD test is performed in duplicate and for each batch test, a glucose control standard (120 mg/L) is added as an additional sample in order to check the validity of the test.
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
• The BOD5 test procedure was utilized also as base to execute an oxygen uptake test on few sludge samples to test the viability of the biomass. In this instance, instead of using HACH Polyseed as source of seed, about 1 g of sludge sample was dispersed in 500 mL of BOD5 dilution water and aerated following the same procedure required for Polyseed. The decanted supernatant was then used directly to fill the BOD bottles with the addition of
0.5 g of glucose as biodegradable organic. The bottles where incubated for a period of about 20 hours and the DO difference between the initial and final values was recorded as oxygen uptake.
Results Table 3 shows the analytical results for operational parameters of the Bioplant (pH, BOD, SCOD, TCOD, SVI, TSS, VSS and oxygen uptake). Experimental values indicate that the SVI falls in the lower end of the recommended range and that the biomass appears to be viable as per the 20 hours oxygen uptake measured. However, oxygen uptake appears to be much higher in the EQ basins than in the RBCs, which aligns with previous assessments reporting that most of the biological treatment occurs in the EQ basins. BOD5 was assessed at three locations (lift station, influent to RBC2, as a measure of EQ basins BOD reduction, and final effluent near flume) to get an idea of its fate across the treatment system. The results show an overall 83% BOD5 removal and a BOD5 effluent satisfying VPDES daily limits. TCOD and SCOD data need further analysis;
however, the picture portraited by the Bioplant influent data, EQ data and UMS data, suggest that solvent evaporative processes at the EQ basis might be playing a significant role in SCOD removal.
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
Table 3. Characteriza�on of RFAAP samples collected on 2/15/2023 and 3/15/2023.
*Measurement was performed from composite sample (EQ_E_MA and EQ_W_MA).
^values were obtained as difference in DO over a period of 20 hours.
Sample ID Matrix pH BOD5 (mg/L)
SCOD
(mg/L)
TCOD
(mg/L)
*SVI TSS
(g/L)
VSS
(g/L)
^Oxygen Uptake (mg/L)
906-17 #1 S
40.0
0.421 0.281 906-17 #2 L 7.01 335 300 2000 0.083 0.050
EQ E_MA L 7.04
57.6 2670 56.7 0.871 0.685
EQ W_MA L 6.69
59 2590 56.7 0.782 0.628
EQ E_UA L 7.07
37.3
0.830 0.626
EQ W_UA L 6.79 42.1 9.84 8.03
EQ E_S S
36.4 27.3 5.28
EQ W_S S
47.3 38.4 3.51 RBC1_Inf L 7.36
34.7 2910
RBC1_Eff L 7.42
40.0 3540
RBC1_BM S
RBC1_MS S
0.0507° 0.0403° 1.63 RBC2_Inf L 7.52 214 40.3 3100
RBC2_Eff L 7.55
35.2 3190
RBC2_BM S 7.17
39.2
RBC2_MS S
0.0464° 0.0298° 1.81 RBC4_Inf L 7.45
40.3 3040
RBC4_Eff L 7.33
30.5 3450
RBC4_MS S
0.0428° 0.0342° 1.87
C-East L 7.88 52.4
C-West L 7.72 43.6 Effluent L 7.38 82.1
UMS-1 L 6.17 1840
UMS-3 L 7.56 170
UMS-5 L 6.94 750
UMS-6 L 7.03 241
UMS-9 L 6.80 2300
UMS-7B L 7.14 260
T_EW L 7.39
AD#1_EW L 4.27
AD#2_EW L 4.11
SP_EW L 12.32
C_East_EW L 7.35 C_West_EW L 7.38
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
°values are in unit of g/g.
Table 4 presents the results of macronutrients and TOC at different points throughout the Bioplant treatment system (including selected UMSs). Results in Table 4 suggests that the system could benefit from an increase in phosphorous dosage as total phosphorous concentration throughout most of the system were below the detection limit.
Table 4. Results of macronutrients and TOC assessment throughout the Bioplant and collection system.
Table 5 presents the results for selected metals throughout the Bioplant treatment system. The results shown in Table 5 indicate that there is no evidence of degraded Bioplant performance due to metal contamination.
