Bldg 1052 MSDT Drawings.pdf
PDF 6 MB Posted
- Attached to
- 137th SOW Mini-Split Air Conditioning for MSDT
- Solicitation number
- W50S8T26QA021
- Issued by
-
Department of the Army National Guard
About this file
This is a set of architectural and mechanical construction drawings for a mini-split HVAC installation project at Will Rogers Air National Guard Base, Building 1052, for the 17th FTU Squadron.
The project involves installing two 2.5-ton mini-split air conditioning units in a Multi-Service Dining Facility (MSDT) training space. The scope of work includes installation of proposed refrigerate line sets and condensate lines, relocation of existing disconnect/condenser units to new proposed locations, and concealment of mechanical and electrical lines through furring out existing walls. The installation affects the main training area (137), men's lockers (138), women's locker (141), and related spaces. Mechanical notes specify compliance with SMACNA HVAC duct construction standards, requirement for radius elbows on all duct off-sets, manual balancing dampers in branch ducts, and coordination with electrical systems. The contractor must conduct final start-up supervised by a factory-authorized technician and maintain HVAC filters throughout construction, replacing all filters one week before facility occupancy. The project contact is Johnny Tong at 405-686-5003 (johnny.tong@us.af.mil). The drawings include site plans, MSDT layout, reflected ceiling plan, detail drawings, mechanical installation plans, mechanical notes, and electrical panel location specifications across sheets G-100 through E-101.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Solicitation - W50S8T26QA021 137th Mini Splits.pdf | ||
| Solicitation - W50S8T26QA021 137th Mini Splits.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1052 MDST MINI SPLIT
YZEU 262005
INDEX OF SHEETS
WILL ROGERS AIR NATIONAL GUARD BASE
1052 MDST MINI SPLIT
YZEU 262005
WILL ROGERS AIR NATIONAL GUARD BASE
DESCRIPTIONBYNO. DATE
REVISIONS
Phone:
Contact:
Email:
B1052 MSDT MINI SPLIT INSTALLATION
G-100
COVER SHEET
JOHNNY.TONG@US.AF.MIL
405-686-5003
JOHNNY TONG
PROJECT LOCATION
G-101 G-102 A-101
M-101 M-102 M-103
SITE PLAN
MSDT LAYOUT PLAN
REFLECTED CEILING PLAN
EXISTING MECHANICAL PLAN
NEW MECHANICAL INSTALLATION
MECHANICAL NOTES
E-101 ELECTRICAL PANEL PLAN
A-102 DETAIL DRAWING PLAN
A-103 DETAIL FUR OUT DRAWING PLAN
SCOPE OF WORK
NOT IN
SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
NOT IN
SCOPE
SCOPE OF WORK
DESCRIPTIONBYNO. DATE
REVISIONS
Phone:
Contact:
Email:
B1052 MSDT MINI SPLIT INSTALLATION
G-101
SITE PLAN
JOHNNY.TONG@US.AF.MIL
405-686-5003
JOHNNY TONG
AutoCAD SHX Text Building 1052 17TH FTU SQUADRON
DESCRIPTIONBYNO. DATE
REVISIONS
Phone:
Contact:
Email:
B1052 MSDT MINI SPLIT INSTALLATION
G-102
MSDT LAYOUT
JOHNNY.TONG@US.AF.MIL
405-686-5003
JOHNNY TONG
AutoCAD SHX Text
MEN'S LOCKERS
AutoCAD SHX Text
INSTRUCTOR DESK
AutoCAD SHX Text 3'
AutoCAD SHX Text 1'-6"
AutoCAD SHX Text
MSDT'S
MSDT
OC OC
OC OC
OC
9' - 0" A.F.F.
9-04
KEYED NOTES
DESCRIPTIONBYNO. DATE
REVISIONS
Phone:
Contact:
Email:
B1052 MSDT MINI SPLIT INSTALLATION
A-101
REFLECTED CEILING PLAN
JOHNNY.TONG@US.AF.MIL
405-686-5003
JOHNNY TONG
AutoCAD SHX Text
MOVE LIGHT PANELS AS NEEDED.
