CUI_2000 Secure Upgrades Plans.pdf

PDF 8 MB Posted

Attached to
Bldg 2000 Secure Area Upgrades Federal contract opportunity
Solicitation number
W50S8P25BA001
Issued by
Department of the Army National Guard

About this file

These architectural design plans depict detailed specifications for secure area upgrades at Building 2000 in the Rickenbacker Air National Guard Base in Columbus, Ohio. The plans include multiple technical drawings showing floor plans, demolition requirements, electrical and mechanical layouts, and construction details for Room 240, which will be transformed into a secure facility. Key technical specifications include:

Architectural modifications involve removing existing windows, replacing them with CMU walls, installing double gypsum wallboard walls with sound attenuation, replacing acoustical ceiling tiles, and implementing specialized wall construction to achieve Sound Transmission Class (STC) 50 rating. Electrical and mechanical requirements include surface-mounted electrical outlets and data ports, ductwork penetrations with security bars and viewports, and strict regulations around wall penetrations. The design follows UFC 4-010-05 security standards, emphasizing controlled access, RF shielding, and comprehensive security measures for the 775-square-foot space. All work is designed to be completed within 180 calendar days after the Notice to Proceed.

View the file

Other files for this federal contract opportunity

Other files attached to Bldg 2000 Secure Area Upgrades, newest first.
File Type Posted
Bid Opening Sign In Sheet.pdf PDF
1419 Abstract of Offers W50S8P-25-B-A001.pdf PDF
SOW NLZG242008.pdf PDF
Pre-Bid Conference Attendance List.pdf PDF
conformed copy - W50S8P25BA0010001.pdf PDF
_Solicitation Amendment W50S8P25BA0010001 SF 30.pdf PDF
Site Visit Minutes.pdf PDF
Questions and Answers.pdf PDF
SOW for NLZG242008.pdf PDF
SFS Form 3_EAL Request.pdf PDF
Solicitation - W50S8P25BA001.pdf PDF
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

I T

T E

D

B

Y

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

C O

N T

R A

C T

N

O

S O

L I C

I T

A T

I O

N

N

O

I S

S U

E

D

A T

E

S I Z

E

M A

R K

D E

S C

R I P

T I O

N D

A T

E

SHEET ID

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

S

T

C

I V

I L

E

N G

I N

E E

R

S

Q U

A D

R O

N

S

T

A

I R

E F

U E

L I N

G

W

I N

G

R I C

K E

N B

A C

K E

R

A

A T

I O

N A

L

G

U A

D

B

S

E

M

I N

U T

E M

W

Y

L U

M B

U S

O

H

A N

S I

D

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

O

H I O

N L Z

G

B l d g

S

E C

U R

E

A

R E

A

U

P G

R A

D E

S

B U

I L D

I N

G

A

W

I N

E B

R E

N N

E R

S

P

R I C

E

S

P

R I C

E

A

W

I N

E B

R E

N N

E R

F L O

P

L A

N

A

R C

H I T

E C

T U

R A

L

A-101

A

T

I O

N A

L

G

U A

R D

SCALE: 1/2" = 1'-0 '

ARCHITECTURAL FLOOR PLAN

B1

PLAN

NORTH

1. VERIFY EXISTING CONDITIONS. COORDINATE THE EXTENT OF DEMOLITION

WORK AND EXISTING WORK TO REMAIN, WITH NEW WORK.

2. EXISTING FLOOR PLANS ARE BASED ON COPIES OF ARCHIVE DRAWINGS

PROVIDED BY THE GOVERNMENT. ACTUAL EXISTING WALL LOCATION/

ASSEMBLY MAY VARY. REPORT DISCREPANCIES, CONFLICTS OR

UNEXPECTED CONDITIONS TO THE CONTRACTING OFFICER.

3. REPAIR/ PATCH VISIBLE OPENINGS IN WALLS, PARTITIONS, FLOORS AND

CEILINGS WHERE DEMOLITION OCCURS. MATCH EXISTING ADJACENT

SURFACE FINISHES.

4. COORDINATE WITH CONTRACTING OFFICER ALL EQUIPMENT TO BE

SALVAGED.

5. ALL SHUTDOWN OF MECHANICALS, SPRINKLERS, FIRE ALARM AND/ OR

ELECTRICAL SYSTEMS SHALL BE COORDINATED WITH THE COR AND MAY BE

REQUIRED TO OCCUR DURING OR AFTER BUSINESS HOURS.

6. IN-SERVICE EQUIPMENT SHALL BE PROTECTED FROM CONSTRUCTION

ACTIVITIES AT ALL TIMES.

7. MAINTAIN AN UNOBSTRUCTED EXIT PATH TO THE PRIMARY EXITS FOR THE

DURATION OF CONSTRUCTION.

