SHEET NOTE. SEE THE SPECIAL NOTES ON

THAT SHEET FOR THE NOTE NUMBER

INDICATED IN THE HEXAGON.

ITEMS SHOWN DASHED AND RELATIVELY LIGHT

ARE EXISTING UNLESS NOTED OTHERWISE

REVISION CLOUD AND REFERENCE NUMBER

ROOM NUMBERS

SECTION/DETAIL DESIGNATIONS

EQUIPMENT DESIGNATION

TOP = EQUIPMENT TAG

X = SECTION (LETTER) OR DETAIL (NUMBER)

Y = SHEET WHERE DETAIL/SECTION IS REFERENCED

Z = SHEET WHERE DETAIL/SECTION IS SHOWN

BOTTOM = EQUIPMENT NUMBER

X

Z

X

Z

TAG

Y

ASC - APPLICATION SPECIFIC CONTROLLER

ATC - AUTOMATIC TEMPERATURE CONTROL

FAAP - FIRE ALARM ANNUNCIATOR PANEL

GAP - GENERATOR ANNUNCIATOR PANEL

FT - FOOT OR FEET

HP - HORSE POWER

FTU - FAN TERMINAL UNIT

GFI - GROUND FAULT INTERRUPTING

GND - GROUND

HZ - HERTZ (CYCLES PER SECOND)

FCU - FAN COIL UNIT

FLA - FULL LOAD AMPS

EM - EMERGENCY

EWC - ELECTRIC WATER COOLER

EWH - ELECTRIC WATER HEATER

EX - EXISTING

EXTR - EXISTING TO REMAIN

°F - DEGREES FAHRENHEIT

FACP - FIRE ALARM CONTROL PANEL

FATC - FIRE ALARM TERMINAL CABINET

EPO - EMERGENCY POWER OFF

CT - COOLING TOWER

dB - DECIBELS

EF - EXHAUST FAN

EDH - ELECTRIC DUCT HEATER

ELEC - ELECTRIC OR ELECTRICAL

°C - DEGREES CENTIGRADE/CELSIUS

C - CONDUIT

CB - CIRCUIT BREAKER

CCTV - CLOSED CIRCUIT TELEVISION

D/D - DUSK TO DAWN

CONC - CONCRETE

COND - CONDUCTOR

DN - DOWN

AC - ALTERNATING CURRENT

AFG - ABOVE FINISHED GRADE

ATS - AUTOMATIC TRANSFER SWITCH

BG - BELOW GRADE

ABCLG - ABOVE CEILING

APPROX - APPROXIMATELY

BLDG - BUILDING

BESS - BATTERY ENERGY STORAGE SYSTEM

A/C - AIR CONDITIONING

AHU - AIR HANDLING UNIT

AFF - ABOVE FINISHED FLOOR

AL - ALUMINUM

PTAC - PACKAGED TERMINAL AIR CONDITIONER

UNO - UNLESS NOTED OTHERWISE

WH - WATER HEATER

VAV - VARIABLE AIR VOLUME

VFD - VARIABLE FREQUENCY DRIVE

WP - WEATHERPROOF

TYP - TYPICAL

RLA - RUNNING LOAD AMPS

SHT - SHEET

SF - SUPPLY FAN

RTU - ROOF TOP UNIT

RESS - RESIDENTIAL ENERGY STORAGE SYSTEM

UGE - UNDERGROUND ELECTRIC

TTC - TELEPHONE TERMINAL CABINET

TTB - TELEPHONE TERMINAL BOARD

SCP - SECURITY CONTROL PANEL

R - RELOCATE

IDF - INTERMEDIATE DISTRIBUTION FRAME

MTD - MOUNTED

POAU - PACKAGED OUTDOOR AIR UNIT

OAU - OUTDOOR AIR HANDLING UNIT

P - PUMP

PH - PHASE

NTS - NOT TO SCALE

OHE - OVERHEAD ELECTRIC

NO - NORMALLY OPEN

NL - NIGHT LIGHT

NF - NON-FUSED

NIC - NOT IN CONTRACT

NC - NORMALLY CLOSED

LRA - LOCKED ROTOR AMPS

MCA - MINIMUM CIRCUIT AMPACITY

MIN - MINIMUM

REF - REFRIGERATOR

MAX - MAXIMUM

KW - KILOWATT

LA - LIGHTNING ARRESTOR

MH - MANHOLE

MDF - MAIN DISTRIBUTION FRAME

MB - MAIN BREAKER

IN - INCHES

MLO - MAIN LUGS ONLY

U.N.O. - UNLESS NOTED OTHERWISE

ST - SHUNT TRIP

ELECTRICAL SYMBOL LEGENDABBREVIATIONS

GENERAL SYMBOLS

ELECTRICAL SYMBOL NOTES

SR

SYMBOL

LV

UE

EX

UHVE

OHE

OHT

*** DISTANCE TO HIGHEST OPERABLE PART OF EQUIPMENT

PUSH BUTTON

SINGLE RECEPT

SPLIT DUPLEX RECEPT

FOURPLEX RECEPT

DUPLEX RECEPT

RECEPT ON EMERGENCY CKT (DUPLEX SHOWN)

ISOLATED GROUND RECEPT (DUPLEX SHOWN)

240 VOLT RECEPT

EQUIPMENT PLUG

RECEPT ON DROP CORD (DUPLEX SHOWN)

RECEPT ON CORD REEL (DUPLEX SHOWN)

FLOOR RECEPT (DUPLEX SHOWN)

DISTANCES ARE TO CENTER OF DEVICE OR EQUIPMENT UNLESS OTHERWISE NOTED. DEVICES INDICATED AT 48" MAY NOT BE INSTALLED WITH ANY OPERABLE PART HIGHER THAN 48". DEVICES MAY BE INSTALLED IN CONCRETE MASONRY UNITS WITH THE TOP OF THE DEVICE AT 48".

AS NOTED

* DISTANCE ABOVE TOP OF DOOR FRAME

J

** DISTANCE TO TOP OF EQUIPMENT OR DEVICE

AS NOTED

72"**

72"**

PS

FS

R

72"**

72"**

72"**

48"

72"**

72"**

BUS DUCT WITH PLUG UN DISCONNECT (FUSED)

ENCLOSED CIRCUIT BREAKER

PRESSURE SWITCH

RELAY

84"

84"

COMB. MOTOR STARTER (NON-FUSED)

MAG MOTOR STARTER OR CONTACTOR

SAFETY DISC SW (FUSED)

SAFETY DISC SW (NON-FUSED)

COMB MOTOR STARTER (FUSED)

MANUAL MTR STR (W/OVERLOADS)

MOTOR (SEE SCHEDULE)

DAMPER MOTOR

60"***

18"

48"

18"

J

AS NOTED

AS NOTED

J J

P

18"

18"

STATIC GROUND RECEPTACLE

SPECIAL CONNECTION (SEE SCHEDULE)

SPECIAL RECEPT OR CONN (SEE SCHEDULE)

JUNCTION BOX

PULL BOX

POWER POLE (OPEN OFFICE STYLE)

MULTIOUTLET ASSEMBLY

MULTIOUTLET ASSEMBLY

HT AFF

FLEXIBLE CONDUIT OR FIXTURE WHIP

**** DISTANCE BELOW CEILING

EQUIPOTENTIAL GROUND OUTLET

BUZZER

BELL

UNDERFLOOR RACEWAY SYSTEM

CABLE TRAY (TYPE DENOTED)

VOICE/DATA OUTLET (FLUSH MOUNTED IN WALL

18" AFF U.N.O.)

WALL VOICE OUTLET (TYPE DENOTED)

INTERCOM OUTLET LOCATION

TELEPHONE OUTLET (TYPE DENOTED)

WALL DICTATION OUTLET LOCATION

MULTIPLE SERVICE OUTLET (TYPE DENOTED)

DICTATION OUTLET LOCATION

TELEVISION OUTLET

D

W

W

CONDUIT TRANSITION DOWN

CONDUIT TRANSITION UP

BRANCH CIRCUIT HOME RUN (NUMBER AND

SIZE OF CONDUCTORS AS PER N.E.C. -

NUMBERS DENOTE PANEL AND CIRCUIT)

UNDERGROUND HIGH VOLTAGE ELECTRICAL

UNDERGROUND ELECTRICAL

LOW VOLTAGE POWER WIRING

EXISTING CONDUIT

OVERHEAD TELEPHONE

OVERHEAD ELECTRIC

CONDUIT EXPOSED

SURFACE RACEWAY

CONDUIT STUBBED OUT

CONDUIT CONCEALED BELOW FLOOR

CONDUIT CONCEALED IN WALL OR OVERHEAD

DESCRIPTION

UNDERGROUND TELEPHONEUT

UCOM UNDERGROUND COMMUNICATIONS

UTV UNDERGROUND CABLE TELEVISION (CATV OR CCTV)

UFIBR UNDERGROUND FIBER OPTIC

48"

18"

18"

18"

18"

18"

18"

18"

FOURPLEX RECEPTACLE ON EMERGENCY CIRCUIT18"

PB

FLOAT SWITCH

IC

18"

18"

18"

48"***

18"

MULTIPLE SERVICE FLR OUTLET (TYPE DENOTED)

D

G

CHIME

CONDUIT SLEEVE (SIZE DENOTED)

A-1, 3, 5

48"

PROJECTOR CONTROL OUTLET

WEATHERHEAD

ANTENNA

DOOR SIGNAL - APT. UNIT

SPEAKER (WALL OR CEILING MT.)S

MICROPHONE OUTLET

HORN TYPE SPEAKER

VOLUME CONTROLV

D48"***

84"

84"

18"

18"

S

S S

M

P

1,3,5

T1

PP2

SPECIAL CONNECTIONS. THE EQUIPMENT IS INDICATED BY A NUMBER IN A CIRCLE. SEE

THE MOTOR AND EQUIPMENT SCHEDULE FOR THE LOAD DESCRIPTION AND TYPE OF

CONNECTION. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER(S) ADJACENT TO

THE SYMBOL. EXAMPLE: EQUIPMENT NO. 1; 3 PHASE CONNECTION TO CIRCUITS 1, 3, 5.

TRANSFORMERS. THE TRANSFORMER TYPE IS INDICATED BY A NUMBER FOLLOWING

THE UPPER CASE LETTER "T". SEE THE TRANSFORMER SCHEDULE OR THE SINGLE LINE

DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND REQUIREMENTS. EXAMPLE:

TRANSFORMER TYPE "T1".

PANELBOARDS. PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING SIDE OF

RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR DESIGNATION CODES.

CONDUIT SHOWN WITHOUT SLASH MARKS SHALL CONTAIN 2 # 12 CONDUCTORS IN 3/4"

CONDUIT UNLESS SPECIFIC EQUIPMENT REQUIRES A DIFFERENT SIZE.

HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE PANELBOARD DESIGNATION AND

CIRCUITS ARE SHOWN ADJACENT TO THE HOME RUN ARROW. CIRCUIT BREAKER SIZES

(AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANELBOARD SCHEDULE WITH THE

CORRESPONDING PANELBOARD AND CIRCUIT DESIGNATION. EXAMPLE: HOME RUN TO

PANELBOARD RP2; CIRCUITS 1, 3, 5.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE A UNIT

TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

RP2-1,3,5

ELECTRICAL GENERAL NOTES

1. ALL ELECTRICAL WORK SHALL COMPLY WITH THE 2008 NATIONAL ELECTRICAL CODE, THE INDIANA BUILDING CODE, THE NATIONAL FIRE CODES, STATE REQUIREMENTS AND ALL APPLICABLE LOCAL

CODES AND ORDINANCES.

2. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION AND ALL REQUIREMENTS NOT INDICATED ON THE

DRAWINGS.

