W50S7524B0001_146_CES_Repair_Hangar_Bldg_801_Atch-07_RFI_Log_20240530.pdf

PDF 255 KB Posted

Attached to
Solicitation: 146 AW Channel Islands FY24 Maintenance Hanger Repair
Solicitation number
W50S7524B0001
Issued by

About this file

This document is a Request for Information (RFI) related to a federal contract opportunity for the repair and maintenance of Hangar 801 at the 146th Air Wing (146 AW) in Channel Islands, California. The RFI provides detailed responses to 165 questions from potential contractors covering topics such as demolition, roofing, HVAC, fire protection, telecommunications, electrical systems, and furnishings.

The federal contract opportunity is for the solicitation W50S7524B0001, titled "146 AW Channel Islands FY24 Maintenance Hanger Repair". Key details include a site visit on 8 May 2024, RFI questions due by 24 May 2024, and bid opening on 29 May 2024. The contract requires removing and replacing the hangar roof, upgrading HVAC and fire protection systems, and installing new telecommunications and electrical infrastructure. While no furniture procurement is included, the contractor must provide backing for planned furnishings. The government will make utilities available and provide a staging area, but the contractor is responsible for temporary facilities and site access coordination.

View the file

Other files

File Type Posted
W50S7524B0001_146_CES_Repair_Hangar_Bldg_801_Abstract.pdf PDF
W50S75-24-B-0001-00006_Conformed.pdf PDF
W50S7524B0001_146_CES_Repair_Hangar_Bldg_801_Atch-12_AFFF_SPD_SSFR.pdf PDF
W50S7524B0001_146_CES_Repair_Hangar_Bldg_801_Atch-11_C6_AFFF.pdf PDF
W50S75-24-B-0001-00006.pdf PDF
W50S7524B0001_146_CES_Repair_Hangar_Bldg_801_Atch-07_Rev_2_RFI_Log_20240610.pdf PDF
W50S75-24-B-0001-00005.pdf PDF
W50S7524B0001_146_CES_Repair_Hangar_Bldg_801_Atch-07_Rev_1_RFI_Log_20240607.pdf PDF
W50S75-24-B-0001-00005_Conformed.pdf PDF
W50S7524B0001_146_CES_Repair_Hangar_Bldg_801_Atch-08_Sundown_Policy.pdf PDF
W50S75-24-B-0001-00004_Conformed.pdf PDF
W50S7524B0001_146_CES_Repair_Hangar_Bldg_801_Atch-09_ANGETL_15-01-03.pdf PDF
W50S75-24-B-0001-00004.pdf PDF
W50S75-24-B0001-0001.pdf PDF
W50S75-24-B-0001-0003.pdf PDF
W50S75-24-B-0001-0003_Conformed.pdf PDF
W50S75-24-B-0001-0002_Conformed.pdf PDF
W50S75-24-B-0001-0002.pdf PDF
W50S7524B0001_146_CES_Repair_Hangar_Bldg_801_Atch-06_Bid_Breakout_by_CSI.xlsx XLSX spreadsheet
W50S7524B0001_Repair_Hangar_Bldg_801_Pre-Bid_Conference_20240515.pdf PDF
W50S7524B0001_146_CES_Repair_Hangar_Bldg_801_1442_Amendment 1.pdf PDF
W50S7524B0001_146_CES_Repair_Hangar_Bldg_801_1442.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RFI # Question/Clarification Response

In specification section 12 50 00, it mentions that there is an FF&E package attachment. The attachment is no where to be found. Can the government please provide the FF&E package attachment?

FF&E sheets (IF series) and Specification Section 12 50 00.13 10 are provided for reference only. Procurement and installation of new FF&E is not included in the scope of this contract.

Contractor shall provide electrical and telecommunications for planned furniture, and backing where TVs, white boards, and tack boards are shown.

Door W105G counter fire door plan page A502 detail 5&6 show a standard face of wall mount counter door. However, spec section 83313 calls for an Integral Frame Counter door with countertop. This type of door would not match plan details. Also, integral frame doors cannot be motor operated which the specs call for. Please clarify what type is required.

Counter door will not be an integral frame door. Provide 45 min rated motorized door assembly in lieu of 1 1/2 hour indicated in specs.

Spec section 83323 for the roll up doors is calling for Aluminum insulated doors, typically these would be steel. Is Aluminum really required?

Provide curtain slats fabricated from Grade A Steel sheets conforming to ASTM A653/A653M, with the additional requirement of a minimum yield point of 33,000 psi. Provide sheets, galvanized in accordance with ASTM A653/A653M and

ASTM A924/A924M.

Door Operation, Spec section 83323 section 2.2.5 says door S103E only to have motor operator. Section 2.2.4 Says manual operation for AB#2, but there is no door number listed as AB#2. What doors are chain operation & what doors are motor operation?

All roll-up doors with the exception of S-103E shall be manually operated.

From the site walk, we determined the lower roof is PVC or TPO. Are the existing roofs coming off? We need to know what’s under the PVC or TPO (insulation thickness, coverboard, is there another roof under the single ply system)?

Existing roof will be removed. Per as-builts available, existing roofing consists of single-ply membrane over a single layer of rigid board roof insulation (approx. 1") over steel decking.

Drawing TD401. Please confirm that all fiber optic cable and panels are to be removed.

Yes

Do we include the demo of the existing workstation cabling in our bid?

Yes

Do we include the demo of the existing copper and fiber optic backbone in our bid?

Yes

Will the conduit for the PDS system need to be continuous from the wall penetration at the SPRNET room into the new Classified IT cabinet on drawing T-401 detail #1 keynote #3?

Yes, PDS will extend to the classified network cabinet. Note that PDS will not be conduit, it will be a rectangular PDS carrier per spec section 27 05 29.00 10.

