08.2 SPECS - Repair RTS - Multiple Bldgs PDPG262040.pdf
PDF 189 KB Posted
- Attached to
- Repair RTS Multiple Buildings
- Solicitation number
- W50S74-26-Q-A022
- Issued by
-
Department of the Army National Guard
About this file
This is a specification document for a federal repair contract at March Air Reserve Base in California, encompassing door hardware installation and steel doors and frames for multiple buildings.
The contract requires the supply and installation of comprehensive door hardware across multiple building types including billets, bathhouses, and kitchens. Hardware specifications include hinges (Ives brand standard with Stanley as acceptable alternate), mortise locksets and latchsets with Schlage L-series locks, exit devices (Von Duprin standard), surface closers (LCN 4040XP model), and various accessory items such as kick plates, mop plates, door sweeps, seals, and thresholds. The keying system specified is Schlage Everest 29 Primus high-security utility-patented keyway with interchangeable cores; construction keying requires temporary keyed-alike cores to be replaced with permanent cylinders at substantial completion. The finish for all hardware is BHMA 626 Satin Chrome. Seven distinct hardware groups are detailed for application to specific door numbers, with requirements to verify existing conditions prior to ordering and mount head seals before closer arms. Steel doors and frames must comply with SDI/DOOR A250.8 Level 4 specifications with maximum duty classification and insulated cores providing R-factor of 10.0 or greater. Frames require welded corners, minimum hardware reinforcing per SDI/DOOR A250.6, and appropriate anchoring for masonry or stud partition construction. Fire-rated doors and frames must comply with NFPA 80 and NFPA 105 standards with appropriate UL or FM labeling. All doors and frames require factory-primed finish or hot-dip zinc-coated finish with factory primer. Installation must follow SDI/DOOR A250.11 standards with proper plumbing, alignment, and adjustment of hardware before substantial completion.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DR SIZE MTL HDW
BILLETS
50-1 3'-0" x 7'-0" HM 1 50-2 3'-0" x 7'-0" HM 1 51-1 3'-0" x 7'-0" HM 1 51-2 3'-0" x 7'-0" HM 1 52-1 3'-0" x 7'-0" HM 1 52-2 3'-0" x 7'-0" HM 1 53-1 3'-0" x 7'-0" HM 1 53-2 3'-0" x 7'-0" HM 1 54-1 3'-0" x 7'-0" HM 1 54-2 3'-0" x 7'-0" HM 1 55-1 3'-0" x 7'-0" HM 1 55-2 3'-0" x 7'-0" HM 1 56-1 3'-0" x 7'-0" HM 1 56-2 3'-0" x 7'-0" HM 1 57-1 3'-0" x 7'-0" HM 1 57-2 3'-0" x 7'-0" HM 1 58-1 3'-0" x 7'-0" HM 1 58-2 3'-0" x 7'-0" HM 1 59-1 3'-0" x 7'-0" HM 1 59-2 3'-0" x 7'-0" HM 1
BATHHOUSE
91-1 3'-0" x 7'-0" HM 2 91-2 3'-0" x 7'-0" HM 2 91-3 3'-0" x 7'-0" V HM 3 91-4 3'-0" x 7'-0" V HM 3 91-5 3'-0" x 7'-0" V HM 3
KITCHEN
96-1 3'-0" x 7'-0" HM 1 96-2 3'-0" x 7'-0" PR HM 4 96-3 3'-0" x 7'-0" PR HM 4
LEGEND
HM
PR
V
DOOR SCHEDULE
REPAIR RTS
Multiple Buildings March Air Reserve Base California
HOLLOW METAL
PAIR
1' X 2' LOW VENT +14" BTM
REPAIR RTS DOOR HARDWARE
Multiple Buildings 08 71 00 -1 March Air Reserve Base California
SECTION 08 71 00
DOOR HARDWARE
PART 1 - GENERAL
1.1 SUMMARY:
A. Section Includes:
1. Door hardware, including electric hardware.
2. Storefront and entrance door hardware.
3. Card Access control system.
4. Power supplies for electric hardware.
5. Door position switches.
6. Cylinders for doors fabricated with locking hardware.
7. Point-to-point wiring diagrams for electric hardware.
B. Related Divisions:
1. Division 06 – door hardware installation
2. Division 07 – sealant at exterior thresholds
3. Division 08 – metal doors and frames, interior aluminum frames, wood doors, integrated security systems, specialty doors, storefront and glazed curtainwall systems.
4. Division 10 – operable partitions
5. Division 21 – fire and life safety systems
6. Division 28 – security access systems
C. Specific Omissions: Hardware for the following is specified or indicated elsewhere.
1. Windows.
2. Cabinets, including open wall shelving and locks.
3. Signs, except where scheduled.
4. Toilet accessories, including grab bars.
5. Installation.
6. Rough hardware.
7. Conduit, junction boxes & wiring.
8. Folding partitions.
9. Sliding aluminum doors.
10. Access doors and panels.
11. Corner Guards.
12. Welded steel gates and supports.
1.2 REFERENCES:
A. Use date of standard in effect as of Bid date.
1. American National Standards Institute
a) ANSI 156.18 – Materials and Finishes.
2. BHMA – Builders Hardware Manufacturers Association
3. 2022 California Building Code
a) Chapter 11B – Accessibility To Public Buildings, Public Accommodations, Commercial Buildings and Public Housing
4. DHI – Door and Hardware Institute
Multiple Buildings 08 71 00 -2
5. NFPA – National Fire Protection Association
a) NFPA 80 2016 Edition – Standard for Fire Doors and Other Opening Protectives.
b) NFPA 105 – Smoke and Draft Control Door Assemblies
c) NFPA 252 – Fire Tests of Door Assemblies
6. UL – Underwriters Laboratories
a) UL10C – Positive Pressure Fire Tests of Door Assemblies.
b) UL 305 – Panic Hardware
7. WHI – Warnock Hersey Incorporated State of California Building Code
8. Local applicable codes
9. SDI – Steel Door Institute
10. WI – Woodwork Institute
11. AWI – Architectural Woodwork Institute
12. NAAMM – National Association of Architectural Metal Manufacturers
B. Abbreviations
1. Manufacturers: see table at 2.1.A of this section
2. Finishes: see 2.7 of this section.
1.3 SUBMITTALS & SUBSTITUTIONS:
A. SUBMITTALS: Submit six copies of schedule per D. Only submittals printed one sided will be accepted and reviewed. Organize vertically formatted schedule into “Hardware Sets” with index of doors and headings, indicating complete designations of every item required for each door or opening. Minimum 10pt font size. Include following information:
1. Type, style, function, size, quantity and finish of hardware items.
2. Use BHMA Finish codes per ANSI A156.18.
3. Name, part number and manufacturer of each item.
4. Fastenings and other pertinent information.
5. Location of hardware set coordinated with floor plans and door schedule.
6. Explanation of abbreviations, symbols, and codes contained in schedule.
7. Mounting locations for hardware.
8. Door and frame sizes, materials and degrees of swing.
9. List of manufacturers used and their nearest representative with address and phone number.
10. Catalog cuts.
11. Point-to-point wiring diagrams.
12. Manufacturer’s technical data and installation instructions for electronic hardware.
13. Date of jobsite visit.
B. Bid and submit manufacturer’s updated/improved item if scheduled item is discontinued.
C. Deviations: Highlight, encircle or otherwise identify deviations from “Schedule of Finish Hardware” on submittal with notations clearly designating those portions as deviating from this section.