8. WORK AREA SHALL BE KEPT CLEAN OF DEBRIS AND DUST AT THE END OF

EACH WORK DAY.

9. PER REGULATIONS, CAMERAS, PHONES OR ANY OTHER TRANSMITTING AND

RECEIVING ELECTRONICS WILL NOT BE PERMITTED WITHIN THE WORK

AREAS AND ADJACENT OFFICES AND HALLWAY.

10. ALL WORK WILL COMPLY WITH UFC 4-010-05 (26 MAY 2023)

GENERAL ARCHITECTURAL NOTES

ARCHITECTURAL KEYNOTES

1. PREPARE WALLS BY PATCHING HOLES/PENETRATIONS TO MATCH ADJACENT

SURFACE AND APPLY FINISH PER FINISH SCHEDULE A-104 FOR ALL WALLS IN

HATCHED AREA. WALL FINISH WILL SPAN FROM FINISHED FLOOR TO ROOF

DECK. REFER TO UFC 4-010-05.

2. REMOVE AND REPLACE ACOUSTICAL CEILING TILE, EDGE PROFILE AND GRID

SIZE- SQUARE

". TILE DIMENSIONS 24" X 48" X

" , WHITE, EXPOSED TEE

SYSTEM, WHITE. REFER TO SHEET A-103.

3. WINDOWS TO BE REMOVED AND REPLACED WITH CMU IN KIND TO REST OF

CMU. FURRING GWB FINISH ON WALL TO MATCH SURRONDING FURRING.

4. INSTALL NEW WALL ACCORDING TO DETAILS ON A-102. DOUBLE WALL GWB

ON BOTH SIDES.

Continuous acoustic sealant in void - both sides of partition

Scheduled wall Base (both sides of partition)

3 12" (89mm) sound attenuation material, fastened to prevent sliding down and leaving void at the top

8" Gypsum Wall Board (GWB) - sound group 4 requires additional layer of 58" GWB with foil backing or layer of approved ultra radiant R Foil

Entire wall assembly shall be finished and painted from true floor to true ceiling

Metal angle moldings and steel support grid systems

Acoustical ceiling

Fire safe non-shrink grout, or acoustic sealant in all voids above track (note 2)

- both sides of partition

Bottom of Deck

Structural floor Finished floor

16 gauge continuous track (top & bottom) w/ anchors at 32" o.c. maximum) - bed in continuous bead of acoustical sealant

Two layers of 58" Gypsum Wall Board (GWB) mounted on 3-5/8" 16 gauge metal framing or 2x4 studs at 16" o.c. For the second layer use GWB with foil backing or layer of approved ultra radiant R Foil

Scheduled wall finish to be continuous above false ceiling and below raised floor

Wall A - Suggested Standard Acoustic Wall Construction for STC 50

Controlled Side Uncontrolled Side

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

I T

T E

D

B

Y

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

E

D

A T

E

S I Z

E

M A

R K

D E

S C

R I P

T I O

N D

A T

E

SHEET ID

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

S

T

C

I V

I L

E

N G

I N

E E

R

S

Q U

A D

R O

N

S

T

A

F

U E

L I N

G

W

I N

G

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

M

I N

U T

E M

L U

M B

U S

O

H

A N

S I

D

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

O

H I O

N L Z

G

B l d g

S

E C

U R

E

A

R E

A

U

P G

R A

D E

S

B U

I L D

I N

G

A

W

I N

E B

R E

N N

E R

S

P

R I C

E

S

P

R I C

E

A

W

I N

E B

R E

N N

E R

F L O

A

N

A

R C

H I T

E C

T U

R A

L

A-102

A

T

I O

N A

L

G

U A

R D

SCALE: 1/2" = 1'-0 '

Standard Acoustic Wall Construction

B1

PLAN

NORTH

1. VERIFY EXISTING CONDITIONS. COORDINATE THE EXTENT OF DEMOLITION

WORK AND EXISTING WORK TO REMAIN, WITH NEW WORK.

2. EXISTING FLOOR PLANS ARE BASED ON COPIES OF ARCHIVE DRAWINGS

PROVIDED BY THE GOVERNMENT. ACTUAL EXISTING WALL LOCATION/

ASSEMBLY MAY VARY. REPORT DISCREPANCIES, CONFLICTS OR

UNEXPECTED CONDITIONS TO THE CONTRACTING OFFICER.

3. REPAIR/ PATCH VISIBLE OPENINGS IN WALLS, PARTITIONS, FLOORS AND

CEILINGS WHERE DEMOLITION OCCURS. MATCH EXISTING ADJACENT

SURFACE FINISHES.

4. COORDINATE WITH CONTRACTING OFFICER ALL EQUIPMENT TO BE

SALVAGED.

