MISC HVAC QUESTIONS AND ANSWERS:

1) QUESTION: Building 2812‐ Does the new unit need to be directly pulled into the Bacnet Network, or is a Bacnet capable thermostat acceptable?

ANSWER: No, per the updated SOW. “All installed equipment should be open protocol, BACnet compatible. Building 2815 and 2902 equipment needs to be tied into currently installed Automated Logic BMS.”

2) QUESTION: Would the Customer like us to use the existing base Controls Contactor to pull the new units at 2812? If Yes, Who is the Preferred contractor we should get a Price from?

ANSWER: No, they just have to be open protocol and BACnet compatible.

3) QUESTION: Building 2812‐Square ft of area served for Hot water coil sizing?

ANSWER: Recruiting Side‐ 500 SqFt and CATM is 2400 SqFt.

4) QUESTION: Building 2815‐ Steam Coils are to be replaced or left in service?

ANSWER: Not replacing steam coils, they are to be left in service.

5) QUESTION: Is that any Brand of unit that is required?

ANSWER: No Brand Requirements, all technical specifications need to meet or exceed current equipment and/or specified in the SOW.

6) QUESTION: Is that any Seer Rating that needs to be met ANSWER: Min SEER is 13.