MS Air National Guard
186 Air Refueling Wing
6225 M Street
Meridian, MS 39307
AIR
NAT I
NALO
GUA
RD
R protecting Mississippi's vital flow...one call at a time
CALL BEFORE YOU DIG!
601.555.1212
Ù
PROJECT
LOCATION
WAGGONER
Inspire. Engage. Deliver.
Jackson, MSHernando, MSGulfport, MS
Ruston, LA New Orleans, LA www.waggonereng.com
1-800-661-3733
AutoCAD SHX Text
MAY 2021
AutoCAD SHX Text KEY FIELD AIR NATIONAL GUARD BASE REPAIR FIRE SUPPRESSION SYSTEM, B104 186TH AIR REFUELING WING PROJECT# MDVL192129
AutoCAD SHX Text
INDEX TO DRAWINGS
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
TITLE
AutoCAD SHX Text
COVER SHEET
AutoCAD SHX Text
FA - 001
AutoCAD SHX Text
FIRST FLOOR PLAN - FIRE ALARM (EXISTING)
AutoCAD SHX Text
FA - 002
AutoCAD SHX Text
FIRST FLOOR PLAN - FIRE ALARM (NEW)
AutoCAD SHX Text
FA - 003
AutoCAD SHX Text
SECOND FLOOR PLAN - FIRE ALARM (EXISTING) AND FIRE ALARM (NEW)
AutoCAD SHX Text
FP - 001
AutoCAD SHX Text
FIRE PROTECTION - FIRST FLOOR PLAN
AutoCAD SHX Text
FP - 002
AutoCAD SHX Text
FIRE PROTECTION - SECOND FLOOR PLAN
AutoCAD SHX Text
FA - 004
AutoCAD SHX Text
ELECTRICAL SCHEDULES AND DETAILS
KEYED NOTES
Ops Floor
A6 Staff
ACOMF Maint. A4
DIRECTOR
Mechanical
103D A3/5/9
103F Elect. / Comm.
103E A3/5/9
103B Battle Cab
103G A3 Director
103J Stairwell
103N A1
103M A1
103L A1
103K
ACOS CC
103H JACCE Director
102D Break Room
111A A6 Director
102A A4
102D Break Room
102C Commander Conference
Room112 A6
CL
FIRE PROTECTION LEGEND
GENERAL FIRE PROTECTION NOTES
FIRE RISER DETAIL
GENERAL CONSTRUCTION NOTES
WAGGONER
Jackson, MS Hernando, MS Gulfport, MS Ruston, LA New Orleans, LA www.waggonereng.com 1-800-661-3733
Inspire. Engage. Deliver.
Scott C. Woods and Associates
Mechanical Engineers
SCWA
FIRE PROTECTION -
FP - OO1
FIRST FLOOR PLAN
FIRST FLOOR PLAN / FIRE PROTECTION
AutoCAD SHX Text
PHASE 1
AutoCAD SHX Text
PHASE 2
AutoCAD SHX Text
PHASE 3
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text AUDITORIUM TABLES ARE NOT MOVEABLE. EXTENDED COVERAGE HEADS SHALL BE USED TO ALLOW FOR INSTALLATION WITHOUT REMOVAL OF TABLES.
AutoCAD SHX Text
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
EXISTING RISER. SEE DETAIL.
AutoCAD SHX Text
ROOM 103 IS LIGHT HAZARD OPEN TO ABOVE
AutoCAD SHX Text CONTRACTOR TO PROVIDE PROTECTION TO RAISED FLOOR FROM SCAFFOLDING, LADDERS, ETC. IF LIFTS ARE USED, DO NOT EXCEED WEIGHT RATING OF FLOOR.
AutoCAD SHX Text
AutoCAD SHX Text 3.
AutoCAD SHX Text 2.
AutoCAD SHX Text 1.
AutoCAD SHX Text
ALL SYSTEMS AND EQUIPMENT SHALL STRICTLY COMPLY WITH NFPA 13 AND ALL
AutoCAD SHX Text
LOCAL CODES.
AutoCAD SHX Text
CALCULATIONS AND SHOP DRAWINGS SHALL BE SUBMITTED TO ENGINEER AND
AutoCAD SHX Text
ARCHITECT FOR APPROVAL BEFORE INSTALLING FIRE PROTECTION SYSTEM.
AutoCAD SHX Text
ALL FIRE PROTECTION WORK SHALL BE COORDINATED WITH OTHER TRADES TO
AutoCAD SHX Text
AVOID CONFLICTS.
AutoCAD SHX Text 4.
AutoCAD SHX Text
SPRINKLER HEADS SHALL BE INSTALLED IN CENTER OF CEILING TILES WHERE
AutoCAD SHX Text
POSSIBLE.
AutoCAD SHX Text
ORDINARY HAZARD GROUP II
AutoCAD SHX Text
LIGHT HAZARD
AutoCAD SHX Text 5.
AutoCAD SHX Text
SPRINKLER HEADS SHALL BE SEMI-RECESSED TYPE IN SPACES WITH CEILINGS.
AutoCAD SHX Text
SPACES WITHOUT CEILINGS SHALL HAVE UPRIGHT HEADS WITH HEAD GUARDS.
AutoCAD SHX Text 6.