5. ALL SHUTDOWN OF MECHANICALS, SPRINKLERS, FIRE ALARM AND/ OR

ELECTRICAL SYSTEMS SHALL BE COORDINATED WITH THE COR AND MAY BE

REQUIRED TO OCCUR DURING OR AFTER BUSINESS HOURS.

6. IN-SERVICE EQUIPMENT SHALL BE PROTECTED FROM CONSTRUCTION

ACTIVITIES AT ALL TIMES.

7. MAINTAIN AN UNOBSTRUCTED EXIT PATH TO THE PRIMARY EXITS FOR THE

DURATION OF CONSTRUCTION.

8. WORK AREA SHALL BE KEPT CLEAN OF DEBRIS AND DUST AT THE END OF

EACH WORK DAY.

9. PER REGULATIONS, CAMERAS, PHONES OR ANY OTHER TRANSMITTING AND

RECEIVING ELECTRONICS WILL NOT BE PERMITTED WITHIN THE WORK

AREAS AND ADJACENT OFFICES AND HALLWAY.

10. ALL WORK WILL COMPLY WITH UFC 4-010-05 (26 MAY 2023)

GENERAL ARCHITECTURAL NOTES

ARCHITECTURAL KEYNOTES

1. CTTA REQUIRED COUNTERMEATURES (FOIL BACKED GWB OR LAYER OF

APPROVED ULTRA RADIANT R-FOIL) SHALL BE INSTALLED IAW BEST

PRACTICES FOR ARCHITECTURAL RAIDO FREQUENCY (RF) SHIELDING. FOIL

SHALL BE LOCATED BETWEEN THE TWO LAYERS OF GWB.

2. PARTITION SHALL BE SEALED CONTINUOUSLY WITH ACOUSTICAL SEALANT

WHENEVER IT ABUTS ANOTHER ELEMENT (E.G. WALL, COLUMN, MULLION,

ETC.)

3. ANY ELECTRICAL OR COMMUNICATIONS OUTLETS REQUIRED ON THE

PERIMETER WALL SHALL BE SURFACE MOUNTED.

OFFICE

OFFICE

OFFICE

2'-0" X 4'-0" ACOUSTICAL CEILING TILE

2'-0" X 4'-0" LED LIGHT FIXTURE

2'-0" X 4'-0" LED LIGHT FIXTURE W/BATTERY

BACK-UP

2'-0" X 2'-0" LED LIGHT FIXTURE W/BATTERY

BACK-UP

1'-0" X 4'-0" LED PENDANT LIGHT FIXTURE

1'-0" X 4'-0" LED PENDANT LIGHT FIXTURE

W/BATTERY BACK-UP

2'-0" X 2'-0" MECHANICAL DIFFUSER

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

I T

T E

D

B

Y

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

E

D

A T

E

S I Z

E

M A

R K

D E

S C

R I P

T I O

N D

A T

E

SHEET ID

S

T

C

I V

I L

E

N G

I N

E E

R

S

Q U

A D

R O

N

S

T

A

F

U E

L I N

G

W

I N

G

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

M

I N

U T

E M

L U

M B

U S

O

H

A N

S I

D

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

O

H I O

N L Z

G

B l d g

S

E C

U R

E

A

R E

A

U

P G

R A

D E

S

B U

I L D

I N

G

A

W

I N

E B

R E

N N

E R

S

P

R I C

E

S

P

R I C

E

A

W

I N

E B

R E

N N

E R

F L O

A

N

A

R C

H I T

E C

T U

R A

L

A-103

A

T

I O

N A

L

G

U A

R D

SCALE: 1/2" = 1'-0 '

Ceiling Grid Details

B1

PLAN

NORTH

1. VERIFY EXISTING CONDITIONS. COORDINATE THE EXTENT OF DEMOLITION

WORK AND EXISTING WORK TO REMAIN, WITH NEW WORK.

2. EXISTING FLOOR PLANS ARE BASED ON COPIES OF ARCHIVE DRAWINGS

PROVIDED BY THE GOVERNMENT. ACTUAL EXISTING WALL LOCATION/

ASSEMBLY MAY VARY. REPORT DISCREPANCIES, CONFLICTS OR

UNEXPECTED CONDITIONS TO THE CONTRACTING OFFICER.

3. REPAIR/ PATCH VISIBLE OPENINGS IN WALLS, PARTITIONS, FLOORS AND

CEILINGS WHERE DEMOLITION OCCURS. MATCH EXISTING ADJACENT

SURFACE FINISHES.

4. COORDINATE WITH CONTRACTING OFFICER ALL EQUIPMENT TO BE

SALVAGED.