D. If discrepancy between drawings and scheduled material in this section, bid the more expensive of the two choices, note the discrepancy in the submittal and request direction from Architect for resolution.
E. Substitutions per Division 1. Include product data and indicate benefit to the Project.
Furnish operating samples on request.
Multiple Buildings 08 71 00 -3
F. Items listed with no substitute manufacturers have been requested by Owner to meet existing standard.
G. Furnish as-built/as-installed schedule with closeout documents, including keying schedule, riser and point-to-point wiring diagrams, manufacturers’ installation, adjustment and maintenance information, and supplier’s final inspection report.
1.4 QUALITY ASSURANCE:
A. Qualifications:
1. Hardware supplier: direct factory contract supplier who employs a hardware consultant, available at reasonable times during course of work for project hardware consultation to Owner, Architect and Contractor.
a) Responsible for detailing, scheduling and ordering of finish hardware.
Detailing implies that the submitted schedule of hardware is correct and complete for the intended function and performance of the openings.
B. Hardware: Free of defects, blemishes and excessive play. Obtain each kind of hardware (latch and locksets, exit devices, hinges and closers) from one manufacturer.
C. Exit Doors: Operable from inside with single motion without the use of a key or special knowledge or effort.
D. Fire-Rated Openings: NFPA 80 compliant. Hardware UL10C (positive pressure) compliant for given type/size opening and degree of label. Provide proper latching hardware, non-flaming door closers, approved-bearing hinges, and resilient seals.
Coordinate with wood door section for required intumescent seals. Furnish openings complete.
E. Furnish hardware items required to complete the work in accordance with specified performance level and design intent, complying with manufacturers’ instructions and code requirements.
F. Pre-Installation Meetings: Initiate and conduct with supplier, installer and related trades, coordinate materials and techniques, and sequence complex hardware items and systems installation. Include manufacturers' representatives of locks, panic hardware and door closers in the meetings. Convene prior to commencement of related work.
1.5 DELIVERY, STORAGE AND HANDLING:
A. Delivery: coordinate delivery to appropriate locations (shop or field).
1. Permanent keys and cores: secured delivery direct to Owner’s representative.
B. Acceptance at Site: Items individually packaged in manufacturers’ original containers, complete with proper fasteners and related pieces. Clearly mark packages to indicate contents, locations in hardware schedule and door numbers.
C. Storage: Provide securely locked storage area for hardware, protect from moisture, sunlight, paint, chemicals, dust, excessive heat and cold, etc.
1.6 PROJECT CONDITIONS AND COORDINATION:
A. Electrified hardware: Electrical drawings and electrical specifications are based on the specific electrified hardware components specified in hardware sets. These electronic hardware components have been specified as an assembly. Changes to these components shall be submitted to the Architect for approval.
Multiple Buildings 08 71 00 -4
B. Where exact types of hardware specified are not adaptable to finished shape or size of members requiring hardware, provide suitable types having as nearly as practical the same operation and quality as type specified, subject to Architect’s approval.
C. Coordination: Coordinate hardware with other work. Furnish hardware items of proper design for use on doors and frames of the thickness, profile, swing, security and similar requirements indicated, as necessary for proper installation and function, regardless of omissions or conflicts in the information on the Contract Documents. Furnish related trades with the following information:
1. Location of embedded and attached items to concrete.
2. Location of wall-mounted hardware, including wall stops.
3. Location of finish floor materials and floor-mounted hardware.
4. At masonry construction, coordinate with the anchoring and hollow metal supplier prior to frame installation by placing a strip of insulation, wood, or foam, on the back of the hollow metal frame behind the rabbet section for continuous hinges, as well as at rim panic hardware strike locations, silencers, coordinators, and door closer arm locations. When the frame is grouted in place, the backing will allow drilling and tapping without dulling or breaking the installer’s bits.
5. Locations for conduit and raceways as needed for electrical, electronic and electro-pneumatic hardware items. Fire/life-safety system interfacing. Point-to-point wiring diagrams plus riser diagrams to related trades.
6. Coordinate: low-voltage power supply locations.
7. Coordinate: flush top rails of doors at outswinging exteriors, and throughout where adhesive-mounted seals occur.
8. Manufacturers’ templates to door and frame fabricators.
D. Check Shop Drawings for doors and entrances to confirm that adequate provisions will be made for proper hardware installation.
E. Environmental considerations: segregate unused recyclable paper and paper product packaging, uninstalled metals, and plastics, and have these sent to a recycling center.
F. Prior to submittal, carefully inspect existing conditions to verify finish hardware required to complete Work, including sizes, quantities, existing hardware scheduled for re-use, and sill condition material. If conflict between the specified/scheduled hardware and existing conditions, submit request for direction from Architect. Include date of jobsite visit in the submittal.
1. Submittals prepared without thorough jobsite visit by qualified hardware expert will be rejected as non-compliant.
1.7 WARRANTY:
A. Part of respective manufacturers’ regular terms of sale. Provide manufacturers’ written warranties.
B. Include factory order numbers with close-out documents to validate warranty information, required for Owner in making future warranty claims:
C. Minimum warranties:
Multiple Buildings 08 71 00 -5
1. Locksets: Ten years
2. Extra Heavy Duty Cylindrical Lock: Ten Years
Three Years electrical
3. Exit Devices: Ten years mechanical
Three years electrical
4. Closers: Thirty years mechanical
5. Hinges: One year
6. Other Hardware Two years
1.8 COMMISSIONING:
A. Conduct these tests prior to request for certificate of substantial completion:
1. With installer present, test door hardware operation with climate control system and stairwell pressurization system both at rest and while in full operation.
2. With installer, access control contractor and electrical contractor present, test electrical, electronic and electro-pneumatic hardware systems for satisfactory operation.
3. With installer and electrical contractor present, test hardware interfaced with fire/life-safety system for proper operation and release.