3. IT IS THE INTENT OF THESE PLANS AND SPECIFICATIONS THAT A COMPLETE AND WORKABLE ELECTRICAL INSTALLATION BE PROVIDED FOR ALL THE EQUIPMENT DESCRIBED OR SHOWN AS BEING IN THIS CONTRACT. ANY ITEMS WHICH ARE CLEARLY NECESSARY FOR THE COMPLETION OF THE WORK OR ITS APPURTENANCES SHALL BE CONSIDERED A PORTION OF THE WORK AND SHALL BE PROVIDED AND

INSTALLED BY THE CONTRACTOR EVEN THOUGH NOT DIRECTLY SPECIFIED.

4. THE PLANS AND SPECIFICATIONS ARE COMPLIMENTARY, AND THAT WHICH IS CALLED FOR BY ONE SHALL BE AS BINDING AS IF CALLED FOR BY BOTH. IN THE EVENT THAT THE PLANS AND SPECIFICATIONS CONFLICT, THE MORE STRINGENT SHALL APPLY. ANY DISCREPANCIES IN THE DRAWINGS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE DESIGN PROFESSIONAL PRIOR TO SUBMITTAL OF BID.

5. THE PLANS INDICATE THE GENERAL ARRANGEMENT OF THE WORK TO BE PERFORMED AND ARE DIAGRAMATIC ONLY. ALL DIMENSIONS AND EQUIPMENT LOCATIONS SHALL BE VERIFIED IN THE FIELD.

6. VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE

RECOGNIZED.

7. THE CONTRACTOR SHALL THOROUGHLY REVIEW THE PROJECT TO ENSURE THAT ALL WORK SHALL MEET OR EXCEED THE ABOVE REQUIREMENTS. ANY ALLEGED DISCREPANCIES SHALL BE BE BROUGHT

TO THE OWNER'S AND ENGINEER'S ATTENTION PRIOR TO THE START OF WORK.

8. THE CONTRACTOR IS DIRECTED TO OBTAIN COPIES OF ALL RELATED PLANS, SPECIFICATIONS, SHOP

DRAWINGS AND ADDENDUM TO COORDINATE THE RELATED WORK AND SCHEDULING.

9. COORDINATE ELECTRICAL EQUIPMENT, LIGHTING FIXTURE AND DEVICE LOCATIONS WITH

ARCHITECTURAL PLANS AND EQUIPMENT OF ALL TRADES.

10. PROVIDE ACCESS PANELS IN WALLS AND CEILINGS WHERE REQUIRED FOR OPERATION, SERVICING, INSPECTION AND MAINTENANCE OF ALL EQUIPMENT.

11. VERIFY EXISTING CONDITIONS IN FIELD AND COORDINATE WITH ALL TRADES PRIOR TO INSTALLING OR

FABRICATING EQUIPMENT.

12. DRAWINGS ARE DIAGRAMMATIC IN NATURE. COORDINATE EXACT LOCATION OF ALL CEILING MOUNTED EQUIPMENT SO ALL SERVICEABLE COMPONENTS CAN BE EASILY ACCESSED. REMOVAL OR RELOCATION

OF LIGHTING FIXTURES FOR SERVICE ACCESS IS NOT ACCEPTABLE. THE CONTRACTOR SHALL

REINSTALL EQUIPMENT THAT HAS INADEQUATE OR UNSAFE ACCESSIBILITY. LOCATE ALL OTHER

EQUIPMENT WITH MANUFACTURER RECOMMENDED ACCESS FOR OPERATION AND MAINTENANCE.

13. PRIOR TO BID, COORDINATE ALL ELECTRICAL WORK WITH MECHANICAL WORK AND OTHER TRADES.

SEE SPECIFICATIONS FOR REQUIREMENTS.

14. CONTRACTOR SHALL NOT CONCEAL ANY WORK UNTIL INSPECTED BY ELECTRICAL INSPECTOR AND/OR ARCHITECT/ENGINEER. CONTRACTOR SHALL NOTIFY A/E OF A SCHEDULED INSPECTIONTIME WITHIN 72

HOURS. GENERAL CONTRACTOR SHALL NOT CONCEAL WORK UNTIL APPROVED, REGARDLESS OF

SCHEDULE.

15. PRIME CONTRACTOR IS RESPONSIBLE TO HAVE LICENSED AND QUALIFIED SUBCONTRACTORS

PERFORMING ALL WORK.

16. ALL CHANGES MADE IN THE FIELD SHALL BE RECORDED BY THE CONTRACTOR(S) ON AS-BUILT

DRAWINGS, SHOP DRAWINGS, AND IN MAINTENANCE MANUALS.

17. THE SIZE, LOCATION AND ELECTRICAL REQUIREMENTS AND SERVICE CLEARANCES OF EQUIPMENT INSTALLED UNDER DIVISION 26, ELECTRICAL, SHALL BE COORDINATED WITH ALL OTHER TRADES.

18. WHERE CROWDED LOCATIONS EXIST OR WHERE THERE IS A POSSIBILITY OF CONFLICT BETWEEN

TRADES, CONTRACTOR SHALL MAKE COMPOSITE DRAWINGS SHOWING THE EXACT LOCATION OF

PANELBOARDS, SWITCHBOARDS, TRANSFORMERS, CONDUIT AND EQUIPMENT AND MECHANICAL PIPING, DUCTWORK, AND OTHER ARCHITECTURAL APPURTENANCES. DRAWINGS SHALL BE BASED ON FIELD

MEASUREMENTS AND, AFTER CONSULTATION AND AGREEMENT BETWEEN THE TRADES, SHALL BE

APPROVED BY THE ARCHITECT/ENGINEER PRIOR TO INSTALLATION OF THE WORK.

19. NOTIFY ARCHITECT/ENGINEER OF ANY CONFLICTS PRIOR TO PURCHASING EQUIPMENT AND PRIOR TO

CUTTING OPENINGS.

20. ALL BARE METAL SURFACES SHALL BE PRIMED AND PAINTED TO PREVENT ANY RUST, INCLUDING, BUT

NOT LIMITED TO, ANGLE FRAMING, UNIT SUPPORTS, MOUNTING HARDWARE, ETC.

21. ALL WORK SHALL BE CONSTRUCTED TO MEET ANY PHASING REQUIREMENTS OF THE PROJECT AS MAY

BE OUTLINED IN THE DRAWINGS AND/OR SPECIFICATIONS.

22. RACEWAYS AND ELECTRICAL EQUIPMENT HAVE BEEN LOCATED AND ARRANGED TO MINIMIZE THE

INTERFERENCE OF EQUIPMENT WITH THE STRUCTURE. THE CONTRACTOR SHALL THOROUGHLY

FAMILIARIZE THEMSELVES WITH THE WORK TO BE PERFORMED BY OTHER TRADES AND THE PHYSICAL CHARACTERISTICS OF THE STRUCTURE IN ORDER TO SCHEDULE AND INSTALL EQUIPMENT AND TO MINIMIZE POSSIBLE INTERFERENCE. FAILURE TO PROPERLY COMMUNICATE AND SCHEDULE WORK WITH OTHER TRADES RESULTING IN ADDITIONAL WORK AND MATERIAL, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. THE MODIFICATIONS REQUIRED TO RESOLVE THE CONFLICT SHALL BE DECIDED BY

THE OWNER AND THE COST OF THE MODIFICATIONS SHALL BE BORNE BY THE CONTRACTOR.

23. ALL PANELBOARDS SHALL BE PROVIDED WITH A PRINTED DIRECTORY SHOWING CIRCUIT NUMBERS AND

A COMPLETE DESCRIPTION OF EACH CIRCUIT.

24. MINIMUM TRADE SIZE CONDUIT PERMITTED SHALL BE 3/4 INCH UNLESS NOTED OTHERWISE. TYPE AC AND TYPE MC CABLE SHALL NOT BE PERMITTED FOR USE ANYWHERE EXCEPT FOR LIGHTING FIXTURE

WHIPS NOT EXCEEDING 6'-0" IN LENGTH.

25. ALL SECONDARY FEEDERS AND BRANCH CIRCUIT CONDUCTORS SHALL BE COPPER WITH 600 VOLT INSULATION TYPE THHN, THW OR THWN. (MINIMUM SIZE SHALL BE NO. 12 AWG.) CONTRACTOR SHALL PROVIDE AND INSTALL ALL PHASE (A, B, C, AS REQUIRED) CONDUCTORS, NEUTRAL CONDUCTORS, AND

GROUND CONDUCTORS AS NECESSARY FOR A COMPLETE AND OPERABLE SYSTEM. NO INDIVIDUAL

CONDUCTOR SPECIFICATION SHALL BE CONSTRUED AS REQUIRING ONLY ONE CONDUCTOR. A

COMPLETE AND OPERABLE SYSTEM IS INTENDED BY THE CONSTRUCTION DOCUMENTS AND THE

CONTRACTOR SHALL PROVIDE AND INSTALL ALL NECESSARY WIRING AND CONDUCTORS AS REQUIRED

TO DELIVER A COMPLETE AND OPERABLE ELECTRICAL SYSTEM TO THE OWNER. NO ADDITIONAL

COMPENSATION WILL BE MADE TO THE CONTRACTOR FOR UNDER-ESTIMATING AND/OR MIS-

CALCULATING THEIR WIRING AND CABLING RESPONSIBILITIES.

26. ALL ELECTRICAL WIRING DEVICES INDICATED TO BE INSTALLED IN MASONRY WALLS OR FLOORS SHALL

BE FLUSH MOUNTED, UNLESS OTHERWISE NOTED.

27. ALL CONDUIT RUNS SHALL BE CONCEALED UNLESS SPECIFICALLY NOTED OTHERWISE OR PRIOR

APPROVED BY OWNER FOR SURFACE MOUNTING.

28. ALL CONDUITS SHALL HAVE A SEPARATE GREEN GROUND CONDUCTOR INSTALLED FOR GROUNDING.

29. ALL FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR THE MAXIMUM VOLTAGE DROP

ALLOWED. THE ELECTRICAL CONTRACTOR SHALL CALCULATE VOLTAGE DROP AND ADJUST

CONDUCTORS AS NEEDED. FOR DESIGN LOADS, A MAXIMUM VOLTAGE DROP OF 2% IS PERMITTED FOR FEEDER CONDUCTORS AND A MAXIMUM VOLTAGE DROP OF 3% IS PERMITTED FOR BRANCH CIRCUIT

CONDUCTORS. CONTRACTOR SHALL NOT DECREASE CONDUCTOR SIZES NOTED ON PLAN.

CONTRACTOR SHALL ONLY INCREASE CONDUCTOR SIZES NOTED IF NEEDED TO MEET MINIMUM CODE

REQUIREMENTS.

30. FOR MULTI-WIRE BRANCH CIRCUITS, ADD SEPARATE NEUTRALS AND PROVIDE & INSTALL MULTI-POLE

CIRCUIT BREAKERS PER NEC, ARTICLE 210.4.

31. THE CONTRACTOR SHALL PROVIDE AND INSTALL CHROME FINISHED METAL ESCUTCHEONS TO FINISH THE HOLES OR SLEEVES OFF, INCLUDING THE OUTSIDE AND INSIDE OF THE EXTERIOR WALLS AND ANY OTHER PLACE WHERE THE PENETRATION IS VISIBLE, FOR ALL ELECTRICAL PIPES, CONDUITS, AND PENETRATIONS MADE OR OTHERWISE NECESSARY FOR CONSTRUCTION OF THE ELECTRICAL SYSTEMS.