5. ALL SHUTDOWN OF MECHANICALS, SPRINKLERS, FIRE ALARM AND/ OR

ELECTRICAL SYSTEMS SHALL BE COORDINATED WITH THE COR AND MAY BE

REQUIRED TO OCCUR DURING OR AFTER BUSINESS HOURS.

6. IN-SERVICE EQUIPMENT SHALL BE PROTECTED FROM CONSTRUCTION

ACTIVITIES AT ALL TIMES.

7. MAINTAIN AN UNOBSTRUCTED EXIT PATH TO THE PRIMARY EXITS FOR THE

DURATION OF CONSTRUCTION.

8. WORK AREA SHALL BE KEPT CLEAN OF DEBRIS AND DUST AT THE END OF

EACH WORK DAY.

9. PER REGULATIONS, CAMERAS, PHONES OR ANY OTHER TRANSMITTING AND

RECEIVING ELECTRONICS WILL NOT BE PERMITTED WITHIN THE WORK

AREAS AND ADJACENT OFFICES AND HALLWAY.

10. ALL WORK WILL COMPLY WITH UFC 4-010-05 (26 MAY 2023)

GENERAL ARCHITECTURAL NOTES

ARCHITECTURAL KEYNOTES.

1. REMOVE AND REPLACE IN KIND 2' X 4' ACOUSTICAL CEILING TILE AND GRID.

S

E

S

C H

E D

U L E

SEE SCHEDULE

0'-2"

S E

E

S

C H

E D

U L E

SEE SCHEDULE

DOOR SCHEDULE

DOOR FRAME

HARDWAR

E GROUP

REMARKS

MARK WIDTH HEIGHT WIDTH TYPE MATERIAL TYPE MATERIAL

240 3'-0" 7'-0" 1-3/4" F H.M. 1 H.M. 1

DOOR HARDWARE SCHEDULE (BUILDERS MANUFACTURES HARDWARE ASSOCIATION ANSI/BHMA A156)

HARDWARE GROUP 1 (DOOR 240)

3 EA, 4 1/2" x 4 1/2" HINGE A8111 BY 652 BY NRP (NON-REMOVABLE PIN)

1 EA DOOR CLOSURE C02011 WITH OPTION PT4C

1 EA HIGH SECURITY PEDESTRIAN

DOOR DEADBOLT DEVICE

FEDERAL SPECIFICATION FF-L-2890C TYPE 1- PDPL-ANSI/BHMA A156.2 GRADE 1 F44 COMPLETE WITH STAND-ALONE ACCESS CONTROL

CAPABILITY - COMBINATION PRE-ASSEMBLED LOCK. COMPLETE WITH FEDERAL SPECIFICATION FF-L-2740 COMBINATION LOCK.

1 EA KICK PLATE J102 BY 630 ON PUSH SIDE OF DOOR

FINISH SCHEDULE

SPACE FLOOR

WALLS (BASED ON PLAN NORTH)

CEILING

FINISH

REMARKS

ROOM

ROOM

NAME

MATERIAL

MATERIAL

BASE

NORTH EAST SOUTH WEST

240 EXISTING EXISTING P-1 P-1 P-1 P-1

ACT SHERWIN WILLIAMS PAINT TO MATCH EXISTING PAINT.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

I T

T E

D

B

Y

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

E

D

A T

E

S I Z

E

M A

R K

D E

S C

R I P

T I O

N D

A T

E

SHEET ID

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

S

T

C

I V

I L

E

N G

I N

E E

R

S

Q U

A D

R O

N

S

T

A

F

U E

L I N

G

W

I N

G

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

M

I N

U T

E M

L U

M B

U S

O

H

A N

S I

D

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

O

H I O

N L Z

G

B l d g

S

E C

U R

E

A

R E

A

U

P G

R A

D E

S

B U

I L D

I N

G

A

W

I N

E B

R E

N N

E R

S

P

R I C

E

S

P

R I C

E

A

W

I N

E B

R E

N N

E R

F L O

A

N

A

R C

H I T

E C

T U

R A

L

A-104

A

T

I O

N A

L

G

U A

R D

SCALE: 3/4" = 1'-0 '

DOOR DETAILS

B1

PLAN

NORTH

1. VERIFY EXISTING CONDITIONS. COORDINATE THE EXTENT OF DEMOLITION

WORK AND EXISTING WORK TO REMAIN, WITH NEW WORK.

2. EXISTING FLOOR PLANS ARE BASED ON COPIES OF ARCHIVE DRAWINGS

PROVIDED BY THE GOVERNMENT. ACTUAL EXISTING WALL LOCATION/

ASSEMBLY MAY VARY. REPORT DISCREPANCIES, CONFLICTS OR

UNEXPECTED CONDITIONS TO THE CONTRACTING OFFICER.