10 Please confirm the wall type for the SPRNET room will be drywall.

Existing wall for SIPRNET Room (W102C) is metal stud wall with gypsum board. This wall will remain as-is and be painted in accordance with finish schedule on sheet I-001.

Drawing T-401 detail #1. Keynote #17 calls for the existing ladder rack to be reused. The existing ladder rack is not currently laid out as indicated on detail #1, plus there is insufficient ladder rack existing to reconfigure to the new ladder rack layout. Please confirm that an additional ladder rack is required.

Intent is for ladder rack in comm room W101J to be replaced and installed to match layout on 1/T-401. Keynotes will be revised.

Can you please confirm if the existing door frames are to be reused?

Modifying the existing frames sometimes makes it difficult for the new hardware to be incorporated. Please confirm.

Some existing door frames are to remain. See door schedule on sheet A-601.

13 What are the cable requirements for the symbol below?

This is public address volume control, see G-007. Cabling as required by spec section 27 51 16.

How many category 6 UTP cables are required for the symbol below?

These data outlets are to be deployed in mechanical and electrical rooms. Number of active connectors as required to support required networking of building management systems including mechanical controls, lighting controls, smart meters, etc.

15 Are there particular cabinets and racks that this site uses? Racks and cabinets are specified in 27 10 00.

Drawing T-401 keynote #14 calls for a fiber optic enclosure for fiber optic horizontal cables. Drawings T-501 and T-502 do not show any fiber optic workstation outlets. Please confirm that fiber optic horizontal cabling is required and where these workstation outlets are located.

Classified work area outlets in SIPR W102C will each have four duplex OM3 fiber drops terminated with LC connectors as shown on detail 1/T-501. Only the classified network cabinet in comm room W101J requires fiber patch panels. Will be clarified.

Drawing T-402. How high should the PDS user drop box be installed A.F.F.?

Per Spec Section 27 05 29.00 10, para 3.3.2.1, coordinate drop box location with furniture, fixtures, and equipment that will be used in the vicinity (provided by others). Surface mount drop boxes on the wall partition approximately 4 to 5 feet above final floor line depending on room furniture height and layout.

Please confirm that all workstation outlet (WO) cable is unshielded

(UTP).

Correct.

Requests For Information (RFIs) - W50S7524B0001 Repair Maintenance Hangar

19 What are the cabling requirements in the SIPR Room W102C?

Classified work area outlets in SIPR W102C will each have four duplex OM3 fiber drops terminated with LC connectors as shown on detail 1/T-501.

20 Please confirm that floor bax WO require (4) category 6 UTP cables. Correct.

21 Drawings T-104 and T-106. How high is the cable tray A.F.F.?

Cable tray runs along bottom chord of roof truss, approximately 46 feet above finished floor.

Ref A-108, Keynote 3 – While cited note calls for existing metal roof to be repainted, we are unable to identify a specification for this work. Please identify the specification section.

Refer to spec 09 90 00 applicable sections 3.1, 3.2, (especially

3.2.1 for existing coatings), 3.3, but not limited to only these sections and paint tables at end of section for interior/exterior components.

Ref A-112, Keynote 4 – While cited note calls for the entire underside of the roof to be repainted, Section 09 90 00 does not address the repainting of existing, interior ferrous metals nor the repainting of existing, interior galvanized decking. Please provide a specification for this work.

Refer to spec 09 90 00 applicable sections 3.1, 3.2, (especially

3.2.1 for existing coatings), 3.3, but not limited to only these sections and paint tables at end of section for interior/exterior components.

Ref A-201, Keynote 1 – While cited note calls for the existing metal wall panels to be repainted, Section 09 90 00 does not address this work. Please provide a specification for this work.

Refer to spec 09 90 00 applicable sections 3.1, 3.2, (especially

3.2.1 for existing coatings), 3.3, but not limited to only these sections and paint tables at end of section for interior/exterior components.

Ref A-201, Keynote 7 – While cited note says to prepare (exterior) ladders, cages, stairs and railings as required for proper painting, this work is covered by Section 09 97 13.27, and the only surface preparation described within cited specification is abrasive blasting to near white metal, which entails removing the paint. Is it the Engineer’s intent that the existing paint be prepared for proper painting in accordance with the paint manufacturer’s recommendations or shall we assume that all (exterior) ladders, cages, stairs and railings be removed via abrasive blasting?

Yes, existing painting preparation should be in accordance with paint mfrs recommendations and may or may not include abrasive blasting.

Is a FEDEX’ed or UPS’ed package delivery considered “hand delivered” or is the intent to have the bidders hand carry their submission personally to the bid opening?

Bid packages may be submitted using any commercial delivery service (FedEx, UPS, Postal Service, etc.) so long as the bid package is received prior to date and time of Bid Opening. Note that the Government cannot be held liable if the delivery driver is not eligible to access the installation. Bidders should ensure they obtain a tracking number and proof of delivery.

Can you please verify the date Pre-Bid Inquiries are due for the above mentioned project?

Pre-Bid Inquiries are due 5 working days prior to Bid Opening.

The plans call for 12" cove integral base. Typically, we do not install a cover base in these settings, and if we do it would be 6' max. 12' cove will add significant cost. Is integral cove base necessary?

A 6" epoxy floor base is acceptable.

Is there an enlarge detail for the 3,500 sf of Hangar Traffic Markings?

No.

Are we going to be performing the demo/abatement of the existing cabling?

As stated in general note 6 on the TD series drawings, "Unless noted otherwise, contractor shall disconnect and remove all backbone and horizontal fiber and copper cabling, including connectors, back to the cabinet or rack. Unused existing underground conduits shall be capped and abandoned in place."

Is anything of the existing copper cabling, fiber cabling, network equipment, paging horns, paging cabling, paging system, jacks, plates, raceway, etc. going to be reused?