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
Table 5. Selected metals concentration throughout the Bioplant and collection system.
Graphite levels were assessed throughout the system. For most of the samples, graphite was not detected; however elevated levels were found in the unmixed area of the west equalization basin and in the sludge of both EQs (1673, 8008, and 7095 mg/L in EQW_UA, EQE_S, and EQW_S samples, respectively). Graphite concentrations between 4 and 10 mg/L were found in the biomass scraped from RBCs 1, 2 , and 4.
The presence of NG and its degradation products throughout the Bioplant system has been a concern for the facility operator. An assessment of NG in the system was performed and the results are presented in Table 6. As observed in the table, high NG concentration levels were measured in UMS 1, 3, and 9, while concentration levels between 7 and 20 mg/L of 1,3 DNG (dinitroglycerin) were measured in the supernatant return line from the clarifiers and aerobic digestors. UMS 3 showed a high concentration of 1,2 DNG at the time of the sampling.
Moreover, another energetic of concern, DNT (assessed as a mixture of 2,4 and 2,6 DNT) was only found in the UMS 6 sample (96 µg/L).
Table 7 presents the results of the Microtox assessment (expressed as 15 minutes EC50% concentration). As the table shows, is a strong correlation between toxicity and the presence of high NG concentration in the sample. This might be one of the reasons of the Bioplant operational upsets, if the contribution of a high NG concentration stream to the total daily flow
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other at a given time is significant , microbial activity might be affected and proper biological treatment diminished.
Table 6. NG and denitrated byproducts assessment (concentra�on expressed and mg/L).
Evalua�on of Bioaugmenta�on products (BGPs) for RFAAP Bioplant: oxygen uptake tests Introduction A set of commercial bioaugmentation products (BGPs) samples (3) were obtained from RFAAP during the sampling events in February and March 2023 and delivered at the Center for Environmental Systems (CES) (Stevens Institute of Technology). The samples were prepackaged dry powders of 1 lb. each in weight; each sample represents a commercial product for enhancement of COD removal from wastewater from different vendors. Specifications and information on each of the samples can be found in Table 8 below.
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
Table 7. Microtox toxicity assessment.
*pH related, extrapolate data, test repeated ** without pH adjustment very toxic at all levels.
The listed BGPs are currently used at the RFAAP Bioplant to improve and support the efficacy of plant’s biological processes (i.e., RBC) in degradation of COD loads. As such, the products are also thought to support degradation of residual NG and derivative compounds (i.e., DNGs, MNGs) concentrations in the plant influent. In order to evaluate the extent of such performance and verify the claim, the team at Stevens designed and performed a series of qualitative oxygen (O2) uptake tests based on the established methodology for BOD5 assessment. Samples and blanks were prepared using the received BGPs (individual and mixed) and a synthetic solution containing
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other fixed concentrations of NG and byproducts; the testing program was carried out by monitoring two main parameters:
1. O2 uptake
2. NG and byproducts concentrations
Table 8. Bioaugmentation products description.
Methodology A series of samples and blanks were prepared following standards procedures listed for BOD5 assessment (standard method 5210B). Briefly, the method consists of filling with diluted and seeded sample an airtight bottle with a ground-glass stopper and a flared mouth of specified size (300 mL) and incubating it in a dark environment at 20°C for 5 days; in this case, the incubation period was fixed to 48 hours. Dissolved oxygen concentrations were measured at the beginning and at the end of the incubation period with the difference representing oxygen uptake which related to organic carbon sources consumption. A total of four (4) samples were prepared to test each individual BGPs plus a mixed sample with all BGPs to evaluate any synergistic effects. The concentration of each BGPs was fixed by simulating a final bacterial count (CFU/g) comparable to that of standard BOD test inoculum (i.e., Polyseed, HACH) (Table 9). Each BGPs was activated following standards procedure outlined for activation of the Polyseed (i.e., mix fixed amount of product in 1 L of oxygen saturated dilution water for 1 hour, settle 30 minutes, decant; use 4 mL
Sample ID Vendor Description Operational pH MB2 Novozymes
Biologicals Inc blend of bacteria for degradation of petrochemical, chemical , pharmaceutical, tar distillation and phenolic species
6.5-9.0
MB8 Novozymes Biologicals Inc microorganisms that target a wide range of organics found in a variety of industries
6.5-9.0
MicroSolv 118 Environmental Leverage Inc bacteria-laden, powdered formulation containing a blend of microorganisms, micro/macro nutrients, fungi, and surface tension suppressants/penetrants.
