The project involves installing two 2.5-ton mini-split air conditioning units in a Multi-Service Dining Facility (MSDT) training space. The scope of work includes installation of proposed refrigerate line sets and condensate lines, relocation of existing disconnect/condenser units to new proposed locations, and concealment of mechanical and electrical lines through furring out existing walls. The installation affects the main training area (137), men's lockers (138), women's locker (141), and related spaces. Mechanical notes specify compliance with SMACNA HVAC duct construction standards, requirement for radius elbows on all duct off-sets, manual balancing dampers in branch ducts, and coordination with electrical systems. The contractor must conduct final start-up supervised by a factory-authorized technician and maintain HVAC filters throughout construction, replacing all filters one week before facility occupancy. The project contact is Johnny Tong at 405-686-5003 (johnny.tong@us.af.mil). The drawings include site plans, MSDT layout, reflected ceiling plan, detail drawings, mechanical installation plans, mechanical notes, and electrical panel location specifications across sheets G-100 through E-101.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1052 MDST MINI SPLIT

YZEU 262005

INDEX OF SHEETS

WILL ROGERS AIR NATIONAL GUARD BASE

1052 MDST MINI SPLIT

YZEU 262005

WILL ROGERS AIR NATIONAL GUARD BASE

DESCRIPTIONBYNO. DATE

REVISIONS

Phone:

Contact:

Email:

B1052 MSDT MINI SPLIT INSTALLATION

G-100

COVER SHEET

JOHNNY.TONG@US.AF.MIL

405-686-5003

JOHNNY TONG

PROJECT LOCATION

G-101 G-102 A-101

M-101 M-102 M-103

SITE PLAN

MSDT LAYOUT PLAN

REFLECTED CEILING PLAN

EXISTING MECHANICAL PLAN

NEW MECHANICAL INSTALLATION

MECHANICAL NOTES

E-101 ELECTRICAL PANEL PLAN

A-102 DETAIL DRAWING PLAN

A-103 DETAIL FUR OUT DRAWING PLAN

SCOPE OF WORK

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

SCOPE OF WORK

DESCRIPTIONBYNO. DATE

REVISIONS

Phone:

Contact:

Email:

B1052 MSDT MINI SPLIT INSTALLATION

G-101

SITE PLAN

JOHNNY.TONG@US.AF.MIL

405-686-5003

JOHNNY TONG

AutoCAD SHX Text Building 1052 17TH FTU SQUADRON

DESCRIPTIONBYNO. DATE

REVISIONS

Phone:

Contact:

Email:

B1052 MSDT MINI SPLIT INSTALLATION

G-102

MSDT LAYOUT

JOHNNY.TONG@US.AF.MIL

405-686-5003

JOHNNY TONG

AutoCAD SHX Text

MEN'S LOCKERS

AutoCAD SHX Text

INSTRUCTOR DESK

AutoCAD SHX Text 3'

AutoCAD SHX Text 1'-6"

AutoCAD SHX Text

MSDT'S

MSDT

OC OC

OC OC

OC

9' - 0" A.F.F.

9-04

KEYED NOTES

DESCRIPTIONBYNO. DATE

REVISIONS

Phone:

Contact:

Email:

B1052 MSDT MINI SPLIT INSTALLATION

A-101

REFLECTED CEILING PLAN

JOHNNY.TONG@US.AF.MIL

405-686-5003

JOHNNY TONG

AutoCAD SHX Text

MOVE LIGHT PANELS AS NEEDED.

