Renovate Alert Rooms, 3390
NJANG Project No. PTFL 192102
NEW JERSEY AIR NATIONAL GUARD
108TH Wing
Joint Base McGuire-Dix-Lakehurst, New Jersey
July 15, 2022
Specifications
1029340907M Cross-Out
NJ Air National Guard Joint Base McGuire-Dix-Lakehurst
Project #PTFL 192102
July 15, 2022
TABLE OF CONTENTS 000110 - 3
SECTION 000110
TABLE OF CONTENTS
DIVISION 09 -- FINISHES
09 5113 – Ceramic Tile 09 5113 – Acoustical Panel Ceilings 09 6500 – Resilient Flooring 09 9000 – Painting and Coating
DIVISION 10 -- SPECIALTIES
10 2800 – Toilet and Bath Accessories
DIVISION 12 - CABNIETRY
12 3661 – Solid Surface Countertops
DIVISION 22 – PLUMBING
22 0523.12 – General Ball Valves for Plumbing Piping 22 0523.14 – Check Valves for Plumbing Piping 22 0719 – Plumbing Piping Insulation 22 1116 – Domestic Water Piping 22 1119 – Domestic Water Piping Specialties 22 1316 – Sanitary Water and Vent 22 1319 – Sanitary Waste Piping Specialties 22 1319.13 – Sanitary Drains 22 4213 – Commercial Water Closets
22 4216 – Commercial Lavatories 22 4223 – Commercial Showers
SECTION 09 30 00
SECTION 09 30 00
CERAMIC TILE, QUARRY TILE, AND PAVER TILE
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM A 185/A 185M (2007) Standard Specification for SteelWelded Wire Reinforcement, Plain, for Concrete
ASTM C 1026 (1987; R 2002) Standard Test Method for Measuring the Resistance of Ceramic Tile to Freeze-Thaw Cycling
ASTM C 1027 (1999; R 2004) Standard Test Method for Determining Visible Abrasion Resistance of Glazed Ceramic Tile
ASTM C 1028 (2007) Standard Test Method for Determining the Static Coefficient of Friction of Ceramic Tile and Other Like Surfaces by the Horizontal Dynamometer Pull-Meter Method
ASTM C 1178/C 1178M (2006) Standard Specification for Glass Mat Water-Resistant Gypsum Backing Panel
ASTM C 144 (2004) Standard Specification for Aggregate for Masonry Mortar
ASTM C 150 (2007) Standard Specification for Portland Cement
ASTM C 206 (2003) Standard Specification for Finishing Hydrated Lime
ASTM C 207 (2006) Standard Specification for Hydrated Lime for Masonry Purposes
ASTM C 241 (1990; R 2005) Standard Specification for Abrasion Resistance of Stone Subjected to Foot Traffic
ASTM C 33 (2007) Standard Specification for Concrete Aggregates
ASTM C 373 (1988; R 2006) Water Absorption, Bulk Density, Apparent Porosity, and Apparent Specific Gravity of Fired Whiteware Products
SECTION 09 30 00
ASTM C 482 (2002) Bond Strength of Ceramic Tile to Portland Cement
ASTM C 501 (1984; R 2002) Relative Resistance to Wear of Unglazed Ceramic Tile by the Taber Abraser
ASTM C 648 (2004) Breaking Strength of Ceramic Tile
ASTM C 847 (2006) Standard Specification for Metal Lath
ASTM D 2103 (2005) Standard Specification for Polyethylene Film and Sheeting
ASTM D 226 (2006) Standard Specification for Asphalt- Saturated Organic Felt Used in Roofing and Waterproofing
ASTM F 446 (1985; R 2004e1) Grab Bars and Accessories Installed in the Bathing Area
MARBLE INSTITUTE OF AMERICA (MIA)
MIA Design Manual (2003) Dimension Stone Design Manual NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA)
NFPA 99 (2005; Errata 2005) Health Care Facilities TILE COUNCIL OF AMERICA
(TCA)
TCA Hdbk (2007) Handbook for Ceramic Tile Installation
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings Detail Drawings; G
Drawings showing ceramic tile pattern elevations and floor plans.
SD-03 Product Data
Tile; G Setting-Bed; G Mortar, Grout, and Adhesive; G
Manufacturer's catalog data and preprinted installation and cleaning instructions.
SD-04 Samples
Tile; G Accessories; G Marble Thresholds; G Grout; G
Samples of sufficient size to show color range, pattern, type and joints.
SD-06 Test Reports Testing; G Copy of results for electrical resistance tests.
SD-07 Certificates Tile; G Mortar, Grout, and Adhesive; G
Certificates indicating conformance with specified requirements.
Furnish a master grade certificate for tile.
SD-11 Closeout Submittals Local/Regional Materials; (LEED) LEED documentation relative to local/regional materials credit in accordance with LEED Reference Guide. Include in LEED Documentation Notebook.
Tile; (LEED)
Reinforcing Wire Fabric; (LEED)
LEED documentation relative to recycled content credit in accordance with LEED Reference Guide. Include in LEED Documentation Notebook.
Adhesives; (LEED)
LEED documentation relative to low-emitting materials credit in accordance with LEED Reference Guide. Include in LEED Documentation Notebook.
1.3 DELIVERY AND STORAGE
Deliver materials to the project site in manufacturer's original unopened containers with seals unbroken and labels and hallmarks intact. Protect materials from weather, and stored under cover in accordance with manufacturer's printed instructions.
1.4 ENVIRONMENTAL REQUIREMENTS
Do not perform ceramic tile work unless the substrate and ambient temperature is at least 50 degrees F and rising. Maintain temperature above50 degrees F while the work is being performed and for at least 7 days after completion of the work. When temporary heaters are used, ventilate the area to the outside to avoid carbon dioxide damage to new tilework.