3. REPAIR/ PATCH VISIBLE OPENINGS IN WALLS, PARTITIONS, FLOORS AND

CEILINGS WHERE DEMOLITION OCCURS. MATCH EXISTING ADJACENT

SURFACE FINISHES.

4. COORDINATE WITH CONTRACTING OFFICER ALL EQUIPMENT TO BE

SALVAGED.

5. ALL SHUTDOWN OF MECHANICALS, SPRINKLERS, FIRE ALARM AND/ OR

ELECTRICAL SYSTEMS SHALL BE COORDINATED WITH THE COR AND MAY BE

REQUIRED TO OCCUR DURING OR AFTER BUSINESS HOURS.

6. IN-SERVICE EQUIPMENT SHALL BE PROTECTED FROM CONSTRUCTION

ACTIVITIES AT ALL TIMES.

7. MAINTAIN AN UNOBSTRUCTED EXIT PATH TO THE PRIMARY EXITS FOR THE

DURATION OF CONSTRUCTION.

8. WORK AREA SHALL BE KEPT CLEAN OF DEBRIS AND DUST AT THE END OF

EACH WORK DAY.

9. PER REGULATIONS, CAMERAS, PHONES OR ANY OTHER TRANSMITTING AND

RECEIVING ELECTRONICS WILL NOT BE PERMITTED WITHIN THE WORK

AREAS AND ADJACENT OFFICES AND HALLWAY.

10. ALL WORK WILL COMPLY WITH UFC 4-010-05 (26 MAY 2023)

GENERAL ARCHITECTURAL NOTES

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

I T

T E

D

B

Y

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

E

D

A T

E

S I Z

E

M A

R K

D E

S C

R I P

T I O

N D

A T

E

SHEET ID

S

T

C

I V

I L

E

N G

I N

E E

R

S

Q U

A D

R O

N

S

T

A

F

U E

L I N

G

W

I N

G

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

M

I N

U T

E M

L U

M B

U S

O

H

A N

S I

D

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

O

H I O

N L Z

G

B l d g

S

E C

U R

E

A

R E

A

U

P G

R A

D E

S

B U

I L D

I N

G

A

W

I N

E B

R E

N N

E R

S

P

R I C

E

S

P

R I C

E

A

W

I N

E B

R E

N N

E R

F L O

A

N

D

E M

O L I T

I O

N

D-101

A

T

I O

N A

L

G

U A

R D

DEMOLITION PLAN

B1

PLAN

NORTH

1. VERIFY EXISTING CONDITIONS. COORDINATE THE EXTENT OF DEMOLITION

WORK AND EXISTING WORK TO REMAIN, WITH NEW WORK.

2. EXISTING FLOOR PLANS ARE BASED ON COPIES OF ARCHIVE DRAWINGS

PROVIDED BY THE GOVERNMENT. ACTUAL EXISTING WALL LOCATION/

ASSEMBLY MAY VARY. REPORT DISCREPANCIES, CONFLICTS OR

UNEXPECTED CONDITIONS TO THE CONTRACTING OFFICER.

3. REPAIR/ PATCH VISIBLE OPENINGS IN WALLS, PARTITIONS, FLOORS AND

CEILINGS WHERE DEMOLITION OCCURS. MATCH EXISTING ADJACENT

SURFACE FINISHES.

4. COORDINATE WITH CONTRACTING OFFICER ALL EQUIPMENT TO BE

SALVAGED.

5. ALL SHUTDOWN OF MECHANICALS, SPRINKLERS, FIRE ALARM AND/ OR

ELECTRICAL SYSTEMS SHALL BE COORDINATED WITH THE COR AND MAY BE

REQUIRED TO OCCUR DURING OR AFTER BUSINESS HOURS.

6. IN-SERVICE EQUIPMENT SHALL BE PROTECTED FROM CONSTRUCTION

ACTIVITIES AT ALL TIMES.

7. MAINTAIN AN UNOBSTRUCTED EXIT PATH TO THE PRIMARY EXITS FOR THE

DURATION OF CONSTRUCTION.

8. WORK AREA SHALL BE KEPT CLEAN OF DEBRIS AND DUST AT THE END OF

EACH WORK DAY. PROTECT SURROUNDING AREA FROM DUST AND DEBRIS.

9. PER REGULATIONS, CAMERAS, PHONES OR ANY OTHER TRANSMITTING AND

RECEIVING ELECTRONICS WILL NOT BE PERMITTED WITHIN THE WORK

AREAS AND ADJACENT OFFICES AND HALLWAY.