AutoCAD SHX Text

IF NEEDED, REINSTALL PANELS TO ANOTHER LOCATION WITH NOTIFICATION/APPROVAL

SHOWN IS REFLECTING CEILING PLAN, NOT ALL DEVICES AND SPRINKLERS ARE SHOWN

EXISTING MECHANICAL /

ELECTRIC LINES

NEW INSTALLED

MECHANICAL / ELECTRIC

LINES IN THIS AREA

DESCRIPTIONBYNO. DATE

REVISIONS

Phone:

Contact:

Email:

B1052 MSDT MINI SPLIT INSTALLATION

A-102

DETAIL DRAWING PLAN

JOHNNY.TONG@US.AF.MIL

405-686-5003

JOHNNY TONG

LENGTH TO VARY TO

ACCOMMODATE ALL

LINES TO BE HIDDEN

M

ATCH

EXISTING W

IDTH

KEYED NOTES

DESCRIPTIONBYNO. DATE

REVISIONS

Phone:

Contact:

Email:

B1052 MSDT MINI SPLIT INSTALLATION

A-103

DETAIL FUR OUT DRAWING PLAN

JOHNNY.TONG@US.AF.MIL

405-686-5003

JOHNNY TONG

FUR OUT WALL TO HIDE THE EXISTING AND NEW PIPE / LINES.

T

T

T

U

V

W

X

Y

Z

S

WOMEN'S

LOCKER

TRAINING

MEN'S

LOCKERS

CORRIDOR

136BRIEFING

SM 4

131B

BRIEFING

LG 1

131A

SB

SB

SA

RB

M2

M2

SC

SC

SC

SC

250 SC

SC

SC

SC

SB

x1

RA

SD

EA

EA 165

EA

EA

EA

EA

FPVAV-9

FPVAV-3

DESCRIPTIONBYNO. DATE

REVISIONS

Phone:

Contact:

Email:

B1052 MSDT MINI SPLIT INSTALLATION

M-101

EXISTING MECHANICAL PLAN

JOHNNY.TONG@US.AF.MIL

TSA

x1

SDEA

FPVAV-9

PROPOSED

REFRIGERATE LINE SET

PROPOSED

CONDENSATE LINES

EXISTING DISCONNECT/CONDENSER

NEW PROPOSED LOCATION

DISCONNECT/CONDENSER

2.5 TON MINI SPLIT

2.5 TON MINI SPLIT

DESCRIPTIONBYNO. DATE

REVISIONS

Phone:

Contact:

Email:

B1052 MSDT MINI SPLIT INSTALLATION

M-102

NEW MECHANICAL INSTALLATION

JOHNNY.TONG@US.AF.MIL

405-686-5003

JOHNNY TONG

AutoCAD SHX Text 8'

AutoCAD SHX Text

SCALE: 3/32"=1'-0"

AutoCAD SHX Text

AutoCAD SHX Text 8'

4'

1. ALL DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE

GENERAL ARRANGEMENTS OR GEOMETRICAL RELATIONSHIPS

OF DUCTWORK, PIPING, AND EQUIPMENT. DO NOT SCALE

DRAWINGS. THE EXACT LOCATION AND ROUTING OF

EQUIPMENT DUCTWORK PIPING ETC. UNLESS SPECIFICALLY

DIMENSIONED ON THE DRAWINGS, SHALL BE DETERMINED IN

THE FIELD. THEY ARE NOT INTENDED TO SPECIFY OR SHOW

EVERY OFFSET, SEQUENCE, DEVICE, OPTION, FITTING, OR

COMPONENT. MAKE REASONABLE MODIFICATIONS IN THE

INSTALLATION SO ALL DUCTWORK AND PIPING FITS PROPERLY

AND EQUIPMENT CAN BE SERVICED.

2. MATERIALS AND EQUIPMENT SHALL BE NEW AND INSTALLED

AS INDICATED ON THE DRAWINGS AND/OR SPECIFICATIONS.

THEY SHALL BE INSTALLED PLUMB LEVEL AND TRUE-TO-LINE

WITH ADJACENT WORK WHERE INSTALLATION METHODS ARE

NOT SPECIFICALLY COVERED BY THE DRAWINGS AND/OR

SPECIFICATIONS, FIRST CLASS TRADE PRACTICES AND

MANUFACTURER’S INSTRUCTIONS AND RECOMMENDATIONS

SHALL GOVERN.