This product is for pulp & paper wastewater applications
5.2-9.0
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other of supernatant x test bottle). The pH of all samples and control blanks was kept in a range compatible with the operational range indicated by the BGPs specs (pH range 6.70-7.20).
For preparation of the NG and derivatives synthetic solution, a concentrated NG stock solution in methanol (5% w:w) was used as source. In order to reduce interference from solvent, the NG solutions was prepared by evaporating 20 mL of NG methanol stock for 24 hours and then diluting up to 1 L with DI water. The solution was then mixed for 48 hours or until complete dissolution of NG. The solution was then further diluted to obtain levels of NG and derivatives compounds comparable to those found in the plant influent (Table 10).
Table 9. Concentration and bacterial count for each BGPs used in oxygen uptake tests.
* Dosage adjusted based on the consideration of additional elements (i.e., nutrients) per weight of product and lower CFU/g ^ Calculated ** MB2+MB8+M118 in equal amounts
Table 10. Composition of prepared NG stock solution in DI water used for the tests. *NG derivatives originally present in stock solution.
Along with the test bottles, two (2) sets of controls and a set of blanks were prepared for each BGPs and their mix in order to assess the viability of the bacteria population as well as offset for any contribution of trace solvents residuals to the oxygen uptake. The negative controls consisted of each BGPs without any external carbon source while the positive control consisted of BGPs plus glucose. The glucose control was prepared following a theoretical oxygen demand of 120 mg/L as recommended for BOD tests. For each sample, the test was performed in duplicate and for each batch of BOD tests, a glucose-glutamic standard was added as an additional sample in order to check the validity of the test.
Before and after the end of the incubation period, NG and deriving organic by products such as 1,2 dinitro glycerin (1,2-DNG) and 1,3 dinitro glycerin (1,3-DNG) were quantified using high-performance liquid chromatography (HPLC) (Agilent, Infinity Series, 1260). A Hypersil ODS
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other column reverse phase (RP) (Thermo Scientific) was used for the separation of NG and byproducts using a gradient mobile phase consisting of deionized water and acetonitrile at a flow rate of 1.0 mL/min and detector wavelength at 210 nm. Certified reference standards (1000 mg/L) in acetonitrile (Sigma Aldrich) were utilized for calibration of the analytical method for NG and respective byproducts.
Results Oxygen uptake in relation to organic load consumption was evaluated by measuring the dissolved oxygen (DO) concentrations in all samples, blanks, and controls before and after the established incubation period (i.e., 48 hours). Difference between the initial and final DO concentrations are reported in Figure 4; as expected, the negative controls showed minimal difference in the initial and final DO concentrations resulting in a non-significant oxygen uptake (i.e., ≤ 6% uptake). On the other hand, positive controls showed significant oxygen uptake (i.e., average 9.0 mg/L) which was consistent with viable bacteria population for each of the tested BGPs.
In addition to the positive controls, significant uptake was also observed in the solvent (methanol) blanks followed by an average uptake of 3.0 mg/L in the NG-containing samples; the higher uptake in the solvent blanks indicates that any solvent residue (although most likely insignificant) in the synthetic NG solution would not affect the activity of the BGPs.
Overall, the uptake in the NG containing samples could not compare with either blanks or positive control although a slight increase in uptake was observed for the mix matrix (MB2+MB8+M118) sample.
Figure 4. Oxygen uptake by BGPs (MB2, MB8, M118) in presence of NG and derivative compounds, methanol blank and controls; Uptake time period: 48 hours; Mix= MB2+MB8+M118. Error bars represent standard deviations from two replicates.
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
The low oxygen uptake in the BGPs-NG samples was consistent with the minimal NG removal observed at the end of the incubation period (Figure 5a). In fact, across all samples tested, the NG removal averaged only to about 10%; in addition, the removal could not be attributed to degradation or decomposition of the main glycerin chain but most likely to denitration mechanisms resulting in transformation of the NG to DNGs compounds. Such hypothesis can be further supported by increases in the DNGs concentrations observed in some BGPs samples at the end of the incubation period (Figure 5c).