AutoCAD SHX Text
IF NEEDED, REINSTALL PANELS TO ANOTHER LOCATION WITH NOTIFICATION/APPROVAL
SHOWN IS REFLECTING CEILING PLAN, NOT ALL DEVICES AND SPRINKLERS ARE SHOWN
EXISTING MECHANICAL /
ELECTRIC LINES
NEW INSTALLED
MECHANICAL / ELECTRIC
LINES IN THIS AREA
DESCRIPTIONBYNO. DATE
REVISIONS
Phone:
Contact:
Email:
B1052 MSDT MINI SPLIT INSTALLATION
A-102
DETAIL DRAWING PLAN
JOHNNY.TONG@US.AF.MIL
405-686-5003
JOHNNY TONG
LENGTH TO VARY TO
ACCOMMODATE ALL
LINES TO BE HIDDEN
M
ATCH
EXISTING W
IDTH
KEYED NOTES
DESCRIPTIONBYNO. DATE
REVISIONS
Phone:
Contact:
Email:
B1052 MSDT MINI SPLIT INSTALLATION
A-103
DETAIL FUR OUT DRAWING PLAN
JOHNNY.TONG@US.AF.MIL
405-686-5003
JOHNNY TONG
FUR OUT WALL TO HIDE THE EXISTING AND NEW PIPE / LINES.
T
T
T
U
V
W
X
Y
Z
S
WOMEN'S
LOCKER
TRAINING
MEN'S
LOCKERS
CORRIDOR
136BRIEFING
SM 4
131B
BRIEFING
LG 1
131A
SB
SB
SA
RB
M2
M2
SC
SC
SC
SC
250 SC
SC
SC
SC
SB
x1
RA
SD
EA
EA 165
EA
EA
EA
EA
FPVAV-9
FPVAV-3
DESCRIPTIONBYNO. DATE
REVISIONS
Phone:
Contact:
Email:
B1052 MSDT MINI SPLIT INSTALLATION
M-101
EXISTING MECHANICAL PLAN
JOHNNY.TONG@US.AF.MIL
TSA
x1
SDEA
FPVAV-9
PROPOSED
REFRIGERATE LINE SET
PROPOSED
CONDENSATE LINES
EXISTING DISCONNECT/CONDENSER
NEW PROPOSED LOCATION
DISCONNECT/CONDENSER
2.5 TON MINI SPLIT
2.5 TON MINI SPLIT
DESCRIPTIONBYNO. DATE
REVISIONS
Phone:
Contact:
Email:
B1052 MSDT MINI SPLIT INSTALLATION
M-102
NEW MECHANICAL INSTALLATION
JOHNNY.TONG@US.AF.MIL
405-686-5003
JOHNNY TONG
AutoCAD SHX Text 8'
AutoCAD SHX Text
SCALE: 3/32"=1'-0"
AutoCAD SHX Text
AutoCAD SHX Text 8'
4'
1. ALL DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE
GENERAL ARRANGEMENTS OR GEOMETRICAL RELATIONSHIPS
OF DUCTWORK, PIPING, AND EQUIPMENT. DO NOT SCALE
DRAWINGS. THE EXACT LOCATION AND ROUTING OF
EQUIPMENT DUCTWORK PIPING ETC. UNLESS SPECIFICALLY
DIMENSIONED ON THE DRAWINGS, SHALL BE DETERMINED IN
THE FIELD. THEY ARE NOT INTENDED TO SPECIFY OR SHOW
EVERY OFFSET, SEQUENCE, DEVICE, OPTION, FITTING, OR
COMPONENT. MAKE REASONABLE MODIFICATIONS IN THE
INSTALLATION SO ALL DUCTWORK AND PIPING FITS PROPERLY
AND EQUIPMENT CAN BE SERVICED.
2. MATERIALS AND EQUIPMENT SHALL BE NEW AND INSTALLED
AS INDICATED ON THE DRAWINGS AND/OR SPECIFICATIONS.