32. THE CONTRACTOR SHALL MAKE AND PERFORM ALL EXOTHERMIC WELDING PROCEDURES (CADWELD) IN ACCORDANCE WITH THE APPLICABLE ANSI STANDARDS INCLUDING SAFETY IN WELDING AND CUTTING, AND IN STRICT ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTALLATION AND HANDLING INSTRUCTIONS. ALL EXOTHERMIC WELDS (CADWELDS) SHALL BE INDIVIDUALLY DOCUMENTED AND CERTIFIED BY THE INSTALLING CONTRACTOR AND SHALL BE UNIQUELY RECORDED ON THE AS-BUILT

DRAWINGS. ALL DOCUMENTATION SHALL BEAR THE CONTRACTORS SIGNED CERTIFICATION OF

PROPERLY COMPLETED WELDS AND SHALL BE SUBMITTED TO THE OWNER FOR THEIR PERMANENT

RECORDS.

33. ALL ELECTRICAL EQUIPMENT FEEDERS, BRANCH CIRCUIT CONDUCTORS, AND DEVICE AND EQUIPMENT

TERMINATIONS SHALL BE RATED FOR A MINIMUM OF 75ºC UNLESS OTHERWISE NOTED.

RACEWAY & CONDUCTORSDEVICES

SYMBOLHT AFF DESCRIPTION

COMMUNICATIONS

PROVIDE SINGLE GANG PLATE WITH DOUBLE GANG OUTLET BOX. ONE (1) 1"C.

MINIMUM STUBBED TO ACCESSIBLE CEILING SPACE. PROVIDE INSULATED THROAT

BUSHINGS ON EACH END OF CONDUIT STUB PROVIDE TWO BLUE CAT-6 CABLES.

TERMINATE ON MATCHING COLOR RJ45 JACKS WITH T-568A WIRING PATTERN AT

EACH DEVICE LOCATION. PROVIDE AND INSTALL ONE (1) CAT. 6 CABLE TO EACH

VOICE/DATA JACK. ALL EIGHT CONDUCTORS OF EACH CABLE TO BE PROPERLY

TERMINATED FOR EACH JACK. LEAVE A MINIMUM OF TWELVE INCHES (12") OF CABLE

SLACK NEATLY COILED INSIDE OUTLET BOX FOR EACH CABLE. CONTRACTOR SHALL

REFER TO LATEST FLARNG-J6 TELECOMMUNICATIONS SPECIFICATIONS FOR

ADDITIONAL INFORMATION.

TAG-# OR

72"** CIRCUIT BREAKER PANEL

72"**

72"**

T1

POWER OR DISTRIBUTION PANEL

TRANSFORMER (TYPE DENOTED)

SPECIAL CABINET

GENERATOR (KVA DENOTED)25 KVA

VARIABLE FREQUENCY DRIVE

EQUIPMENT

VFD

NOTE: NOT ALL ELECTRICAL SYMBOLS MAY BE USED ON THESE PLANS/DRAWINGS.

VOICE/DATA OUTLET (CEILING MOUNTED)

L

V LOW VOLTAGE DIGITLA LIGHT SWITCH

O S

LOW VOLTAGE DIGITLA LIGHT SWITCH WITH

OCCUPANCY SENSOR

OS CEILING MOUNTED OCCUPANCY SENSOR

48"

48"

DS DOOR POSITION SWITCH

AIRCRAFT GROUND WELL

SIMPLEX RECEPTACLE, MOUNTED AT CEILING

DUPLEX RECEPTACLE, MOUNTED AT CEILING

PC DAYLIGHTING PHOTOCONTROLLER

L A

Y O

U T

D R

A W

N

R E

V

IE

W E

D

D sheetsof

R E

V

IS

IO

N

D A

T E

H a n s o n N o

F ile n a m e

S c a le

D a te d

W in g

Il lin o is

A ir

N a ti o n a l G u a rd

S p ri n g fi e ld

Il lin o is

-2

H a n s o n

P ro fe s s io n a l S e rv ic e s I n c

S o u th S ix th

S tr e e t

P h o n e

(2

-2

O k la m h o m a C it y

O K

-7

N G

B I

D

IQ

C o n tr a c t

W

L

-1

-D

B ro a d w a y E x te n s io n

S u it e

P h o n e

(4

-2

C o p yr ig h t H a n so n

P ro fe ss io n a l S e rv ic e s In c

R E

P A

IR

C

R F

B

U

IL

D

IN

G P

-1

S P

R

IN

G F

IE

L

D

IL

ISSUED FOR CONSTRUCTION 3 MAY 2021

S

IG

N E

D

/1

/2

E X

P

IR

E S

/3

/2

C U s e rs \ b ra n s

\ D o c u m e n ts

\ 1 D

E le c v s b ra n s o n .r v t

/2

/2

:1

: 0

P M

/1

/1

E L

E C

T R

IC

A

L S

Y M

B O

L S

A N

D N

O T

E S

E-001

S K

B

G T

R

G T

R /0

/2

/0

/2

/0

/2

17 16

29 19

13 12

POS

POS

20 P O

S

W

W

POSPOSREX

K P

E S

POSREX

KP

E S

A N

N

P O

S P

O S

P O

S

POSPOSPOSPOSPOSPOS W

W

20 20 20

21 21

21 21 21 21

21 21 21 21

21 21

L A

Y O

U T

D R

A W

N

R E

V

IE

W E

D

D sheetsof

R E

V

IS

IO

N

D A

T E

H a n s o n N o

F ile n a m e

S c a le

D a te d

W in g

Il lin o is

A ir

N a ti o n a l G u a rd

S p ri n g fi e ld

Il lin o is

-2

H a n s o n

P ro fe s s io n a l S e rv ic e s I n c

S o u th

S ix th S tr e e t

P h o n e

(2

-2

O k la m h o m a C it y

O K

-7

N G

B I

D

IQ

C o n tr a c t

W

L

-1

-D

B ro a d w a y E x te n s io n

S u it e

P h o n e

(4

-2

C o p yr ig h t H a n so n

P ro fe ss io n a l S e rv ic e s In c

R E

P A

IR

C

IL

D

IN

G P

-1

S P

R

IN

G F

IE

L

D

IL

ISSUED FOR CONSTRUCTION 3 MAY 2021

S

IG

N E

/1

/2

E X

P

IR

E S

/3

/2

C U s e rs \ b ra n s

\ D o c u m e n ts

\ 1 D

E le c v s b ra n s o n .r v t

/2

/2

:4

: 1

P M

/2

/1

E L

E C

T R

IC

A

L D

E M

O L

IT

IO

N P

L A

N

ED-101

S K

B

G T

R

G T

R /0

/2

/0

/2

/0

/2

3/32" = 1'-0"

ELECTRICAL DEMOLITION PLAN

PLAN

NORTH

TRUE

NORTH

GENERAL NOTES:

1. UNLESS SPECIFICALLY NOTED ON THIS SHEET, ALL BUILDING ELECTRICAL

COMPONENTS TO BE REMOVED AS PART OF BUILDING DEMOLITION.

KEYED NOTES:

1. EXISTING PADMOUNT PRIMARY SWITCH TO REMAIN (NO WORK).

2. EXISTING PADMOUNT PRIMARY SWITCH TO REMAIN. CONTRACTOR SHALL

DISCONNECT EXISTING PRIMARY CABLES SUPPLYING BUILDING P-17 TRANSFORMER.

3. CONTRACTOR SHALL REMOVE EXISTING PRIMARY CABLES FROM EXISTING CONDUIT.

EXISTING CONDUIT TO REMAIN FOR REUSE - PROTECT FROM DAMAGE.

4. EXISTING PAD MOUNT TRANSFORMER AND PAD TO BE REMOVED. EXISTING

CONCRETE ENCASED PRIMARY CONDUITS TO REMAIN. PROTECT FROM DAMAGE

DURING PAD REMOVAL.

5. NOT USED.

6. EXISTING SECONDARY CONDUITS AND CONDUCTORS TO BUILDING TO BE REMOVED

BY CONTRACTOR.

7. EXISTING BUILDING MAIN SWITCHBOARD TO BE REMOVED AS PART OF BUILDING

DEMOLITION.

8. EXISTING PRIMARY DUCTBANK TO REMAIN; PROTECT FROM DAMAGE.

9. EXISTING COMMUNICATIONS MANHOLE TO REMAIN.

10. EXISTING ABANDONED TELECOMMUNICATIONS TERMINAL BOARD. CONTRACTOR

SHALL REMOVE ABANDONED UNSHIELDED TWISTED PAIR (UTP) AND COAXIAL

CABLES FROM TERMINAL BOARD TO COMMUNICATIONS MANHOLE AND CUT

REMOVED CABLES IN MANHOLE. REMAINING CABLES IN DUCTBANKS FROM

MANHOLE SHALL BE REMOVED BY GOVERNMENT.

11. SEE ELEVATION 2 THIS SHEET FOR DEMOLITION WORK.

12. EXISTING FIBER OPTIC CABLE TO BE DISCONNECTED FROM EXISTING DATA RACK BY

GOVERNMENT.

13. EXISTING UTP PUNCH-DOWN BLOCK TO BE REMOVED AS PART OF BUILDING

DEMOLITION. CONTRACTOR SHALL DISCONNECT EXISTING UTP SERVICE CABLE

FROM PUNCH-DOWN BLOCK PRIOR TO ITS REMOVAL. EXISTING UTP CABLE TO BE

REUSED FOR NEW BUILDING; CONTRACTOR SHALL PRESERVE AS MUCH OF

EXISTING CABLE AS POSSIBLE DURING DISCONNECTION FROM PUNCH-DOWN

BLOCK.

14. CONTRACTOR SHALL REMOVE EXISTING UTP AND FIBER OPTIC SERVICE CABLES

BACK TO COMMUNICATIONS MANHOLE. EXISTING SERVICE CABLES ARE TO BE

REUSED FOR NEW BUILDING; CONTRACTOR SHALL COIL EXISTING CABLES IN

COMMUNICATIONS MANHOLE AND PROTECT FROM DAMAGE.

15. EXISTING PULL BOX ON BUILDING EXTERIOR TO BE REMOVED BY CONTRACTOR.

16. CONTRACTOR SHALL EXCAVATE EXISTING 4” CONDUITS SERVING PULL BOX TO

BELOW GRADE. EXISTING CONDUITS TO BE CUT BELOW GRADE AND CUT ENDS

PREPARED FOR EXTENSION INTO NEW BUILDING; PROTECT REMAINING CONDUITS

FROM DAMAGE.

17. CONTRACTOR SHALL CUT TWO (2) EXISTING 4” CONDUITS CONTAINING ABANDONED

COMMUNICATIONS CABLING BELOW GRADE AND CAP ENDS WATERTIGHT. BELOW

GRADE CONDUITS FROM BUILDING TO COMMUNICATIONS MANHOLE TO REMAIN

ABANDONED IN PLACE.

18. SEE ELEVATION 3 THIS SHEET FOR DEMOLITION.

19. CONTRACTOR SHALL DISCONNECT EXISTING FIBER OPTIC CABLES FROM EXISTING

FIBER OPTIC TERMINATION BOXES AND REMOVE CABLES BACK TO

COMMUNICATIONS MANHOLE. CONTRACTOR SHALL CUT EXISTING CABLES AT

MANHOLE; REMAINING CABLES IN DUCTBANKS FROM MANHOLE SHALL BE REMOVED

BY GOVERNMENT.

20. CONTRACTOR SHALL REMOVE EXISTING DOOR ACCESS KEYPAD, ELECTRIC LOCK,

AND/OR DOOR POSITION SWITCH AT DOOR. EXISTING DOOR ACCESS COMPONENTS

TO BE RETAINED FOR REUSE; CONTRACTOR SHALL COORDINATE WITH EXISTING

DOOR ACCESS SYSTEM VENDOR ON COMPONENT REMOVAL AND PROTECT

COMPONENTS FROM DAMAGE.

