RFI AND ANSWERS.pdf
PDF 173 KB Posted
- Attached to
- Razorback Range Tower Repair - CANCELLED Federal contract opportunity
- Solicitation number
- W50S6Q21B0006
- Issued by
- Department of the Army National Guard
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| OF 1419 Abstract of Offers signed.pdf | ||
| RFI ANSWERS 9 SEP 21.pdf | ||
| W50S6Q21B0006 AMENDMENT 0003.pdf | ||
| RFI AND ANSWERS 25 Aug.pdf | ||
| site visit sign in.pdf | ||
| TOWER PICTURES.pdf | ||
| W50S6Q21B0006 AMENDMENT 0002.pdf | ||
| W50S6Q21B0006 AMENDMENT 0001.pdf | ||
| Range Tower Specifications.pdf | ||
| W50S6Q21B0006 RANGE TOWER REPAIR SOLICITATION.pdf | ||
| Pre Bid Site Visit Directions Map.PNG | PNG image |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
24 August 2021
Responses to RFI's for Range Tower (W50S6Q21B0006):
1. How tall is the tower structure?
Per range personnel, tower height is 50’ to floor of cab.
2. Are 2x2 ceiling grids an authorized substitute?
Specification Section 09 51 00 (Acoustical Ceilings) para 2.2.1.3 actually specifies acoustical tile units with a nominal size of 24 inch by 24 inch.
3. What is the cleanup requirement for the sandblasting?
They will need to put down visqueen, plastic or something to catch the paint chips and sand and dispose of the chips and sand off of Fort Chaffee according to state and city guidelines for disposal.
4. Are lifts/cranes authorized for use at the range?
Yes. Coordination with Razorback Range through COR will be required for scheduling.
5. Can the chain link fence around the building at top of tower be replaced instead of repainted?
If the contractor would prefer replacement then they will need to provide submittals for the replacement for approval