Multiple Buildings 08 71 00 -6
PART 2 - PRODUCTS
2.1 MANUFACTURERS:
A. Listed acceptable alternate manufacturers: these will be considered; submit for review products with equivalent function and features of scheduled products.
ITEM: MANUFACTURER: ACCEPTABLE ALTERNATE:
Hinges (IVE) Ives Stanley
Continuous Hinges (IVE) Ives Select
Pivots (IVE) Ives Rixson
Key System (SCH) Schlage Owner Standard
Mechanical Locks (SCH) Schlage Owner Standard
Exit Devices (VON) Von Duprin Owner Standard
Closers (LCN) LCN Owner Standard
Auto Flush Bolts (IVE) Ives Trimco
Coordinators (IVE) Ives Trimco
Silencers (IVE) Ives Trimco
Push & Pull Plates (IVE) Ives Trimco
Kickplates (IVE) Ives Trimco
Wall Stops (IVE) Ives Trimco
Overhead Stops (GLY) Glynn-Johnson ABH
Thresholds (ZER) Zero NGP
Seals & Bottoms (ZER) Zero NGP
Hold Opens (AMA) Amazon Owner Standard
2.2 HINGING METHODS:
A. Drawings typically depict doors at 90 degrees, doors will actually swing to maximum allowable. Use wide-throw conventional or continuous hinges as needed up to 8 inches in width to allow door to stand parallel to wall for true 180-degree opening. Advise architect if 8-inch width is insufficient.
B. Conform to manufacturer’s published hinge selection standard for door dimensions, weight and frequency, and to hinge selection as scheduled. Where manufacturer’s standard exceeds the scheduled product, furnish the heavier of the two choices, notify Architect of deviation from scheduled hardware.
Multiple Buildings 08 71 00 -7
C. Conventional Hinges: Steel or stainless steel pins and approved bearings. Hinge open widths minimum, but of sufficient throw to permit maximum door swing.
1. Outswinging exterior doors: non-ferrous with non-removable (NRP) pins.
2. Non-ferrous material exteriors and at doors subject to corrosive atmospheric conditions.
D. Continuous Hinges:
1. Geared-type aluminum.
a) Use wide-throw units where needed for maximum degree of swing, advise architect if commonly available hinges are insufficient.
b) If units are used at storefront openings, color-coordinate hinge finish with storefront color. Custom anodizing and custom powdercoat finishes subject to Architect approval.
2. Pinned steel/stainless steel type: continuous stainless steel, 0.25-inch diameter stainless-steel hinge pin.
a) Use engineered application-specific wide-throw units as needed to provide maximum swing degree of swing, advise architect if required width exceeds 8 inches.
E. Pivots: high-strength forged bronze or stainless steel, tilt-on precision bearing and bearing pin.
1. Bottom and intermediate pivots: adjustability of minus 0.063 inch, plus 0.125 inch.
2.3 LOCKSETS, LATCHSETS, DEADBOLTS:
A. Mortise Locksets and Latchsets: as scheduled.
1. Chassis: cold-rolled steel, handing field-changeable without disassembly.
2. Universal lock case – 10 functions in one case.
3. Floating mounting tabs automatically adjusts to fit a beveled door edge.
4. Latchbolts: 0.75 inch throw stainless steel anti-friction type.
5. Lever Trim: through-bolted, accessible design, cast lever or solid extruded bar type levers as scheduled. Filled hollow tube design unacceptable.
a) Spindles: security design independent breakaway. Breakage of outside lever does not allow access to inside lever’s hubworks to gain wrongful entry.
b) Inside lever applied by screwless shank mounting – no exposed trim mount screws.
c) Levers rotate up or down for ease of use.
d) Vandalgard locks: locked lever freely rotates down while remaining securely locked. This feature prevents damage to internal lock components when subjected to excessive force.
6. Furnish solid cylinder collars with wave springs. Wall of collar to cover rim of mortise cylinder.
7. Turnpieces: accessible offset turn-lever design not requiring pinching or twisting motions to operate.
8. Deadbolts: stainless steel 1-inch throw.
9. Electric operation: Manufacturer-installed continuous duty solenoid.
10. Strikes: 16 gage curved steel, bronze or brass with 1 inch deep box construction, lips of sufficient length to clear trim and protect clothing.
11. Scheduled Lock Series and Design: Schlage L series, design as scheduled.
12. Certifications:
Multiple Buildings 08 71 00 -8
a) ANSI A156.13, Grade 1 Operational.
b) ANSI/ASTM F476-84 Grade 31 UL Listed.
13. Accessibility: Require not more than 5 lb to retract the latchbolt or deadbolt, or both, per CBC 2022 11B-404.2.7 and 11B-309.4.
2.4 EXIT DEVICES / PANIC HARDWARE:
A. General features:
1. Independent lab-tested 1,000,000 cycles.
2. Push-through push-pad design. No exposed push-pad fasteners, no exposed cavities when operated. Return stroke fluid dampeners and rubber bottoming dampeners, plus anti-rattle devices.
3. Deadlocking latchbolts, 0.75 inch projection.
4. End caps: impact-resistant, flush-mounted. No raised edges or lips to catch carts or other equipment.
5. No exposed screws to show through glass doors.
6. Non-handed basic device design with center case interchangeable with all functions, no extra parts required to effect change of function.
7. Releasable in normal operation with 15-pound maximum operating force per
UBC Standard 10-4, and with 32-pound maximum pressure under 250-pound load to the door.
8. Exterior doors scheduled with XP-series devices: Static load force resistance of at least 2000 pounds.
9. Accessibility: Require not more than 5 lb to retract the latchbolt, per CBC 2022 11B-404.2.7 and 11B-309.4.
a) Mechanical method: Von Duprin “AX-“ feature, where touchpad directly retracts the latchbolt with 5 lb or less of force. Provide testing lab certification confirming that the mechanical device is independent third-party tested to meet this 5 lb requirement.
B. Specific features:
1. Non-Fire Rated Devices: cylinder dogging with indication.
2. Lever Trim: breakaway type, forged brass or bronze escutcheon min. 0.130 inch thickness, compression spring drive, match lockset lever design.
3. Fire-Labeled Devices: UL label indicating “Fire Exit Hardware”. Vertical rod devices less bottom rod (LBR) unless otherwise scheduled.
4. Electrically Operated Devices: Single manufacturer source for electric latch retraction devices, electrically controlled trim, power transfers, power supplies, monitoring switches and controls.
5. Removable Mullions: Removable with single turn of building key. Securely reinstalled without need for key. Furnish storage brackets for securely stowing the mullion away from the door when removed.
6. Accepted substitutions: None, Owner Standard.
2.5 CLOSERS:
A. Surface Closers: [4041XP]
1. Full rack-and-pinion type cylinder with removable non-ferrous cover and cast iron body. Double heat-treated pinion shaft, single piece forged piston, chrome-silicon steel spring.
