MDVL192129, Repair Fire Suppression System at Bldg 104 – RFI#1 27 July 2021

Question #1 – Please confirm the Panel Label L1A on Sheet FA‐004?

The power riser on Sheet FA‐004 shows the 120/208V panel as a two‐section panel labeled

Panel L1A. This panel should have been designated as Panel ML on the riser diagram and is a single panel as indicated in the panel schedules on same sheet.

Question #2 – Please provide the weight limit for the raised floor system?

Existing flooring system is a Tec‐Crete 1250 bare finish panel system. The floor system is rated for concentrated loads up to 1,250 psi, uniform loads up to 600 psf, and rolling loads of 1,300 pounds. Additional data may be available from the manufacturer.