As stated in general note 6 on the TD series drawings, "Unless noted otherwise, contractor shall disconnect and remove all backbone and horizontal fiber and copper cabling, including connectors, back to the cabinet or rack. Unused existing underground conduits shall be capped and abandoned in place." A new PA system is required as shown on the T- series drawings.

On the plan it states that all cabling is to be pulled back to the comm rooms including the fiber backbone. It also states that the existing cable tray that goes over the hangar is to be reused for new cabling.

Which is correct?

Both statements are accurate. Existing horizontal and backbone cabling is to be disconnected and removed. The existing cable tray spanning the open hangar will be reused for new backbone cabling.

Where does the outside copper and fiber enter the building?

- Is this the main telecom room?

- Please identify the main telecom room.

Primary comm room and entrance facility is E102D as illustrated on T-601.

Are we to reconnect to the existing incoming fiber and copper?

- How many OSP copper pair?

- How many OSP fiber strands?

- Armored?

Existing OSP will be protected and reused. Contractor to field verify existing conditions.

Please confirm if one person can fulfill multiple roles for the project, and if so, which roles can be combined. (CQM, Superintendent, SSHO, Environmental Manager, and Project Manager)

The Site Safety and Health Officer may not serve as the Quality Control System Manager or Superintendent. The Quality Control System Manager will not serve in any other roles. See Specification Sections 01 30 00, 01 35 26 and 01 45 00.00 10 for detailed requirements for each position. There are no limitations on the Environmental Manager or Project Manager serving multiple roles. If there are conflicts between this RFI response and the requirements of any Specifications sections, the Specifications take precedence.

Please confirm whether we can utilize the existing power and water sources for this project.

Government will make all reasonably required utilities available from existing outlets and supplies. Reasonable amounts of the following utilities will be made available without charge:

Electricity, Potable Water, Natural Gas, Sanitary Sewer.

Government coordination and approval is required prior to actual tie-in.

37 Are only US citizens allowed to work in this area?

There is no requirement for only US citizens to work on this project. However, all contractor personnel must meet standard base access requirements and background screening.

The specifications state that the General Contractor (GC) needs to provide an Administrative Field Office, a QCM Field Office, and a Resident Engineer’s Office for the project. Do we really need all these trailer offices? Please confirm how many office trailers need to be provided for this project.

It is acceptable for contractor to provide one trailer to serve as Administrative Field Office and QCM Field Office. 146 CES will provide space for Resident Engineer. Contractor does not need to provide Resident Engineer trailer. Government coordination and approval is required prior to placement.

The Bid Breakout by CSI in attachment 6 provided with amendment 02 is not editable due to the cell or chart being on a protected sheet.

Can you please provide the unprotected Bid Breakout Excel file?

An unprotected file will not be provided. This is necessary to ensure that all bidders are providing their data in the same format. This spreadsheet allows all requested/required data to be filled in. It is understood that there may be minor differences in rounding/calculation.

Ref A-108, Keynote 3 – While cited note calls for existing metal roof to be repainted, we are unable to identify a specification for this work. Please identify the specification section.

Refer to spec 09 90 00 applicable sections 3.1, 3.2, (especially

3.2.1 for existing coatings), 3.3, but not limited to only these sections and paint tables at end of section for interior/exterior components.

Ref A-112, Keynote 4 – While cited note calls for the entire underside of the roof to be repainted, Section 09 90 00 does not address the repainting of existing, interior ferrous metals nor the repainting of existing, interior galvanized decking. Please provide a specification for this work.

Refer to spec 09 90 00 applicable sections 3.1, 3.2, (especially

3.2.1 for existing coatings), 3.3, but not limited to only these sections and paint tables at end of section for interior/exterior components.

Ref A-201, Keynote 1 – While cited note calls for the existing metal wall panels to be repainted, Section 09 90 00 does not address this work. Please provide a specification for this work.

Refer to spec 09 90 00 applicable sections 3.1, 3.2, (especially

3.2.1 for existing coatings), 3.3, but not limited to only these sections and paint tables at end of section for interior/exterior components.

Ref A-201, Keynote 7 – While cited note says to prepare (exterior) ladders, cages, stairs and railings as required for proper painting, this work is covered by Section 09 97 13.27, and the only surface preparation described within cited specification is abrasive blasting to near white metal, which entails removing the paint. Is it the Engineer’s intent that the existing paint be prepared for proper painting in accordance with the paint manufacturer’s recommendations or shall we assume that all (exterior) ladders, cages, stairs and railings be removed via abrasive blasting?

Yes, existing painting preparation should be in accordance with paint mfrs recommendations and may or may not include abrasive blasting.

We found existing 300 lb, (2) 1/4T, (2) 1/2T monorail hoists on the plans but the keynotes on S-111 (not attached to any specific location) are asking for a new 1/2T and 1T electric hoists. Can the project clarify which monorails hoists need to be replaced, how they are current electrified, and confirm ALL the track cross sections are as shown in detail 1/S-111.

Keynotes 2 and 3 on Sheet SD111 indicate the existing 1/2 Ton and 1 Ton monorail hoists and trolleys to be demolished. These two hoists are currently manual hoist and are not currently electrified. Keynotes 3 and 4 on sheet S-111 indicate the new electrical monorail hoists to be provided. The remaining monorail hoists identified are for information only and are not required to be replaced. Track cross section shown in detail 1/S- 111 is based off of existing as-builts and should be verified by the Contractor during construction.

Can the project confirm they need a wire rope monorail hoist?

Chain hoists are more typical for such low capacities.

Electric chain hoists can be provided at Contractor's option.

Electric chain hoist shall conform to ASME HST-1, NEMA ICS 8, NEMA MG 2, and NEMA ESPG. Hoisting chain shall be welded link load chain, include a chain stop or dead end connection to prevent the load chain from running out of the hoist at its fully extended position, and for chain hoists with 3 m (10 foot) lift or more provide a load chain bucket.