2. ISO 2000 certified. Units stamped with date-of-manufacture code.
3. Independent lab-tested 10,000,000 cycles.
4. Non-sized, non-handed, and adjustable. Place closer inside building, stairs, and rooms.
Multiple Buildings 08 71 00 -9
5. Plates, brackets and special templating when needed for interface with particular header, door and wall conditions and neighboring hardware.
6. Adjust doors to open with not more than 5.0-pounds pressure to open at exterior doors and 5.0-pounds at interior doors. As allowed per 2022 California Building Code Section 11B-404.2.9, local authority may increase the allowable pressure for fire doors to achieve positive latching, but not to exceed 15-pounds.
a) Exception: exterior doors’ pressure-to-open may be increased to 8.5-pounds if: at a single location, and one of a bank of eight leafs or fraction of eight, and one leaf of this bank is fitted with a low- or high-energy operator.
7. Separate adjusting valves for closing speed, latching speed and backcheck, fourth valve for delayed action where scheduled.
8. Extra-duty arms (EDA) at exterior doors scheduled with parallel arm units.
9. Exterior door closers: tested to 100 hours of ASTM B117 salt spray test, furnish data on request.
10. Exterior doors: seasonal adjustments not required for temperatures from 120 degrees F to -30 degrees F, furnish checking fluid data on request.
11. Non-flaming fluid, will not fuel door or floor covering fires.
12. Pressure Relief Valves (PRV) not permitted.
13. Accepted substitutions: None, Owner Standard.
2.6 OTHER HARDWARE:
A. Automatic Flush Bolts: Low operating force design.
B. Overhead Stops: Non-plastic mechanisms and finished metal end caps. Field-changeable hold-open, friction and stop-only functions.
C. Kick Plates: Four beveled edges, .050 inches minimum thickness, height and width as scheduled. Sheet-metal screws of bronze or stainless steel to match other hardware.
D. Door Stops: Provide stops to protect walls, casework or other hardware.
1. Unless otherwise noted in Hardware Sets, provide floor type with appropriate fasteners. Where floor type cannot be used, provide wall type. If neither can be used, provide overhead type.
2. Locate overhead stops for maximum possible opening. Consult with Owner for furniture locations. Minimum: 90deg stop / 95deg deadstop. Note degree of opening in submittal.
E. Seals: Four-fingered type at head & jambs. Inelastic, rigid back, not subject to stretching.
Self-compensating for warp, thermal bow, door settling, and out-of-plumb. Adhesive warranted for life of installation.
1. Proposed substitutions: submit for approval.
2. Three-fingered type at hinge jambs of doors fitted with continuous hinges where jamb leaf of hinge is fastened to the frame reveal.
F. Thresholds: As scheduled and per details. Comply with CBC 2022 11B-404.2.5.
Substitute products: certify that the products equal or exceed specified material’s thickness. Proposed substitutions: submit for approval.
1. Saddle thresholds: 0.125 inches minimum thickness.
2. Exteriors: Seal perimeter to exclude water and vermin. Use sealant complying with requirements in Division 7 "Thermal and Moisture Protection". Minimum 0.25 inch diameter fasteners and lead expansion shield anchors, or Red-Head #SFS-1420 (or approved equivalent) Flat Head Sleeve Anchors. National Guard Products’ “COMBO” or Pemko Manufacturing’s “FHSL”.
Multiple Buildings 08 71 00 -10
3. Fire-rated openings, 90-minutes or less duration: use thresholds to interrupt floor covering material under the door where that material has a critical radiant flux value less than 0.22 watts per square centimeter, per NFPA 253. Use threshold unit as scheduled. If none scheduled, include a 0.25in high 5in wide saddle in the bid, and request direction from Architect.
4. Fire-rated openings, 3-hour duration: Thresholds, where scheduled, to extend full jamb depth.
5. Acoustic openings: Set units in full bed of Division-7-compliant, leave no air space between threshold and substrate.
6. Plastic plugs with wood or sheet metal screws are not an acceptable substitute for specified fastening methods.
7. Fasteners: Generally, exposed screws to be Phillips or Robertson drive. Pinned TORX drive at high security areas. Flat head sleeve anchors (FHSL) may be slotted drive. Sheet metal and wood screws: full-thread. Sleeve nuts: full length to prevent door compression.
G. Through-bolts: Do not use. Coordinate with wood doors; ensure provision of proper blocking to support wood screws for mounting panic hardware and door closers.
Coordinate with metal doors and frames; ensure provision of proper reinforcement to support machine screws for mounting panic hardware and door closers.
1. Exception: surface-mounted overhead stops, holders, and friction stays.
H. Silencers: Interior hollow metal frames, 3 for single doors, 4 for pairs of doors. Leave no unfilled/uncovered pre-punched silencer holes. Intent: door bears against silencers, seals make minimal contact with minimal compression – only enough to effect a seal.
2.7 FINISH:
A. Generally: BHMA 626 Satin Chrome.
B. Door closers: factory powder coated to match other hardware, unless otherwise noted.
2.8 KEYING REQUIREMENTS:
A. Key System: Schlage Everest 29 Primus high-security utility-patented keyway, interchangeable core throughout. Utility patent protection to extend at least until 2014 2029. Key blanks available only from factory-direct sources, not available from after-market keyblank manufacturers. For estimate use factory GMK charge. Initiate and conduct meeting(s) with Owner and Allegion representatives to determine system keyway(s), keybow styles, structure, stamping, degree of physical security and degree of geographic exclusivity. Furnish Owner’s written approval of the system; do not order keys or cylinders without written confirmation of actual requirements from the Owner.
Contractor will install permanent cylinders/cores.
1. Existing factory-registered master key system.
2. Primus Level 9 (verify)
3. Construction keying: furnish temporary keyed-alike cores. Remove at substantial completion and install permanent cylinders/cores in Owner’s presence.
Demonstrate that construction key no longer operates.
4. Temporary cylinders/cores remain supplier’s property.
5. Furnish 10 construction keys.
6. Furnish 2 construction control keys.
7. Furnish 2 Emergency keys per each L9485 Faculty Restroom Lock
8. Key Cylinders: furnish 6-pin solid brass construction.
B. Cylinders/cores: keyed at factory of lock manufacturer where permanent records are maintained. Locksets and cylinders same manufacturer.
