VAV IP 01422-1MH612z.pdf

PDF 410 KB Posted

Attached to
Z2DA--CFM - Rebalance HVAC System Federal contract opportunity
Solicitation number
36C256
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--CFM - Rebalance HVAC System, newest first.
File Type Posted
AHU capacitiesz.pdf PDF
INP L03z.pdf PDF
230593 Testing Adjusting and Balancing for HVAC 7 22 20.pdf PDF
DNT L05 Fz.pdf PDF
DNT L03i D-Ez.pdf PDF
DNT L03 F-Gz.pdf PDF
OUT L01 Hz.pdf PDF
DNT L05 Gz.pdf PDF
INP L02z.pdf PDF
CEP L03z.pdf PDF
DNT L03 D-Ez.pdf PDF
Campus AMS inventory 06262020z.pdf PDF
DNT L02i F-Gz.pdf PDF
TLR L03z.pdf PDF
TLR L01z.pdf PDF
TLR L05z.pdf PDF
DNT L01 F-Gz.pdf PDF
13 Results.docx DOCX document
DNT L03i F-Gz.pdf PDF
TLR L04z.pdf PDF
OUT L01 J2z.pdf PDF
DNT L02i D-E.pdf PDF
VAV OP 03038-3MH615z.pdf PDF
DNT L04 D-Ez.pdf PDF
RESEARCH East Mechanicalz.pdf PDF
VAV CEP 120-7MH613z.pdf PDF
230923 DDC Control Revised 7 24 20.pdf PDF
DNT L02i D-Ez.pdf PDF
VAV DNT 02302-2MH627z.pdf PDF
TLR L02z.pdf PDF
DNT L04i F-Gz.pdf PDF
INP L01z.pdf PDF
VAV DNT 02301-2MH626z.pdf PDF
OUT L01 J1z.pdf PDF
DNT L02 F-Gz.pdf PDF
S06- Amendment- 0002.pdf PDF
DNT L01i D-Ez.pdf PDF
Site Plan-AIR HANDLERS LOCATIONSz.pdf PDF
DNT L04 F-Gz.pdf PDF
Existing Ceiling Grille Inventoryz.pdf PDF
RESEARCH West Mechanicalz.pdf PDF
DNT L05 Dz.pdf PDF
VAV IP 01421-1MH611z.pdf PDF
Show all 43

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES:

1. REFER TO DRAWING MH603 AND 604 FOR

TERMINAL UNIT SCHEDULES.

2. REFER TO DRAWINGS MH608 AND

MH609 FOR FCU AND CAC UNIT SCHEDULE.

3. REQUIRES EMERGENCY POWER.

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

1MH612

BLDG 1 HVAC TERMINAL UNIT AND FAN COIL

UNIT SCHEDULE

KJS DCDFebruary 29, 2012

01629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE

ARCHITECTURAL ENGINEERING/ PLUMBING

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT

I.S.C. GROUP, INC./ IRRIGATION

DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE

Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

WP_08

CONSTRUCTION DOCUMENTS 1

FULLY SPRINKLERED

SUPPLY TERMINAL UNIT SCHEDULE � THIRD FLOOR AREA B1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 3B120 01 3B1 B2 325 CFM 175 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 2 3B C02 01 3B1 D2 800 CFM 800 1.5 CV DETAIL 1/MH821 NOTE (1)

S 3 3B114 01 3B1 A3 250 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 4 01 3B1 B2 350 CFM 350 0.75 CV DETAIL 3/MH821 NOTE (1)

S 5 3B C05 01 3B1 B3 300 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 6 3B C05 01 3B1 A3 150 CFM 100 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 7 3B105 01 3B1 D2 800 CFM 800 1.5 CV DETAIL 1/MH821 NOTE (1)

S 8 01 3B1 D3 875 CFM 425 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 9 3B104 01 3B1 B3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 10 3B102 01 3B1 D2 900 CFM 200 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 11 3B103 01 3B1 C2 600 CFM 300 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 12 3B118 01 3B1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 13 3B118 01 3B1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 14 3B C03 01 3B1 C3 550 CFM 550 1.0 CV DETAIL 2/MH821 NOTE (1)

S 15 3B C03 01 3B1 E2 1050 CFM 1050 2.0 CV DETAIL 1/MH821 NOTE (1)

S 16 3B C03 01 3B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 17 3B C03 01 3B1 C3 550 CFM 550 1.0 CV DETAIL 2/MH821 NOTE (1)

S 18 3B C03 01 3B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 19 3B C03 01 3B1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 20 3B C03 01 3B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 21 3B C03 01 3B1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 22 3B C03 01 3B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 23 3B C03 01 3B1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 24 3B C03 01 3B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 25 3B C03 01 3B1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 26 3B C03 01 3B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