1.5 SUSTAINABLE DESIGN REQUIREMENTS
1.5.1 Local/Regional Materials
Use materials or products extracted, harvested, or recovered, as well as manufactured, within a 500 mile radius from the project site, if available from a minimum of three sources.See Section 01 33 29 LEED(tm) DOCUMENTATION for cumulative total local material requirements. Tile materials may be locally available.
1.6 WARRANTY
Provide manufacturer's standard performance guarantees or warranties that extend beyond a 1-year period.
1.7 EXTRA STOCK
Supply an extra two percent of each type tile used in clean and marked cartons.
1.8 DETAIL DRAWINGS
Dimension and draw detail drawings at a minimum scale of 1/4 inch = 1 foot. Include drawings of pattern at inside corners, outside corners, termination points and location of all equipment items such as thermostats, switch plates, mirrors and toilet accessories mounted on surface.
PART 2 PRODUCTS
2.1 TILE
Conform to TCA Hdbk for standard grade tile. Provide grade sealed containers. Mark seals with the marks on the signed master grade certificate. Provide an impact resistant tile with a minimum floor breaking strength for wall tile of 90 pound and for floor tile of 250 pound in accordance with ASTM C 648. The manufacturer will provide a frost resistant rating for tile used in cold climate projects as determined by ASTM C 1026.
Provide a 0.50 maximum percent water absorption in accordance with ASTM C 373.
Provide a minimum coefficient of friction of
0.50 wet and dry in accordance with ASTM C 1028. Identify floor tile as Class III- Medium Heavy Traffic, durability classification as rated by the manufacturer when tested in accordance with ASTM C 1027 for abrasion resistance as related to foot traffic.
Coordinate the color as indicated.
Tile shall contain a minimum of 5 percent post-consumer recycled content, or a minimum of 20 percent post-industrial recycled content, unless specified otherwise.See Section 01 33 29 LEED(tm) DOCUMENTATION for cumulative total recycled content requirements. Tile may contain post-consumer or post- industrial recycled content.
2.1.1 Mosaic Tile
Furnish ceramic mosaic tile and trim shall be unglazed natural clay with cushion edges.
Provide tile size as indicated. Coordinate color with Section 09 06 90 COLOR
SCHEDULE.
2.1.2 Quarry Tile
Furnish an unglazed quarry tile and trim with smooth surface. Quarry tile shall contain a minimum of 17 percent post-industrial recycled content.
Usesize indicated. Coordinate color with Section 09 06 90 COLOR SCHEDULE .
2.1.3 Paver Tile
Furnish indicated size paver tile unglazed. Coordinate color with Section 09 06 90
COLOR SCHEDULE .
2.1.4 Detectable Warning Tile
Furnish an unglazed detectable warning tile with raised truncated domes with a diameter of nominal 0.9 inch at a height of nominal 0.2 inch and a center- to-center spacing of nominal 2.35 inch that contrast visually with adjoining surfaces. Provide tile size indicated. Coordinate color with Section 09 06
90 COLOR SCHEDULE .
2.1.5 Porcelain Tile
Furnish an unglazed porcelain tile and trim with the color extending uniformly through the body of the tile. Porcelain tile shall contain a minimum of 70 percent post-industrial feldspar. Provide a nominal size indicated by 5/16 inch thick. Criteria for tile to meet or exceed is as follows: Abrasive wear in accordance with ASTM C 501 and bonding strength in accordance with ASTM C 482. Comply with 36 CFR 1191 for coefficient of friction for interior tiled floors. Coordinate color with Section 09 06 90 COLOR
SCHEDULE .
2.1.6 Glazed Wall Tile
Provide glazed wall tile with cushioned edges and trim edged with lead-free matte finish.
Provide tile of size indicated. Coordinate color with Section 09 06 90 COLOR
SCHEDULE .
2.1.7 Accessories
Provide built-in type accessories of the same materials and finish as the wall tile. Provide accessories as follows in quantities and locations indicated on the Drawings:
a. Recessed soap holders
b. Tumbler holders
c. Combination tumbler and toothbrush holders
d. Towel bars, stainless steel length as indicated, two towel posts
e. Robe hooks
f. Roll paper holder
g. Recessed soap holder and hand hold combination:
support static load in compliance with ASTM F 446
2.2 SETTING-BED
Compose the setting-bed of the following materials.
2.2.1 Aggregate for Concrete Fill
Conform to ASTM C 33 for aggregate fill. Do not exceed one-half the thickness of concrete fill for maximum size of coarse aggregate.
2.2.2 Portland Cement
Conform to ASTM C 150 for cement, Type I, white or gray depending on color and type of tile selected.
2.2.3 Sand
Conform to ASTM C 144 for sand.
2.2.4 Hydrated Lime
Conform to ASTM C 206 for hydrated lime, Type S or ASTM C 207, Type S.
2.2.5 Metal Lath
Conform to ASTM C 847 for flat expanded type metal lath, and weighing a minimum 2.5 pound/square yard.
2.2.6 Reinforcing Wire Fabric
Conform to ASTM A 185/A 185M for wire fabric. Provide 2 by 2 inch mesh, 16/16 wire .
Wire fabric shall be manufactured from a minimum of 80 percent recycled post-consumer waste and a minimum of 10 percent recycled post- industrial waste.See Section 01 33 29 LEED(tm) DOCUMENTATION for cumulative total recycled content requirements. Wire fabric may contain post-consumer or post-industrial recycled content.
2.3 WATER
Provide potable water.
2.4 MORTAR, GROUT, AND ADHESIVE
Interior adhesives, sealants, primers and sealants used as filler must meet the requirements of LEED low emitting materials credit. Conform to, and to the following for mortar, grout, adhesive, and sealant.