46 What are the cable requirements for the symbol below?

This is public address volume control, see G-007. Cabling as required by spec section 27 51 16.

How many category 6 UTP cables are required for the symbol below?

These data outlets are to be deployed in mechanical and electrical rooms. Number of active connectors as required to support required networking of building management systems including mechanical controls, lighting controls, smart meters, etc.

48 Do we include the PDS system in our bid? Yes 49 Do we include the 12”Wx4”D cable tray in our bid? Yes

Please confirm that the workstation outlets clouded below are required.

51 Is there a standard cable manufacturer for this site? Cabling is specified in 27 10 00 52 Are there particular cabinets and racks that this site uses? Racks and cabinets are specified in 27 10 00

Drawing T-401 keynote #14 calls for a fiber optic enclosure for fiber optic horizontal cables. Drawings T-501 and T-502 do not show any fiber optic workstation outlets. Please confirm that fiber optic horizontal cabling is required and where these workstation outlets are located.

Classified work area outlets in SIPR W102C will each have four duplex OM3 fiber drops terminated with LC connectors as shown on detail 1/T-501. Only the classified network cabinet in comm room W101J requires fiber patch panels. Will be clarified.

Drawing T-402. How high should the PDS user drop box be installed A.F.F.?

Per Spec Section 27 05 29.00 10, para 3.3.2.1, coordinate drop box location with furniture, fixtures, and equipment that will be used in the vicinity (provided by others). Surface mount drop boxes on the wall partition approximately 4 to 5 feet above final floor line depending on room furniture height and layout.

55 Will an area for material storage be provided?

See sheet C-100 for Contractor's staging area. If additional space is required, that may be requested through the Contracting Officer after award. Coordination with the Contracting Officer Representative is required prior to final approval and usage of the material storage/staging area.

Please confirm that all workstation outlet (WO) cable is unshielded

(UTP).

Yes, see spec 27 10 00

57 Will j-hooks from cable tray to WO be needed for the project?

Non-continuous cable supports are not permitted. All cabling from the work area outlet will be in conduit to the cable tray as shown in details on T-501. Non-continuous cable supports are not included in specification 27 10 00.

58 Do we include the Public Address system? Yes

59 What are the cabling requirements in the SIPR Room W102C?

Classified work area outlets in SIPR W102C will each have four duplex OM3 fiber drops terminated with LC connectors as shown on detail 1/T-501.

60 Please confirm that floor box WO require (4) category 6 UTP cables. Yes

Drawing T-503 detail #4 shows EZ-Path firestop devices. Do we include these in our bid?

Yes

62 Drawings T-104 and T-106. How high is the cable tray A.F.F.?

Cable tray runs along bottom chord of roof truss, approximately 46 feet above finished floor.

Drawing TD401 detail #2 keynote #3. Please confirm that all fiber optic cable and panels are to be removed from the top rack.

Yes. The only existing fiber panels to be retained are those supporting the ITN function in comm room E102D. See detail 3/T-401.

Will the conduit for the PDS system need to be continuous from the wall penetration at the SPRNET room into the new Classified IT cabinet on drawing T-401 detail #1 keynote #3?

Yes, PDS will extend to the classified network cabinet. Note that PDS will not be conduit, it will be a rectangular PDS carrier per spec section 27 05 29.00 10.

65 Please confirm the wall type for the SPRNET room will be drywall.

Existing wall for SIPRNET Room (W102C) is metal stud wall with gypsum board. This wall will remain as-is and be painted in accordance with finish schedule on sheet I-001.

Drawing T-401 detail #1. Keynote #17 calls fo the existing ladder rack to be reused. The existing ladder rack is not currently layed out as indicated on detail #1, plus there is insufficient ladder rack existing to reconfigure to the new ladder rack layout. Please confirm that additional ladder rack is required.

Intent is for ladder rack in comm room W101J to be replaced and installed to match layout on 1/T-401. Keynotes will be revised.

A-504 detail #7 for instance. Is the roof corrugated steel with concrete fill for cable tray and j-hook attachment?

No concrete fill is shown on 7/A-504. No hanging loads to be attached to metal roof deck.

Are office walls full height from floor to roof? This will determine the amount of fire penetrations needed.

Refer to Sheet A-004. Partition types A and B go the deck.

Would the client have furniture typical in place already, or is this something the client would need our assistance developing and proposing? There is no specification we can use to specify furniture based on the information provided.

FF&E sheets (IF series) and Specification Section 12 50 00.13 10 are provided for reference only. Procurement and installation of new FF&E is not included in the scope of this contract.

Contractor shall provide electrical and telecommunications for planned furniture, and backing where TVs, white boards, and tack boards are shown.

Could you please clarify/confirm where the RS1 shades will be located? We checked out all files available and we didn't find any information about the location and shade details for the window shades. Spec 122413 calls for single and dual; Fascia/Headbox/Shade Pocket; Blackout; etc.

the XXX shades are to be installed at all exterior windows.

Will this project be phased or will we have access to the entire building at once?

See 01 14 00 para 1.2.5. The project will not be phased. Full access will be provided to the entire building. Temporary facilities for the users are within the scope of this contract however.

72 Will this building be occupied during construction?

See 01 14 00 para 1.2.4. The building will not be occupied during construction. Note Comm Room E102D acts as an ITN for surrounding facilities. The ITN OSP functions must remain active for the duration of construction and must be protected.

The contractor will provide temporary power and cooling as required when outages occur. Contractor must also provide power from Building 801 to temporary facilities during construction.

In the areas that are "open to structure", please identify what all needs to be painted (i.e. pipes, ducts, steel members, etc.)

All items are to be painted in exposed areas. Refer to spec 09 90 00 paragraph 1.11 for components painted in open to structure and General note 4 on reflected ceiling plans.

Please confirm that all items in the furniture legend on sheets IF010 - IF106 are GFGI?