10. STABILIZE AREA OF WORK.

11. ALL WORK WILL COMPLY WITH UFC 4-010-05 (26 MAY 2023)

GENERAL DEMOLITION NOTES

DEMOLITION KEYNOTES

1. DEMO GWB WALL.

2. REMOVE WINDOWS FOR INFILL.

3. DEMO ACOUSTICAL CEILING TILE AND GRID AS REQUIRED TO FACILITATE

NEW GWB WALL AND ABOVE CEILING WORK.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

I T

T E

D

B

Y

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

E

D

A T

E

S I Z

E

M A

R K

D E

S C

R I P

T I O

N D

A T

E

SHEET ID

S

T

C

I V

I L

E

N G

I N

E E

R

S

Q U

A D

R O

N

S

T

A

F

U E

L I N

G

W

I N

G

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

M

I N

U T

E M

L U

M B

U S

O

H

A N

S I

D

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

O

H I O

N L Z

G

B l d g

S

E C

U R

E

A

R E

A

U

P G

R A

D E

S

B U

I L D

I N

G

A

W

I N

E B

R E

N N

E R

S

P

R I C

E

S

P

R I C

E

A

W

I N

E B

R E

N N

E R

F L O

A

N

E

L E

C T

R I C

A L

E-101

A

T

I O

N A

L

G

U A

R D

SCALE: 1/2" = 1'-0 '

ARCHITECTURAL FLOOR PLAN

B1

PLAN

NORTH

1. VERIFY EXISTING CONDITIONS. COORDINATE THE EXTENT OF ELECTRICAL

WORK AND EXISTING WORK TO REMAIN, WITH NEW WORK.

2. EXISTING FLOOR PLANS ARE BASED ON COPIES OF ARCHIVE DRAWINGS

PROVIDED BY THE GOVERNMENT. ACTUAL EXISTING WALL LOCATION/

ASSEMBLY MAY VARY. REPORT DISCREPANCIES, CONFLICTS OR

UNEXPECTED CONDITIONS TO THE CONTRACTING OFFICER.

3. NEW UTILITIES SHALL BE SURFACE MOUNTED ON BOTH THE CONTROLLED

SIDE OF THE ROOM AND THE UNCONTROLLED WALL OF ROOM 236 AND ALL

PENETRATIONS INTO THE CONTROLLED SIDE SHALL BE PROPERLY SEALED

TO STC 50 STANDARDS AND INCLUDE DIELECTRIC BREAKS AT THE POINT OF

PENETRATION.

1. COORDINATE WITH CONTRACTING OFFICER ALL EQUIPMENT TO BE

SALVAGED.

2. ALL SHUTDOWN OF MECHANICALS, SPRINKLERS, FIRE ALARM AND/ OR

ELECTRICAL SYSTEMS SHALL BE COORDINATED WITH THE COR AND MAY BE

REQUIRED TO OCCUR DURING OR AFTER BUSINESS HOURS.

3. IN-SERVICE EQUIPMENT SHALL BE PROTECTED FROM CONSTRUCTION

ACTIVITIES AT ALL TIMES.

4. MAINTAIN AN UNOBSTRUCTED EXIT PATH TO THE PRIMARY EXITS FOR THE

DURATION OF CONSTRUCTION.

5. WORK AREA SHALL BE KEPT CLEAN OF DEBRIS AND DUST AT THE END OF

EACH WORK DAY.

6. PER REGULATIONS, CAMERAS, PHONES OR ANY OTHER TRANSMITTING AND

RECEIVING ELECTRONICS WILL NOT BE PERMITTED WITHIN THE WORK

AREAS AND ADJACENT OFFICES AND HALLWAY.

7. ALL WORK WILL COMPLY WITH UFC 4-010-05 (26 MAY 2023)

GENERAL ELECTRICAL NOTES

ELECTRICAL KEYNOTES

1. ALL REINSTALLED ELECTRICAL OUTLETS AND DATA PORTS TO BE INSTALLED

ON EXTERIOR OF WALL IN CONDUIT SURFACE MOUNTED.

ELECTRICAL

OUTLET

DATA

CONNECTION

PORT

3 4 5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

I T

T E

D

B

Y

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

E

D

A T

E

S I Z

E

M A

R K

D E

S C

R I P

T I O

N D

A T

E

SHEET ID

S

T

C

I V

I L

E

N G

I N

E E

R

S

Q U

A D

R O

N

S

T

A

F

U E

L I N

G

W

I N

G

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

M

I N

U T

E M

L U

M B

U S

O

H

A N

S I

D

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

O

H I O

N L Z

G

B l d g

S

E C

U R

E

A

R E

A

U

P G

R A

D E

S

B U

I L D

I N

G

A

W

I N

E B

R E

N N

E R

S

P

R I C

E

S

P

R I C

E

A

W

I N

E B

R E

N N

E R

F L O

A

N

M

E C

H A

N I C

A L

M-101

A

T

I O

N A

L

G

U A

R D

SCALE: 1/2" = 1'-0 '

ARCHITECTURAL FLOOR PLAN

B1

PLAN

NORTH

1. VERIFY EXISTING CONDITIONS. COORDINATE THE EXTENT OF DEMOLITION

WORK AND EXISTING WORK TO REMAIN, WITH NEW WORK.