2.4.1 Dry-Set Portland Cement Mortar TCA Hdbk.
2.4.2 Conductive Dry-Set Mortar TCA Hdbk.
2.4.3 Latex-Portland Cement Mortar TCA Hdbk.
2.4.4 Ceramic Tile Grout
TCA Hdbk; petroleum-free and plastic-free latex-portland cement grout.
2.4.5 Organic Adhesive
TCA Hdbk, Type I. Water-resistant. Comply with applicable regulations regarding toxic and hazardous materials and as specified.
2.4.6 Epoxy Resin Grout TCA Hdbk.
2.4.7 Furan Resin Grout
TCA Hdbk and consist of an intimate mixture of furfuryl-alcohol resin with carbon filler and catalyst.
2.4.8 Sealants
Comply with applicable regulations regarding toxic and hazardous materials and as specified.
2.4.9 Cementitious Backer Board
Provide cementitious backer units, for use as tile substrate over wood sub- floors, in accordance with TCA Hdbk. Furnish 1/2 inch thick cementitious backer units.
2.4.10 Glass Mat Gypsum Backer Panel
Provide glass mat water-resistant gypsum backer board, for use as tile substrate over wood subfloors, in accordance with ASTM C 1178/C 1178M. Provide 1/2 inch thick glass mat gypsum backer board.
2.5 MARBLE THRESHOLDS
Provide marble thresholds of size required by drawings or conditions. Categorize marble Group A as classified by MIA Design Manual. Provide a fine sand-rubbed finish marble with white pink or gray in color as approved by the Contracting Officer. Provide minimum
12.0 marble abrasion when tested in accordance with ASTM C 241.
2.6 MEMBRANE MATERIALS
Conform to ASTM D 226, Type 1 for 15 pound waterproofing membrane, asphalt-saturated building felt. Conform to ASTM D 2103 4 mil for polyethylene film.
PART 3 EXECUTION
3.1 PREPARATORY WORK AND WORKMANSHIP
Inspect surface to receive tile in conformance to the requirements of TCA Hdbk for surface conditions for the type setting bed specified and for workmanship. Provide variations of tiled surfaces that fall within maximum values shown below:
TYPE WALLS FLOORS
Dry-Set Mortar 1/8 inch in 8 ft. 1/8 inch in 10 ft.
Organic Adhesives 1/8 inch in 8 ft. 1/16 inch in 3 ft.
Latex Portland Cement Mortar 1/8 inch in 8 ft. 1/8 inch in 10 ft.
Epoxy 1/8 inch in 8 ft. 1/8 inch in 10 ft.
3.2 GENERAL INSTALLATION REQUIREMENTS
Do not start tile work until roughing in for mechanical and electrical work has been completed and tested, and built-in items requiring membrane waterproofing have been installed and tested. Do not start floor tile installation in spaces requiring wall tile until after wall tile has been installed. Apply tile in colors and patterns indicated in the area shown on the drawings. Install tile with the respective surfaces in true even planes to the elevations and grades shown. Provide special shapes as required for sills, jambs, recesses, offsets, external corners, and other conditions to provide a complete and neatly finished installation. Solidly back tile bases and coves with mortar.
3.3 INSTALLATION OF WALL TILE
Install wall tile in accordance with the TCA Hdbk, for the installation method specified.
3.3.1 Workable or Cured Mortar Bed
Install tile over workable mortar bed or a cured mortar bed at the option of the Contractor.
Install a 4 mil polyethylene membrane, metal lath, and scratch coat. Conform to TCA Hdbk for workable mortar bed, materials, and installation of tile. Conform to TCA Hdbk for cured mortar bed and materials.
3.3.2 Dry-Set Mortar and Latex-Portland Cement Mortar
Use Dry-set or Latex-Portland Cement to install tile in accordance with TCA Hdbk. Use Latex Portland Cement when installing porcelain ceramic tile.
Organic Adhesive
Conform to TCA Hdbk for the organic adhesive installation of ceramic tile.
3.3.3 Furan Mortar and Grout
Conform to TCA Hdbk for furan mortar and grout installation.
3.4 INSTALLATION OF FLOOR TILE
Install floor tile in accordance with TCA Hdbk method for the installation method indicated. Install shower receptors in accordance with TCA Hdbk method B414 or B415.
3.4.1 Workable or Cured Mortar Bed
Install floor tile over a workable mortar bed or a cured mortar bed at the option of the Contractor. Conform to TCA Hdbk for workable mortar bed materials and installation.
Conform to TCA Hdbk for cured mortar bed materials and installation. Provide minimum 1/4 inch to maximum 3/8 inch joints in uniformed width.
3.4.2 Dry-Set and Latex-Portland Cement
Use dry-set or Latex-Portland cement mortar to install tile directly over properly cured, plane, clean concrete slabs in accordance with TCA Hdbk. Use Latex Portland cement when installing porcelain ceramic tile.
3.4.3 Resinous Grout
When resinous grout is indicated, grout quarry tile with either furan or epoxy resin grout.
Rake and clean joints to the full depth of the tile and neutralize when recommended by the resin manufacturer. Install epoxy resin grout in conformance with TCA Hdbk. Install resin grout in accordance with manufacturer's printed installation instructions. Provide a coating of wax applied from the manufacturer on all tile installed and furan resin. Follow manufacturer's printed installation instructions of installed resin grout for proportioning, mixing, installing, and curing. Maintain the recommended temperature in the area and on the surface to be grouted. Protect finished grout of grout stain.
3.4.4 Ceramic Tile Grout
Prepare and install ceramic tile grout in accordance with TCA Hdbk.
3.4.5 Waterproofing
Shower pans are specified in Section 22 00 00 PLUMBING, GENERAL PURPOSE.
Conform to the requirements of Section 07 12 00 BUILT-UP BITUMINOUS WATERPROOFING for waterproofing under concrete fill.