21. CONTRACTOR SHALL REMOVE EXISTING AIRCRAFT GROUNDING SYSTEM IN FLOOR

SLAB IN ENTIRETY, INCLUDING ALL GROUND RODS, GROUND WELLS, AND GROUND

ELECTRODE CONDUCTORS. CUT EXISTING GROUND ELECTRODE CONDUCTORS AT

CONNECTIONS TO BUILDING COLUMNS.

22. EXISTING ABANDONED UTP PUNCH-DOWN BLOCKS TO BE REMOVED AS PART OF

BUILDING DEMOLITION.

23. EXISTING FIBER OPTIC CABLE TERMINATION BOXES TO BE REMOVED AS PART OF

BUILDING DEMOLITION.

24. EXISTING TERMINAL BOARD TO BE REMOVED AS PART OF BUILDING DEMOLITION.

25. EXISTING CONDUITS, WIRE, BOXES, AND DEVICES TO BE REMOVED AS PART OF

BUILDING DEMOLITION.

26. EXISTING DOOR ACCESS EQUIPMENT CABINET TO BE REMOVED BY CONTRACTOR.

EXISTING DOOR ACCESS EQUIPMENT TO BE RETAINED FOR REUSE IN NEW

BUILDING; CONTRACTOR SHALL COORDINATE WITH EXISTING DOOR ACCESS

SYSTEM VENDOR ON EQUIPMENT REMOVAL AND PROTECT EQUIPMENT FROM

DAMAGE.

27. EXISTING DATA RACK AND INTERIOR COMPONENTS TO BE REMOVED BY

GOVERNMENT.

28. EXISTING HORIZONTAL CABLING AND CONDUITS TO BE REMOVED AS PART OF

BUILDING DEMOLITION.

29. EXISTING TELEPHONE INSTRUMENT(S) TO BE REMOVED BY GOVERNMENT. DATA

OUTLET(S) TO BE REMOVED AS PART OF BUILDING DEMOLITION.

30. EXISTING BLOCK HEATER LOAD CENTER SUPPLIED FROM BUILDING P-17 TO BE

REMOVED.

31. REMOVE EXISTING CONDUCTORS SUPPLYING BLOCK HEATERS FROM EXISTING

CONDUIT. REMOVE EXISTING CONDUIT TO BELOW GRADE; EXISTING CONDUIT

BELOW GRADE TO BE ABANDONED IN PLACE.

32. EXISTING SECURITY CAMERA ON BUILDING EXTERIOR TO BE REMOVED BY

CONTRACTOR AND RETAINED FOR REUSE; PROTECT FROM DAMAGE.

33. EXISTING SAFETY SWITCH ON BUILDING EXTERIOR TO BE REMOVED AS PART OF

BUILDING DEMOLITION. REMOVE ABANDONED CONDUIT AND WIRE BELOW GRADE

FROM SAFETY SWITCH TO EQUIPMENT PAD.

34. BLOCK HEATER LOADCENTER PREVIOUSLY REMOVED. REMOVE EXISTING CONDUITS

TO BELOW GRADE.

1" = 1'-0"

EXISTING DATA EQUIPMENT RACK

ELEVATION- DEMOLITION

1" = 1'-0"

EXISTING DOOR ACCESS SYSTEM

EQUIPMENT ELEVATION - DEMOLITION

T

T

T

TA

B

C

D

E

1 2 3 4 5 6 7 8

B.5

B.9

C.3

C.6

B.1

B.6

C.1

C.5

C.9

1.1

RP3

RP2

T-2

T-3

EF-6

IR-1 IR-2

IR-3 IR-4

EF-1A

EF-1B

EF-3

FCU-2 FCU-1

CU-3

FCU-3

FCU-4

FCU-5

HP-1HP-2HP-3

CU-2 CU-1

MEZZANINE

ABOVE E-101

E-104

UH-4B

UH-4A

UH-3

UH-1

EF-5

H-2

EF-4

MDP

RP1-20,22

RP1-24,26

RP1-28,30

RP1-19

RP1-21

RP1-23RP4-22

RP4-24, 26, 28

CF-1 CF-2

RP4-31 RP4-31

RP4-33 RP4-33

7 7

7 7

CDO-1

RP4-35

RP4

PP2-13,15,17

RP4-30, 32, 34

PP2-8,10,12 PP2-2,4,6

EF-7

RP3-49,51 RP3-45,47

RP3-19

RP1-23

RP1-23

PP1-14,16,18

CDO-2

RP4-37

PP2-19,21,23

CDO-3

RP4-39

CDO-4

RP2-15

RP2-8

OAP-1

PP2-26,28,30

RP3-41,43

RP3-21

RP3-19

PP2-14,16,18

RP2-10,12,14

RP2-8

CDO-5

RP2-17

FACP

RP1-53

RP1-25 9

RP1-25

B

4 5 6

B.5

MAU-1

DOAS-1

H-1

PP-2

PP2-20,22,24

PP2-1,3,5

PP2-7,9,11

L A

Y O

U T

D R

A W

N

R E

V

IE

W E

D

D sheetsof

R E

V

IS

IO

N

D A

T E

H a n s o n N o

F ile n a m e

S c a le

D a te d

W in g

Il lin o is

A ir

N a ti o n a l G u a rd

S p ri n g fi e ld

Il lin o is

-2

H a n s o n

P ro fe s s io n a l S e rv ic e s I n c

S o u th S ix th

S tr e e t

P h o n e

(2

-2

O k la m h o m a C it y

O K

-7

N G

B I

D

IQ

C o n tr a c t

W

L

-1

-D

B ro a d w a y E x te n s io n

S u it e

P h o n e

(4

-2

C o p yr ig h t H a n so n

P ro fe ss io n a l S e rv ic e s In c

R E

P A

IR

C

IL

D

IN

G P

-1

S P

R

IN

G F

IE

L

D

IL

ISSUED FOR CONSTRUCTION 3 MAY 2021

S

IG

N E

/1

/2

E X

P

IR

E S

/3

/2

C U s e rs \ b ra n s

\ D o c u m e n ts

\ 1 D

E le c v s b ra n s o n .r v t

/2

/2

:1

: 1

P M

/2

/1

E L

E C

T R

IC

A

L P

O W

E R

P L

A N

E-101

S K

B

G T

R

G T

R /0

/2

/0

/2

/0

/2

1/8" = 1'-0"

ELECTRICAL POWER PLAN

KEYED NOTES

1 EXISTING PRIMARY DUCTBANK. PROVIDE NEW PRIMARY CABLES IN

CONDUIT BETWEEN NEW TRANSFORMER AND EXISTING PADMOUNT

SWITCH.

EXISTING PADMOUNT SWITCH SW7. TERMINATE NEW PRIMARY CABLES

ON EXISTING BUILDING P-17 SWITCH. PROVIDE NEW FUSES IN SWITCH.

TWO (2) EMPTY 2 1/2" CONDUITS FOR FUTURE GFGI PAINT AND SANDING

BOOTH DX COOLING UNITS. EXTEND CONDUITS ABOVE CEILING TO

LOCATION SHOWN AND CAP.

ONE (1) EMPTY 2 1/2" CONDUIT AND ONE (1) EMPTY 3” CONDUIT FOR

FUTURE GFGI PAINT AND SANDING BOOTHS. EXTEND CONDUITS ABOVE

CEILING AND TURN INTO SHEET METAL SHOP 100 AND CAP.

VARIABLE FREQUENCY DRIVE (VFD) FOR EF-6. ELECTRICAL

CONTRACTOR TO PROVIDE VFD AND POWER WIRING FROM PANEL RP2

TO VFD AND FROM VFD TO EF-8; VENTILATING CONTRACTOR TO

PROVIDE ALL CONTROL WIRING.

NEW FEEDER FOR PANEL RP4. SEE ONE-LINE DIAGRAM.

PROVIDE SIMPLEX RECEPTACLE AT CEILING FOR RE-INSTALLED

INFRARED HEATER.

EXISTING UNDERGROUND PRIMARY DUCTBANK - PROTECT FROM

DAMAGE.

PROVIDE RECEPTACLE 90" AFF FOR FCU CONDENSATE PUMP.

PLAN

NORTH

TRUE

NORTH

1/8" = 1'-0"

MEZZANINE PARTIAL POWER PLAN

1. SEE PANELBOARD SCHEDULES ON SHEETS E-602 AND E-603 FOR

BRANCH CIRCUIT CONDUIT AND WIRE INFORMATION.

2. SEE EQUIPMENT CONNECTION SCHEDULE ON SHEET E-602 FOR

ADDITIONAL INFORMATION REGARDING EQUIPMENT

CONNECTIONS.

3. ROUTE CONDUITS BELOW FLOOR SLAB ABOVE VAPOR BARRIER.

GENERAL NOTES

SB

RP1 - 11

RP1 - 11RP1 - 11

RP1 - 11

RP1 - 9 RP1 - 9

RP1 - 9

RP1 - 13

RP1 - 7

RP1 - 7

RP1 - 15

RP1 - 9

RP1 - 5

RP1 - 5

RP1 - 15

RP1 - 1 RP1 - 1

RP1 - 15

RP1 - 3

RP1 - 3RP1 - 3

RP3 - 3

RP3 - 1

RP3 - 1

RP3 - 3

RP3 - 1

RP3 - 3

RP3 - 1

RP3 - 3

RP1 - 13

RP1 - 13

RP1 - 15

SERVICE

DISCONNECT

A

B

C

D

E

1 2 3 4 5 6 7 8

B.5

B.9

C.3

C.6

B.1

B.6

C.1

C.5

C.9

1.1

METALS TECH. #2

METALS TECH #1

WOMEN

COMMUNICATIONS

CLOSET

MECHANICAL

A.G.E. #1

MEN

OFFICE

VEST.

CORR.

MEZZANINE

ABOVE E-102

WPI

GFCI

+42"

RP1 - 11

RP1 - 13

+42" +42" +42" +42"

+42"

+42"

+42"

+42" +42"

+42"

+42"

RP1 - 1

AC

GFCI

AC

GFCI

RP1 - 5

GFCI

2 1 1

1 1

RP1 - 7

GFCI

+42" RP1 - 7

RP1 - 7

GFCI

RP1 - 7 GFCI

+42"

GFCI

+42"

RP4-1

+42"

RP4-1

+42"

RP4-1

RP4-3

+42"

RP4-3

+42"

RP4-3

+42"

+42"

RP2-13

+42"

RP3-5

+42"

RP3-5

+42"

RP3-5 +42"

RP3-5

+42"

PR3-5

WPI

GFCI

RP1-15

+42"+42"+42"

+42"

+42"

+42" +42"

+42"

WPI

GFCI

RP1-9

WPI

GFCI

RP3-3

MANUAL TRANSFER

SWITCH

+42"

RP2-13

+42"

RP2-11

+42"

RP2-11

+42"

RP2-11

+42"

RP2-11

+42"

RP2-13

+42"

RP2-13

RP3-1

+42"

B

4 5

B.5

RP4-3

+36"

L A

Y O

U T

D R

A W

N

R E

V

IE

W E

D

D sheetsof

R E

V

IS

IO

N

D A

T E

H a n s o n N o

F ile n a m e

S c a le

D a te d

W in g

Il lin o is

A ir

N a ti o n a l G u a rd

S p ri n g fi e ld

Il lin o is

-2

H a n s o n

P ro fe s s io n a l S e rv ic e s I n c

S o u th S ix th

S tr e e t

P h o n e

(2

-2

O k la m h o m a C it y

O K

-7

N G

B I

D

IQ

C o n tr a c t

W

L

-1

-D

B ro a d w a y E x te n s io n

S u it e

P h o n e

(4

-2

C o p yr ig h t H a n so n

P ro fe ss io n a l S e rv ic e s In c

R E

P A

IR

C

IL

D

IN

G P

-1

S P

R

IN

G F

IE

L

D

IL

ISSUED FOR CONSTRUCTION 3 MAY 2021

S

IG

N E

/1

/2

E X

P

IR

E S

/3

/2

C U s e rs \ b ra n s

\ D o c u m e n ts

\ 1 D

E le c v s b ra n s o n .r v t

/2

/2

:1

: 1

P M

/3

/1

E L

E C

T R

IC

A

L

E

C E

P T

A C

L E

P L

A N

E-102

S K

B

G T

R

G T

R /0

/2

/0

/2

/0

/2

PLAN

NORTH

TRUE

NORTH

1/8" = 1'-0"

ELECTRICAL RECEPTACLE PLAN

1/8" = 1'-0"

MEZZANINE PARTIAL RECEPTACLE

PLAN

KEYED NOTES

1 DOUBLE DUPLEX WORKSTATION RECEPTACLE. ONE RECEPTACLE ALWAYS -ON,

ONE RECEPTACLE SWITCHED WITH ROOM LIGHTING CIRCUIT. SEE LIGHTING

CONTROL WIRING DIAGRAM SHEET E-605.