3. CAREFULLY EXAMINE ALL ARCHITECTURAL, STRUCTURAL,

PLUMBING, HVAC, FIRE PROTECTION, AND ELECTRICAL

DRAWINGS PERTAINING TO CONSTRUCTION PRIOR TO BID.

COOPERATE WITH OTHER TRADES IN LOCATING DUCTWORK,

PIPING, EQUIPMENT, ETC. IN ORDER TO AVOID CONFLICT WITH

OTHER TRADE’S WORK. NO CLAIM FOR COSTS WILL BE

ALLOWED FOR RELOCATING EQUIPMENT, PIPING, DUCTWORK,

ETC. WHICH INTERFERES WITH OTHER TRADE’S WORK.

4. HVAC EQUIPMENT, DUCTS AND INSTALLATION SHALL COMPLY

WITH THE REQUIREMENTS OF ALL AUTHORITIES HAVING

JURISDICTION, BUILDING DEPARTMENTS, APPLICABLE TO THE

LATEST EDITION OF THE APPROVED BUILDING CODES,

APPLICABLE OSHA AND NFPA STANDARDS, COUNTRY AND CITY

BUILDING REGULATIONS AND CODES.

5. FABRICATION AND INSTALLATION OF DUCTWORK SHALL BE IN

ACCORDANCE WITH SMACNA HVAC DUCT CONSTRUCTION

STANDARDS, STATE MECHANICAL CODE AND APPLICABLE

NFPA STANDARDS.

6. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.

7. PROVIDE AIR TURNING VANES IN ALL SQUARE ELBOWS IN ALL

SYSTEM TYPES, EXHAUST, SUPPLY AND RETURN.

8. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF

EQUIPMENT.

9. PERSONNEL SHALL BE THOROUGHLY TRAINED AND

EXPERIENCED IN THE PRODUCTS INVOLVED AND

RECOMMENDED METHODS FOR THEIR FABRICATION AND

INSTALLATION SHALL BE MADE FOR LACK OF SKILL ON THE

PARK OF THE WORKMAN IN THE ACCEPTANCE AND/OR

REJECTION OF COMPLETED WORK.

10. MECHANICAL CONTRACTOR SHALL FURNISH ALL LABOR,

MATERIAL, TOOLS, AND EQUIPMENT TO INSTALL ALL HVAC

SYSTEMS AS INDICATED ON THESE DRAWINGS.

11. INFORMATION AND COMPONENTS SHOWN ON RISER

DIAGRAMS OR DETAILS, BUT NOT SHOWN ON PLANS, AND VICE

VERSA, SHALL BE PROVIDED AS IF EXPRESSLY REQUIRED BY

BOTH.

12. MECHANICAL CONTRACTOR SHALL ARRANGE AND PAY FOR

MECHANICAL PERMITS AND INSPECTIONS AS REQUIRED BY

LOCAL ORDINANCES.

13. DELIVER MATERIALS TO PROJECT IN GOOD CONDITION. STORE

MATERIALS OFF OF GROUND AND PROTECT FROM WEATHER

AND THE ELEMENTS.

14. VERIFY DIMENSIONS IN THE FIELD. VERIFY STRUCTURAL

DETAILS BEFORE INSTALLING DUCTWORK. NO EXTRA

COMPENSATION WILL BE CONSIDERED BECAUSE OF

DIFFERENCED BETWEEN ACTUAL MEASURED DIMENSIONS AND

THOSE INDICATED ON THE DRAWINGS.

15. ALL PENETRATIONS THROUGH WALLS SHALL BE PROVIDED

WITH PROPERLY SIZED SLEEVES. SEAL ALL PIPE SLEEVES

WITH APPROPRIATE CAULKING. ALL PENETRATIONS THROUGH

FIRE RATED WALLS AND/OR FLOORS SHALL BE INSTALLED IN

ACCORDANCE WITH APPROPRIATE 3M FIRE STOP SYSTEM (OR

APPROVED EQUAL). ALL PIPING SLEEVES SHALL BE SCHEDULE

40, CARBON STEEL ASTM A53, GRADE B.