3.4.6 Concrete Fill
Provide a 3,500 psi concrete fill mix to dry as consistency as practicable. Compose concrete fill by volume of 1 part Portland cement to 3 parts fine aggregate to 4 parts coarse aggregate, and mix with water to as dry a consistency as practicable. Spread, tamp, and screed concrete fill to a true plane, and pitch to drains or levels as shown. Thoroughly damp concrete fill before applying setting-bed material. Reinforce concrete fill with one layer of reinforcement, with the uncut edges lapped the width of one mesh and the cut ends and edges lapped a minimum 2 inch. Tie laps together with 18 gauge wire every 10 inch along the finished edges and every 6 inch along the cut ends and edges. Provide reinforcement with support and secure in the centers of concrete fills. Provide a continuous mesh; except where expansion joints occur, cut mesh and discontinue across such joints. Provide reinforced concrete fill under the setting-bed where the distance between the under-floor surface and the finished tiles floor surface is a minimum 2 inch, and of the same thickness that the mortar setting-bed over the concrete fill with the thickness required in the specified TCA Hdbk method.
3.5 INSTALLATION OF CONDUCTIVE FLOORING
Install conductive ceramic mosaic tile floors in accordance with TCA Hdbk.
3.6 INSTALLATION OF MARBLE THRESHOLDS
Install thresholds where indicated, in a manner similar to that of the ceramic tile floor.
Provide thresholds full width of the opening. Install head joints at ends not exceeding 1/4 inch in width and grouted full.
3.7 TESTING
Perform electrical resistance tests on conductive flooring, in the presence of the Contracting Officer, by a technician experienced in such work.
Furnish a copy of the test results. Provide test procedures, testing apparatus, and test results in accordance with the provisions for Conductive Flooring in NFPA 99.
3.8 EXPANSION JOINTS
Form and seal joints as specified in Section 07 92 00JOINT SEALANTS.
3.8.1 Walls
Provide expansion joints at control joints in backing material. Wherever backing material changes, install an expansion joint to separate the different materials.
3.8.2 Floors
Provide expansion joints over construction joints, control joints, and expansion joints in concrete slabs. Provide expansion joints where tile abuts restraining surfaces such as perimeter walls, curbs and columns and at intervals of 24 to 36 feet each way in large interior floor areas and 12 to 16 feet each way in large exterior areas or areas exposed to direct sunlight or moisture. Extend expansion joints through setting-beds and fill.
3.9 CLEANING AND PROTECTING
Upon completion, thoroughly clean tile surfaces in accordance with manufacturer's approved cleaning instructions. Do not use acid for cleaning glazed tile. Clean floor tile with resinous grout or with factory mixed grout in accordance with printed instructions of the grout manufacturer. After the grout has set, provide a protective coat of a noncorrosive soap or other approved method of protection for tile wall surfaces. Cover tiled floor areas with building paper before foot traffic is permitted over the finished tile floors. Provide board walkways on tiled floors that are to be continuously used as passageways by workmen. Replace damaged or defective tiles.
3.10 WASTE MANAGEMENT
Separate waste, including metal and cardboard, in accordance with the Waste Management Plan and recycle or reuse. Place materials defined as hazardous or toxic waste, including used sealant and adhesive tubes and containers, in designated containers and areas. Close and seal tightly partly used sealant and adhesive containers and store in protected, well-ventilated, fire-safe area at moderate temperature. Place materials defined as hazardous or toxic waste, including used sealant and adhesive tubes and containers, in designated containers and areas and dispose of properly.
-- End of Section --
Renovate Alert Rooms, 3390
Project #PTFL 192102
ACOUSTICAL PANEL CEILINGS 095113 - 1
SECTION 095113 - ACOUSTICAL PANEL CEILINGS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section includes acoustical panels and exposed suspension systems for ceilings.
1.3 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project site.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product.
B. Samples for Verification: For each component indicated and for each exposed finish required, prepared on Samples of size indicated below.
1. Acoustical Panel: Set of 6-inch- (150-mm-) square Samples of each type, color, pattern, and texture.
2. Exposed Suspension-System Members, Moldings, and Trim: Set of 6-inch- (150-mm-) long Samples of each type, finish, and color.
1.5 INFORMATIONAL SUBMITTALS
A. Coordination Drawings: Reflected ceiling plans, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved:
1. Suspended ceiling components.
2. Structural members to which suspension systems will be attached.
3. Size and location of initial access modules for acoustical panels.
4. Items penetrating finished ceiling including the following:
a. Lighting fixtures.
b. Air outlets and inlets.
c. Speakers.
d. Sprinklers.
e. Access panels.
Renovate Alert Rooms, 3390
Project #PTFL 192102
ACOUSTICAL PANEL CEILINGS 095113 - 2
f. A/V equipment
5. Perimeter moldings.
B. Product Test Reports: For each acoustical panel ceiling, for tests performed by manufacturer and witnessed by a qualified testing agency. Evaluation Reports: For each acoustical panel ceiling suspension system and anchor and fastener type, from ICC-ES.
1.6 CLOSEOUT SUBMITTALS
A. Maintenance Data: For finishes to include in maintenance manuals.
1.7 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Acoustical Ceiling Panels: Full-size panels equal 2 percent of quantity installed.
2. Suspension-System Components: Quantity of each exposed component equal to 2 percent of quantity installed.
1.8 DELIVERY, STORAGE, AND HANDLING
A. Deliver acoustical panels, suspension-system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, temperature extremes, direct sunlight, surface contamination, and other causes.
B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content.
C. Handle acoustical panels carefully to avoid chipping edges or damaging units in any way.
1.9 FIELD CONDITIONS
A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use.
1. Pressurized Plenums: Operate ventilation system for not less than 48 hours before beginning acoustical panel ceiling installation.