FF&E sheets (IF series) and Specification Section 12 50 00.13 10 are provided for reference only. Procurement and installation of new FF&E is not included in the scope of this contract.

Contractor shall provide electrical and telecommunications for planned furniture, and backing where TVs, white boards, and tack boards are shown.

If RFI's are due 5 days before the bid due date, can we get a bid due date extension to address the RFI answers?

Bid Opening was extended until 12 June and future extensions will be considered based on timeliness of RFI responses.

Is there existing Access Control or Intrusion Systems that must remain? If yes, please provide the existing systems manufacturers.

All access controls are being upgraded with this project. See general note 11 on all TD series drawings and general note 1 on all TY series drawings. All access control components, including card readers and controllers, must be compatible with existing base-wide Advantor system and integrated with the existing Access Control System user database.

Plan pages do not show any wireless access point locations.

Please confirm if this is correct.

Wireless access is not a project requirement.

Specification SECTION 275116 (Public Address System) lists microphones for the paging system. Please specify the locations on the plans where the microphones are to be installed.

Commander Assistant, room W101C and Command Annex W114. Locations to be confirmed with contracting officer before rough-in.

79 How many output Zones are needed for Public Address System?

Building will be separated into four major zones:

Zone 1 - Office areas west of Hangar Zone 2 - Shops west of Hangar Zone 3 - Open Hangar Zone 4 - Shops and offices east of Hangar

Contractor may propose additional zoning if needed during submittals and shop drawings.

What is the existing phone system manufacturer for integrating with the PA System.

Base currently uses AVAYA CM7 trunked to the SIRCOM paging

Is it acceptable to use Bosch Security systems for Intrusion and Access Control?

All access control components, including card readers and controllers, must be compatible with existing base-wide Advantor system and integrated with the existing Access Control System user database.

Fire alarm plans indicate that all fire alarm cable shall be run class B, however the specification state to run all notification appliance circuits as class A. Please specify if class A circuits will be required for notification devices.

Fire alarm circuits shall be run Class B to comply with UFC 3- 600-01 Section 9-18.9.1 and UFC 4-021-01 Sections 4-6.1 and 5- 7.1.1

Sheet A-115 shows a drywall ceiling in Fire Riser Room E106, Finish Schedule on I-001 calls for an exposed ceiling. Please clarify what is needed.

Fire Riser Room E106 will have a 1 hour rated assembly lid comprised of 5/8" type "x" gyp board on each face with 3 1/2" fiberglass insulation. Refer to structural dwgs for metal stud framing components. Ceiling height of the room is 10'-0".

84 Where does the outside copper and fiber enter the building?

Contractor to field verify existing conditions. OSP entrance to be protected in place.

85 Please identify where the main telecom room is?

Contractor to field verify existing conditions. Understanding is that E102D is existing EF and functions as a ITN/ITB providing services outward to other nearby facilities that must remain functional.

"Are we reconnecting to the existing incoming fiber and copper?

- How many OSP copper pairs?

- How many OSP fiber strands?

- Is it armored?

OSP cabling is existing to remain. Contractor to field verify existing conditions, including strand/pair counts. Contractor responsible to install backbone cabling as indicated in T-601.

On sheet I-001, window shades RS1, please clarify where these are going?

RS1 Mecho Shades to be installed at all exterior windows.

Please clarify specification section 01 20 00 section 1.3 Unit price pay items. This is a lump sum project.

Unit price pay item for structural steel is included in the case that quantities of steel for structural repairs exceeds the FAR allowance. In addition to the lump sum bid, bidders should provide a unit price for structural repairs per ton of steel.

Please clarify specification section 01 20 00 section 1.3 Unit price pay items. The unit price pay item identified is Structural Steel Reinforcement, the Measurement portion states, “the total quantity of excavated material…”. Structural Steel Reinforcement is not an item we can apply the Measurement method to.

Paragraph 1.3.1.2. will be edited to read, "Total weight of steel reinforcement for which payment will be made will be calculated by measuring the length, width, and thickness of plate steel and multiplying by the unit weight of 490 pounds per cubic foot of steel."

Please clarify specification section 01 30 00 Paragraph 1.10 Partnering and 1.10.1 Facilitated (Formal) Partnering. Section 10.1 says to host the partnering meeting within 45 Calendar Days of contract award, Section 1.10.1 says to hold 35 calendar days after award.

Contractor shall host the partnering session within 35 days after contractor award and prior to the start of work.

Please confirm you require a Government Field Office for this project per 01 50 00 Paragraph 3.6.

It is acceptable for contractor to provide one trailer to serve as Administrative Field Office and QCM Field Office. 146 CES will provide space for Resident Engineer. Contractor does not need to provide Resident Engineer office detailed in paragraph 3.6.1 and 3.6.2. Government coordination and approval is required prior to placement.

The specifications reference an FF&E Package Attachment. Please provide.

FF&E sheets (IF series) and Specification Section 12 50 00.13 10 are provided for reference only. Procurement and installation of new FF&E is not included in the scope of this contract.

Contractor shall provide backing where TVs, white boards, and tack boards are shown.

96 Please confirm FF&E is part of the scope of work.

FF&E sheets (IF series) and Specification Section 12 50 00.13 10 are provided for reference only. Procurement and installation of new FF&E is not included in the scope of this contract.

Contractor shall provide electrical and telecommunications for planned furniture, and backing where TVs, white boards, and tack boards are shown.

Please clarify note 3 on sheet AD100: - All exiting FF&E to be salvaged for reuse on other projects is to be removed by Government and Stored Off Site Prior to Commencement of Work. Confirm this means that FFE will be removed and salvaged by Others. Government is to Determine if FFE Items are to be removed or Stored for Reinstallation, Contractors is to execute as Directed by Government. Does this mean that the successful contractor on this contract is to reinstall, as needed, existing FFE? Does this mean that FFE shown on the IF sheets could potentially reduce in scope due to some FFE already existing? What should we base our bid on?