16. ANY CUTTING OR PATCHING OF NEW OR EXISTING SURFACES

THAT IS REQUIRED SHALL BE BY THIS CONTRACTOR AND

SHALL BE REPLACED WITH MATERIAL OF THE SAME QUALITY

AND THICKNESS AS THE EXISTING SURFACE. ANY DAMAGES

TO EXISTING MATERIALS SHALL BE REPAIRED OR REPLACED

TO MATCH EXISTING.

17. ALL DUCTWORK SHALL BE IDENTIFIED AFTER INSULATION

WITH PLASTIC DUCT SIGNAGE/MARKERS. THESE MARKERS

SHALL BE MANUFACTURER’S STANDARD LAMINATED PLASTIC

IN THE FOLLOWING COLOR CODES INDICATING BACKGROUND

COLOR THEN LETTER COLOR: A. BLUE/ WHITE: SUPPLY AIR B.

RED/ WHITE: RETURN AIR C. GREEN/ WHITE: OUTSIDE AIR/

INTAKE AIR D. YELLOW/ BLACK: RELIEF AIR/ EXHAUST AIR.

18. ENGAGE AN INDEPENDENT TESTING, ADJUSTING AND

BALANCING (TAB) AGENT CERTIFIED BY EITHER AABC OR NEBB

FOR ALL TESTING, ADJUSTING AND BALANCING. SEE THE TAB

SPECIFICATION FOR MORE INFORMATION.

19. THERMOSTATS/HUMIDISTATS/CO2 SENSORS SHALL BE

LOCATED AS PER PLANS 48 INCHES ABOVE FINISHED FLOOR.

ANY THERMOSTAT THAT IS REQUIRED TO EB MOUNTED ON AN

EXTERIOR WALL MUST BE MOUNTED ON AN INSULATED BASE.

INSTALL WIRING IN CONDUIT PROVIDED BY DIVISION 26. AT A

MINIMUM, PROVIDE CONDUIT IN THE WALL FROM THE

JUNCTION BOX TO 6”ABOVE THE CEILING.

MECHANICAL GENERAL NOTES

20. MECHANICAL CONTRACTOR SHALL HAVE THE FINAL START-UP

OR ALL HVAC EQUIPMENT SUPERVISED AND MONITORED BY A

FACTOR AUTHORIZED TECHNICIAN.

21. HOUSEKEEPING PADS: EXCEPT WHERE STRUCTURAL

EQUIPMENT SUPPORT PADS ARE CALLED FOR ON THE PLANS,

PROVIDE CONCRETE HOUSEKEEPING PADS FOR ALL GROUND

AND/OR FLOOR MOUNTED EQUIPMENT. UNLESS OTHERWISE

INDICATED, PADS MUST BE MINIMUM OF 6 INCHES THICK WITH

CHAMFERED EDGES. WHERE PADS ARE INSTALLED ON

CONCRETE FLOORS, DOWEL RODS PENETRATING INTO BOUT

THE PAD AND THE FLOOR (MINIMUM 4 RODS PER PAD) MUST

BE USED TO ANCHOR PADS IN POSITION.

22. ALL WIRING INSTALLED FOR CONTROLS, POWER, INTERLOCKS,

ETC WHICH ARE TO BE INSTALLED IN OCCUPIED SPACES OR IN

RETURN PLENUMS MUST BE PLENUM RATED OR INSTALLED IN

CONDUIT UNLESS OTHERWISE INDICATED. ALL SUCH

INSTALLATIONS MUST MEET NFPA AND NEC REQUIREMENTS

AND LOCAL CODES.

23. SEAL ALL ROOF AND WALL PENETRATIONS. FLASH AND

COUNTER-FLASH ALL ROOF PENETRATIONS. MINIMUM

ACCEPTABLE HEIGHT OF FLASHING IS EIGHT (8) INCHES ABOVE

ROOF.

