This document is a Request for Information (RFI) response providing answers to 20 questions submitted by potential contractors for the 152 AW Base-wide Fall Protection project (Solicitation W50S8C26QA007) as of April 8, 2026.
The RFI clarifies fall protection requirements across multiple buildings at the installation. Guardrail systems will be Safety Yellow to match existing base installations, with Building 67 requiring guardrails instead of a warning line. The preferred benchmark product is Guardian Fall Protection's Quickset Multi-Directional Baseplate (Part #15178), as installed on Building 56. Building-specific requirements include: Building 9 requiring two 136-foot runs (north and south sides) and hatch surrounds with 42" x 35" dimensions; Building 67 requiring 80-foot runs on the east side; Building 76 needing a self-closing gate with returns on the north ladder; Building 88 requiring standing seam fall protection south of EF-3 with 43" x 36" hatch dimensions; Building 130 with 43" x 37" hatch dimensions; Building 600 with approximately 42" x 36" hatches; Building 700 requiring two hatches (42" x 36") and seven guardrail locations; and Building 800 requiring two corner installations with 40" x 34" hatch dimensions. The RFI excludes Buildings 82, 300, 400-406, 500, and MSAT from the project scope. All mounting bases require rubber pads and roof pads for membrane protection. AT-OPSEC training, conducted on base during the first day of work in a classroom setting, is mandatory and provided at no cost to contractors.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation: W50S8C26QA007
Title: 152 AW Base-wide Fall Protection
RFI-00001
Providing answers to RFIs received as of 8 April 2026.
1. What is the specific color of the guardrail systems (to match the existing roof color)?
1a. Answer: We are changing the color to be Safety Yellow to match pre-existing guardrails around base.
2. What are the specifics for the Warning Line on Bldg. 67?
2a. Answer: The requirement for Bldg. 67 will be changed from a warning line to guard rails.
3. Will Roof pictures be provided?
3a. Answer: Yes, pictures of the roofs can be provided.
4. When and where will the AT-OPSEC training be completed? Is there a cost associated with it?
4a. Answer: AT Training is most often completed in a classroom setting on base, on the first day of work. Class typically takes approximately 1 hour and is free of charge.
5. Clarification on Building 67 and the option for an R-Panel metal roof to have a guardrail in Lieu of a warning line
5a. Answer: Please see question 2 above, and the updated PWS.
6. Section 5.0.3 (Are these two requirements the same?)
4. Mounting Bases: Provide rubber pads on bottom of bases
5. Roof pads shall be provided under each base to protect roof membrane
6a. Answer: These two are the same requirement.
7. What are the preferred manufacturer examples, product references, or previously installed systems that may serve as a benchmark?
7a. Answer: An existing system installed on building 56 is from Guardian Fall Protection:
Quickset Multi-Directional Baseplate Part #: 15178. (See reference photos)
8. BLDG 9 RFI states – (2) 136’ straight runs and two hatch surrounds.
Pictures show five total locations highlighted in yellow. Two on the north side and three on the south side. Is the place to have one 136’ run on both the north and south side? Also – on the hatch surrounds, please advise roof hatch dimensions.
8a. Answer: Yes, the 136’ runs are on the north and south sides. Roof hatch dimensions are 42” x 35”.
9. BLDG 067 - Marking warning line (1) 80’ run
Is this to be installed on the east side of the roof between EF-1 and EVAP COOLER 1?
Please confirm.
9a. Answer: Yes, fall protection is to be installed on the east side of each of those units.
10. BLDG 076 - Please advise location of (1) ladder kit.
Is your group referring to a self closing gate with returns? Please advise. Is there a specific product you could reference?
10a. Answer: Yes, the ladder on the north side of the building needs a self-closing gate with returns.
11. BLDG 082 - This is not referenced in the RFI.
Please advise. Pictures show need for guardrail system. If this will be included, please advise how many LF needed.
11a. Answer: 82 is not a requirement and should not be included in the bid.
12. BLDG 88
Please advise location of standing seam fall protection.
Please advise roof hatch dimensions.
12a. Answer: Standing seam fall protection will be installed south of EF-3. Roof hatch dimensions are: 43” x 36”
13. BLDG 130 – No picture included.
Please provide picture, locations and dimensions of hatches.
13a. Answer: Dimensions are: 43” x 37”.
14. BLDG 400-406 – Not listed in RFI.
Will this be included in the RFI? Is the ask for warning lines? Please advise length and locations.
14a. Answer: Buildings 400-406 are not included in the PWS and should not be included in the bid.
15. BLDG 300 – No picture included.
Please provide picture, location and dimensions of hatch.
15a. Answer: 300 is no longer a requirement for this PWS and will be removed with the addendum.
16. BLDG 500 – Not included in RFI.
If included, please provide length of rail and dimensions of hatch.
16a. Answer: Building 500 is not listed in the PWS and should not be included in the bid.
17. BLDG 600 – please provide dimensions of hatch.
17a. Answer: Approximately 42” x 36”.
18. BLDG 700 – RFI shows (1) hatch. Pictures show (2) hatches. Please advise and provide dimensions.
Picture appears to show (7) guardrail locations. RFI shows (6). Please advise.
18a. Answer: Please include 2 roof hatches and 7 guardrail locations per the google maps image. Roof hatches dimensions are 42” x 36”.
19. BLDG 800 – Pictures show (2) corners. RFI requests (1) corner. Please advise number and location. Please advise roof hatch dimensions.
19a. Answer: Please include 2 corners as listed in the picture; one in the NW corner and one SE of the solar heat rejector. Roof hatch dimensions are 40” x 34”.
20. Pictures show MSAT BLDG. Not included in RFI. Is this included? Pictures show 258’ total LF of guardrail. Is this accurate? Please advise.
20a. Answer: MSAT building is not listed in the PWS and should not be included in the bid.