Per 01 14 00 para 1.2.4, Provide dust covers or protective enclosures to protect existing work that remains, and Government material located in the building during the construction period.

Relocate movable furniture as required to perform the work, protect the furniture, and replace the furniture in its original location upon completion of the work. Leave attached equipment in place, and protect it against damage, or temporarily disconnect, relocate, protect, and reinstall it at the completion of the work.

FF&E sheets (IF series) and Specification Section 12 50 00.13 10 are provided for reference only. Procurement and installation of new FF&E is not included in the scope of this contract.

Contractor shall provide electrical and telecommunications for planned furniture, and backing where TVs, white boards, and tack boards are shown.

8. Specification 01 11 00 Paragraph 1.2.1 – please provide details on required minimum size of temporary facilities. Size, number offices, number of employees, location, etc. are all needed. The information provided in this section is vague and it is unclear what is required.

Details of users' temporary facilities are shown in Spec Section 01 50 00 See spec section 01 50 00 para 3.6 and drawing sheet C-102.

The period of performance Is not long enough for a project of this magnitude. There are long lead items in excess of 30 weeks+ as well as deferred submittals that need time preparing and reviewing.

Please consider extending to 730 CD.

Contractor shall deliver long-lead item submittals within 30 days of contract award. Bidders are encouraged to detail in proposals how they will manage schedule challenges.

Sheet FD001 Note 8 says to protect walls, ceilings, floors and other existing finish work that are to remain and are exposed during selective demo operations. Are portions of the building going to be occupied?

See 01 14 00 para 1.2.4. No portion of the building will be occupied during construction. However, note Comm Room E102D acts as an ITN for surrounding facilities. The ITN OSP functions must remain active for the duration of construction and must be protected. The contractor will provide temporary power and cooling as required when outages occur. Contractor must also provide power from Building 801 to temporary facilities during construction.

Sheet FD001 Note 9 says to cover and protect furniture and equipment that have not been removed. Please clarify any furniture to remain in place.

Equipment to remain in place:

Metal Tech Equipment:

CNC Machine Water Jet (RR Shop) Large Shear

RR Shop:

Wheel Washer

NDI Shop:

Penetrant Line Electromagnetic

Furniture to remain in place: Typical office desks, filing cabinets, TVs, book shelves, and office chairs may remain in the building after turnover to the contractor. Items to remain and be reused should be confirmed by the Contracting Officer following contract award. Specific weights, quantities, and dimensions are not available at this time. These items shall be protected in place, or if the contractor chooses, removed from the building and stored for the duration of construction. These items shall be placed back in the building at the locations directed by the contracting officer upon construction completion.

Sheet FD001 Note 10 says to erect and maintain dust proof partitions to limit dust and dirt mitigation. Can you clarify location of partitions? Are portions of the building going to be occupied?

The building will not be occupied. Note 10 on FD001 does not apply.

Plan AD108 legend shows Existing Parapet to be Demolished. Please clarify – Is the parapet being removed or just the parapet flashing?

The metal coping cover and flashing are to be removed, not the parapet.

Plan ID104 says desks with and “E” shall be wrapped, packed, and tagged for reuse in in room MOF102, removed by the government off site prior to commencement of work. The government is removing. Is the government also wrapping? Is the government brining the equipment back? Is the government storing in government supplied containers or in a government supplied location?

The government is responsible for the wrapping, packing, and tagging of these items. They have been included in the set for coordination purposes.

Plan MD101 note 2 says the demolished equipment will remain property of the government. Contractor will consult with contracting officer for direction on proper disposal or storage of all demolished equipment. Please provide a list of equipment. Please advise – how should we bid this item of work if we are unsure if the government will want to keep or dispose of equipment? If the government wants to keep, who is transporting the equipment?

Where?

Demolished equipment noted on MD101 will not remain the property of the government and may be disposed of in accordance with 01 74 19 Construction Waste Management and Disposal and any other applicable specifications.

Plan MD101 note 8 says to refer to 02 82 00 Asbestos Remediation and 02 83 00 Lead Remediation. Please provide these specification sections.

Note will be edited to read, "It is not expected any hazardous materials, such as PCBs, lead paints, or friable/non-friable asbestos exist within Building 801. However, if material(s) that may be hazardous to human health upon disturbance are encountered during construction operations, contractor shall respond in accordance with 01 35 26." See paragraphs 3.1.3 of that section.

SD101 and S-501 – is the intent to protect the welded wire fabric in place when removing the existing 4” slab? Contractor cannot create a clean edge without removing reinforcing. Contractor cannon reinstall vapor barrier, base, piping, etc. without removing reinforcing.

Ref. 1/S-501. 12" minimum of existing slab reinforcement to remain on all sides of slab demo.

SD101 and S-501 – is the intent to protect the existing reinforcing and leave in place while removing the existing 6” slab? Contractor cannot create a clean edge without removing reinforcing.

Contractor cannon reinstall vapor barrier, base, piping, etc. without removing reinforcing.

Ref. 1/S-501. 12" minimum of existing slab reinforcement to remain. Note 3 on 1/S-501 indicates that at 6" (min) slabs, at Contractor's option, existing reinforcement may be removed and #4 dowels at 18" o.c. to be drilled and epoxied with 6" minimum embedment.

S-501 Detail 1 Note 3 – Confirm drill and epoxy dowl is at contractor’s option? So there is no requirement to drill and dowel?

Drill and dowel is not required when 12" minimum existing slab reinforcement is maintained as shown on 1/S-501.

S-501 Detail 1 Note 2 – there are sections on SD101 that are wider than 6’0”. Please advise – Note 2 states to contact Contracting Officer for Direction. We are requesting direction.