24. MAINTAIN A MINIMUM OF 15’-0”BETWEEN ALL FRESH AIR

INTAKES AND PLUMBING VENTS, EXHAUST FAN DISCHARGE

FLUE, ETC. COORDINATE WITH ALL OTHER CONTRACTORS ON

SITE.

25. EXTERIOR DUCTWORK EXPOSED TO WEATHER: CROWN TOP

SURFACE FOR WATER RUNOFF AND COMPLETELY SEAL ALL

JOINTS WITH UV RESISTANT WEATHERPROOF SEALANT.

26. DURING CONSTRUCTION, AFTER START-UP OF HVAC

SYSTEMS, CONTRACTOR MUST MAINTAIN AND/OR REPLACE ON

A REGULAR SCHEDULE ALL FILTERS IN THE HVAC SYSTEM. ON

(1) WEEK BEFORE THE FACILITY IS OCCUPIED, THE

CONTRACTOR MUST REPLACE ALL AIR FILTERS WITH NEW

FILTERS. DO NOT OPERATE HVAC SYSTEMS WITHOUT FILTER.

27. INDOOR AIR QUALITY MEASURERS: PROTECT INSIDE OF

(INSTALLED AND DELIVERED) DUCTWORK AND HVAC UNITS

FROM EXPOSURE TO DUST, DIRT, PAINT, AND MOISTURE.

REPLACE INSULATION THAT HAS GOTTEN WET AT ANY TIME

DURING CONSTRUCTION, DRYING THE INSULATION IS NOT

ACCEPTABLE. SEAL ANY TEARS OR JOINTS OF INTERNAL

FIBERGLASS INSULATION. REMOVE DEBRIS FROM

CEILING/RETURN AIR PLENUM INCLUDING DUST.

28. COORDINATE LOCATION OF ROOF MOUNTED HVAC

EQUIPMENT AND ROOF PENETRATIONS WITH THE

ARCHITECTURAL AND STRUCTURAL DRAWINGS.

29. INSTALL DUCTWORK AND PIPING PARALLEL TO BUILDING

COLUMN LINES UNLESS OTHERWISE SHOWN OR NOTED.

30. COORDINATE LOCATION OF EQUIPMENT SUPPORTS WITH

LOCATION OF EQUIPMENT ACCESS PANELS/DOORS TO ENABLE

SERVICE OF EQUIPMENT AND/OR FILTER REPLACEMENT.

31. PROVIDE WALL OR DUCT ACCESS PANELS OR DOOR FOR

ACCESS TO FIRE AND FIRE/SMOKE DAMPERS. ACCESS PANEL

OR DOOR SHALL BE MINIMUM SIZE OF 10”X10”AND SHALL BE

INSTALLED WITHIN 12”OF DAMPER. PROVIDE A REMOVABLE

DUCT SECTION WHERE DUCT SIZE IS TOO SMALL FOR A 10”X10”

ACCESS DOOR.

32. PROVIDE A MANUAL BALANCING DAMPER IN EACH BRANCH

DUCT TAKEOFF FROM MAIN SUPPLY, RETURN, OUTDOOR AND

EXHAUST AIR DUCTS.

33. PROVIDE A PREFABRICATED 45 DEGREE, HIGH EFFICIENCY,

RECTANGULAR/ROUND BRANCH DUCT TAKE-OFF FITTING WITH

MANUAL BALANCING DAMPER AND LOCKING QUADRANT FOR

BRANCH DUCT CONNECTIONS AND TAKE-OFFS TO INDIVIDUAL

DIFFUSERS, REGISTERS AND GRILLES.

34. BRANCH DUCTWORK TO AIR OUTLETS SHALL BE SAME SIZE AS

OUTLET NECK SIZE UNLESS OTHERWISE INDICATED.

35. FLEXIBLE DUCTWORK SHALL NOT EXCEED 5’-0”IN LENGTH AND

SHALL BE INSTALLED AND SUPPORTED TO AVOID SHARP

BENDS AND SAGGING. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS.

36. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT

LOCATION OF ALL CEILING MOUNTED AIR DEVICES.

37. MECHANICAL CONTRACTOR SHALL SUPPLY SMOKE DETECTOR

IN RETURN DUCT OF AIR HANDLERS OVER 2000 CFM AND FOR

UNITS WHICH SERVE AREAS OF EGRESS FOR INSTALLATION BY

ELECTRICAL CONTRACTOR. DETECTORS SHALL BE MOUNTED,

PHOTOELECTRIC TYPE COMPATIBLE WITH EXISTING FIRE

ALARM SYSTEM WITH INTEGRAL RELAY FOR SHUTDOWN OF

UNIT UPON ACTIVATION OF DETECTOR.

38. ALL DUCT OFF-SETS ARE TO BE MADE WITH RADIUS ELBOWS.

39. PROVIDE TRANSITIONS FOR ALL EQUIPMENT CONNECTIONS.

40. THE CONTRACTOR SHALL COORDINATE AND VERIFY THE

FOLLOWING DIVISIONS 23 AND 26 PRIOR TO BID:

DISCONNECTS:

WHERE NOT FURNISHED WITH EQUIPMENT: FURNISHED UNDER

DIVISION 26, INSTALLED UNDER DIVISION 26. WHERE

FURNISHED WITH EQUIPMENT: FURNISHED UNDER DIVISION 23,

INSTALLED UNDER DIVISION 26.

1. THIS DRAWING DIAGRAMMATICALLY REPRESENTS THE LAYOUT

OF EXISTING CONDITIONS WITH MAJOR MECHANICAL AND

ELECTRICAL COMPONENTS. THEY ARE NOT INTENDED TO

SHOW ACCESSORIES OR INCIDENTALS COMMON TO

EQUIPMENT INDICATED. THROUGH THESE ITEMS ARE TO BE

REMOVED, ACCESSIBILITY TO DEMOLITION ITEMS SHALL NOT

BE INFERRED. THE CONTRACTOR SHALL BE RESPONSIBLE

FOR FIELD VERIFICATION OF BUILDING AND EXISTING

CONDITIONS, PRIOR TO BID SUBMISSION.

2. DEMOLITION SHALL INCLUDE ALL HANGERS, FITTINGS,

DAMPERS, VALVES, ETC.

3. REPAIR ANY INSULATION DAMAGED DURING REMOVAL. REPAIR

WORK TO BE SAME AS NEW.

4. COORDINATE WALL AND FLOOR PATCHING REQUIREMENTS

WITH THE GENERAL CONTRACTOR. PATCHWORK SHALL

MATCH MATERIALS, FINISH AND TEXTURE OF ADJACENT

SURFACES. REFERENCE ARCHITECTURAL PLANS.

5. CONTRACTOR SHALL PATCH/REPAIR ALL UNUSED OPENINGS

AND MODIFIED FINISH SURFACES. PATCH SHALL MATCH

MATERIALS, FINISH AND TEXTURE AND ADJACENT SURFACES.

6. OWNER SHALL RETAIN FIRST SALVAGE RIGHTS TO ALL

REMOVED EQUIPMENT AND MATERIALS. UNLESS NOTED

OTHERWISE, CONTRACTOR SHALL BE RESPONSIBLE FOR

PROPER AND TIMELY DISPOSAL OF ALL CONSTRUCTION

DEBRIS INCLUDING BUT NOT LIMITED TO EQUIPMENT AND

MATERIALS NOT CLAIMED BY OWNER TO AN EPA APPROVED,

ENVIRONMENTALLY RESPONSIBLE, RECYCLE FACILITY OR

LANDFILL.