Multiple Buildings 08 71 00 -11
C. Permanent keys: use secured shipment direct from point of origination to Owner.
1. For estimate: 3 keys per change combination, 5 master keys per group, 5 grand-master keys, 3 control keys.
2. For estimate: VKC stamping plus “DO NOT DUPLICATE”.
D. Bitting List: use secured shipment direct from point of origination to Owner at completion.
E. Key Control software: Include one Sitemaster 200 key control system with new key system.
PART 3 - EXECUTION
3.1 ACCEPTABLE INSTALLERS:
A. Can read and understand manufacturers’ templates, suppliers’ hardware schedule and printed installation instructions. Can readily distinguish drywall screws from manufacturers’ furnished fasteners. Available to meet with manufacturers’ representatives and related trades to discuss installation of hardware.
3.2 PREPARATION:
A. Ensure that walls and frames are square and plumb before hardware installation. Make corrections before commencing hardware installation. Installation denotes acceptance of wall/frame condition.
B. Locate hardware per SDI-100 and applicable building, fire, life-safety, accessibility, and security codes.
1. Notify Architect of code conflicts before ordering material.
2. Locate latching hardware between 34 inches to 44 inches above the finished floor, per California Building Code, Section 1010.1.9.2 and 11B-404.2.7.
3. Locate panic hardware between 36 inches to 44 inches above the finished floor.
4. Where new hardware is to be installed near existing doors/hardware scheduled to remain, match locations of existing hardware.
C. Overhead stops: before installing, determine proposed locations of furniture items, fixtures, and other items to be protected by the overhead stop's action.
D. Existing frames and doors to be retrofitted with new hardware:
1. Field-verify conditions and dimensions prior to ordering hardware. Fill existing hardware cut outs not being reused by the new hardware. Remove existing hardware not being reused, return to Owner unless directed otherwise.
2. Remove existing floor closers not scheduled for reuse, fill cavities with non-shrinking concrete and finish smooth.
3. Cut and weld existing steel frames currently prepared with 2.25 inch height strikes. Cut an approximate 8 inch section from the strike jamb and weld in a reinforced section to accommodate specified hardware’s strike.
4. Patch and weld flush filler pieces into existing door hardware preparations in steel doors and frames, leave surfaces smooth.
5. Glue in solid wood block fillers to fill cut outs in existing wood doors, sand surfaces smooth. Alternatively, use an approved epoxy-based wood filler product, submit product data for approval.
Multiple Buildings 08 71 00 -12
3.3 INSTALLATION:
A. Install hardware per manufacturer’s instructions and recommendations. Do not install surface-mounted items until finishes have been completed on substrate. Set units level, plumb and true to line and location. Adjust and reinforce attachment substrate for proper installation and operation. Remove and reinstall or replace work deemed defective by Architect.
1. Gaskets: install jamb-applied gaskets before closers, overhead stops, rim strikes, etc; fasten hardware over and through these seals. Install sweeps across bottoms of doors before astragals, cope sweeps around bottom pivots, trim astragals to tops of sweeps.
2. When hardware is to be attached to existing metal surface and insufficient reinforcement exists, use RivNuts, NutSerts or similar anchoring device for screws.
3. Use manufacturers' fasteners furnished with hardware items, or submit Request for Substitution with Architect.
4. Replace fasteners damaged by power-driven tools.
B. Locate floor stops no more that 4 inches from walls and not within paths of travel. See paragraph 2.2 regarding hinge widths, door should be well clear of point of wall reveal.
Point of door contact no closer to the hinge edge than half the door width. Where situation is questionable or difficult, contact Architect for direction.
C. Core concrete for exterior door stop anchors. Set anchors in approved non-shrink grout.
D. Locate overhead stops for minimum 90 degrees at rest and for maximum allowable degree of swing.
E. Drill pilot holes for fasteners in wood doors and/or frames.
F. Lubricate and adjust existing hardware scheduled to remain. Carefully remove and give to Owner items not scheduled for reuse.
G. Field-verify existing conditions and measurements prior to ordering hardware. Fill existing hardware cut outs not being used by the new hardware.
H. Remove existing hardware not being reused. Tag and bag removed hardware, turn over to Owner.
I. Where existing wall conditions will not allow door to swing using the scheduled hinges, provide wide-throw hinges and if needed, extended arms on closers.
J. Provide manufacturer’s recommended brackets to accommodate the mounting of closers on doors with flush transoms.
3.4. ADJUSTING:
A. Adjust and check for proper operation and function. Replace units, which cannot be adjusted to operate freely and smoothly.
1. Hardware damaged by improper installation or adjustment methods: repair or replace to Owner’s satisfaction.
2. Adjust doors to fully latch with no more than 1 pound of pressure.
a) Door closer valves: turn valves clockwise until at bottom – do not force.
Turn valves back out one and one-half turns and begin adjustment process from that point. Do not force valves beyond three full turns counterclockwise.
3. Adjust delayed-action closers on fire-rated doors to fully close from fully-opened position in no more than 10 seconds.
Multiple Buildings 08 71 00 -13
4. Adjust door closers per 1.9 this section.
B. Fire-rated doors:
1. Wood doors: adjust to 0.125 inches clearance at heads, jambs, and meeting stiles.
2. Steel doors: adjust to 0.063 inches minimum to 0.188 inches maximum clearance at heads, jambs, and meeting stiles.
3. Adjust wood and steel doors to 0.75 inches maximum clearance (undercut) above threshold or finish floor material under door.
C. Final inspection: Installer to provide letter to Owner that upon completion installer has visited the Project and has accomplished the following:
1. Has re-adjusted hardware.
2. Has evaluated maintenance procedures and recommend changes or additions, and instructed Owner’s personnel.
3. Has identified items that have deteriorated or failed.
4. Has submitted written report identifying problems.
3.5 DEMONSTRATION:
A. Demonstrate mechanical hardware and electrical and electronic hardware systems, including adjustment and maintenance procedures.
3.6 PROTECTION/CLEANING:
A. Cover installed hardware, protect from paint, cleaning agents, weathering, carts/barrows, etc. Remove covering materials and clean hardware just prior to substantial completion.
B. Clean adjacent wall, frame and door surfaces soiled from installation / reinstallation process.
3.7 SCHEDULE OF FINISH HARDWARE:
A. See door schedule in drawings for hardware set assignments.
B. Do not order material until submittal has been reviewed, stamped, and signed by Architect’s door hardware consultant.
C. The hardware sets represent the design intent and direction of the owner and architect.
They are a guideline only and should not be considered a detailed hardware schedule.
Discrepancies, conflicting hardware and missing items should be brought to the attention of the architect with corrections made prior to the bidding process. Omitted items not included in a hardware set should be scheduled with the appropriate additional hardware required for proper application and functionality.