It is acceptable to provide slab demo and infill as shown on

SD101.

S-501 Detail 1 – Does the 4” slab replacement require WWF when we replace or does it require #4 @ 18” O/C EW?

#4@18" O/C EW

SD101 – some of the 6” slab demolition areas are 1’ wide, it will be impractical to drill and epoxy dowels in these locations. Please advise.

Drill and epoxy dowels are not required. Maintain existing slab reinforcement per 1/S-501.

Please confirm retrofit measures in seismic evaluation report are reflected in the project drawings. Meaning, if retrofit measures are NOT part of the Design-Bid-Build drawings, but may be in the seismic evaluation report, then the Government will not require that measure as part of the project.

Confirmed that retrofit measures are reflected in the project drawings and specifications.

The plans show an existing 300 LB, (2) ¼ Ton, (2) ½ Ton monorail hoists. The keynotes on S-111 ask for a new 1/2T and 1T electric hoist. Can you clarify which monorail hoists are being replaced?

How are the existing monorail hoists being electrified?

The 1/2 ton and 1 ton monorail hoists identified with keynotes 3 and 4 on sheet S-111 are the two hoists to be replaced.

Existing monorail hoists to remain are not being electrified. The two new electric hoists are being electrified as shown on sheet E-103.

Please confirm that ALL track cross sections for the monorail hoists are as shown on 1/S-111.

Monorail track cross section shown on 1/S-111 is as shown on the as-built drawings and is to be verified by the Contractor.

Please confirm if the project needs a wire rope monorail hoist?

Chain hoists are more typical for such low capacities, most vendors sell a 2T minimum. The specifications look like they were pulled from a project with a higher capacity requirement.

Electric chain hoists can be provided at Contractor's option.

Electric chain hoist shall conform to ASME HST-1, NEMA ICS 8, NEMA MG 2, and NEMA ESPG. Hoisting chain shall be welded link load chain, include a chain stop or dead end connection to prevent the load chain from running out of the hoist at its fully extended position, and for chain hoists with 3 m (10 foot) lift or more provide a load chain bucket.

Local Concrete Ready Mix Suppliers do not stock or utilize Class N Fly Ash or Ultra Fine Fly Ash. Please revise this specification, as written currently, we cannot provide concrete that meets the specifications from local suppliers. This quantity is not large enough for them to bring in Class N or Ultra Fine Fly Ash, that would be cost prohibitive.

Specification does not specifically require Class N Fly Ash or Ultra Fine Fly Ash to be utilized in the concrete mix. Class N Fly Ash and Ultra Fine Fly Ash are not required.

ED601 shows 5 sets of conduit to existing Service XFMR. E-601 shows 6 sets of conduit. Can we re-use existing conduit? Is there a trench detail for the additional conduit?

Provide new conductors as shown on E-601 via existing (5) 4"C as shown on ED601. Remove existing conductors as shown on

ED601

Please provide a copy of the Sundown Policy Change 2 (2022) referenced in 21 13 13. It does not appear to be available on line.

Refer to attached Sundown Policy.

Please provide a copy of the ANGETL 15-01-03 referenced in 21 13

13. It does not appear to be available on line.

Refer to attached ANGETL 15-01-03 document.

Please provide a copy of the Base Standards referenced FD001 (Demolition Note 4). It does not appear to be available on line.

Base standards are not applicable to demolition. Demolition Note 4 from FD001 is not required.

Plans call for proper collection and offsite disposal of existing AFFF foam (reference FD001 Note 19, as well as Notes 4 & 18). This is a significant task. As it appears that the AFFF Concentrate Tanks are full (as well as potentially the closed-head overhead fire sprinkler systems), please describe the required method of preparing the piping for “clean pipe” demolition. If detailed specifications are not available (none are currently included in the bid documents), please confirm that draining all Tanks and piping of contents (AFFF Concentrate & Solution), followed by triple-rinsing of all piping now or formerly in contact with AFFF (basically all piping), followed then by Lab analysis of Concentrate and rinse water (all AFFF is already know to contain PFOA & PFOS), and finally offsite (out-of-state, since no in-state facility accepts AFFF) disposal, as otherwise outlined in Note 18 (note that this will require venting and draining of all branch lines as they are the highest piping components that do not readily / fully fill and drain).

The proposed procedure outlined in the question is acceptable.

Door S105B is shown as a pair door on A-103 but not noted as a pair door on A-601. Is this a pair or single door?

Its a pair door of (2) 2'-6" wide panels.

Ref A-108, Keynote 3 – While cited note calls for existing metal roof to be repainted, we are unable to identify a specification for this work. Please identify the specification section.

Refer to spec 09 90 00 applicable sections 3.1, 3.2, (especially

3.2.1 for existing coatings), 3.3, but not limited to only these sections and paint tables at end of section for interior/exterior components.

Ref A-112, Keynote 4 – While cited note calls for the entire underside of the roof to be repainted, Section 09 90 00 does not address the repainting of existing, interior ferrous metals nor the repainting of existing, interior galvanized decking. Please provide a specification for this work.

Refer to spec 09 90 00 applicable sections 3.1, 3.2, (especially

3.2.1 for existing coatings), 3.3, but not limited to only these sections and paint tables at end of section for interior/exterior components.

Ref A-201, Keynote 1 – While cited note calls for the existing metal wall panels to be repainted, Section 09 90 00 does not address this work. Please provide a specification for this work.

Refer to spec 09 90 00 applicable sections 3.1, 3.2, (especially

3.2.1 for existing coatings), 3.3, but not limited to only these sections and paint tables at end of section for interior/exterior components.

Ref A-201, Keynote 7 – While cited note says to prepare (exterior) ladders, cages, stairs and railings as required for proper painting, this work is covered by Section 09 97 13.27, and the only surface preparation described within cited specification is abrasive blasting to near white metal, which entails removing the paint. Is it the Engineer’s intent that the existing paint be prepared for proper painting in accordance with the paint manufacturer’s recommendations or shall we assume that all (exterior) ladders, cages, stairs and railings be removed via abrasive blasting?