THEY SHALL BE INSTALLED PLUMB LEVEL AND TRUE-TO-LINE
WITH ADJACENT WORK WHERE INSTALLATION METHODS ARE
NOT SPECIFICALLY COVERED BY THE DRAWINGS AND/OR
SPECIFICATIONS, FIRST CLASS TRADE PRACTICES AND
MANUFACTURER’S INSTRUCTIONS AND RECOMMENDATIONS
SHALL GOVERN.
3. CAREFULLY EXAMINE ALL ARCHITECTURAL, STRUCTURAL,
PLUMBING, HVAC, FIRE PROTECTION, AND ELECTRICAL
DRAWINGS PERTAINING TO CONSTRUCTION PRIOR TO BID.
COOPERATE WITH OTHER TRADES IN LOCATING DUCTWORK,
PIPING, EQUIPMENT, ETC. IN ORDER TO AVOID CONFLICT WITH
OTHER TRADE’S WORK. NO CLAIM FOR COSTS WILL BE
ALLOWED FOR RELOCATING EQUIPMENT, PIPING, DUCTWORK,
ETC. WHICH INTERFERES WITH OTHER TRADE’S WORK.
4. HVAC EQUIPMENT, DUCTS AND INSTALLATION SHALL COMPLY
WITH THE REQUIREMENTS OF ALL AUTHORITIES HAVING
JURISDICTION, BUILDING DEPARTMENTS, APPLICABLE TO THE
LATEST EDITION OF THE APPROVED BUILDING CODES,
APPLICABLE OSHA AND NFPA STANDARDS, COUNTRY AND CITY
BUILDING REGULATIONS AND CODES.
5. FABRICATION AND INSTALLATION OF DUCTWORK SHALL BE IN
ACCORDANCE WITH SMACNA HVAC DUCT CONSTRUCTION
STANDARDS, STATE MECHANICAL CODE AND APPLICABLE
NFPA STANDARDS.
6. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
7. PROVIDE AIR TURNING VANES IN ALL SQUARE ELBOWS IN ALL
SYSTEM TYPES, EXHAUST, SUPPLY AND RETURN.
8. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF
EQUIPMENT.
9. PERSONNEL SHALL BE THOROUGHLY TRAINED AND
EXPERIENCED IN THE PRODUCTS INVOLVED AND
RECOMMENDED METHODS FOR THEIR FABRICATION AND
INSTALLATION SHALL BE MADE FOR LACK OF SKILL ON THE
PARK OF THE WORKMAN IN THE ACCEPTANCE AND/OR
REJECTION OF COMPLETED WORK.
10. MECHANICAL CONTRACTOR SHALL FURNISH ALL LABOR,
MATERIAL, TOOLS, AND EQUIPMENT TO INSTALL ALL HVAC
SYSTEMS AS INDICATED ON THESE DRAWINGS.
11. INFORMATION AND COMPONENTS SHOWN ON RISER
DIAGRAMS OR DETAILS, BUT NOT SHOWN ON PLANS, AND VICE
VERSA, SHALL BE PROVIDED AS IF EXPRESSLY REQUIRED BY
BOTH.
12. MECHANICAL CONTRACTOR SHALL ARRANGE AND PAY FOR
MECHANICAL PERMITS AND INSPECTIONS AS REQUIRED BY
LOCAL ORDINANCES.
13. DELIVER MATERIALS TO PROJECT IN GOOD CONDITION. STORE
MATERIALS OFF OF GROUND AND PROTECT FROM WEATHER
AND THE ELEMENTS.
14. VERIFY DIMENSIONS IN THE FIELD. VERIFY STRUCTURAL
DETAILS BEFORE INSTALLING DUCTWORK. NO EXTRA
COMPENSATION WILL BE CONSIDERED BECAUSE OF
DIFFERENCED BETWEEN ACTUAL MEASURED DIMENSIONS AND
THOSE INDICATED ON THE DRAWINGS.