Renovate Alert Rooms, 3390
Project #PTFL 192102
ACOUSTICAL PANEL CEILINGS 095113 - 3
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency.
Identify products with appropriate markings of applicable testing agency.
1. Flame-Spread Index: Comply with ASTM E 1264 for Class A materials.
2. Smoke-Developed Index: 50 or less.
B. Fire-Resistance Ratings: Comply with ASTM E 119; testing by a qualified testing agency.
Identify products with appropriate markings of applicable testing agency.
1. Indicate design designations from UL's "Fire Resistance Directory" or from the listings of another qualified testing agency.
2.2 ACOUSTICAL PANELS, GENERAL
A. Source Limitations: Obtain each type of acoustical ceiling panel and supporting suspension system from single source from single manufacturer.
B. Glass-Fiber-Based Panels: Made with binder containing no urea formaldehyde.
C. Acoustical Panel Standard: Provide manufacturer's standard panels of configuration indicated that comply with ASTM E 1264 classifications as designated by types, patterns, acoustical ratings, and light reflectances unless otherwise indicated.
1. Mounting Method for Measuring NRC: Type E-400; plenum mounting in which face of test specimen is 15-3/4 inches (400 mm) away from test surface according to ASTM E 795.
D. Acoustical Panel Colors and Patterns: Match appearance characteristics indicated for each product type.
2.3 ACOUSTICAL PANELS (ACP-1)
A. Basis-of-Design Product: Subject to compliance with requirements, provide Armstrong World Industries Mesa 2’x2’ Tegular Tile for 15/16” grid, Item 686 or comparable product by one of the following:
1. CertainTeed Corp.
2. USG Interiors, Inc.; Subsidiary of USG Corporation.
B. Classification: Provide Class A panels complying with ASTM E 1264 for type, form, and pattern as follows:
1. Type and Form: Type III, mineral base with painted finish; Form 2, water felted.
2. Pattern: CE (perforated, small holes and lightly textured).
http://www.specagent.com/LookUp/?ulid=344&mf=04&mf=95&src=wd&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456792923&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456815586&mf=04&src=wd
Renovate Alert Rooms, 3390
Project #PTFL 192102
ACOUSTICAL PANEL CEILINGS 095113 - 4
C. Color: White
D. LR: ASTM E 1477; White Panel: Light Reflectance not less than 0.85.
E. NRC: ASTM C 423; Classified with UL label on product carton, not less than 0.60.
F. CAC: ASTM C 1414; Classified with UL label on product carton, not less than 40.
G. Edge/Joint Detail: Angled Tegular for interface with Prelude XL 15/16” Exposed Tee.
H. Thickness: 3/4”.
I. Modular Size: 24 by 24 inches.
J. Fungicide and Bactericide Treatment: Provide acoustical panels treated with manufacturer's standard antimicrobial formulation that inhibits fungus, mold, mildew, and gram- positive and gram-negative bacteria and showing no mold, mildew, or bacterial growth when tested according to ASTM D 3273 and evaluated according to ASTM D 3274 or ASTM G 21.
2.4 METAL SUSPENSION SYSTEMS, GENERAL
A. Metal Suspension-System Standard: Provide manufacturer's standard direct-hung metal suspension systems of types, structural classifications, and finishes indicated that comply with applicable requirements in ASTM C 635/C 635M.
1. High-Humidity Finish at Toilet Rooms and other wet areas: Comply with ASTM
C 635/C 635M requirements for "Coating Classification for Severe Environment Performance" where high-humidity finishes are indicated.
B. Components: Main runner and cross tees shall be double-web hot dipped galvanized steel construction per ASTM A635 with 15/16” type exposed flange design, unless otherwise indicated.
Members shall be fire/flame rated and seismic zone rated. Each exposed bottom flange shall be continuous with unbroken roll formed cap the length of the member. Cap shall be steel, finished as specified below.
1. Structural Classification: Intermediate duty.
2. Main Beam: Routed 6” center to center, continuously along the length of its web to locate intersecting cross tees. Web Height shall be 1-1/2”.
3. 4’ Cross Tees: Web height shall be 1-1/2”.
4. 2’ Cross Tees: Web height shall be 1-3/8”.
5. End condition of Cross Tees: Staked-on (stab) end detail with override flange.
C. Cross Tee shall be double web bulb section of steel conforming to ASTM A 366, web height 1-
1/2” and have a 15/16” bottom flange. Exposed bottom flange shall be continuous with unbroken roll formed cap the length of the member.
D. Attachment Devices: Size for five times the design load indicated in ASTM C 635/C 635M, Table
1, "Direct Hung," unless otherwise indicated. Comply with seismic design requirements.
Renovate Alert Rooms, 3390
Project #PTFL 192102
ACOUSTICAL PANEL CEILINGS 095113 - 5
E. Wire Hangers, Braces, and Ties: Provide wires complying with the following requirements:
1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper.
2. Size: Select wire diameter so its stress at three times hanger design load (ASTM
C 635/C 635M, Table 1, "Direct Hung") will be less than yield stress of wire but provide not less than 12 gauge diameter wire.
F. Hanger Rods or Flat Hangers: Mild steel, zinc coated or protected with rust-inhibitive paint.
G. Angle Hangers: Angles with legs not less than 7/8 inch (22 mm) wide; formed with 0. 04- inch-
(1-mm-) thick, galvanized-steel sheet complying with ASTM A 653/A 653M, G90 (Z275) coating designation; with bolted connections and 5/16-inch- (8-mm-) diameter bolts.
H. Hanger Channels shall be 1 1/2”; 0.475 lb. per 1,000 ft.; cold rolled steel or 1.12 lb. per 1,000 ft.
hot rolled steel for integrating with metal stud framing for supporting suspended ceiling system.
