WV006-Cross_Lanes-C9-CSS_9035-Schedule_PNL_G-Replace_Circuit_Breakers.xlsx
XLSX spreadsheet 16 KB Posted
- Attached to
- Replace Circuit Breakers in Training Building in Cross Lanes, WV 25313 Federal contract opportunity
- Solicitation number
- W15QKN-18-Q-1120
About this file
Schedule-Panel G
View the file
Other files for this federal contract opportunity
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| Panel G | ||||||||||
| 3 Phase 4 wire 400A 120V/208V MLO Surface Mounted | 8/15/17 | |||||||||
| W/ Top Mounted 150A 3Pole Sub Breaker for PNL -F, A. I. C Raiting Amps 10,000 RMS | ||||||||||
| Circuit # | Description: | Pole | Amp | A | B | C | Pole | Amp | Description: | Circuit # |
| 1 | Room 225 IAC-D | 2 | 25A | 17.9 | 2 | 20A | Room 226 IAC-C | 2 | ||
| 3 | 17.9 | 4 | ||||||||
| 5 | Room 226 IAC-C | 2 | 20A | 15.2 | 2 | 20A | Room 226 IAC-C | 6 | ||
| 7 | 15.2 | 8 | ||||||||
| 9 | Room 227 IAC-C | 2 | 20A | 15.2 | 2 | 20A | Room 227 IAC-C | 10 | ||
| 11 | 15.2 | 12 | ||||||||
| 13 | Room 227 IAC-C | 2 | 20A | 15.2 | 2 | 20A | Room 228 IAC-C | 14 | ||
| 15 | 15.2 | 16 | ||||||||
| 17 | Room 228 IAC-C | 2 | 20A | 2 | 20A | Room 228 IAC-C | 18 | |||
| 19 | 20 | |||||||||
| 21 | Room 229 IAC-C | 2 | 20A | 2 | 20A | Room 229 IAC-C | 22 | |||
| 23 | 24 | |||||||||
| 25 | Room 229 IAC-C | 2 | 20A | 2 | 20A | Room 229 IAC-C | 26 | |||
| 27 | 28 | |||||||||
| 29 | Room 242 IAC-D | 2 | 25A | 2 | 25A | Room 242 IAC-D | 30 | |||
| 31 | 32 | |||||||||
| 33 | Room 245 IAC-D | 2 | 25A | 2 | 25A | Room 245 IAC-D | 34 | |||
| 35 | 36 | |||||||||
| 37 | Space | 38 | ||||||||
| 39 | AC-2 2nd Fl. Roof Unit | 3 | 80A | Space | 40 | |||||
| 41 | Space | 42 | ||||||||
| Totals: | 33.1 | 63.5 | 30.4 |