15. ALL PENETRATIONS THROUGH WALLS SHALL BE PROVIDED
WITH PROPERLY SIZED SLEEVES. SEAL ALL PIPE SLEEVES
WITH APPROPRIATE CAULKING. ALL PENETRATIONS THROUGH
FIRE RATED WALLS AND/OR FLOORS SHALL BE INSTALLED IN
ACCORDANCE WITH APPROPRIATE 3M FIRE STOP SYSTEM (OR
APPROVED EQUAL). ALL PIPING SLEEVES SHALL BE SCHEDULE
40, CARBON STEEL ASTM A53, GRADE B.
16. ANY CUTTING OR PATCHING OF NEW OR EXISTING SURFACES
THAT IS REQUIRED SHALL BE BY THIS CONTRACTOR AND
SHALL BE REPLACED WITH MATERIAL OF THE SAME QUALITY
AND THICKNESS AS THE EXISTING SURFACE. ANY DAMAGES
TO EXISTING MATERIALS SHALL BE REPAIRED OR REPLACED
TO MATCH EXISTING.
17. ALL DUCTWORK SHALL BE IDENTIFIED AFTER INSULATION
WITH PLASTIC DUCT SIGNAGE/MARKERS. THESE MARKERS
SHALL BE MANUFACTURER’S STANDARD LAMINATED PLASTIC
IN THE FOLLOWING COLOR CODES INDICATING BACKGROUND
COLOR THEN LETTER COLOR: A. BLUE/ WHITE: SUPPLY AIR B.
RED/ WHITE: RETURN AIR C. GREEN/ WHITE: OUTSIDE AIR/
INTAKE AIR D. YELLOW/ BLACK: RELIEF AIR/ EXHAUST AIR.
18. ENGAGE AN INDEPENDENT TESTING, ADJUSTING AND
BALANCING (TAB) AGENT CERTIFIED BY EITHER AABC OR NEBB
FOR ALL TESTING, ADJUSTING AND BALANCING. SEE THE TAB
SPECIFICATION FOR MORE INFORMATION.
19. THERMOSTATS/HUMIDISTATS/CO2 SENSORS SHALL BE
LOCATED AS PER PLANS 48 INCHES ABOVE FINISHED FLOOR.
ANY THERMOSTAT THAT IS REQUIRED TO EB MOUNTED ON AN
EXTERIOR WALL MUST BE MOUNTED ON AN INSULATED BASE.
INSTALL WIRING IN CONDUIT PROVIDED BY DIVISION 26. AT A
MINIMUM, PROVIDE CONDUIT IN THE WALL FROM THE
JUNCTION BOX TO 6”ABOVE THE CEILING.
MECHANICAL GENERAL NOTES
20. MECHANICAL CONTRACTOR SHALL HAVE THE FINAL START-UP
OR ALL HVAC EQUIPMENT SUPERVISED AND MONITORED BY A
FACTOR AUTHORIZED TECHNICIAN.
21. HOUSEKEEPING PADS: EXCEPT WHERE STRUCTURAL
EQUIPMENT SUPPORT PADS ARE CALLED FOR ON THE PLANS,
PROVIDE CONCRETE HOUSEKEEPING PADS FOR ALL GROUND
AND/OR FLOOR MOUNTED EQUIPMENT. UNLESS OTHERWISE
INDICATED, PADS MUST BE MINIMUM OF 6 INCHES THICK WITH
CHAMFERED EDGES. WHERE PADS ARE INSTALLED ON
CONCRETE FLOORS, DOWEL RODS PENETRATING INTO BOUT
THE PAD AND THE FLOOR (MINIMUM 4 RODS PER PAD) MUST
BE USED TO ANCHOR PADS IN POSITION.
22. ALL WIRING INSTALLED FOR CONTROLS, POWER, INTERLOCKS,
ETC WHICH ARE TO BE INSTALLED IN OCCUPIED SPACES OR IN
RETURN PLENUMS MUST BE PLENUM RATED OR INSTALLED IN
CONDUIT UNLESS OTHERWISE INDICATED. ALL SUCH
INSTALLATIONS MUST MEET NFPA AND NEC REQUIREMENTS
AND LOCAL CODES.