RECEPTACLE FOR EWC-1. COORDINATE LOCATION WITH EWC MANUFACTURER'S

MOUNTING TEMPLATE.

0 41 42 43

51 5

5 76

1 8

868788

98 99

107108

111 112

115116 a b

A

AIR FLOW

PUMP

AIR FLOW

PUMP

SB

B

B

RP2

RP3

PP1

RP1

MDP

T-2

T-1

A

B

C

D

E

1 2 3 4 5 6 7 8

B.5

B.9

C.3

C.6

B.1

B.6

C.1

C.5

C.9

1.1

SHEET METAL SHOP #1

MECHANICAL

COMMUNICATIONS

CLOSET

MEN

WOMEN

CORR.

VEST.

OFFICE

METALS TECH #1

METALS TECH. #2

T

A

B

C

D

E

1 2 3 4 5 6 7 8

B.5

B.8

C.3

C.6

B.1

B.6

C.2

C.9

1.1

A.8

A.2

D.2

D.8

0.90.8

B.9

4 4 3

T

RP1-10

RP1-14,16,18

RP1-2,4,6

RP1-8

PP1-8,10,12

RP4-19,21,23

RP4-25,27,29

RP4-20

RP1-12

PP1-2,4,6

RP4-10,12

RP4-14,16,18

RP4-6,8

RP4-2,4

RP4-7,9,11

RP4-5

RP4-13,15,17

RP2-7

RP2-1

RP2-5

RP2-3

RP2-9

R

P -7

R P

-9

R P

-1

R P

-1

RP3-

28,30,32

RP3-

23,25,27

RP3-34,36,38

RP3-29,31,33

RP3-22,24,26

RP3-35,37,39RP3-46,48,50

RP3-14,16,18;20

RP3-2,4,6

RP3-8,10,12

PP1-20,22,24

RP3-40,42,44 2

2 RP2-2,4,6

RP4

RP4-36,38,40

R P

-1

R P

-1

T-3

L A

Y O

U T

D R

A W

N

R E

V

IE

W E

D

D sheetsof

R E

V

IS

IO

N

D A

T E

H a n s o n N o

F ile n a m e

S c a le

D a te d

W in g

Il lin o is

A ir

N a ti o n a l G u a rd

S p ri n g fi e ld

Il lin o is

-2

H a n s o n

P ro fe s s io n a l S e rv ic e s I n c

S o u th S ix th

S tr e e t

P h o n e

(2

-2

O k la m h o m a C it y

O K

-7

N G

B I

D

IQ

C o n tr a c t

W

L

-1

-D

B ro a d w a y E x te n s io n

S u it e

P h o n e

(4

-2

C o p yr ig h t H a n so n

P ro fe ss io n a l S e rv ic e s In c

R E

P A

IR

C

IL

D

IN

G P

-1

S P

R

IN

G F

IE

L

D

IL

ISSUED FOR CONSTRUCTION 3 MAY 2021

S

IG

N E

/1

/2

E X

P

IR

E S

/3

/2

C U s e rs \ b ra n s

\ D o c u m e n ts

\ 1 D

E le c v s b ra n s o n .r v t

/2

/2

:1

: 1

P M

/0

/1

E L

E C

T R

IC

A

L S

H O

P E

Q U

IP

M

E N

T P

L A

N

E-103

S K

B

G T

R

G T

R /0

/2

/0

/2

/0

/2

1/8" = 1'-0"

ELECTRICAL SHOP EQUIPMENT PLAN

PLAN

NORTH

TRUE

NORTH

GENERAL NOTES

1. SEE ONE-LINE DIAGRAM SHEET E-601 AND PANELBOARD SCHEDULES

SHEETS E-602 AND E-603 FOR CONDUIT & WIRE INFORMATION.

2. SEE EQUIPMENT CONNECTION SCHEDULE ON SHEET E-602 FOR

ADDITIONAL INFORMATION.

KEYED NOTES

COMBINATION ENCLOSED CIRCUIT BREAKER AND 200A, 3P + G PIN AND SLEEVE

RECEPTACLE FOR ITEM 122. SEE ONE LINE DIAGRAM ON SHEET E-601 FOR

CONNECTION TO TRANSFORMER T-2.

DISCONNECT FOR HOIST. COORDINATE LOCATION AND CONNECTIONS WITH

HOIST MANUFACTURER.

PROVIDE SINGLE FLOOR MOUNTED METAL STRUT SUPPORT POST FOR

RECEPTACLE. ROUTE RECEPTACLE SUPPLY CONDUIT FOR RECEPTACLE BELOW

FLOOR SLAB.

PROVIDE TWO FLOOR MOUNTED METAL STRUT SUPPORT POSTS FOR SAFETY

SWITCH. ROUTE SAFETY SWITCH SUPPLY CONDUIT BELOW FLOOR SLAB.

ITEM 46 TO HAVE GFCI 20KVA, 208 X 440V TRANSFORMER AS PART OF

EQUIPMENT PACKAGE. CONTRACTOR SHALL PROVIDE ALL CONDUIT, WIRING,

AND CONNECTIONS TO TRANSFORMER AND BETWEEN TRANSFORMER AND

EQUIPMENT.

SB

E

1 2

C.9

1.1

D

E

1 2

C.9

1.1

D.2

D.8

0.90.8

SEE STRUCTURAL PLANS FOR

MORE DETAILED INFORMATION

ON THIS CANOPY FOOTING

TEMPORARY GENERATOR

CONNECTION CABINET

DWH-1AC-2

EF-2

AC-1

RP1-32,34,36

RP1-38,40,42

RP1-17

RP1-33

M

J

M

MANUAL TRANSFER SWITCH

MDP

T-1

RP1

PP1

UH-2

RP1-21

RP1-23

FCU-6

CP-1

RP1-33

M

RP1-27

RP1-31

RP1-29

SERVICE DISCONNECT

PADMOUNT

SERVICE

TRANSFORMER

E-606

E-606

+90"

RP1-25

L A

Y O

U T

D R

A W

N

R E

V

IE

W E

D

D sheetsof

R E

V

IS

IO

N

D A

T E

H a n s o n N o

F ile n a m e

S c a le

D a te d

W in g

Il lin o is

A ir

N a ti o n a l G u a rd

S p ri n g fi e ld

Il lin o is

-2

H a n s o n

P ro fe s s io n a l S e rv ic e s I n c

S o u th S ix th

S tr e e t

P h o n e

(2

-2

O k la m h o m a C it y

O K

-7

N G

B I

D

IQ

C o n tr a c t

W

L

-1

-D

B ro a d w a y E x te n s io n

S u it e

P h o n e

(4

-2

C o p yr ig h t H a n so n

P ro fe ss io n a l S e rv ic e s In c

R E

P A

IR

C

IL

D

IN

G P

-1

S P

R

IN

G F

IE

L

D

IL

ISSUED FOR CONSTRUCTION 3 MAY 2021

S

IG

N E

/1

/2

E X

P

IR

E S

/3

/2

C U s e rs \ b ra n s

\ D o c u m e n ts

\ 1 D

E le c v s b ra n s o n .r v t

/2

/2

:1

: 1

P M

/3

/1

P A

R T

IA

L

E L

E C

T R

IC

A

L P

L A

N M

E C

H /E

L E

C T

R

IC

A L

R O

O M

E-104

S K

B

G T

R

G T

R /0

/2

/0

/2

/0

/2

PLAN

NORTH

TRUE

NORTH

1/2" = 1'-0"

PARTIAL ELECTRICAL PLAN - MECH /

ELECT. ROOM

KEYED NOTES

1 EXISTING UNDERGROUND PRIMARY ELECTRIC DUCT BANK TO REMAIN.

PROTECT FROM DAMAGE

EXISTING PRIMARY CONDUIT TO PRIMARY SWITCH. SEE E-101 FOR

CONTINUATION.

COORDINATE NEW TRANSFORMER PAD WITH EXISTING PRIMARY DUCTBANK

SO NEW PRIMARY CABLES IN EXISTING CONDUIT CAN BE PROPERLY

TERMINATED AT TRANSFORMER.

NEW UNDERGROUND BUILDING SERVICE LATERAL.

EMERGENCY FEEDER FROM TEMPORARY GENERATOR CONNECTION

CABINET TO MANUAL TRANSFER SWITCH.

UNDERGROUND 1 1/4" SCHEDULE 80 PVC CONDUIT WITH ONE (1) #3/0 BARE

STRANDED COPPER GROUND ELECTRODE CONDUCTOR.

1 1/4" SCHEDULE 80 PVC CONDUIT WITH ONE (1) #3/0 BARE STRANDED

COPPER GROUND ELECTRODE CONDUCTOR.

PROVIDE PIPE GROUND CLAMP ON NEW DOMESTIC WATER SERVICE PIPE.

NEW GROUND BAR. SEE DETAIL 3/E-606.

BOND NEW GROUND ELECTRODE CONDUCTOR TO EXISTING BUILDING

STRUCTURAL STEEL WITH EXOTHERMIC WELD.

NEW BUILDING GROUND FIELD. THREE (3) 3/4" X 10’ GROUND RODS IN A 20’

EQUILATERAL TRIANGLE INTERCONNECTED WITH #3/0 BARE STRANDED

COPPER GROUND ELECTRODE CONDUCTOR.

1” SCHEDULE 80 PVC WITH #2 BARE STRANDED COPPER GROUND

ELECTRODE CONDUCTOR.

MOUNT SPD DIRECTLY ABOVE SERVICE DISCONNECT. ROUTE SPD

CONDUCTORS DIRECTLY FROM SPD ENCLOSURE INTO SERVICE

DISCONNECT ENCLOSURE.

DIGITAL METER PACKAGE (DMP) COMPATIBLE WITH EXISTING BASE ENERGY

MANAGEMENT SYSTEM.

NEW GAS SERVICE METER WITH PULSE OUTPUT BY PLUMBING

CONTRACTOR.

NEW WATER SERVICE METER WITH PULSE OUTPUT BY PLUMBING

CONTRACTOR.

1/2" CONDUIT WITH #18 UNSHIELDED TWISTED PAIR CABLE. PULSED METER

OUTPUT TO DMP.

PROVIDE THE FOLLOWING ENGRAVED PLASTIC WARNING SIGNS AT

TEMPORARY GENERATOR CONNECTION CABINET:

“WARNING: FOR CONNECTION OF A NON-SEPARATELY DERIVED (FLOATING

NEUTRAL) GENERATOR ONLY.”