I. Stiffening Brace shall be provided to the entire grid system of vestibule areas leading to the exterior and within 10 feet of exterior doors in areas exposed to wind uplift of up to 90 lbs./sq.
ft. Brace shall be attached between the upper and lower ties on each vertical hanger wire.
Combine with hold-down clips.
J. Hold-Down Clips: Where indicated, provide manufacturer's standard hold-down clips spaced 24 inches o.c. on all cross tees.
K. Impact Clips: Where indicated, provide manufacturer's standard impact-clip system designed to absorb impact forces against acoustical panels.
L. Lighting fixtures to have lighting fixture support clips in addition to being supported from above independent of ceiling grid.
M. Seismic Stabilizer Bars: Manufacturer's standard perimeter stabilizers designed to accommodate seismic forces.
N. Seismic Struts: Manufacturer's standard compression struts designed to accommodate seismic forces.
O. Seismic Clips: Manufacturer's standard seismic clips designed and spaced to secure acoustical panels in place.
2.5 METAL SUSPENSION SYSTEM (ACP 1)
A. Manufacturers: Subject to compliance with requirements, provide products by the following
B. Basis-of-Design Product: Subject to compliance with requirements, provide Armstrong Prelude XL 15/16” Exposed Tee or comparable product by one of the following:
1. CertainTeed Corp.
2. USG Interiors, Inc.; Subsidiary of USG Corporation.
http://www.specagent.com/LookUp/?ulid=345&mf=04&mf=95&src=wd&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456792930&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456815587&mf=04&src=wd
Renovate Alert Rooms, 3390
Project #PTFL 192102
ACOUSTICAL PANEL CEILINGS 095113 - 6
C. Wide-Face, Capped, Double-WebSteel Suspension System: Main and cross runners roll formed from cold-rolled steel sheet; prepainted, electrolytically zinc coated, or hot-dip galvanized according to ASTM A 653/A 653M, not less than G30 (Z90) coating designation; with prefinished 15/16-inch- (24-mm-) wide metal caps on flanges.
1. Structural Classification: Intermediate-duty system.
2. End Condition of Cross Runners: Override (stepped) type.
3. Face Design: Flat, flush.
4. Cap Material: Steel or aluminum cold-rolled sheet.
5. Cap Finish: Pre-finishaed galvanized steel (aluminum or stainless steel) in baked polyester paint.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, including structural framing to which acoustical panel ceilings attach or abut, with Installer present, for compliance with requirements specif ied in this and other Sections that affect ceiling installation and anchorage and with requirements for installation tolerances and other conditions affecting performance of acoustical panel ceilings.
B. Examine acoustical panels before installation. Reject acoustical panels that are wet, moisture damaged, or mold damaged.
C. Pre-Installation Conference: Prior to the start of acoustical ceiling installation, meet at the Project Site with the Installers of related work, including lighting, sprinklers, ductwork and similar work in the ceiling plenum. Review areas of potential interference and resolve conflicts before proceeding with the work. Coordinate ceiling layout with the layout of other work that penetrates or is supported by the ceiling in each space of the building.
D. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Measure each ceiling area and establish layout of acoustical panels to balance border widths at opposite edges of each ceiling. Unless otherwise indicated on the drawings, avoid using less-than-half-width panels at borders, and comply with layout shown on reflected ceiling plans.
3.3 INSTALLATION
A. General: Install acoustical panel ceilings to comply with ASTM C 636, according to manufacturer's written instructions and CISCA's "Ceiling Systems Handbook." Comply with governing regulations, referenced standards, industry standards applicable to the work and as shown on final approved shop drawings.
Renovate Alert Rooms, 3390
Project #PTFL 192102
ACOUSTICAL PANEL CEILINGS 095113 - 7
1. Fire-Rated Assembly: Install fire-rated ceiling systems according to tested fire-rated design.
B. Suspend ceiling hangers from building's structural members and as follows:
1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structure or of ceiling suspension system.
2. Splay hangers only where required and, if permitted with fire-resistance-rated ceilings, to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means.
3. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with location of hangers at spacings required to support standard suspension-system members, install supplemental suspension members and hangers in form of trapezes or equivalent devices.
4. Secure wire hangers to ceiling-suspension members and to supports above with a minimum of three tight turns. Connect hangers directly either to structures or to inserts, eye screws, or other devices that are secure and appropriate for substrate and that will not deteriorate or otherwise fail due to age, corrosion, or elevated temperatures.
5. Secure flat, angle, channel, and rod hangers to structure, including intermediate framing members, by attaching to inserts, eye screws, or other devices that are secure and appropriate for both the structure to which hangers are attached and the type of hanger involved. Install hangers in a manner that will not cause them to deteriorate or fail due to age, corrosion, or elevated temperatures.
6. Do not support ceilings directly from permanent metal forms or floor deck. Fasten hangers to cast-in-place hanger inserts, postinstalled mechanical or adhesive anchors, or power-actuated fasteners that extend through forms into concrete.
7. When steel framing does not permit installation of hanger wires at spacing required, install carrying channels or other supplemental support for attachment of hanger wires.
8. Do not attach hangers to steel deck tabs.
9. Do not attach hangers to steel roof deck. Attach hangers to structural members.
10. Space hangers not more than 48 inches o.c. along each member supported directly from hangers unless otherwise indicated; provide hangers not more than 8 inches from ends of each member.
11. Size supplemental suspension members and hangers to support ceiling loads within performance limits established by referenced standards and publications.
C. Secure bracing wires to ceiling suspension members and to supports with a minimum of four tight turns. Suspend bracing from building's structural members as required for hangers, without attaching to permanent metal forms, steel deck, or steel deck tabs. Fasten bracing wires into concrete with cast-in-place or postinstalled anchors.