23. SEAL ALL ROOF AND WALL PENETRATIONS. FLASH AND
COUNTER-FLASH ALL ROOF PENETRATIONS. MINIMUM
ACCEPTABLE HEIGHT OF FLASHING IS EIGHT (8) INCHES ABOVE
ROOF.
24. MAINTAIN A MINIMUM OF 15’-0”BETWEEN ALL FRESH AIR
INTAKES AND PLUMBING VENTS, EXHAUST FAN DISCHARGE
FLUE, ETC. COORDINATE WITH ALL OTHER CONTRACTORS ON
SITE.
25. EXTERIOR DUCTWORK EXPOSED TO WEATHER: CROWN TOP
SURFACE FOR WATER RUNOFF AND COMPLETELY SEAL ALL
JOINTS WITH UV RESISTANT WEATHERPROOF SEALANT.
26. DURING CONSTRUCTION, AFTER START-UP OF HVAC
SYSTEMS, CONTRACTOR MUST MAINTAIN AND/OR REPLACE ON
A REGULAR SCHEDULE ALL FILTERS IN THE HVAC SYSTEM. ON
(1) WEEK BEFORE THE FACILITY IS OCCUPIED, THE
CONTRACTOR MUST REPLACE ALL AIR FILTERS WITH NEW
FILTERS. DO NOT OPERATE HVAC SYSTEMS WITHOUT FILTER.
27. INDOOR AIR QUALITY MEASURERS: PROTECT INSIDE OF
(INSTALLED AND DELIVERED) DUCTWORK AND HVAC UNITS
FROM EXPOSURE TO DUST, DIRT, PAINT, AND MOISTURE.
REPLACE INSULATION THAT HAS GOTTEN WET AT ANY TIME
DURING CONSTRUCTION, DRYING THE INSULATION IS NOT
ACCEPTABLE. SEAL ANY TEARS OR JOINTS OF INTERNAL
FIBERGLASS INSULATION. REMOVE DEBRIS FROM
CEILING/RETURN AIR PLENUM INCLUDING DUST.
28. COORDINATE LOCATION OF ROOF MOUNTED HVAC
EQUIPMENT AND ROOF PENETRATIONS WITH THE
ARCHITECTURAL AND STRUCTURAL DRAWINGS.
29. INSTALL DUCTWORK AND PIPING PARALLEL TO BUILDING
COLUMN LINES UNLESS OTHERWISE SHOWN OR NOTED.
30. COORDINATE LOCATION OF EQUIPMENT SUPPORTS WITH
LOCATION OF EQUIPMENT ACCESS PANELS/DOORS TO ENABLE
SERVICE OF EQUIPMENT AND/OR FILTER REPLACEMENT.
31. PROVIDE WALL OR DUCT ACCESS PANELS OR DOOR FOR
ACCESS TO FIRE AND FIRE/SMOKE DAMPERS. ACCESS PANEL
OR DOOR SHALL BE MINIMUM SIZE OF 10”X10”AND SHALL BE
INSTALLED WITHIN 12”OF DAMPER. PROVIDE A REMOVABLE
DUCT SECTION WHERE DUCT SIZE IS TOO SMALL FOR A 10”X10”
ACCESS DOOR.
32. PROVIDE A MANUAL BALANCING DAMPER IN EACH BRANCH
DUCT TAKEOFF FROM MAIN SUPPLY, RETURN, OUTDOOR AND
EXHAUST AIR DUCTS.
33. PROVIDE A PREFABRICATED 45 DEGREE, HIGH EFFICIENCY,
RECTANGULAR/ROUND BRANCH DUCT TAKE-OFF FITTING WITH
MANUAL BALANCING DAMPER AND LOCKING QUADRANT FOR
BRANCH DUCT CONNECTIONS AND TAKE-OFFS TO INDIVIDUAL
DIFFUSERS, REGISTERS AND GRILLES.
34. BRANCH DUCTWORK TO AIR OUTLETS SHALL BE SAME SIZE AS
OUTLET NECK SIZE UNLESS OTHERWISE INDICATED.