Multiple Buildings 08 71 00 -14
156143 OPT0494842 Version 2
HARDWARE GROUP NO. 01
For use on Door #(s):
50-1 50-2 51-1 51-2 52-1 52-2 53-1 53-2 54-1 54-2 55-1 55-2 56-1 56-2 57-1 57-2 58-1 58-2 59-1 59-2
3 EA HINGE 5BB1 4.5 X 4.5 NRP 630 IVE
1 EA ENTRANCE W/DEADBOLT L9453T 06A L583-363 626 SCH
1 EA PRIMUS CORE 20-740 EV29 626 SCH
1 EA SURFACE CLOSER 4040XP HEDA 689 LCN
1 EA MOP PLATE 8400 12" X 1" LDW B-CS 630 IVE
1 EA KICK PLATE 8400 12" X 2" LDW B-CS 630 IVE
1 EA FLOOR STOP FS18S/L AS REQ'D BLK IVE
1 EA RAIN DRIP 142AA (OMIT @ OVERHANG) AA ZER
1 SET SET SEAL 429AA-S (@ HEAD & JAMBS) AA ZER
1 EA DOOR SWEEP 39A A ZER
1 EA THRESHOLD 103A-223 (OR AS REQ'D. OR PER
DETAILS/CONDITIONS)
A ZER
VERIFY EXISTING CONDITIONS PRIOR TO ORDERING HARDWARE.
MOUNT HEAD SEAL BEFORE CLOSER ARM(S).
HARDWARE GROUP NO. 02
For use on Door #(s):
91-1 91-2
3 EA HINGE 5BB1HW 4.5 X 4.5 630 IVE
1 EA CLASSROOM DEAD LOCK L9463T XB11-720 626 SCH
1 EA PRIMUS CORE 20-740 EV29 626 SCH
1 EA PULL PLATE 8303 10" 4" X 16" CFT G 630 IVE
1 EA SURFACE CLOSER 4040XP H 689 LCN
1 EA MOP PLATE 8400 12" X 1" LDW B-CS 630 IVE
1 EA KICK PLATE 8400 12" X 2" LDW B-CS 630 IVE
1 EA PUSH PLATE 8200 8" X 36" CFC
(ENGINEERING SPECIAL)
630 IVE
1 EA WALL STOP WS406/407CVX AS REQ'D 630 IVE
1 SET SET SEAL 429AA-S (@ HEAD & JAMBS) AA ZER
1 EA DOOR SWEEP 111AA AA ZER
1 EA THRESHOLD 103A-223 (OR AS REQ'D. OR PER
DETAILS/CONDITIONS)
A ZER
VERIFY EXISTING CONDITIONS PRIOR TO ORDERING HARDWARE.
Multiple Buildings 08 71 00 -15
HARDWARE GROUP NO. 03
91-3
3 EA HINGE 5BB1 4.5 X 4.5 NRP 630 IVE
1 EA STOREROOM LOCK L9080T 06A 626 SCH
1 EA PRIMUS CORE 20-740 EV29 626 SCH
1 EA SURFACE CLOSER 4040XP SHCUSH 689 LCN
1 EA MOP PLATE 8400 12" X 1" LDW B-CS 630 IVE
1 EA KICK PLATE 8400 12" X 2" LDW B-CS 630 IVE
1 EA RAIN DRIP 142AA (OMIT @ OVERHANG) AA ZER
1 SET SET SEAL 429AA-S (@ HEAD & JAMBS) AA ZER
1 EA DOOR SWEEP 39A A ZER
1 EA THRESHOLD 103A-223 (OR AS REQ'D. OR PER
DETAILS/CONDITIONS)
A ZER
VERIFY EXISTING CONDITIONS PRIOR TO ORDERING HARDWARE.
MOUNT HEAD SEAL BEFORE CLOSER ARM(S).
HARDWARE GROUP NO. 04
91-5
3 EA HINGE 5BB1 4.5 X 4.5 630 IVE
1 EA STOREROOM LOCK L9080T 06A 626 SCH
1 EA PRIMUS CORE 20-740 EV29 626 SCH
1 EA MOP PLATE 8400 12" X 1" LDW B-CS 630 IVE
1 EA KICK PLATE 8400 12" X 2" LDW B-CS 630 IVE
1 EA HOLD OPEN MAGNETIC, 304 SS, HEAVY
DUTY WALL MNT - HOMMYZONE
630 AMA
1 SET SET SEAL 429AA-S (@ HEAD & JAMBS) AA ZER
1 EA DOOR SWEEP 111AA AA ZER
1 EA THRESHOLD 103A-223 (OR AS REQ'D. OR PER
DETAILS/CONDITIONS)
Multiple Buildings 08 71 00 -16
HARDWARE GROUP NO. 05
91-4
1 EA CLASSROOM LOCK L9070T 06A 626 SCH
1 EA PRIMUS CORE 20-740 EV29 626 SCH
1 EA HOLD OPEN MAGNETIC, HEAVY DUTY 304
SS, WALL MNT - HOMMYZONE
630 AMA
1 EA MOP PLATE 8400 12” X 1” LDW B-CS 630 IVE
1 EA KICK PLATE 8400 12” X 1” LDW B-CS 630 IVE
1 SET SET SEAL 429AA-S (@ HEAD & JAMBS) AA ZER
1 EA DOOR SWEEP 111AA AA ZER
1 EA THRESHOLD 103A-223 (OR AS REQ'D. OR PER
DETAILS/CONDITIONS)
A ZER
VERIFY EXISTING CONDITIONS PRIOR TO ORDERING HARDWARE.