D. Install edge moldings and trim of type indicated at perimeter of acoustical ceiling area and where necessary to conceal edges of acoustical panels.
1. Apply acoustical sealant in a continuous ribbon concealed on back of vertical legs of moldings before they are installed.
2. Screw attach moldings to substrate at intervals not more than 16 inches o.c. and not more than 3 inches from ends, leveling with ceiling suspension system to a tolerance of 1/8 inch in 12 feet. Miter corners accurately and connect securely.
3. Do not use exposed fasteners, including pop rivets, on moldings and trim.
Renovate Alert Rooms, 3390
Project #PTFL 192102
ACOUSTICAL PANEL CEILINGS 095113 - 8
E. Suspend main runners not more than 48" center-to-center, from overhead structure by not less than #12 gauge galvanized steel wire spaced 48", center-to-center, accurately leveled. Join cross tees to main runners through pre-routed openings in runners, locking webs together by means of die-formed end tabs to form a positive interlock. Main runners and cross tees shall rest on angel moldings at walls.
F. Install suspension-system runners so they are square and securely interlocked with one another.
Remove and replace dented, bent, or kinked members.
G. Install acoustical panels with undamaged edges and fit accurately into suspension-system runners and edge moldings. Scribe and cut panels at borders and penetrations to provide a neat, precise fit.
1. Arrange directionally patterned acoustical panels as indicated on reflected ceiling plans.
2. For square-edged panels, install panels with edges fully hidden from view by flanges of suspension-system runners and moldings.
3. For reveal-edged panels on suspension-system runners, install panels with bottom of reveal in firm contact with top surface of runner flanges.
4. For reveal-edged panels on suspension-system members with box-shaped flanges, install panels with reveal surfaces in firm contact with suspension-system surfaces and panel faces flush with bottom face of runners.
5. Paint cut edges of panel remaining exposed after installation; match color of exposed panel surfaces using coating recommended in writing for this purpose by acoustical panel manufacturer.
6. Install hold-down and/or impact clips in areas indicated, in areas required by author ities having jurisdiction, and for fire-resistance ratings; space as recommended by panel manufacturer's written instructions unless otherwise indicated.
7. Protect lighting fixtures and air ducts to comply with requirements indicated for fire-resistance-rated assembly.
H. Apply acoustic sealant, concealed on backs of vertical legs of trim moldings; at ceiling perimeters;
around penetrating fixtures and elsewhere as required.
3.4 COORDINATION
A. Cooperate with other trades for installation of their materials and equipment, particularly with those installing the ductwork ceiling diffusers, electrical fixtures and plumbing fixtures so that diffusers, lighting fixtures and other items are located on center lines of tile or on centers of joints, as shown on approved shop drawings.
B. Where light fixtures or other recessed items occur in ceilings, frame properly to permit installation of such recessed items, and do all necessary cutting and fitting of acoustical materials and suspension systems to accommodate work. Cut neatly around all pipes passing through ceilings.
3.5 CLEANING AND PROTECTION
Renovate Alert Rooms, 3390
Project #PTFL 192102
ACOUSTICAL PANEL CEILINGS 095113 - 9
A. Clean exposed surfaces of acoustical ceilings, including trim, edge moldings and suspension members; comply with manufacturer's instruction for cleaning and touch-up of minor finish damage. Remove and replace work which cannot be successfully cleaned and repaired to permanently eliminate evidence of damage.
B. The Installer shall advise the Contractor of required protection for the acoustical ceilings, including temperature and humidity limitations and dust control, so that the work will be without damage and deterioration at the time of acceptance by the Owner.
END OF SECTION 095113
RESILIENT FLOORING 096500 -
SECTION 096500 - RESILIENT FLOORING
1.2 DESCRIPTION OF WORK
A. Provide all labor, materials, accessories, equipment and incidentals to complete Resilient Flooring work, as shown and/or specified, including but not necessarily limited to the following:
1. Luxury Vinyl Flooring.
2. Resilient Flooring Accessories.
3. Inspection and preparation of subfloors.
B. Related Sections Specified Elsewhere:
Cast-In-Place Concrete Division 3 Miscellaneous Metals Division 5 Rough Carpentry Division 6
1.3 QUALITY ASSURANCE
A. Installer Qualifications: Engage an experienced installer to perform work of this Section who has specialized in installing resilient floor coverings of the type(s) required for this Project and with a record of successful in-service performance and who is certified or approved by the flooring manufacturer.
B. Source Limitations: Obtain each type, color, and pattern of each type of resilient flooring product specified from one source for each resilient floor covering product with resources to provide products of consistent quality in appearance and physical properties without delaying the Work.
C. Fire Test Performance: Provide resilient flooring products and accessories that comply with the following fire performance characteristics as determined by testing products per ASTM test method indicated below by UL or another testing and inspecting agency acceptable to authorities having jurisdiction.
1. Critical Radiant Flux: Class II, Not less than 0.22 watts per sq. cm when tested in conformance with ASTM E 648.
2. Smoke Density: Less than 450 in conformance with ASTM E 662.
3. Static Coefficient of Friction: Greater than 0.6 for level surfaces and greater than 0. 8 for ramped surfaces in accordance with ASTM D 2047.
1.4 SUBMITTALS
A. Product data: Submit manufacturer’s product data, installation instructions, and maintenance recommendations for each type of product specified.
B. Shop Drawings: Show layout of special tile, patterns, logos, details and color coding for verification of correct color and pattern locations coordinated with layout on Architectural drawings. Show locations of seams, expansion joints, edges, columns, doorways, enclosing partitions, built-in furniture, cabinets, and cutouts.
C. Samples for selection purposes of each type of flooring, base and accessory consisting of actual tiles or 6-by-9 inch sections showing full range of colors and patterns available for each type of product indicated for approval and color selection.