“WARNING: BUILDING CONNECTED LOAD EXCEEDS MAXIMUM TEMPORARY

GENERATOR CAPACITY. MANUAL MANAGEMENT OF BUILDING LOAD

REQUIRED WHEN TEMPORARY GENERATOR CONNECTED.”

1 1/4" SCHEDULE 80 PVC WITH ONE (1) #3/0 BARE STRANDED COPPER

GROUND ELECTRODE CONDUCTOR TO FIRE PROTECTION WATER SERVICE IN

ROOM 108 - METALS TECH #2. SEE E-101 FOR CONTINUATION.

1" SCHEDULE 80 PVC WITH ONE (1) #2 BARE STRANDED COPPER GROUND

ELECTRODE CONDUCTOR TO GROUND BAR IN ROOM 111 - COMMUNICATIONS

CLOSET. SEE E-301 FOR CONTINUATION.

FCU CONDENSATE PUMP.

GENERAL NOTES

1. SEE ONE-LINE DIAGRAM SHEET E-601 FOR ADDITIONAL CONDUIT AND

WIRE INFORMATION.

2. SEE PANELBOARD SCHEDULES ON SHEETS E-602 AND E-603 FOR

BRANCH CIRCUIT CONDUIT AND WIRE INFORMATION.

LV

V

L V

LV

L V

LV

LV

L V L

V L V

LV

L V

L V

T

OS

O S

L V

LV LV

LV

L V L

V

LV

LV

OS

OSOS

OS

OS

OS OS

OS

OS

LV

a

A

B

C

D

E

1 2 3 4 5 6 7 8

B.5

B.9

C.3

C.6

B.1

B.6

C.1

C.5

C.9

1.1

METALS TECH. #2

METALS TECH #1

SHEET METAL SHOP #1

COMMUNICATIONS

CLOSET

MECHANICAL

A.G.E. #1

SHEET METAL SHOP

E-201

E-201

SEE ENLARGED PLAN

A2

PP-1

a

A2

PP-1

a

A2

PP-1

a

2 2

A1E

PP1-3

p

A1

PP1-3

p p p G1E

PP1-5

q q

DE

PP1-3

q

B

PP1-1

a,b

A2

PP1-3

l,m

A2E

PP1-3

l,m

A2

PP1-3

l,n

A2

PP1-3

l,n

A2

PP1-3

l,n

A2

PP1-3

l,m l a

G1E

PP1-5

aX

PP1-1

B

PP1-1

a,c

B

PP1-1

a,c

B

PP1-1

a,c B

PP1-1

a,c

B

PP1-1

a,c

B

PP1-1

a,c

BE

PP1-1

a,c

B

PP1-1

a,b

B

PP1-1

a,b

B

PP1-1

a,c

B

PP1-1

a,c

B

PP1-1

a,c

B

PP1-1

a,c

BE

PP1-1

a,c

BE

PP1-1

a,b

BE

PP1-1

a,c

BE

PP1-1

a,c B

PP1-1

a,c

X

PP1-1

G2E

PP1-5

G2

PP1-5

G1

PP1-5

G1

PP1-5

X

PP1-1

a x a

X

PP1-1

r

G1

PP1-5

X

PP1-3

x

A2E

PP1-3

x

A2E

PP1-3

x

A2E

PP1-3

x

A2E

PP1-3

x

A2

PP1-3

x

A2

PP1-3

x

A2

PP1-3

x

A2

PP1-3

x

A2

PP1-3

x

A2

PP1-3

x

A2

PP1-3

x

A2

PP1-3

x

A2

PP1-3

x

A2

PP1-3

x

A2

PP1-3

x

G1E

PP1-5

X PP1-3 x

X PP1-3r

6G1E

PP1-5

A2

PP1-3

u,w

A2

PP1-3

u,w

A2

PP1-3

u,v

A2E

PP1-3

u,v j u

A2

PP1-3

r,t

A2E

PP1-3

r,s

A2

PP1-3

r

A2

PP1-3

r,s

A2

PP1-3

r,t

A2

PP1-3

r,t

A2

PP1-3

r,t

A2

PP1-3

r,s

A2

PP1-3

r,s

A2E

PP1-3

r

A2E

PP1-3

r,t

A2E

PP1-3

r,s

G1E

PP1-5

X

PP1-3

r m n

PC

PC

b

PC

c

PC

PC

PC

PC

b b c

PC

c

PC

c

PC

t

PC

s

PC

t

PC

s

PC

t

PC

s

PC

v

PC

w x

PC

c

PC

c

PC

c

PC

c

PC

c

PC

c

D

E

3 4 5 6

C2

PP1-3

e,f

C2

PP1-3

e,f

C2

PP1-3

e,g

C2E

PP1-3

e,g eC1E

PP1-3

h h h X

PP1-3

e

E

PP1-3

j

E

PP1-3

j

EE

PP1-3

j

E

PP1-3

j j j j

F1

PP1-3

j

F2

PP1-3

k g k

E

PP1-3

k

E

PP1-3

k

E

PP1-3

k

EE

PP1-3

k

E

PP1-3

k k i i

X

PP1-3

C1E

PP1-3

i

C1

PP1-3

i i

MOUNT 7'-0"

AFF TO CENTER

OF FIXTURE

MOUNT 7'-0"

AFF TO CENTER

OF FIXTURE

PC

f

PC

g

B

4 5 6

B.5

A1

PP1-1

d

A1E

PP1-1

d

A1

PP1-1

d d d

3 3 3

L A

Y O

U T

D R

A W

N

R E

V

IE

W E

D

D sheetsof

R E

V

IS

IO

N

D A

T E

H a n s o n N o

F ile n a m e

S c a le

D a te d

W in g

Il lin o is

A ir

N a ti o n a l G u a rd

S p ri n g fi e ld

Il lin o is

-2

H a n s o n

P ro fe s s io n a l S e rv ic e s I n c

S o u th S ix th

S tr e e t

P h o n e

(2

-2

O k la m h o m a C it y

O K

-7

N G

B I

D

IQ

C o n tr a c t

W

L

-1

-D

B ro a d w a y E x te n s io n

S u it e

P h o n e

(4

-2

C o p yr ig h t H a n so n

P ro fe ss io n a l S e rv ic e s In c

R E

P A

IR

C

IL

D

IN

G P

-1

S P

R

IN

G F

IE

L

D

IL

ISSUED FOR CONSTRUCTION 3 MAY 2021

S

IG

N E

/1

/2

E X

P

IR

E S

/3

/2

C U s e rs \ b ra n s

\ D o c u m e n ts

\ 1 D

E le c v s b ra n s o n .r v t

/2

/2

:1

: 1

P M

/1

/1

L

IG

H T

IN

G

P L

A N

E-201

S K

B

G T

R

G T

R /0

/2

/0

/2

/0

/2

1/8" = 1'-0"

LIGHTING PLAN

PLAN

NORTH

TRUE

NORTH

KEYED NOTES

1 MOUNT FIXTURES 26' AFF.

MOUNT FIXTURES TO UNDERSIDE OF MEZZANINE.

SUSPEND FIXTURES TO 10' ABOVE MEZZANINE FLOOR. COORDINATE LOCATIONS WITH

HVAC EQUIPMENT AND DUCTWORK.

MOUNT FIXTURES 10' AFF.

MOUNT FIXTURES 12' AFF.

MOUNT FIXTURE 9' ABOVE FINISHED GRADE.

FIXTURE TO BE MOUNTED ON BUILDING WALL AT BOTTOM OF OVER HANG.

MOUNT FIXTURE 12' ABOVE FINISHED GRADE.

1/4" = 1'-0"

PARTIAL LIGHTING PLAN - OFFICES &

TOILETS

1/8" = 1'-0"

MEZZANINE LIGHTING PLAN

PRIMARY DAYLIGHTING CONTROL ZONE

SECONDARY DAYLIGHTING CONTROL ZONE

J

J

L V

LV LV

LV

A

B

C

D

E

1 2 3 4 5 6 7 8

B.5

B.9

C.3

C.6

B.1

B.6

C.1

C.5

C.9

1.1

E-301

W 107-01

WAP-02

WAP-01

101-01 101-02

101-03

101-04

101-05 101-06

W 100-03

WAP-03

100-06 W

W 100-04

W 110-01

110-02 W

108-01 W

109-01 W

W 108-02

110-03 W

W 100-01

10 W 106-01

+36" 106-02

10 10

+36" 100-02

110-04 +36"

100-05 +36"

+36" 109-02

11 CAM-01

A

B

C

D

E

1 2 3 4 5 6 7 8

B.5

B.8

C.3

C.6

B.1

B.6

C.2

C.9

1.1

A.8

A.2

D.2

D.8

0.90.8

B.9

D S

D S 14

107-02 12

102-01

D S15

D S15

DS

DSDS

DS

DS

D S 14

D S 15

DD

C.9C.9

111-01

L A

Y O

U T

D R

A W

N

R E

V

IE

W E

D

D sheetsof

R E

V

IS

IO

N

D A

T E

H a n s o n N o

F ile n a m e

S c a le

D a te d

W in g

Il lin o is

A ir

N a ti o n a l G u a rd

S p ri n g fi e ld

Il lin o is

-2

H a n s o n

P ro fe s s io n a l S e rv ic e s I n c

S o u th S ix th

S tr e e t

P h o n e

(2

-2

O k la m h o m a C it y

O K

-7

N G

B I

D

IQ

C o n tr a c t

W

L

-1

-D

B ro a d w a y E x te n s io n

S u it e

P h o n e

(4

-2

C o p yr ig h t H a n so n

P ro fe ss io n a l S e rv ic e s In c

R E

P A

IR

C

IL

D

IN

G P

-1

S P

R

IN

G F

IE

L

D

IL

ISSUED FOR CONSTRUCTION 3 MAY 2021

S

IG

N E

/1

/2

E X

P

IR

E S

/3

/2

C U s e rs \ b ra n s

\ D o c u m e n ts

\ 1 D

E le c v s b ra n s o n .r v t

/2

/2

:1

: 2

P M

/2

/1

C O

M M

U N

IC

A

T

IO

N S

A N

D S

E C

U R

IT

Y

P L

A N

E-301

S K

B

G T

R

G T

R /0

/2

/0

/2

/0

/2

1/8" = 1'-0"

COMMUNICATIONS AND SECURITY

PLAN

PLAN

NORTH

TRUE

NORTH

1/2" = 1'-0"

ENLARGED DATA CLOSET 111 PLAN

4” COMMUNICATIONS SERVICE CONDUIT EXTENDED FROM EXISTING OUTSIDE OF

BUILDING. STUB CONDUIT UP 6” AFF.

SEE COMMUNICATIONS FLOOR PLAN THIS SHEET FOR CONTINUATION.

4’ X 8’ X 3/4" FIRE TREATED PLYWOOD TERMINAL BOARD. MOUNT BOARD VERTICALLY.

PULL SALVAGED BUILDING FIBER OPTIC SERVICE CABLE FROM EXISTING MANHOLE IN

EXTENDED CONDUIT TO TERMINATION PANEL IN NEW DATA EQUIPMENT RACK. TERMINATE

ALL OPTICAL FIBERS IN TERMINATION CABINET.

NEW 50 PAIR TYPE 110 UNSHIELDED TWISTED PAIR (UTP) PUNCH-DOWN BLOCK WITH

SERVICE ARRESTERS. PULL SALVAGED BUILDING UTP SERVICE CABLE FROM EXISTING

MANHOLE IN EXTENDED CONDUIT TO PUNCH-DOWN BLOCK. TERMINATE UTP CABLE TO

PUNCH-DOWN BLOCK.

NEW DATA RACK. SEE SCHEDULE AND DETAILS ON SHEET E-605.

DOOR ACCESS SYSTEM HEAD-END EQUIPMENT SALVAGED FROM EXISTING BUILDING.

