1807 out 06-26-24 contractor rfi responses.pdf

PDF 115 KB Posted

Attached to
LRXQ172402; Renovate Base Supply, B180
Solicitation number
W50S7H23B0001
Issued by

About this file

This document appears to be a compilation of contractor Requests for Information (RFIs) and responses related to a federal contract opportunity for the renovation of Building 180 at the 172nd Airlift Wing of the Mississippi Air National Guard in Flowood, MS.

The key details are:

  • The solicitation number is W50S7H23B0001 for the LRXQ172402 project to Renovate Base Supply, B180.
  • The contract is a single firm-fixed price for construction services, with a North American Industry Classification System (NAICS) code of 236220 and a small business size standard of $45 million average annual revenue.
  • The project magnitude is between $5,000,000 - $10,000,000.
  • The RFI responses address items such as missing drawings, sprinkler head requirements, voltage needs for the fire pump, roofing insulation specifications, and clarifications on tile requirements and overhead door enclosures.
  • The solicitation details, including a pre-bid conference and bid opening date, can be found in the attached Solicitation Form 1442.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W50S7H23B0001 – LRXY172402 B180 Renovation Contractor RFIs

As of 25 June 2024

1. Q/A #3 references revised sheet A10.0 in Addendum 01. This sheet was not provided.

Please see revised A10.0 per Addendum 02.

2. Per the RFI responses, it states that the door schedule has been revised per revised drawings A10 and A10.1. However, these drawings were not provided in addendum 01 revised drawings.

Please see revised A10.0 and A10.1 per Addendum 02.

3. The sprinkler heads specified for the warehouse area are for 40’ high storage with a maximum building height of 45’. The existing building has a maximum height of 52’. The sprinkler heads specified are not approved for a building of this height. Please specify the design criteria you wish to use for this area of the building.

Per Specification section 21 13 00, fire protection system shall be in accordance with NFPA 13.

Provide compliant sprinkler heads.

4. There are no voltage requirements for the fire pump shown. Please specify the voltage requirements for the fire pump.

See Addendum 02, Item #7.

5. Are we to figure 24 ga or 22 ga copings?

This can be found in Specification section 07 62 00.

6. Specs call for R-25 which is app 4.5” of ISO however plans call for 2.5” ISO at high roof and 3.5” minimum ISO at the low roofs with taper, please advise.

See updated Specification section 07 54 23 per Addendum 02. See also revised A5.0 and A9.0 per Addendum 02.

7. Definition of symbols MT, ML1 & MM1. These are on drawing E0.1 See revised sheet E0.1 per Addendum 02.

8. CAN WE GET CARIFICATION ON THE TILE? WE NEED A SERIES FOR THE ANATOLIA TILE AND IS

THE TILE 1 USED FOR THE FLOOR TILE AS WELL?

See revised Specification section 09 30 00 2.01 per Addendum 02.

9. Concerning the overhead doors. Specs indicate wanting enclosure IP54 rated NEMA3 Equivalent.

Motors from Raynor’s operator is either NEMA12(dust proof) or NEMA4(watertight enclosure).

Can not be both.

Raynor is not listed in the Specification but may provide equal products. We do not pre-approve or add products during the bid process. Substitutions will be reviewed for consideration after award and approved if they meet all of the specification requirements stated in the project construction documents.

*There are previous RFI questions that refer to Addendum 01, but are answered here instead.

Please refer to all RFI answers, as well as Addendum 01 and 02.

File details come from the government source that posted it. Updated .