This document is a Request for Information (RFI) with answers to six technical questions regarding HVAC and fan installation for a military construction project. The questions cover details such as fire alarm system connections, ductwork modifications, and fan mounting specifications for new HVAC units at a drill hall in Amherst, NY. Key responses include: new HVAC units will not be connected to the fire alarm system, return ducts can be relocated high with grill on mixing box, walls will require drywall patching and painting after ductwork removal, and outbuilding fans should be ceiling-mounted instead of wall-mounted due to potential vibration and weight issues. The contractor is instructed to verify existing fire alarm connections prior to removal.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. Existing AHU’s are not connected to the fire Alarm system, should new units be connected? No
2. Existing units return duct are run down the wall to the floor, for the new units return up high with grill on mixing box acceptable? Please note that walls will need drywall patching and painting once the duct is removed as it's recessed into wall. Yes
3. Existing units return ducts run down the wall to the floor, for the new units is the return up high with a grill on the mixing box acceptable? Yes Also once ductwork is removed are the voids from the removals framed drywalled and painted to match existing? Yes
4. The SOW indicates demolition of existing fire alarms associated with the HVAC units however no fire alarm appears to be currently installed with the existing units.
Please clarify. The units may or may not be connected. Contractor shall verify prior to removal.
5. . Are the new HVAC units to have fire alarm system components installed, for example Duct Detectors. Please advise if fire alarm system components will be required and the scope required. No
6. In regard to the outbuilding fans sizing would the following fan spec be acceptable?
10-foot diameter, six anodized airfoils, direct drive motor, wall mounted variable speed controller also on a timer, max 124 RPM. Yes Would not prefer wall mounted as it will eventually come off the wall from the vibration of the fan and the weight of the fan will make it sag down and eventually come off the wall. We would prefer ceiling mounted.