Responses to Questions_Rpr DFAC HVAC.pdf
PDF 50 KB Posted
- Attached to
- Repair B300 DFAC HVAC Federal contract opportunity
- Solicitation number
- W50S91-22-Q-0013
- Issued by
- Department of the Army National Guard
About this file
This document contains a federal solicitation for repair work to the HVAC system at a dining facility on an Army National Guard base. The solicitation will result in a firm fixed price contract award for repair of the DFAC HVAC, including furnishing and installing all labor and materials required by the statement of work. Interested vendors must respond by April 13, 2022 and the period of performance is 180 days from notice to proceed. The requirement is set aside 100% for small businesses with a NAICS code of 238220 and size standard of $16.5 million. A site visit will be held on April 1st and all questions must be submitted by April 6th. The selected contractor will be responsible for coordinating any required subcontracting or verification of the HVAC system integration with the existing Siemens controls system.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Responses to Questions_Rpr DFAC HVAC_Amendment 4.pdf | ||
| W50S91-22-Q-0013_Rpr DFAC HVAC_Amendment 4.pdf | ||
| W50S91-22-Q-0013_Rpr DFAC HVAC_Amendment 3.pdf | ||
| Attachment 1_SOW_JLSQ222003_Repair_B300_DFAC_HVAC_Rev 1.pdf | ||
| W50S91-22-Q-0013_Rpr DFAC HVAC_Amendment 2.pdf | ||
| W50S91-22-Q-0013_Rpr DFAC HVAC_Amendment 1.pdf | ||
| W50S91-22-Q-0013_Rpr DFAC HVAC_Solicitation.pdf | ||
| Attachment 2_Wage Determination.pdf | ||
| Attachment 1_SOW_JLSQ222003_Repair_B300_DFAC_HVAC_Final.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Responses to Questions (Q&A), 10 May 2022, RFQ: W50S91-22-Q-0013
Q1 – Due to the extent of the requested sheet-metal duct(s) and insulation replacement work, we respectfully request another site visit prior to bid due date to have a sheet-metal and insulator subcontractor review the work. Is this acceptable?
A1 – Yes
Q2 - Per section 3.3.9 page 5 (Statement of Work) Seal Class A – is defined as Static Pressure of
4.0 inches or more. (SMACNA HVAC Duct Construction Standards) All traverse joints, longitudinal seams and duct wall penetrations. What are the static pressures of the existing unit(s)? The small make-up air unit model number lists the unit as a standard blower assembly (5 H.P.) not listed as a (high CFM) drive. The large RTU-1 unit model number lists the unit as equipped with a 525 RPM 10 H.P. fan motor that is not listed as a (High CFM) drive.
A2 – The Seal Class A requirement has been removed from the SOW. The government has included HVAC drawings in Attachment III as supplemental information and has changed the SOW accordingly. See revised SOW, see paragraph 3.3.9, 3.3.9.1 and 3.3.9.2.
Q3 - Fabricate outdoor air intake ducts and plenums with watertight soldered or brazed joints and seams. Are there any other duct sealing practices acceptable that meet Seal Class A requirements other than soldered or brazed joints?
A3 – This requirement has been removed from the SOW. The government has included HVAC drawings in Attachment III as supplemental information and has changed the SOW accordingly.
See revised SOW, see paragraph 3.3.9.
Q4 - Do we need permit for our Company furnished Crane at your facility? Will Air Traffic Control Tower need to be notified?
A4 – The Government COR will submit the FAA request and will provide you the contact information to notify the tower when the crane is in operation and when the crane work is done.
The contractor will need to supply the government information such as the type of crane, boom height, requested dates and times of crane operation, and crane position.
Q5 - Are we responsible for subcontracting Siemens to verify programming of the DDC connection points upon completion of work or is this the responsibility of ARW?
A5 – It is the contractor’s responsibility to determine the best method to connect and verify that the new HVAC systems works with the current Siemens DDC system. Subcontracting Siemens is not a requirement of this SOW nor the responsibility of the government.