D. Certification by manufacturer of each type of resilient flooring product that products provided for resilient flooring installation comply with local regulations controlling use of volatile organic compounds (VOC's).
E. Installer Certifcates: Signed by the certifying that installers comply with specified requirements.
F. Maintenance Data: Submit three copies of manufacturer's recommended maintenance practices for each type of resilient flooring product and accessory required.
1.5 DELIVERY, STORAGE AND HANDLING
A. Deliver resilient flooring and accessory products and installation accessories to the Project site in manufacturer’s original unopened cartons and containers each bearing names of product and manufacturer, Project identification, and shipping and handling instructions.
B. Store and handle materials in strict compliance with manufacturer’s recommendations.
C. Store materials in dry spaces protected from the weather with ambient temperatures maintained between 50 deg F (10 deg C) and 90 deg F (32 deg C) or as otherwise recommended by the manufacturer. Store tiles on flat surfaces. Store rolls upright.
D. Move resilient products and installation accessories into spaces where they will be installed at least 72 hours in advance of installation.
E. Deliver Materials sufficiently in advance of installation to condition materials to room temperature prior to installation.
1.6 PROJECT CONDITIONS
A. Maintain temperature of not less than 70 deg F (21 deg C) or more than 95 deg F (35 deg C) in spaces to receive resilient flooring products for at least 72 hours prior to installation, during installation, and for not less than 72 hours after installation. Subsequently, maintain a temperature of not less than 55 deg F (13 deg C) or more than 95 deg F (35 deg C) in areas where work is completed.
B. Do not install resilient flooring materials and accessories until they are at the same temperature as the space where they are to be installed.
C. Maintain relative humidity in spaces to receive resilient flooring products and accessories before, during, and after installation within the range recommended in writing by manufacturer.
D. Close spaces to traffic during flooring installation and for time period after installation recommended in writing by manufacturer.
E. Install resilient flooring and accessories after other finishing operations, including painting and ceiling operations, have been completed. Moisture content of concrete slabs and environmental conditions must be within limits recommended by manufacturer of products being installed for sufficient bonding with adhesives as determined by moisture tests.
1.7 ADDITIONAL STOCK
A. Deliver additional stock to Owner. Furnish additional materials matching products installed, packaged with protective covering for storage and identified with labels clearly describing contents. Furnish not less than one box for each 50 boxes or fraction thereof, of each type, color, pattern class, wearing surface and size of each resilient tile flooring item installed. Furnish not less than 10 linear feet (3 linear m) in roll form for each 500 linear feet (150 linear m) or fraction thereof, of each type, color, pattern, and size of resilient accessory installed.
2.1 MATERIALS
A. Luxury Vinyl Tile Flooring: (LVT-# as noted in the Interior Finishes Schedule) Armstrong Flooring – Parallel Collection, Redondo, Beach J6219 - 12 in. Wide x 24 in. Long, Low Gloss.
B. Resilient Base: Refer to Section 096513 Resilient Base and Accessories
C. Resilient Edge Strips: Homogenous vinyl or rubber composition; 1/8" thick; not less than 1" wide;
tapered or bullnose edge as selected by the Architect.
D. Metal Edge Strips: Extruded aluminum with mill finish of width shown, of height required to protect exposed edge of tiles, and in maximum available lengths to minimize running joints.
E. Concrete Slab Primer: Nonstaining type as approved and recommended by the flooring product
F. Trowelable Underlayment, Leveling and Patching Compounds: Latex-modified, portland-cement-based or blended hydraulic cement based formulation provided by or approved by the resilient product manufacturer for applications intended.
G. Adhesives (Cements): Water-resistant adhesive of type recommended by the flooring manufacturer to suite resilient flooring products and substrate conditions indicated.
H. Epoxy Caulking Compound: Water-resistant type two-component epoxy caulking compound by the tread manufacturer to suite resilient flooring products and substrate conditions.
3.1 EXAMINATION
A. Prior to installation, inspect subfloors and surfaces to verify that conditions are satisfactory for flooring installation and comply with resilient flooring manufacturer's requirements and those specified in this section. Notify Architect in writing of any serious defects or conditions which will interfere or prevent a satisfactory installation and do not proceed with work until unsatisfactory conditions are corrected. Starting of installation shall imply acceptance of the surface. Comply with manufacturer’s recommendations including the following:
1. Substrates shall be dry and clean.
2. Substrates shall be free of depressions, raised areas, or other defects that would telegr aph through installed flooring.
3. Temperature of resilient flooring and substrate shall be tested and within specified tolerances.
4. Moisture condition and adhesive bond tests shall be performed as specified and recorded.
B. For applications on concrete, verify that concrete slabs and substrates are dry and free of curing compounds, sealers, hardeners, and other materials that may interfere with adhesive bond.
Determine adhesion and dryness characteristics by performing bond, moisture, and pH tests recommended in wring by the flooring manufacturer. Do not proceed with installation until improper conditions have been removed or corrected have been removed as specified and in accordance with resilient product manufacturer’s written requirements.
C. For applications on concrete slab on grade or below grade, verify vapor barrier below slab was installed. If no vapor barrier was installed, do not proceed with work unless written acceptance of such conditions is received and submitted.
D. Perform moisture condition test in each major area, minimum 1 per 1,000 square feet, prior to installation. Moisture condition shall not exceed 3 pounds per 1,000 square feet per 24 hour day and in accordance with flooring manufacturers recommended test method. Do not proceed with work until results of moisture condition tests are acceptable.
E. Perform adhesive bond test in each major area, minimum 1 per 1,000 square feet, prior to installation. Examine after 72 hours to determine whether bond is solid and no moisture is present.
Do not proceed with work until results of bond test are acceptable.
3.2 PREPARATION
A. Comply with ASTM F 710 and manufacturer’s…