35. FLEXIBLE DUCTWORK SHALL NOT EXCEED 5’-0”IN LENGTH AND
SHALL BE INSTALLED AND SUPPORTED TO AVOID SHARP
BENDS AND SAGGING. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS.
36. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT
LOCATION OF ALL CEILING MOUNTED AIR DEVICES.
37. MECHANICAL CONTRACTOR SHALL SUPPLY SMOKE DETECTOR
IN RETURN DUCT OF AIR HANDLERS OVER 2000 CFM AND FOR
UNITS WHICH SERVE AREAS OF EGRESS FOR INSTALLATION BY
ELECTRICAL CONTRACTOR. DETECTORS SHALL BE MOUNTED,
PHOTOELECTRIC TYPE COMPATIBLE WITH EXISTING FIRE
ALARM SYSTEM WITH INTEGRAL RELAY FOR SHUTDOWN OF
UNIT UPON ACTIVATION OF DETECTOR.
38. ALL DUCT OFF-SETS ARE TO BE MADE WITH RADIUS ELBOWS.
39. PROVIDE TRANSITIONS FOR ALL EQUIPMENT CONNECTIONS.
40. THE CONTRACTOR SHALL COORDINATE AND VERIFY THE
FOLLOWING DIVISIONS 23 AND 26 PRIOR TO BID:
DISCONNECTS:
WHERE NOT FURNISHED WITH EQUIPMENT: FURNISHED UNDER
DIVISION 26, INSTALLED UNDER DIVISION 26. WHERE
FURNISHED WITH EQUIPMENT: FURNISHED UNDER DIVISION 23,
INSTALLED UNDER DIVISION 26.
1. THIS DRAWING DIAGRAMMATICALLY REPRESENTS THE LAYOUT
OF EXISTING CONDITIONS WITH MAJOR MECHANICAL AND
ELECTRICAL COMPONENTS. THEY ARE NOT INTENDED TO
SHOW ACCESSORIES OR INCIDENTALS COMMON TO
EQUIPMENT INDICATED. THROUGH THESE ITEMS ARE TO BE
REMOVED, ACCESSIBILITY TO DEMOLITION ITEMS SHALL NOT
BE INFERRED. THE CONTRACTOR SHALL BE RESPONSIBLE
FOR FIELD VERIFICATION OF BUILDING AND EXISTING
CONDITIONS, PRIOR TO BID SUBMISSION.
2. DEMOLITION SHALL INCLUDE ALL HANGERS, FITTINGS,
DAMPERS, VALVES, ETC.
3. REPAIR ANY INSULATION DAMAGED DURING REMOVAL. REPAIR
WORK TO BE SAME AS NEW.
4. COORDINATE WALL AND FLOOR PATCHING REQUIREMENTS
WITH THE GENERAL CONTRACTOR. PATCHWORK SHALL
MATCH MATERIALS, FINISH AND TEXTURE OF ADJACENT
SURFACES. REFERENCE ARCHITECTURAL PLANS.
5. CONTRACTOR SHALL PATCH/REPAIR ALL UNUSED OPENINGS
AND MODIFIED FINISH SURFACES. PATCH SHALL MATCH
MATERIALS, FINISH AND TEXTURE AND ADJACENT SURFACES.
6. OWNER SHALL RETAIN FIRST SALVAGE RIGHTS TO ALL
REMOVED EQUIPMENT AND MATERIALS. UNLESS NOTED
OTHERWISE, CONTRACTOR SHALL BE RESPONSIBLE FOR
PROPER AND TIMELY DISPOSAL OF ALL CONSTRUCTION
DEBRIS INCLUDING BUT NOT LIMITED TO EQUIPMENT AND
MATERIALS NOT CLAIMED BY OWNER TO AN EPA APPROVED,
ENVIRONMENTALLY RESPONSIBLE, RECYCLE FACILITY OR
LANDFILL.