2. EXISTING FLOOR PLANS ARE BASED ON COPIES OF ARCHIVE DRAWINGS

PROVIDED BY THE GOVERNMENT. ACTUAL EXISTING WALL LOCATION/

ASSEMBLY MAY VARY. REPORT DISCREPANCIES, CONFLICTS OR

UNEXPECTED CONDITIONS TO THE CONTRACTING OFFICER.

3. REPAIR/ PATCH VISIBLE OPENINGS IN WALLS, PARTITIONS, FLOORS AND

CEILINGS WHERE DEMOLITION OCCURS. MATCH EXISTING ADJACENT

SURFACE FINISHES.

4. COORDINATE WITH CONTRACTING OFFICER ALL EQUIPMENT TO BE

SALVAGED.

5. ALL SHUTDOWN OF MECHANICALS, SPRINKLERS, FIRE ALARM AND/ OR

ELECTRICAL SYSTEMS SHALL BE COORDINATED WITH THE COR AND MAY BE

REQUIRED TO OCCUR DURING OR AFTER BUSINESS HOURS.

6. IN-SERVICE EQUIPMENT SHALL BE PROTECTED FROM CONSTRUCTION

ACTIVITIES AT ALL TIMES.

7. MAINTAIN AN UNOBSTRUCTED EXIT PATH TO THE PRIMARY EXITS FOR THE

DURATION OF CONSTRUCTION.

8. WORK AREA SHALL BE KEPT CLEAN OF DEBRIS AND DUST AT THE END OF

EACH WORK DAY.

9. PER REGULATIONS, CAMERAS, PHONES OR ANY OTHER TRANSMITTING AND

RECEIVING ELECTRONICS WILL NOT BE PERMITTED WITHIN THE WORK

AREAS AND ADJACENT OFFICES AND HALLWAY.

10. ALL WORK WILL COMPLY WITH UFC 4-010-05 (26 MAY 2023)

GENERAL MECHANICAL NOTES

MECHANICAL KEYNOTES

1. 42"X42" DUCT WORK PENETRATION. PERMANENTLY AFFIXED BARS AS

REFERENCED IN UFC 4-010-05 PARA. 3-4.12 VENTS AND DUCTS. ADD

VIEWPORT AS SEEN ON M-102 DETAILS.

2. 10"X10" DUCT WORK PENETRATION. ADD VIEWPORT AS SEEN ON M-102

DETAILS.

3. 12"X12" DUCT WORK PENETRATION. ADD VIEWPORT AS SEEN ON M-102

DETAILS.

4. 42"X42" DUCT WORK PENETRATION. ADD VIEWPORT AS SEEN ON M-102

DETAILS.

5. 14"X14 DUCT WORK PENETRATION. ADD VIEWPORT AS SEEN ON M-102

DETAILS.

3"X2"X1/4" OR HEAVIER ANGLES

SNUG TO WALL OR FLOOR AND

SLEEVE ALL AROUND ( NOTE A)

CAP

OR

WALL

DUCT

MANBARS

(NOTE C)

S-TYPE SLIP

CONNECTOR (TYP.)

DUCT

NOTES:

A. SHOP WELD SLEEVE ASSEMBLY. ALL SHOP WELDS SHALL BE CONTINUOUS 1/8"

(MIN) THICK. WELDED ANGLES SHALL BE LOCATED OUT OF THE SPECIAL USE

BOUNDARY; BLOT, SCREW, RIVET, OR TACKWELD CONNECTIONS SHALL BE WITHIN

THE SPECIAL USE BOUNDARY; SEE ARCHITECTURE FOR SPECIAL USE BOUNDARY

LOCATIONS.

B.

PROVIDE MINIMUM 12"X12" ACCESS DOOR WITHIN SPECIAL USE BOUNDARY, SEE

ARCHITECTURE FOR SPECIAL USE BOUNDARY LOCATIONS. LOCATE DOOR ON

BOTTOM OF DUCT IF INSUFFICIENT DEPTH OF DUCT. INCREASE DUCT SIZE AS

REQUIRED TO ACCOMMODATE ACCESS DOOR.

C.

PROVIDE MANBARS IN SLEEVE.

14 GA OR HEAVIER SLEEVE

NONSECURE SIDE SECURE SIDE

FLEXIBLE NON-CONDUCTIVE

BREAK AT WALL

ACOUSTICALLY LINED, THRU-WALL DUCT

INSULATED ACCESS

HATCH (IN BOTTOM

0F DUCT) SEE NOTE B.