7. IT IS ESSENTIAL TO MINIMIZE DISRUPTIONS. COORDINATE ALL

DEMOLITION WITH OWNER, GENERAL CONTRACTOR OR

CONSTRUCTION MANAGER BEFORE SHUTTING DOWN ANY

UTILITY OR SIMILAR SYSTEM. SHUTDOWNS FOR UTILITIES OR

SIMILAR SYSTEMS SHALL BE REQUESTED WELL IN ADVANCE

AND PRE-APPROVED BY THE PROPER AUTHORITY (S) HAVING

JURISDICTION BEFORE BEGINNING WORK.

8. ALL WORK WITHIN THE CONTRACT DOCUMENTS, WHICH

INCLUDE THIS DRAWING, SHALL BE COMPLETED IN A SAFE

WORKMANLIKE MANNER AND IN ACCORDANCE WITH ALL

APPLICABLE STATE, LOCAL AND NATIONAL CODES,

REGULATIONS AND ORDINANCES. IF ANY CONFLICTS ARISE

BETWEEN THE CONTRACT DOCUMENTS AND THE APPLICABLE

CODE, REGULATIONS OR ORDINANCE, THE CONTRACTOR

SHALL BE RESPONSIBLE TO HAVE ALL WORK CONFORM TO

THE STRICTER OF SAID REQUIREMENTS.

9. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL

PERMITS AND INSPECTIONS AS REQUIRED FOR ELECTRICAL,

FIRE PROTECTION, PLUMBING, MECHANICAL AND BACKFLOW

PREVENTION INSTALLATIONS. IT SHALL BE THE

CONTRACTOR’S RESPONSIBILITY TO PROVIDE BOTH A

COMPLETE AND COMPLIANT INSTALLATION AS MAY BE

DETERMINED BY THE AUTHORITY (S) HAVING JURISDICTION.

10. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE

WATERTIGHT AND WEATHER-PROOF INTEGRITY OF ROOFS,

WALLS AND FLOORS DURING CONSTRUCTION. EACH TRADE

SHALL LOCATE/DIMENSION/COORDINATE THEIR ROOF, FLOOR

AND WALL OPENINGS WITH THE GC OR CONSTRUCTION

MANAGER.

MECHANICAL DEMOLITION NOTES

(AFF, AFG, UNLESS NOTED OTHERWISE)

THERMOSTATS (USER ADJUSTABLE)(TOP OF DEVICE) 48"

CONTROLS (TOP OF DEVICE) 48"

STANDARD MOUNTING HEIGHTS

DESCRIPTIONBYNO. DATE

REVISIONS

Phone:

Contact:

Email:

B1052 MSDT MINI SPLIT INSTALLATION

M-103

MECHANICAL NOTES

JOHNNY.TONG@US.AF.MIL

TRAINING

MECHANICAL

COMM

CLOSET

130A

ELECTRICAL

BREAK

ROOM

MEETING

ROOM

130B

BRIEFING LG

L3

EWC

+80"

+80"

+80"

+80"

+80"

+80"

+72"

L1-37

KEYED NOTES

EXISTING DISCONNECT/CONDENSER

NEW PROPOSED LOCATION

DISCONNECT/CONDENSER

MOVE EXISTING OUTLET

OUT TO FINISHED WALL

DESCRIPTIONBYNO. DATE

REVISIONS

Phone:

Contact:

Email:

B1052 MSDT MINI SPLIT INSTALLATION

E-101

ELECTRICAL PANEL

JOHNNY.TONG@US.AF.MIL

405-686-5003

JOHNNY TONG

AutoCAD SHX Text

USE EXISTING PANEL L3

INSTALL NEW DISCONNECTS IN APPROPRIATE AREA SHOWN

Sheets and Views
Bldg 1052 MSDT V1-COVER SHEET
Bldg 1052 MSDT V1-G-101
Bldg 1052 MSDT V1-G-102
Bldg 1052 MSDT V1-A-101
Bldg 1052 MSDT V1-A-102
Bldg 1052 MSDT V1-A-103
Bldg 1052 MSDT V1-M-101
Bldg 1052 MSDT V1-M-102
Bldg 1052 MSDT V1-M-103
Bldg 1052 MSDT V1-E-101