CONTRACTOR TO INSTALL EQUIPMENT ON NEW TERMINAL BOARD. CONTRACTOR TO

COORDINATE WITH EXISTING DOOR ACCESS SYSTEM VENDOR FOR REINSTALLATION AND

RECONNECTION OF EXISTING EQUIPMENT.

TELECOMMUNICATIONS EQUIPMENT GROUND BAR. SEE DETAIL 3 ON SHEET E-606.

PROVIDE 1” SCH. 80 PVC CONDUIT WITH #2 AWG BARE STRANDED COPPER BONDING

CONDUCTOR FROM GROUND BAR TO SERVICE GROUND BAR IN MECHANICAL ROOM 107.

COMMUNICATIONS OUTLET FOR FIRE ALARM EQUIPMENT. COORDINATE WITH FIRE ALARM

SYSTEM SUPPLIER.

PROVIDE 3/4" CONDUIT WITH NUMBER OF CABLES AS NOTED FROM COMMUNICATIONS

OUTLET BOX TO DATA RACK IN DATA CLOSET 111.

CONTRACTOR TO REINSTALL SALVAGED CAMERA TO BUILDING EXTERIOR EVE. PROVIDE

CAST BOX WITH BLANK GASKETED COVER FOR DATA PORT; LOCATE PORT INSIDE OUTLET

BOX.

COMMUNICATIONS OUTLET FOR PANEL MDP DIGITAL METER PACKAGE (DMP).

CONTRACTOR TO PROVIDE JUNCTION BOX AT DOOR FOR NEW ACCESS CONTROL SYSTEM

COMPONENTS. PROVIDE 3/4" CONDUIT FROM JUNCTION BOX TO ACCESS CONTROL

SYSTEM HEAD-END EQUIPMENT IN ROOM 111. PROVIDE 1/2" CONDUIT FROM JUNCTION

BOX TO ACCESS CONTROL COMPONENTS AT DOOR. ACCESS CONTROL COMPONENTS

AND WIRING BY ACCESS CONTROL SYSTEM VENDOR.

EXISTING DOOR POSITION SWITCH TO BE RE-INSTALLED AT NEW DOOR LOCATION BY

ACCESS CONTROL SYSTEM VENDOR. CONTRACTOR TO PROVIDE 1/2" CONDUIT FROM

DOOR TO ACCESS CONTROL SYSTEM HEAD-END EQUIPMENT IN ROOM 111. NEW WIRE

FROM DOOR LOCATION TO ROOM 111 BY ACCESS CONTROL SYSTEM VENDOR.

NEW DOOR POSITION SWITCH FOR NEW COILING DOOR BY ACCESS CONTROL SYSTEM

VENDOR. CONTRACTOR TO PROVIDE 1/2" CONDUIT FROM DOOR TO ACCESS CONTROL

SYSTEM HEAD-END EQUIPMENT IN ROOM 111. NEW WIRE FROM DOOR LOCATION TO

ROOM 111 BY ACCESS CONTROL SYSTEM VENDOR.

PROVIDE EXTENSION OF EXISTING 4" COMMUNICATIONS CONDUITS FROM BUILDING

EXTERIOR TO COMMUNICATIONS CLOSET 111.

KEYED NOTES

1. SEE SCHEDULES ON SHEET E-605 FOR CABLE TERMINATIONS AT PATCH PANELS AND

FOR COMMUNICATIONS EQUIPMENT RACK LAYOUT.

2. CONTRACTOR SHALL UTILIZE EXISTING SLACK IN SERVICE FIBER OPTIC AND COPPER

COMMUNICATIONS CABLES IN EXISTING COMMUNICATIONS MANHOLE AS REQUIRED

TO PROVIDE SUFFICIENT CABLE LENGTH IN BUILDING TO REACH NEW TERMINATION

POINTS.

3. CONTRACTOR SHALL INCLUDE ALL COSTS FROM ACCESS CONTROL SYSTEM

VENDOR FOR ACCESS CONTROL SYSTEM MODIFICATIONS IN THEIR BID.

GENERAL NOTES

SERVICE TRANSFORMER

12.47 x 480Y/277V, 3Ø, 750KVA

N G

SERVICE

DISCONNECT

TEMPORARY GENERATOR

CONNECTION CABINET

400A, 3Ø, 4W + G.

P

50A

Δ Y

X0G

BASE

PRIMARY

LOOP

BASE

PRIMARY

LOOP

TO

PRIMARY

SWITCH

SW7A

EXISTING

PRIMARY

SWITCH

SW7

N

G

DMP 17

N

G

10SPD

NG NG

PANEL

PP1

PANEL

PP2

NG

Δ

Y X0

G

11T-1

PANEL

RP1

NG

Δ

Y X0

G

11T-2

PANEL

RP2

NG

Δ

Y X0

G

11T-3

PANEL

RP3

14 15 15 15

FUTURE GFGI

SANDING

BOOTH

FUTURE GFGI

PAINT BOOTH

FUTURE GFGI

SANDING BOOTH

DX COOLING

UNIT

FUTURE GFGI

PAINT BOOTH

DX COOLING

UNIT

PANEL MDP

1200YS

1200Y

400Y

M M

18 19

10 10 10 10

300Y 100Y 300Y

16 16 16

225AF

200AT

3P

200D

NG

PANEL

RP4

GF

1200 AF

1200 AT

3P

SN

G

1200Y

MANUAL

TRANSFER SWITCH

1200A, 3P

28 28 28 28 28

13 13

20'-0" MINIMUM SPACING

3/4" x 10'-0" COPPER CLAD

GROUND ROD, CONNECT WITH

EXOTHERMIC WELD.

#3/0 AWG BARE STRANDED COPPER

GROUND ELECTRODE CONDUCTOR

(TYP. BETWEEN GROUND RODS)

TO SERVICE TRANSFORMER

GROUND BAR IN

ROOM 107 - MECHANICAL

SEE DETAIL 3, SHEET E-606

TO COMMUNICATIONS

GROUND BAR IN ROOM 111

TO TRANSFORMER T-1

L A

Y O

U T

D R

A W

N

R E

V

IE

W E

D

D sheetsof

R E

V

IS

IO

N

D A

T E

H a n s o n N o

F ile n a m e

S c a le

D a te d

W in g

Il lin o is

A ir

N a ti o n a l G u a rd

S p ri n g fi e ld

Il lin o is

-2

H a n s o n

P ro fe s s io n a l S e rv ic e s I n c

S o u th S ix th

S tr e e t

P h o n e

(2

-2

O k la m h o m a C it y

O K

-7

N G

B I

D

IQ

C o n tr a c t

W

L

-1

-D

B ro a d w a y E x te n s io n

S u it e

P h o n e

(4

-2

C o p yr ig h t H a n so n

P ro fe ss io n a l S e rv ic e s In c

R E

P A

IR

C

IL

D

IN

G P

-1

S P

R

IN

G F

IE

L

D

IL

ISSUED FOR CONSTRUCTION 3 MAY 2021

S

IG

N E

/1

/2

E X

P

IR

E S

/3

/2

C U s e rs \ b ra n s

\ D o c u m e n ts

\ 1 D

E le c v s b ra n s o n .r v t

/2

/2

:1

: 2

P M

/1

/1

O N

E -L

IN

E

D

IA

G R

A M

A N

D D

E T

A

IL

S

E-601

S K

B

G T

R

G T

R /0

/2

/0

/2

/0

/2

NONE

ELECTRICAL ONE-LINE DIAGRAM

KEYED NOTES

1 REMOVE EXISTING FUSES SUPPLYING EXISTING BUILDING P-17 TRANSFORMER AND

PROVIDE NEW 60A FUSES.

REMOVE EXISTING PRIMARY CABLES FROM EXISTING UNDERGROUND DUCTBANK TO

EXISTING BUILDING P-17 TRANSFORMER. PROTECT EXISTING DUCTBANK FROM DAMAGE.

PROVIDE THREE (3) #6 AWG 15KV, 33% CONCENTRIC NEUTRAL, SHIELDED MEDIUM

VOLTAGE CABLES IN EXISTING DUCTBANK.

PROVIDE NEW 200A, 15KV LOADBREAK ELBOW TERMINATIONS ON ENDS OF NEW PRIMARY

CABLES.

BOND NEUTRAL-TO-GROUND AT TRANSFORMER.

TO NEW BUILDING GROUND FIELD. SEE DETAIL 2 THIS SHEET.

BOND NEUTRAL-TO-GROUND IN SERVICE DISCONNECT.

TO BUILDING GROUND BAR IN MECHANICAL ROOM 107. SEE DETAIL 2 THIS SHEET.

SERVICE SURGE PROTECTION DEVICE WITH INTEGRAL DISCONNECT MOUNTED ABOVE

SERVICE DISCONNECT ENCLOSURE.

PROVIDE ENGRAVED NAMEPLATES AT GENERATOR TERMINATION CABINET WITH THE

FOLLOWING TEXT”

“WARNING: FOR CONNECTION OF A NON-SEPARATELY DERIVED (FLOATING

NEUTRAL) GENERATOR ONLY”.

“WARNING: BUILDING CONNECTED LOAD EXCEEDS MAXIMUM TEMPORARY

GENERATOR CAPACITY. MANUAL MANAGEMENT OF BUILDING LOAD REQUIRED

WHEN TEMPORARY GENERATOR CONNECTED.”

DO NOT PROVIDE NEUTRAL-TO-GROUND BOND IN PANELBOARD.

SEE TRANSFORMER SCHEDULE THIS SHEET.

PROVIDE #2 BARE STRANDED COPPER BONDING CONDUCTOR IN 1” SCHEDULE 80 PVC

CONDUIT FROM TRANSFORMER TO BUILDING GROUND BAR IN MECHANICAL ROOM 107. SEE

DETAIL 2 THIS SHEET.

PROVIDE #2/0 BARE STRANDED COPPER BONDING CONDUCTOR IN 1 1/4” SCHEDULE 80 PVC

CONDUIT FROM TRANSFORMER TO BUILDING STRUCTURAL STEEL FRAME (COMMON

GROUND ELECTRODE CONDUCTOR). CONNECT BONDING CONDUCTOR TO BUILDING

STRUCTURAL STEEL FRAME WITH EXOTHERMIC WELD.

EMPTY 3” CONDUIT.

EMPTY 2 1/2" CONDUIT.

ROUTE EMPTY CONDUIT TO LOCATION SHOWN ON FLOOR PLANS AND CAP FOR FUTURE

EXTENSION TO GFGI EQUIPMENT.

DIGITAL METER PACKAGE (DMP) COMPATIBLE WITH EXISTING BASE ENERGY MANAGEMENT

SYSTEM. LOCATE OUTBOARD OF PANEL MDP – DO NOT PROVIDE METERING PACKAGE

THAT IS INTEGRAL TO PANELBOARD.

NEW WATER SERVICE METER WITH PULSE OUTPUT BY PLUMBING CONTRACTOR.

ELECTRICAL CONTRACTOR TO PROVIDE CONNECTION FROM METER TO DMP.

NEW GAS SERVICE METER WITH PULSE OUTPUT BY PLUMBING CONTRACTOR.

ELECTRICAL CONTRACTOR TO PROVIDE CONNECTION FROM METER TO DMP.

ETHERNET CONNECTION FROM DMP TO DATA EQUIPMENT RACK IN ROOM 111 FOR

COMMUNICATION BETWEEN DMP AND BASE ENERGY MANAGEMENT SYSTEM.

ENCLOSED CIRCUIT BREAKER AND 200A, 3P + G PIN AND SLEEVE RECEPTACLE FOR EPU-6

(ITEM 122) ON WALL NEXT TO TRANSFORMER.

DO NOT CONNECT NEUTRAL TO GROUND IN TRANSFER SWITCH.