6" M

AX

6" MAX

CENTER OF FRAME

CENTER OF FRAME

FRAME AND SLEEVE

WELD BARS AND ANGLES AT ALL

INTERSECTIONS AND JOINTS.

1/2" DIA. STEEL

SECURITY BARS

NOTES:

A. USE IN SECURE WALL PENETRATIONS LARGER THAN 96 SQ. IN. OR

IF ONE DIMENSION EXCEEDS 6 IN.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A

B

C

D

E

F

G

H

J

K

L

M

N

P

S U

B M

I T

T E

D

B

Y

C H

E C

K E

D

B

Y

D R

A W

N

B

Y

D E

S I G

N E

D

B

Y

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

I S

S U

E

D

A T

E

S I Z

E

M A

R K

D E

S C

R I P

T I O

N D

A T

E

SHEET ID

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

S

T

C

I V

I L

E

N G

I N

E E

R

S

Q U

A D

R O

N

S

T

A

F

U E

L I N

G

W

I N

G

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

M

I N

U T

E M

L U

M B

U S

O

H

A N

S I

D

R I C

K E

N B

A C

K E

R

A

T

I O

N A

L

G

U A

S

E

O

H I O

N L Z

G

B l d g

S

E C

U R

E

A

R E

A

U

P G

R A

D E

S

B U

I L D

I N

G

A

W

I N

E B

R E

N N

E R

S

P

R I C

E

S

P

R I C

E

A

W

I N

E B

R E

N N

E R

F L O

A

N

M

E C

H A

N I C

A L

M-102

A

T

I O

N A

L

G

U A

R D

SCALE: 1/2" = 1'-0 '

Duct Penetration Through Secure Wall Detail

B1

PLAN

NORTH

1. VERIFY EXISTING CONDITIONS. COORDINATE THE EXTENT OF DEMOLITION

WORK AND EXISTING WORK TO REMAIN, WITH NEW WORK.

2. EXISTING FLOOR PLANS ARE BASED ON COPIES OF ARCHIVE DRAWINGS

PROVIDED BY THE GOVERNMENT. ACTUAL EXISTING WALL LOCATION/

ASSEMBLY MAY VARY. REPORT DISCREPANCIES, CONFLICTS OR

UNEXPECTED CONDITIONS TO THE CONTRACTING OFFICER.

3. REPAIR/ PATCH VISIBLE OPENINGS IN WALLS, PARTITIONS, FLOORS AND

CEILINGS WHERE DEMOLITION OCCURS. MATCH EXISTING ADJACENT

SURFACE FINISHES.

4. COORDINATE WITH CONTRACTING OFFICER ALL EQUIPMENT TO BE

SALVAGED.

5. ALL SHUTDOWN OF MECHANICALS, SPRINKLERS, FIRE ALARM AND/ OR

ELECTRICAL SYSTEMS SHALL BE COORDINATED WITH THE COR AND MAY BE

REQUIRED TO OCCUR DURING OR AFTER BUSINESS HOURS.

6. IN-SERVICE EQUIPMENT SHALL BE PROTECTED FROM CONSTRUCTION

ACTIVITIES AT ALL TIMES.

7. MAINTAIN AN UNOBSTRUCTED EXIT PATH TO THE PRIMARY EXITS FOR THE

DURATION OF CONSTRUCTION.

8. WORK AREA SHALL BE KEPT CLEAN OF DEBRIS AND DUST AT THE END OF

EACH WORK DAY.

9. PER REGULATIONS, CAMERAS, PHONES OR ANY OTHER TRANSMITTING AND

RECEIVING ELECTRONICS WILL NOT BE PERMITTED WITHIN THE WORK

AREAS AND ADJACENT OFFICES AND HALLWAY.

10. ALL WORK WILL COMPLY WITH UFC 4-010-05 (26 MAY 2023)

GENERAL MECHANICAL NOTES

MECHANICAL KEYNOTES

1. Duct access port for inspection.

NLZG242008B2000SECUREAREA_A-101.pdf
Sheets and Views
A-101
CUI_2000 Secure Upgrades Plans.pdf
NLZG242008B2000SECUREAREA_A-102.pdf
Sheets and Views
A-102
NLZG242008B2000SECUREAREA_A-103.pdf
Sheets and Views
A-103
NLZG242008B2000SECUREAREA_A-104.pdf
Sheets and Views
A-104
NLZG242008B2000SECUREAREA_D-101.pdf
Sheets and Views
D-101
NLZG242008B2000SECUREAREA_E-101.pdf
Sheets and Views
E-101
NLZG242008B2000SECUREAREA_M-101.pdf
Sheets and Views
M-101
NLZG242008B2000SECUREAREA_M-102.pdf