7. IT IS ESSENTIAL TO MINIMIZE DISRUPTIONS. COORDINATE ALL
DEMOLITION WITH OWNER, GENERAL CONTRACTOR OR
CONSTRUCTION MANAGER BEFORE SHUTTING DOWN ANY
UTILITY OR SIMILAR SYSTEM. SHUTDOWNS FOR UTILITIES OR
SIMILAR SYSTEMS SHALL BE REQUESTED WELL IN ADVANCE
AND PRE-APPROVED BY THE PROPER AUTHORITY (S) HAVING
JURISDICTION BEFORE BEGINNING WORK.
8. ALL WORK WITHIN THE CONTRACT DOCUMENTS, WHICH
INCLUDE THIS DRAWING, SHALL BE COMPLETED IN A SAFE
WORKMANLIKE MANNER AND IN ACCORDANCE WITH ALL
APPLICABLE STATE, LOCAL AND NATIONAL CODES,
REGULATIONS AND ORDINANCES. IF ANY CONFLICTS ARISE
BETWEEN THE CONTRACT DOCUMENTS AND THE APPLICABLE
CODE, REGULATIONS OR ORDINANCE, THE CONTRACTOR
SHALL BE RESPONSIBLE TO HAVE ALL WORK CONFORM TO
THE STRICTER OF SAID REQUIREMENTS.
9. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL
PERMITS AND INSPECTIONS AS REQUIRED FOR ELECTRICAL,
FIRE PROTECTION, PLUMBING, MECHANICAL AND BACKFLOW
PREVENTION INSTALLATIONS. IT SHALL BE THE
CONTRACTOR’S RESPONSIBILITY TO PROVIDE BOTH A
COMPLETE AND COMPLIANT INSTALLATION AS MAY BE
DETERMINED BY THE AUTHORITY (S) HAVING JURISDICTION.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE
WATERTIGHT AND WEATHER-PROOF INTEGRITY OF ROOFS,
WALLS AND FLOORS DURING CONSTRUCTION. EACH TRADE
SHALL LOCATE/DIMENSION/COORDINATE THEIR ROOF, FLOOR
AND WALL OPENINGS WITH THE GC OR CONSTRUCTION
MANAGER.
MECHANICAL DEMOLITION NOTES
(AFF, AFG, UNLESS NOTED OTHERWISE)
THERMOSTATS (USER ADJUSTABLE)(TOP OF DEVICE) 48"
CONTROLS (TOP OF DEVICE) 48"
STANDARD MOUNTING HEIGHTS
DESCRIPTIONBYNO. DATE
REVISIONS
Phone:
Contact:
Email:
B1052 MSDT MINI SPLIT INSTALLATION
M-103
MECHANICAL NOTES
JOHNNY.TONG@US.AF.MIL
TRAINING
MECHANICAL
COMM
CLOSET
130A
ELECTRICAL
BREAK
ROOM
MEETING
ROOM
130B
BRIEFING LG
L3
EWC
+80"
+80"
+80"
+80"
+80"
+80"
+72"
L1-37
KEYED NOTES
EXISTING DISCONNECT/CONDENSER
NEW PROPOSED LOCATION
DISCONNECT/CONDENSER
MOVE EXISTING OUTLET
OUT TO FINISHED WALL
DESCRIPTIONBYNO. DATE
REVISIONS
Phone:
Contact:
Email:
B1052 MSDT MINI SPLIT INSTALLATION
E-101
ELECTRICAL PANEL
JOHNNY.TONG@US.AF.MIL
405-686-5003
JOHNNY TONG
AutoCAD SHX Text
USE EXISTING PANEL L3
INSTALL NEW DISCONNECTS IN APPROPRIATE AREA SHOWN
| Sheets and Views |
| Bldg 1052 MSDT V1-COVER SHEET |
| Bldg 1052 MSDT V1-G-101 |
| Bldg 1052 MSDT V1-G-102 |
| Bldg 1052 MSDT V1-A-101 |
| Bldg 1052 MSDT V1-A-102 |
| Bldg 1052 MSDT V1-A-103 |
| Bldg 1052 MSDT V1-M-101 |
| Bldg 1052 MSDT V1-M-102 |
| Bldg 1052 MSDT V1-M-103 |
| Bldg 1052 MSDT V1-E-101 |