HARDWARE GROUP NO. 06
96-1
1 EA ENTRANCE W/DEADBOLT L9453T 06A L583-363 626 SCH
1 EA PRIMUS CORE 20-740 EV29 626 SCH
1 EA OH STOP & HOLDER 100H ADJ 630 GLY
1 EA SURFACE CLOSER 4040XP ST-1630 689 LCN
1 EA TOP JAMB MTG PLATE 4040XP-18TJ 689 LCN
1 EA MOP PLATE 8400 12" X 1" LDW B-CS 630 IVE
1 EA KICK PLATE 8400 12" X 2" LDW B-CS 630 IVE
1 SET SET SEAL 429AA-S (@ HEAD & JAMBS) AA ZER
1 EA DOOR SWEEP 111AA AA ZER
1 EA THRESHOLD 103A-223 (OR AS REQ'D. OR PER
DETAILS/CONDITIONS)
Multiple Buildings 08 71 00 -17
HARDWARE GROUP NO. 07
96-2 96-3
6 EA HINGE 5BB1 4.5 X 4.5 630 IVE
1 EA CONST LATCHING BOLT FB51P 630 IVE
1 EA DUST PROOF STRIKE DP1/2 AS REQ'D. 626 IVE
1 EA ENTRANCE W/DEADBOLT L9453T 06A L583-363 626 SCH
1 EA PRIMUS CORE 20-740 EV29 626 SCH
2 EA KICK PLATE 8400 12" X 1" LDW B-CS 630 IVE
2 EA MOP PLATE 8400 12" X 1" LDW B-CS 630 IVE
2 EA MAGNETIC DOOR STOP 304 SS, HEAVY DUTY,
ADJUSTABLE, WALL MOUNT –
AMAZON HOMMYZONE
630 AMA
1 SET SET SEAL 429AA-S (@ HEAD & JAMBS) AA ZER
1 EA DOOR SWEEP 111AA AA ZER
1 EA ASTRAGAL 44STST OR BY DOOR MFG. STST ZER
1 EA THRESHOLD 103A-223 (OR AS REQ'D. OR PER
DETAILS/CONDITIONS)
END OF SECTION
REPAIR RTS - MULTIPLE BUIDINGS MARCH ARB
SECTION 08 11 13
STEEL DOORS AND FRAMES
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel
ASTM INTERNATIONAL (ASTM)
ASTM A653/A653M (2015; E 2016) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A879/A879M (2012) Standard Specification for Steel Sheet, zinc Coated by the Electrolytic Process for Applications Requiring Designation of the Coating Mass on Each Surface
ASTM A924/A924M (2016a) Standard Specification for General Requirements for Steel Sheet, Metallic-Coated by the Hot-Dip Process
ASTM C578 (2016) Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation
ASTM C591 (2016) Standard Specification for Unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation
ASTM C612 (2014) Mineral Fiber Block and Board Thermal Insulation
ASTM D2863 (2013) Measuring the Minimum Oxygen Concentration to Support Candle-Like Combustion of Plastics (Oxygen Index)
ASTM E1300 (2016) Standard Practice for Determining Load Resistance of Glass in Buildings
ASTM F2248 (2012) Standard Practice for Specifying an Equivalent 3-Second Duration Design Loading for Blast Resistant Glazing Fabricated with Laminated Glass
SECTION 08 11 13 Page 1
BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)
ANSI/BHMA A156.115 (2016) Hardware Preparation in Steel Doors and Steel Frames
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 105 (2016) Standard for Installation of Smoke Door Assemblies and Other Opening Protectives
NFPA 252 (2017) Standard Methods of Fire Tests of Door Assemblies
NFPA 80 (2016) Standard for Fire Doors and Other Opening Protectives
STEEL DOOR INSTITUTE (SDI/DOOR)
SDI/DOOR 113 (2001; R2006) Standard Practice for Determining the Steady State Thermal Transmittance of Steel Door and Frame Assemblies
SDI/DOOR A250.11 (2001) Recommended Erection Instructions for Steel Frames
SDI/DOOR A250.4 (2011) Test Procedure and Acceptance Criteria for Physical Endurance for Steel Doors and Hardware Reinforcing
SDI/DOOR A250.6 (2003; R2009) Recommended Practice for Hardware Reinforcing on Standard Steel Doors and Frames
SDI/DOOR A250.8 (2003; R2008) Recommended Specifications for Standard Steel Doors and Frames
UNDERWRITERS LABORATORIES (UL)
UL 10C (2016) UL Standard for Safety Positive Pressure Fire Tests of Door Assemblies
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance to Section 01 81 13 LEED V2009 REQUIREMENTS.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Doors; G
Frames; G
Accessories
SECTION 08 11 13 Page 2
Show elevations, construction details, metal gages, hardware provisions, method of glazing, and installation details.
Schedule of doors; G
Schedule of frames; G
Submit door and frame locations.
SD-03 Product Data
Doors; G
Frames; G
Accessories
Submit manufacturer's descriptive literature for doors, frames, and accessories. Include data and details on door construction, panel (internal) reinforcement, insulation, and door edge construction. When "custom hollow metal doors" are provided in lieu of "standard steel doors," provide additional details and data sufficient for comparison to SDI/DOOR A250.8 requirements.
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver doors, frames, and accessories undamaged and with protective wrappings or packaging. Provide temporary steel spreaders securely fastened to the bottom of each welded frame. Store doors and frames on platforms under cover in clean, dry, ventilated, and accessible locations, with 1/4 inch airspace between doors. Remove damp or wet packaging immediately and wipe affected surfaces dry. Replace damaged materials with new.
PART 2 PRODUCTS
2.1 STANDARD STEEL DOORS
SDI/DOOR A250.8 , except as specified otherwise. Prepare doors to receive door hardware as specified in Section 08 71 00. Undercut where indicated.
Exterior doors shall have top edge closed flush and sealed to prevent water intrusion. Doors shall be 1-3/4 inch thick, unless otherwise indicated.
Provide exterior glazing in accordance with ASTM F2248 and ASTM E1300.
2.1.1 Classification - Level, Performance, Model
2.1.1.1 Maximum Duty Doors
SDI/DOOR A250.8 , Level 4, physical performance Level A, Model with core construction as required by the manufacturer for interior doors and for indicated exterior doors, of size(s) and design(s) indicated. Where vertical stiffener cores are required, the space between the stiffeners shall be filled with mineral board insulation.
2.2 INSULATED STEEL DOOR SYSTEMS
Insulated steel doors shall have a core of polyurethane foam and an R factor of 10.0 or more (based on a k value of 0.16); face sheets, edges, and frames of galvanized steel not lighter than 23 gage, 16 gage, and 16
SECTION 08 11 13 Page 3 gage respectively. Doors and frames shall receive phosphate treatment, rust-inhibitive primer, and baked acrylic enamel finish. Doors shall have been tested in accordance with SDI/DOOR A250.4 and shall have met the requirements for Level C. Prepare doors to receive specified hardware.Doors shall be 1-3/4 inch thick.
2.3 ACCESSORIES
2.3.1 Astragals
For pairs of exterior steel doors which will not have aluminum astragals or removable mullions, as specified in Section 08 71 00 DOOR HARDWARE provide overlapping steel astragals with the doors. For interior pairs of fire rated and smoke control doors, provide stainless steel astragals complying with NFPA 80 for fire rated assemblies and NFPA 105 for smoke control assemblies.
2.3.2 Moldings
Provide moldings around glass of interior and exterior doors. Provide nonremovable moldings on outside of exterior doors and on corridor side of interior doors. Other moldings may be stationary or removable. Secure inside moldings to stationary moldings, or provide snap-on moldings.
Muntins shall interlock at intersections and shall be fitted and welded to stationary moldings.
2.4 INSULATION CORES
Insulated cores shall be of type specified, and provide an apparent U-factor of .48 in accordance with SDI/DOOR 113 and shall conform to:
a. Rigid Cellular Polyisocyanurate Foam: ASTM C591, Type I or II, foamed-in-place or in board form, with oxygen index of not less than 22 percent when tested in accordance with ASTM D2863; or
b. Rigid Polystyrene Foam Board: ASTM C578, Type I or II; or
c. Mineral board: ASTM C612, Type I.