#2 AWG BARE STRANDED COPPER GROUND ELECTRODE CONDUCTOR IN 1” SCHEDULE 80

PVC CONDUIT.

#3/0 AWG BARE STRANDED COPPER GROUND ELECTRODE CONDUCTOR IN 1 1/4"

SCHEDULE 80 PVC CONDUIT.

EXISTING BUILDING STRUCTURAL STEEL COLUMN IN ROOM 111.

DOMESTIC WATER SERVICE MAIN IN ROOM 111.

FIRE PROTECTION WATER SERVICE MAIN IN ROOM 108.

SEE PANELBOARD SCHEDULES ON SHEETS E-602 AND E-603 FOR CONDUIT AND WIRE

SIZES TO CIRCUITS SUPPLIED BY PANELBOARD NOT SHOWN ON THIS SHEET.

NONE

GROUNDING ONE-LINE DIAGRAM

T-3 METALS TECH #2 - RM 108 480 208Y / 120V 3 150

T-2 A.G.E #1 - RM 110 480 208Y / 120V 3 75

T-1 MECH / ELECT - RM 107 480 208Y / 120V 3 75

TAG LOCATION VOLTAGE VOLTAGE PH. kVA

PRIMARY SECONDARY

TRANSFORMER SCHEDULE

NOTE: SEE PANELBOARD SCHEDULES FOR ADDITIONAL CONDUIT AND WIRE SIZES.

1200YS 4 3" 350 KCM 350 KCM -

1200Y 4 3" 350 KCM 350 KCM #4/0 AWG

400Y 1 3 1/2" 500 KCM 500 KCM #2 AWG

300Y 1 3" 350 KCM 350 KCM #4 AWG

200D 1 2" #3/0 AWG - #6 AWG

100Y 1 1 1/4" #2 AWG #2 AWG #6 AWG

TAG # SETS CONDUIT PHASE NEUTRAL GROUND

PER SET SIZES

FEEDER SCHEDULE

Y O

U T

D R

A W

N

R E

V

IE

W E

D

D sheetsof

R E

V

IS

IO

N

D A

T E

H a n s o n N o

F ile n a m e

S c a le

D a te d

W in g

Il lin o is

A ir

N a ti o n a l G u a rd

S p ri n g fi e ld

Il lin o is

-2

H a n s o n

P ro fe s s io n a l S e rv ic e s I n c

S o u th S ix th

S tr e e t

P h o n e

(2

-2

O k la m h o m a C it y

O K

-7

N G

B I

D

IQ

C o n tr a c t

W

L

-1

-D

B ro a d w a y E x te n s io n

S u it e

P h o n e

(4

-2

C o p yr ig h t H a n so n

P ro fe ss io n a l S e rv ic e s In c

R E

P A

IR

C

IL

D

IN

G P

-1

S P

R

IN

G F

IE

L

D

IL

ISSUED FOR CONSTRUCTION 3 MAY 2021

S

IG

N E

/1

/2

E X

P

IR

E S

/3

/2

C U s e rs \ b ra n s

\ D o c u m e n ts

\ 1 D

E le c v s b ra n s o n .r v t

/2

/2

:1

: 2

P M

/1

/1

E L

E C

T R

IC

A

L P

A N

E L

B O

A R

D S

C H

E D

U L

E S

E-602

S K

B

G T

R

G T

R /0

/2

/0

/2

/0

/2

3. DIGITAL METER PACKAGE (DMP) SHALL BE COMPATIBLE WITH EXISTING BASE ENERGY MANAGEMENT SYSTEM.

2. PROVIDE EMPTY CONDUIT TO LOCATION SHOWN ON FLOOR PLANS. PROVIDE PULL STRING IN CONDUIT AND CAP FOR FUTURE EXTENSION TO EQUIPMENT.

1. PROVIDE CIRCUIT BERAKER WITH ADJUSTABLE TRIP SO FINAL TRIP SETTING CAN BE COORDINATED WITH EQUIPMENT ACTUALLY FURNISHED.

NOTES:

895 874 865 DEMAND AMPS / PHASE

1112 1087 1075 CONNECTED AMPS / PHASE TOTAL DEMAND LOAD (kVA): 729.72

OPTIONS: 308.03 301.05 297.88 CONNECTED kVA / PHASE TOTAL CONNECTED LOAD (kVA): 906.95

#12 #12 #12 - DMP (SEE NOTE 3) 60 20 3 6 - - - - - - 12 SPACE - - - -

250 KCM - #4 2 1/2"

RP3 & RP4

(VIA TRANSFORMER T-3)

400 250 3 5 60.29 - 55.08 - 53.77 - 11 SPACE - - - -

#1 - #6 1 1/4"

RP2 & ITEM 122

(VIA TRANSFORMER T-2)

225 125 3 4 21.08 36.00 20.36 36.00 20.78 36.00 10 225 200 3

PAINT BOOTH DX COOLING

(GFGI - SEE NOTES 1 & 2)

- - - 2 1/2"

#1 - #6 1 1/4" RP1 (VIA TRANSFORMER T-1) 225 125 3 3 20.51 36.00 20.09 36.00 20.15 36.00 9 225 200 3

SANDING BOOTH DX COOLING

(GFGI - SEE NOTES 1 & 2)

- - - 2 1/2"

#1/0 #1/0 #6 1 1/2" PP2 225 150 3 2 25.91 41.50 25.91 41.50 25.91 41.50 8 225 200 3

PAINT BOOTH

(GFGI - SEE NOTES 1 & 2)

- - - 2 1/2"

#2 #2 #8 1 1/4" PP1 100 100 3 1 11.35 55.40 10.71 55.40 8.37 55.40 7 400 250 3

SANDING BOOTH

(GFGI - SEE NOTES 1 & 2)

- - - 3"

PH N G C DESCRIPTION FRAME TRIP LEFT RIGHT LEFT RIGHT LEFT RIGHT FRAME TRIP DESCRIPTION PH N G C

CIRCUIT AMP AMP

P O

L E

C K

T # PHASE A kW PHASE B kW PHASE C kW

C K

T

# AMP AMP

P O

L

E CIRCUIT

MAINS: 1200 A MLO SYM. INTERRUPT RATING:

NAME: MDP VOLTAGE: 277 / 480 V, THREE PHASE, 4 WIRE + G ENCLOSURE RATING: NEMA

DISTRIBUTION PANELBOARD SCHEDULE

27 25 20 DEMAND AMPS / PHASE

41 39 30 CONNECTED AMPS / PHASE TOTAL DEMAND LOAD (kVA): 19.93

OPTIONS: INTEGRAL SURGE SUPRESSION 11.35 10.71 8.37 CONNECTED kVA / PHASE TOTAL CONNECTED LOAD (kVA): 30.43

- - - - SPACE 41 - - 42 SPACE - - - -

- - - - SPACE 39 - - 40 SPACE - - - -

- - - - SPACE 37 - - 38 SPACE - - - -

- - - - SPACE 35 - - 36 SPACE - - - -

- - - - SPACE 33 - - 34 SPACE - - - -

- - - - SPACE 31 - - 32 SPACE - - - -

- - - - SPACE 29 - - 30 SPACE - - - -

- - - - SPACE 27 - - 28 SPACE - - - -

- - - - SPACE 25 - - 26 SPACE - - - -

- - - - SPACE 23 - 0.40 24

- - - - SPACE 21 - 0.40 22 20 3 JIB CRANE / HOIST #12 - #12 3/4"

- - - - SPACE 19 - 0.40 20

- - - - SPACE 17 - 0.67 18

- - - - SPACE 15 - 0.67 16 20 3 CUH-1 #12 - #12 3/4"

- - - - SPACE 13 - 0.67 14

- - - - SPACE 11 - 4.00 12

- - - - SPACE 9 - 4.00 10 30 3 POWER SHEARER (ITEM 3) #10 - #10 3/4"

- - - - SPACE 7 - 4.00 8

#12 #12 #12 3/4" LTG - EXTERIOR 1 20 5 0.30 3.00 6

#12 #12 #12 3/4" LTG - RMS 101-111 1 20 3 2.64 3.00 4 20 3 BLAST MEDIA CABINET (ITEM 18) #12 - #12 3/4"

#12 #12 #12 3/4" LTG - ROOM 100 1 20 1 3.28 3.00 2

PH N G C DESCRIPTION RAT. NO. LEFT RIGHT LEFT RIGHT LEFT RIGHT NO. RAT. DESCRIPTION PH N G C

CIRCUIT

P O

L E AMP CKT PHASE A kW PHASE B kW PHASE C kW CKT AMP

P O

L

E CIRCUIT

MAINS: 100 A MLO SYM. INTERRUPT RATING: 14,000 A

NAME: PP1 VOLTAGE: 277 / 480 V, THREE PHASE, 4 WIRE + G ENCLOSURE RATING: NEMA

BRANCH CIRCUIT PANELBOARD SCHEDULE

94 94 94 DEMAND AMPS / PHASE

94 94 94 CONNECTED AMPS / PHASE TOTAL DEMAND LOAD (kVA): 77.73

OPTIONS: INTEGRAL SURGE SUPRESSION 25.91 25.91 25.91 CONNECTED kVA / PHASE TOTAL CONNECTED LOAD (kVA): 77.73

- - - - 41 - - 42 - - - -

- - - - 39 - - 40 - - - -

- - - - 37 - - 38 - - - -

- - - - 35 - - 36 - - - -

- - - - 33 - - 34 - - - -

- - - - 31 - - 32 - - - -

- - - - 29 - 2.67 30

- - - - 27 - 2.67 28 20 3 H-2 #12 - #12 3/4"

- - - - 25 - 2.67 26

23 0.60 1.33 24

#12 - #12 3/4" CF-2 3 15 21 0.60 1.33 22 15 3 H-1 #12 - #12 3/4"

19 0.60 1.33 20

17 0.60 2.50 18

#12 - #12 3/4" CF-1 3 15 15 0.60 2.50 16 15 3 CU-3 #12 - #12 3/4"

13 0.60 2.50 14

11 3.05 6.23 12

#12 - #12 3/4" MAU-1 3 20 9 3.05 6.23 10 35 3 CU-2 #8 - #10 3/4"

7 3.05 6.23 8

5 3.20 5.73 6

#12 - #12 3/4" DOAS-1 3 15 3 3.20 5.73 4 35 3 CU-1 #8 - #10 3/4"

1 3.20 5.73 2

PH N G C DESCRIPTION RAT. NO. LEFT RIGHT LEFT RIGHT LEFT RIGHT NO. RAT. DESCRIPTION PH N G C

CIRCUIT

P O

L E AMP CKT PHASE A kW PHASE B kW PHASE C kW CKT AMP

P O

L

E CIRCUIT

MAINS: 225 A MLO SYM. INTERRUPT RATING: 14,000 A

NAME: PP2 VOLTAGE: 277 / 480 V, THREE PHASE, 4 WIRE + G ENCLOSURE RATING: NEMA

BRANCH CIRCUIT PANELBOARD SCHEDULE

4. PORTABLE EQUIPMENT - NO DEDICATED CIRCUIT.

3. ELECTRICAL CONTRACTOR TO PROVIDE VFD FOR FAN AND POWER WIRING FROM VFD TO FAN. VENTILATING CONTRACTOR TO PROVIDE ALL CONTROL WIRING.

2. EXISTING INFRARED HEATER SALVAGED AND REINSTALLED.

1. UNIT FURNISHED WITH 20 KVA, 208V X 440V TRANSFORMER.

COMMENTS:

2SP TWO SPEED STARTER

GFGI GOVT. FURNISHED GOVT. INSTALLED (NIC) VFD VARIABLE FREQUENCY DRIVE 12 INDOOR, OIL & DUST

TIGHT

EL…