Vertiv_UPS_and_CRV_Units_for_Data_Center_Expansions.docx
DOCX document 18 KB Posted
- Attached to
- Data Centers HVAC and UPS State and local contract opportunity
- Solicitation number
- 2024-IFB-117
- Issued by
- New Haven County, Connecticut
About this file
This document is a detailed specification for HVAC and UPS equipment procurement for two data center expansion projects for the City of New Haven, Connecticut. The project involves supplying equipment for two locations: One Union Ave Data Center and Wintergreen Data Center. For each site, the procurement includes two Liebert CRV Air-Cooled Cooling Systems and one 40kVA/40kW Liebert EXM UPS System. The cooling systems feature 35kW capacity, 208 voltage, 3-phase configuration, advanced control systems, temperature sensors, variable speed fans, and comprehensive monitoring capabilities. The UPS systems offer 40kW capacity with redundant power modules, ethernet/SNMP monitoring, internal battery systems, and external maintenance bypass cabinets.
The contract specifies detailed technical requirements with no substitute items permitted, and includes comprehensive services such as factory testing, certified test reports, on-site startup services, and freight delivery to New Haven, CT. The equipment is precisely configured for data center environments, with specific features like digital scroll compressors, steam generating humidifiers, leak detection sensors, and battery systems providing 9-14 minutes of backup power depending on load. Pricing and funding specifics are not explicitly detailed in the document, but the procurement appears to be a targeted expansion of the city's data center infrastructure with carefully selected, specialized equipment from Vertiv designed to meet specific technical and operational requirements.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| Data_Centers_HVAC_and_UPS.pdf | ||
| Data_Centers_Expansion_-_HVAC_and_UPS_Part_List.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
One Union Ave Data Center:
1. Two (2) Liebert CRV Air-Cooled Cooling System, with the following features:
1. Nominal 35kW, 120 kBtuh at approximately 90F, 27% RH
1. 208 Voltage, 3 Phase, 60 Hz
1. Condensate Pump 65k SCCR
1. Liebert iCOM control system with 9” Color Touch Display
1. 2T temperature sensors to measure air temperature entering server racks
1. Variable speed EC plug fans
1. Digital scroll, variable capacity compressor
1. Electric Reheat
1. Steam Generating Humidifier
1. Locking Disconnect Switch
1. Liebert IntelliSlot Unity Monitoring Card
1. (1) LT460-Z20 Zone Leak Detection Sensor
1. Unit to be located within a row of heat generating IT equipment racks.
1. Liebert MC Air-Cooled Microchannel Condenser
1. Warranty Inspection / Supervised Start Up Services during normal business hours 8x5
1. Freight included to New Haven, CT
1. One (1) 40kVA / 40kW Liebert EXM UPS System, with the following features:
1. 40kW Capacity using 20kW power modules (20kW +1 Redundant when load is less than 20kW)
1. System input and output = 208/120V, 4W+G
1. Monitoring Cards for ethernet/SNMP/Modbus/Bacnet/Output Dry Contacts
1. 9 Minute battery system at full 40kW load and 22 minutes at 20kW load. Batteries are standard 12V VRLA type, internal to UPS cabinet to save on floor space, with isolation breaker
1. External Maintenance Bypass Cabinet – 3-Breaker with SKRU (Key Interlock), mounted to side of UPS cabinet
1. Factory Testing with Certified Test Reports
1. On Site Start Up Services, scheduled 7x24, by manufacturers technician
1. Freight included to New Haven, CT
1. Wintergreen Data Center:
1. Two (2) Liebert CRV Air-Cooled Cooling System, with the following features:
1. Nominal 35kW, 120 kBtuh at approximately 90F, 27% RH
1. 208 Voltage, 3 Phase, 60 Hz
1. Condensate Pump 65k SCCR
1. Liebert iCOM control system with 9” Color Touch Display
1. 2T temperature sensors to measure air temperature entering server racks
1. Variable speed EC plug fans
1. Digital scroll, variable capacity compressor
1. Electric Reheat
1. Steam Generating Humidifier
1. Locking Disconnect Switch
1. Liebert IntelliSlot Unity Monitoring Card
1. (1) LT460-Z20 Zone Leak Detection Sensor
1. Unit to be located within a row of heat generating IT equipment racks.
1. Liebert MC Air-Cooled Microchannel Condenser
1. Warranty Inspection / Supervised Start Up Services during normal business hours 8x5
1. Freight included to New Haven, CT
1. One (1) 40kVA / 40kW Liebert EXM UPS System, with the following features:
1. 40kW Capacity using 20kW power modules (Field Scalable to 60kW total capacity)
1. System input and output = 208/120V, 4W+G
1. Monitoring Cards for ethernet/SNMP/Modbus/Bacnet/Output Dry Contacts
1. 14 Minute battery system at full 40kW load (7 Minutes @ Future 60kW Load). Batteries are standard 12V VRLA type, external in matching battery cabinet
1. External Maintenance Bypass Cabinet – 3-Breaker with SKRU (Key Interlock), mounted to side of UPS cabinet
1. Factory Testing with Certified Test Reports
1. On Site Start Up Services, scheduled 7x24, by manufacturers technician
1. Freight included to New Haven, CT