Yes, existing painting preparation should be in accordance with paint mfrs recommendations and may or may not include abrasive blasting.

Detail 5 on A-504 shows to extend roof system up and over wood blocking under coping. Please confirm the plywood blocking shown vertically along the parapet is existing and not new.

Vertical plywood blocking is existing, but any damaged plywood should be replaced.

Detail 6/A-504 – please confirm that fire retardant wood blocking is existing and not new. We are only installing ice/water shield, rigid insulation, Cover Board, singly ply roof system, metal roof, and prefinished metal Z Closure?

Yes, fire treated blocking is existing, but any damaged blocking should be replaced.

There are symbols on the IF sheets that are not on the legend, for example, C6 (Lactation Room), M1 (Environmental Break), D4 (Various). Please advise, are these in the scope of the project?

FF&E sheets (IF series) and Specification Section 12 50 00.13 10 are provided for reference only. Procurement and installation of new FF&E is not included in the scope of this contract.

Contractor shall provide electrical and telecommunications for planned furniture, and backing where TVs, white boards, and tack boards are shown.

Plans specify that the Access and Intrusion panels are to remain, can the make and models of the existing panels be provided?

Access Control and IDS cabinets can be reused, but controllers are to be replaced. Existing equipment is Advantor. If new controllers do not fit existing cabinets, contractor should provide new cabinets.

Fire alarm plans indicate that all fire alarm cable shall be run class B, however the specification state to run all notification appliance circuits as class A. Please specify if class A circuits will be required for notification devices.

Fire alarm circuits shall be run Class B to comply with UFC 3- 600-01 Section 9-18.9.1 and UFC 4-021-01 Sections 4-6.1 and 5- 7.1.1

E-140 Note 2 says “Make Bonding of the New Existing Grounding Ring to Existing Grounding System within Hangar Bay Area”. Is the grounding ring new or existing? If new, please provide trench repair detail.

Per as-built drawings, there is not any existing building grounding ring besides ground rods located outside around hangar bay area. Provide new ground ring as shown.

Grounding ring detail is shown on detail 2/E-503 and additional requirements on Specifications section 26 41 00 for LPS

Would a NEMA 3R rating for the MNS high powered speakers shown on the fire alarm plans be acceptable as long as they also meet the CIS score of .60?

MNS speakers shall meet the requirements of UFC 3-600-01, UFC 4-211-01, and specification 28 31 76.

Please advise where RS1 Meco Shades go? Specification for shades refers you to I-001. I-001 lists RS-1 in the legend but is not specified to be installed anywhere. Please advise.

the XXX shades are to be installed at all exterior windows.

Sheet A-107 Room E106 Fire Riser Room lists wall type B. Wall Type B is a full height wall from floor to deck (65 FT+). A-115 shows this new room to have gypsum board ceiling. Sheet I-001 lists this room as having ceiling type EXP. Please clarify – what ceiling type is required in E106? What is the wall height required in E106?

Fire Riser Room E106 will have a 1 hour rated assembly lid comprised of 5/8" type "x" gyp board on each face with 3 1/2" fiberglass insulation. Refer to structural dwgs for metal stud framing components. Ceiling height of the room is 10'-0".

Can alternate HVAC equipment be used that differs from the HVAC equipment noted on the mechanical schedule?

HVAC equipment shall meet the requirements and specifications as shown in the contract documents.

138 Will the facility be occupied during construction?

See 01 14 00 para 1.2.4. No portion of the building will be occupied during construction. However, note Comm Room E102D acts as an ITN for surrounding facilities. The ITN OSP functions must remain active for the duration of construction and must be protected. The contractor will provide temporary power and cooling as required when outages occur. Contractor must also provide power from Building 801 to temporary facilities during construction.

Will security escorts be required while working in any areas of the facility?

Security escorts are not currently required in any area of the project work. However, all contractor personnel must meet standard base access requirements and background screening.

Will any after hours or weekend work be required in any areas of the facility?

See 01 14 00 para 1.2.2, 1.2.3, and 1.2.5. Regular work hours consist of an 8 1/2 hour period established by the Contracting Officer, Monday through Friday, excluding Government Holidays. Utility Cutovers and Interruptions must be completed outside regular work hours and be approved 15 calendar days prior to such work.

Will a large laydown yard be available for equipment and materials? The area on C100 will not be large enough if temporary offices as required (per 01 11 00 Paragraph 1.2.1).

If additional laydown space is required, that may be requested through the Contracting Officer after award.

Can materials and equipment be stored in the hangar bay during construction?

There is no limitation on storage of materials and equipment in the hangar bay and may be done at the discretion of the contractor.

143 Will the hangar bay be vacant during construction?

See 01 14 00 para 1.2.4. The hangar bay will be vacant during construction.

Will any temporary heating or air conditioning be required in any of the spaces?

Temporary heating and air conditioning are required for some of the users' temporary facilities, in accordance with 01 50 00.

Note that Comm Room E102D acts as an ITN for surrounding facilities. The ITN OSP functions must remain active for the duration of construction and must be protected. The contractor will provide temporary power and cooling as required when outages occur. Contractor must also provide power from Building 801 to temporary facilities during construction.

Will this project have to be phased? For example, per plan view do we have to construct A,B,C, etc..?

See 01 14 00 para 1.2.4. No phasing is required.

Please provide qualifications of the required Metal Corrosion Expert.

The required Metal Corrosion Expert is expected to evaluate and perform non-destructive testing (NDT) on corroded structural steel members. The nondestructive testing must be performed by a testing agency adequately equipped and competent to perform such services or by the Contractor using suitable equipment and qualified personnel.