WV006-Cross_Lanes-C9-CSS_9035-Schedule_PNL_B-Replace_Circuit_Breakers.xlsx

XLSX spreadsheet 16 KB Posted

Attached to
Replace Circuit Breakers in Training Building in Cross Lanes, WV 25313 Federal contract opportunity
Solicitation number
W15QKN-18-Q-1120
Issued by
Department of the Army Materiel Command Contracting Command Picatinny Arsenal

About this file

Schedule-Panel B

View the file

Other files for this federal contract opportunity

Other files attached to Replace Circuit Breakers in Training Building in Cross Lanes, WV 25313, newest first.
File Type Posted
Amendment_0001_to_Solicitation_W15QKN-18-Q-1120_Released.pdf PDF
WV006-Cross_Lanes-C9-CSS_9035-Schedule_PNL_E-Replace_Circuit_Breakers.xlsx XLSX spreadsheet
WV006-Cross_Lanes-C9-CSS_9035-Schedule_PNL_J-Replace_Circuit_Breakers.xlsx XLSX spreadsheet
WV006-Cross_Lanes-C9-CSS_9035-Second_Floor_Lighting_Plan.pdf PDF
WV006-Cross_Lanes-C9-CSS_9035-First_Floor_Power_Plan.pdf PDF
Solicitation_W15QKN-18-Q-1120_SF1442_Released.pdf PDF
WV006-Cross_Lanes-C9-CSS_9035-Schedule_PNL_G-Replace_Circuit_Breakers.xlsx XLSX spreadsheet
WV006-Cross_Lanes-C9-CSS_9035-Schedule_PNL_D-Replace_Circuit_Breakers.xlsx XLSX spreadsheet
WV006-Cross_Lanes-C9-CSS_9035-First_Floor_Lighting_Plan.pdf PDF
WV006-Cross_Lanes-C9-CSS_9035-Schedule_PNL_A-Replace_Circuit_Breakers.xlsx XLSX spreadsheet
WV006-Cross_Lanes-C9-CSS_9035-Schedule_PNL_L-Replace_Circuit_Breakers.xlsx XLSX spreadsheet
WV006-Cross_Lanes-C9-CSS_9035-Schedule_PNL_H-Replace_Circuit_Breakers.xlsx XLSX spreadsheet
WV006-Cross_Lanes-C9-CSS_9035-Schedule_PNL_K-Replace_Circuit_Breakers.xlsx XLSX spreadsheet
WV006-Cross_Lanes-C9-CSS_9035-Second_Floor_Power_Plan.pdf PDF
WV006-Cross_Lanes-C9-CSS_9035-Schedule_PNL_F-Replace_Circuit_Breakers.xlsx XLSX spreadsheet
WV006-Cross_Lanes-C9-CSS_9035-Schedule_PNL_C-Replace_Circuit_Breakers.xlsx XLSX spreadsheet
WV006-Cross_Lanes-C9-CSS_9035-SOW-Replace_Circuit_Breakers.doc DOC document
Show all 17

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

Panel B
3 Phase 4 wire 225A 120V/208V MLO8/30/17
Circuit #Description:PoleAmpABCPoleAmpDescription:Circuit #
1Rm.134,137,138,141 Lts120A26.42120ARm.131,129,130,132 Lts2
3Room 127 Lights120A37.44120ARm.125,126,129 Lts4
5Rm. 142, 143 Lights120A29.4120ARm.126,146,147,148 Lts6
7Room 145 Lights120A25.76120ARm.133,149,150,153 Lts8
9Rm. 157, 158, 159 Lights120A19.05120A GFIRm. 127, 128 Rec.10
11Rm. 125, 127 Rec.120A27120ARm. 129, 131 Rec.12
13Rm. 130, 132 Rec.120A24120ARm. 132, 133 Rec.14
15Rm. 134, 137, 138 Rec.120A23.08120A GFIRm. 134, 141 Rec.16
17Rm. 138, 140, 141 Rec.120A GFI19.4120ACorridor 126 EWC18
19Corridor 126 Rec.120A15120A GFIRm. 154, 156 Rec.20
21EF-15 Room 158120A7.2120A GFIRm. 154, 156 Rec. CH-122
23EF-18 Room 153120A12.65120ARm. 153, 149, 152 Rec.24
25Room 149, 152 Rec.120A25.15120ARm. 145, 148 Rec26
27Room 146, 149 Rec.120A24120ARm.142,124,142,143Rec28
29Rm.124,121,143,144Rec120A24120ASee Note 1 Below30
31Spare120A120ARm. 127, 128 Rec.32
33Spare120A115ASpare34
35Spare120A115ASpare36
Totals:116.33110.77112.45
Min. AIC Rating 10,000 RMS SYMMETRICAL.

Note 1: Rooms 142, 143, 148, 145, 149 Rec.

File details come from the government source that posted it.