PRE-BID INQUIRY:
Date of Bid Inquiry: 28 May 2020
From: American Mechanical Inc
Address: 1608 E Hwy 54, Andover, KS 67002
Questions as follows:
1. Says haul excess dirt to locate to be determined on range? How far away is it? Answer: Haul route will not exceed 5 miles one way.
2. Do the equipment pads require wire or rebar? Answer: No.
3. What are the size of the bollards? Do they need painted? Answer: 4 inch with 48 inch exposed. Unpainted Galvanized, concrete filled.
4. What Concrete mix /slump is required? Answer: 4000 PSI, 3 +/- 1” slump, 4 to 7% Air.
5. Is an expansion joint required along building for mow strip and would it require any sealant afterwards? Answer: See Sheet S-1. The only expansion along the building is at the addition. No sealant at any joints.
6. Regarding the compacted subgrade under concrete is there material requirements like rock or sand? Answer: No. Existing material or excess dirt may be reused if dry enough to compact.
From: American Mechanical Inc