2.5 STANDARD STEEL FRAMES
SDI/DOOR A250.8 , Level 4, except as otherwise specified. Form frames to sizes and shapes indicated, with welded corners. Provide steel frames for doors, transoms, and sidelights, unless otherwise indicated.
2.5.1 Welded Frames
Continuously weld frame faces at corner joints. Mechanically interlock or continuously weld stops and rabbets. Grind welds smooth.
Weld frames in accordance with the recommended practice of the Structural Welding Code Sections 1 through 6, AWS D1.1/D1.1M and in accordance with the practice specified by the producer of the metal being welded.
2.5.2 Mullions and Transom Bars
Mullions and transom bars shall be closed or tubular construction and be a member with heads and jambs butt-welded thereto. Bottom of door mullions shall have adjustable floor anchors and spreader connections.
SECTION 08 11 13 Page 4
2.5.3 Stops and Beads
Form stops and beads from 20 gage steel. Provide for glazed and other openings in standard steel frames. Secure beads to frames with oval-head, countersunk Phillips self-tapping sheet metal screws or concealed clips and fasteners. Space fasteners approximately 12 to 16 inch on center. Miter molded shapes at corners. Butt or miter square or rectangular beads at corners.
2.5.4 Anchors
Provide anchors to secure the frame to adjoining construction. Provide steel anchors, zinc-coated or painted with rust-inhibitive paint, not lighter than 18 gage.
2.5.4.1 Wall Anchors
Provide at least three anchors for each jamb. For frames which are more than 7.5 feet in height, provide one additional anchor for each jamb for each additional 2.5 feet or fraction thereof.
a. Masonry: Provide anchors of corrugated or perforated steel straps or 3/16 inch diameter steel wire, adjustable or T-shaped;
b. Stud partitions: Weld or otherwise securely fasten anchors to backs of frames. Design anchors to be fastened to closed steel studs with sheet metal screws, and to open steel studs by wiring or welding;
2.5.4.2 Floor Anchors
Provide floor anchors drilled for 3/8 inch anchor bolts at bottom of each jamb member. Where floor fill occurs, terminate bottom of frames at the indicated finished floor levels and support by adjustable extension clips resting on and anchored to the structural slabs.
2.6 FIRE AND SMOKE DOORS AND FRAMES
NFPA 80 and NFPA 105 and this specification. The requirements of NFPA 80 and NFPA 105 shall take precedence over details indicated or specified.
2.6.1 Labels
Fire doors and frames shall bear the label of Underwriters Laboratories (UL), Factory Mutual Engineering and Research (FM), or Warnock Hersey International (WHI) attesting to the rating required. Testing shall be in accordance with NFPA 252 or UL 10C . Labels shall be metal with raised letters, and shall bear the name or file number of the door and frame manufacturer. Labels shall be permanently affixed at the factory to frames and to the hinge edge of the door. Door labels shall not be painted.
2.6.2 Oversized Doors
For fire doors and frames which exceed the size for which testing and labeling are available, furnish certificates stating that the doors and frames are identical in design, materials, and construction to a door which has been tested and meets the requirements for the class indicated.
SECTION 08 11 13 Page 5
2.6.3 Astragal on Fire and Smoke Doors
On pairs of labeled fire doors, conform to NFPA 80 and UL requirements. On smoke control doors, conform to NFPA 105 .
2.7 WEATHERSTRIPPING
As specified in Section 08 71 00 DOOR HARDWARE.
2.8 HARDWARE PREPARATION
Provide minimum hardware reinforcing gages as specified in SDI/DOOR A250.6 .
Drill and tap doors and frames to receive finish hardware. Prepare doors and frames for hardware in accordance with the applicable requirements of SDI/DOOR A250.8 and SDI/DOOR A250.6 . For additional requirements refer to ANSI/BHMA A156.115 . Drill and tap for surface-applied hardware at the project site. Build additional reinforcing for surface-applied hardware into the door at the factory. Locate hardware in accordance with the requirements of SDI/DOOR A250.8 , as applicable. Punch door frames to receive a minimum of two rubber or vinyl door silencers on lock side of single doors and one silencer for each leaf at heads of double doors. Set lock strikes out to provide clearance for silencers.
2.9 FINISHES
2.9.1 Factory-Primed Finish
All surfaces of doors and frames shall be thoroughly cleaned, chemically treated and factory primed with a rust inhibiting coating as specified in SDI/DOOR A250.8 or paintable A25 galvannealed steel without primer. Where coating is removed by welding, apply touchup of factory primer.
2.9.2 Hot-Dip Zinc-Coated and Factory-Primed Finish
Fabricate scheduled doors and frames from hot dipped zinc coated steel, alloyed type, that complies with ASTM A924/A924M and ASTM A653/A653M . The coating weight shall meet or exceed the minimum requirements for coatings having 0.4 ounces per square foot, total both sides, i.e., A40. Repair damaged zinc-coated surfaces by the application of zinc dust paint.
Thoroughly clean and chemically treat to insure maximum paint adhesion.
Factory prime as specified in SDI/DOOR A250.8 .
2.9.3 Electrolytic Zinc-Coated Anchors and Accessories
Provide electrolytically deposited zinc-coated steel in accordance with ASTM A879/A879M , Commercial Quality, Coating Class A. Phosphate treat and factory prime zinc-coated surfaces as specified in SDI/DOOR A250.8 .
2.10 FABRICATION AND WORKMANSHIP
Finished doors and frames shall be strong and rigid, neat in appearance, and free from defects, waves, scratches, cuts, dents, ridges, holes, warp, and buckle. Molded members shall be clean cut, straight, and true, with joints coped or mitered, well formed, and in true alignment. Dress exposed welded and soldered joints smooth. Design door frame sections for use with the wall construction indicated. Corner joints shall be well formed and in true alignment. Conceal fastenings where practicable. Design other frames in exposed masonry walls or partitions to allow sufficient space between the inside back of trim and masonry to receive caulking compound.
SECTION 08 11 13 Page 6
2.10.1 Grouted Frames
For frames to be installed in exterior walls and to be filled with mortar or grout, fill the stops with strips of rigid insulation to keep the grout out of the stops and to facilitate installation of stop-applied head and jamb seals.
2.11 PROVISIONS FOR GLAZING
Materials are specified in Section 08 81 00, GLAZING.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Frames
Set frames in accordance with SDI/DOOR A250.11 . Plumb, align, and brace securely until permanent anchors are set. Anchor bottoms of frames with expansion bolts or powder-actuated fasteners. Build in or secure wall anchors to adjoining construction. Where frames require ceiling struts or overhead bracing, anchor frames to the struts or bracing. Backfill frames with mortar.