The low NG removal and oxygen uptake in the tested BGPs samples overall suggests that such bacteria consortiums will not play key role in degradation of NG and parent compounds in the Bioplant influent; however, efficacy of the same in degradation of other COD contributing sources (i.e., solvents) shall not be considered equally insignificant based on the results of these tests.
Figure 5. (a) NG, (b) 1, 2DNG and (c) 1,3 DNG concentrations at t= 0 and t= 48 h in BGPs samples (MB2, MB8, M118) oxygen uptake tests; Mix= MB2+MB8+M118. Error bars represent standard deviations from two replicates.
Evalua�on of Bioaugmenta�on products (BGPs) for RFAAP Bioplant: microbial iden�fica�on using next genera�on sequencing (NGS) technology Introduction As previously stated, listed BGPs in Table 8 and shown in Figure 6, are currently used at the RFAAP Bioplant to improve and support the performance of the plant’s biological processes (i.e., RBC) for degrada�on of COD loads. As such, the products are also thought to support degrada�on of residual NG and deriva�ve compounds (i.e., DNGs, MNGs) in the plant influent. In order to evaluate the extent of such performance and verify the claim, the team at Stevens designed and performed a series of qualita�ve oxygen (O2) uptake tests based on the established methodology for BOD5 assessment as described in the previous sec�on. In addi�on, next genera�on sequencing technology was performed for each of the samples for iden�fica�on purposes.
(a) (b) (c) (a)
Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other
Figure 6. Appearance of bioaugmenta�on products received and analyzed by CES-SIT.
Methodology Each BGP was activated by following standard procedure outlined for activation of the Polyseed® in BOD tests, and as previously described in functional analysis performed for the same BGP (i.e., mix fixed amount of product in 1 L of oxygen saturated dilution water for 1 hour, settle 30 minutes, decant, use supernatant as needed within 3 hours). After activation of the samples, the biomass was centrifuged at 3500 rpm, and the pellets were frozen until further analysis. DNA extraction and sequencing using high-throughput next generation sequencing (NGS) was performed by an external laboratory (Omega Bioservices, Norcross, GA). Shotgun metagenomic sequencing was chosen to sequence these complex microbial samples to gain insight into their microbial community biodiversity and function. In addition, this method allows culture-free identification and classification of complex microbial communities. The Ribosomal database project (RDP) was used within the Basespace app for identification of the sequences obtained.
Results As stated before, these commercial products are used in the RFAAP Facility for aiding the degradation of residual NG and byproducts in the plant influent together with increasing the efficacy of BOD removal. According to the data sheet of MB-2 commercial product, a highly specialized blend of bacteria that could potentially remove BOD, COD, TOC, phenol, chlorinated hydrocarbons, aromatic and aliphatic hydrocarbons meta and ortho chlorinated phenols, propylene dichloride, styrene, formaldehyde, and alcohols. While MicroSolv 118 contains a specially formulated blend of microorganisms, micro/macro nutrients, fungi, and surface tension suppressants/penetrants, developed for pulp & paper wastewater applications where there are heavy influxes of cellulosic fibrous organic solids.
Microbial composition results obtained from sequencing and analysis are presented in figures 7, 8 and 9 for MB-2, MB-8 and Microsolv 118, respectively. The lowest taxonomy division was achieved, corresponding to genus and species. Overall, the main genus and species identified were similar for the three products. Figure 7 shows that the species identified in this MB-2 blend are Ralstonia sp. MD27 (30%), Comamonas sp.Z1 (10 %), Bacillus spp. (accounting for 14 %), Distribu�on Statement D: Distribu�on authorized to Department of Defense and U.S. DoD contractors only. Other several species of genus Pseudomona (spp.) (representing 15 %) and genus Citrobacter (18 %).
Figure 8 shows that the species identified in this MB-8 blend are Ralstonia sp. MD27 (17 %), Comamonas sp. Z1 (12 %), Bacillus spp. (3 %), Pseudomonas spp.
This is the start of the file's text. The full file is on GovTribe.