AutoCAD SHX Text
CONTRACTOR SHALL VISIT SITE PRIOR TO BID DATE AND FIELD VERIFY EXACT
AutoCAD SHX Text
LOCATION OF THE EXISTING FIRE MAIN.
AutoCAD SHX Text 7.
AutoCAD SHX Text
CONTRACTOR SHALL PROVIDE OFFSETS OR MOVE ANY EXISTING SPRINKLER
AutoCAD SHX Text
PIPE (AT NO ADDITIONAL COST TO THE OWNER) WHICH CONFLICTS WITH
AutoCAD SHX Text
THE INSTALLATION OF THE NEW WORK THAT IS REQUIRED.
AutoCAD SHX Text 8.
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text
CONNECT TO EXISTING 4" VALVE
AutoCAD SHX Text
8" FLANGE
AutoCAD SHX Text 4"
AutoCAD SHX Text
ADD AUXILIARY SYSTEM DRAINS AS REQUIRED FOR POSITIVE DRAINAGE.
AutoCAD SHX Text 1.
AutoCAD SHX Text THE BUILDING WILL REMAIN OCCUPIED DURING CONSTRUCTION AND EXTREME CAUTION MUST BE TAKEN TO PROTECT EXISTING EQUIPMENT.
AutoCAD SHX Text 2.
AutoCAD SHX Text ANY REQUIRED NEW WALL OPENINGS AND/OR PATCH WORK SHALL BE REPAIRED WITH LIKE MATERIALS AND REPAINTED TO MATCH EXISTING SURFACES.
AutoCAD SHX Text 3.
AutoCAD SHX Text CEILING TILES SHALL BE REMOVED AND REPLACED AS REQUIRED. THE CONTRACTOR SHALL REPLACE ANY DAMAGED CEILING TILES OR GRID.
AutoCAD SHX Text 4.
AutoCAD SHX Text DUE TO SECURITY OF THE FACILITY, EACH PHASE OF CONSTRUCTION, ENTRY POINTS OF BUILDING, ETC., SHALL BE APPROVED BY THE CONTRACTING OFFICER BEFORE ANY WORK BEGINS.
AutoCAD SHX Text 5.
AutoCAD SHX Text CONTRACTOR SHALL GIVE 30 DAYS NOTICE IN ADVANCE BEFORE STARTING ANY WORK IN EACH PHASE.
AutoCAD SHX Text 6.
AutoCAD SHX Text
PLEASE NOTE THAT THE LARGEST CURRENT ENTRY TO THE FACILITY IS A 36" DOOR.
AutoCAD SHX Text 6.
AutoCAD SHX Text CONTRACTOR SHALL MAINTAIN A CLEAN WORKING ENVIRONMENT AT ALL TIMES. DAILY CLEAN UP SHALL OCCUR AT THE END OF EACH WORK SHIFT.
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
CO13-063.026
AutoCAD SHX Text
FEB 2021
AutoCAD SHX Text
PROJECT:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
DRAWING TITLE:
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text
SEAL:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DRAWING REVISIONS
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REPAIR FIRE SUPPRESSION SYSYTEM, B104
AutoCAD SHX Text
NTS
AutoCAD SHX Text
GLH
AutoCAD SHX Text
SCW
AutoCAD SHX Text
GLH
AutoCAD SHX Text Ph. (601)859-9864/Fax (601)859-2564/Email www.scweng.com
AutoCAD SHX Text 112 Lone Wolf Dr./Madison, Ms 39110
AutoCAD SHX Text
SCWA# 19-104
AutoCAD SHX Text
PROJECT# MDVL 192129
AutoCAD SHX Text
MS AIR NATIONAL GUARD 186TH AIR REFUELING WING
AutoCAD SHX Text
SCALE: 1/8"=1'-0"
NORTH
Stairwell
VTC Conference
Room 1
Director of Operations
(ACOS/A3)
Ops Floor Mezzanine
VTC Conference
Room 2
WAGGONER
Jackson, MS Hernando, MS Gulfport, MS Ruston, LA New Orleans, LA www.waggonereng.com 1-800-661-3733
Inspire. Engage. Deliver.
Scott C. Woods and Associates
Mechanical Engineers
SCWA
FIRE PROTECTION -
FP - OO2
SECOND FLOOR PLAN
SECOND FLOOR PLAN / FIRE PROTECTION
AutoCAD SHX Text
PHASE 1
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
DESIGNED BY:
AutoCAD SHX Text
CO13-063.026
AutoCAD SHX Text
FEB 2021
AutoCAD SHX Text
PROJECT:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
DRAWING TITLE:
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text
SEAL:
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
REMARKS
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DRAWING REVISIONS
AutoCAD SHX Text
DATE
AutoCAD SHX Text
REPAIR FIRE SUPPRESSION SYSYTEM, B104
AutoCAD SHX Text
NTS
AutoCAD SHX Text
GLH
AutoCAD SHX Text
SCW
AutoCAD SHX Text
GLH
AutoCAD SHX Text Ph. (601)859-9864/Fax (601)859-2564/Email www.scweng.com
AutoCAD SHX Text 112 Lone Wolf Dr./Madison, Ms 39110
AutoCAD SHX Text
SCWA# 19-104
AutoCAD SHX Text
PROJECT# MDVL 192129
AutoCAD SHX Text
MS AIR NATIONAL GUARD 186TH AIR REFUELING WING
AutoCAD SHX Text
SCALE: 1/8"=1'-0"
NORTH