EXHAUST TERMINAL UNIT SCHEDULE � THIRD FLOOR B1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

E 1 3B C02 01 3B1 D3 750 CFM 750 CV DETAIL 2/MH821 NOTE (1)

E 2 3B C02 01 3B1 D3 750 CFM 750 CV DETAIL 2/MH821 NOTE (1)

FAN COIL UNIT SCHEDULE � THIRD FLOOR B1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC 1 3B114 01 3B1 E NOTE (2),(3)

CAC 2 3B155B 01 3B1 D NOTE (2),(3)

FCU 1 01 3B1 4F4 DETAIL 2/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE � THIRD FLOOR AREA B2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 3B C03 01 3B2 E2 1200 CFM 1200 2.25 CV DETAIL 1/MH821 NOTE (1)

S 2 3B C03 01 3B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 3 3B C03 01 3B2 A3 200 CFM 200 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 4 3B C03 01 3B2 B2 350 CFM 350 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 5 3B C03 01 3B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 6 3B C03 01 3B2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 7 3B C03 01 3B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 8 3B C03 01 3B2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 9 3B C03 01 3B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 10 3B C03 01 3B2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 11 3B C03 01 3B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 12 3B C03 01 3B2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 13 3B C03 01 3B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 14 3B C03 01 3B2 B2 300 CFM 300 0.5 CV DETAIL 1/MH821 NOTE (1)

S 15 3B C03 01 3B2 C3 650 CFM 650 1.25 CV DETAIL 2/MH821 NOTE (1)

S 16 3B C03 01 3B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 17 3B166 01 3B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

SUPPLY TERMINAL UNIT SCHEDULE � THIRD FLOOR AREA C1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 3B227 01 3C1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 2 3C C04A 01 3C1 B2 400 CFM 400 0.75 CV DETAIL 1/MH821 NOTE (1)

S 3 3C C04A 01 3C1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 4 3C C04A 01 3C1 C3 550 CFM 550 1.0 CV DETAIL 1/MH821 NOTE (1)

S 5 3C117 01 3C1 B2 375 CFM 225 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 6 3C C04A 01 3C1 C1 500 CFM 500 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 7 3C123 01 3C1 A3 200 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 8 01 3C1 A3 125 CFM 125 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 9 3C102 01 3C1 D1 900 CFM 450 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 10 3C102 01 3C1 B2 350 CFM 350 0.75 CV DETAIL 1/MH821 NOTE (1)

S 11 3C102 01 3C1 B3 275 CFM 175 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 12 3C103 01 3C1 D2 750 CFM 750 1.5 CV DETAIL 1/MH821 NOTE (1)

S 13 3C230 01 3C1 B3 375 CFM 200 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 14 3C C02 1 01 3C1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 15 3C C02 1 01 3C1 C3 650 CFM 650 1.25 CV DETAIL 2/MH821 NOTE (1)

S 16 3C C02 1 01 3C1 E2 1400 CFM 1400 2.5 CV DETAIL 1/MH821 NOTE (1)

S 17 3C C02 1 01 3C1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 18 3C C02 1 01 3C1 C3 650 CFM 650 1.25 CV DETAIL 2/MH821 NOTE (1)

S 19 3C C02 1 01 3C1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 20 3C C02 1 01 3C1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 21 3C C02 1 01 3C1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 22 3C C02 1 01 3C1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 23 3C C02 1 01 3C1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 24 3C C02 1 01 3C1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 25 01 3C1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 26 3C C02 1 01 3C1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

EXHAUST TERMINAL UNIT SCHEDULE � THIRD FLOOR C1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

E 1 3C C06 01 3C1 D3 850 CFM 850 CV DETAIL 2/MH821 NOTE (1)

E 2 3C C06 01 3C1 D3 100 CFM 850 CV DETAIL 2/MH821 NOTE (1)

FAN COIL UNIT SCHEDULE � THIRD FLOOR C1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC 1 3C125 01 3C1 E NOTE (2),(3)

CAC 2 3C152E 01 3C1 D NOTE (2),(3)

FCU 1 01 3C1 4F4 DETAIL 2/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE � THIRD FLOOR AREA C2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 3C C02 1 01 3C2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 2 3C C02 1 01 3C2 B2 350 CFM 350 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 3 3C C02 1 01 3C2 A3 200 CFM 100 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 4 3C C02 1 01 3C2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 5 3C C02 1 01 3C2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 6 3C C02 1 01 3C2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 7 3C C02 1 01 3C2 D2 825 CFM 825 1.5 CV DETAIL 1/MH821 NOTE (1)

S 8 3C C02 1 01 3C2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 9 3C C02 1 01 3C2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 10 3C C02 1 01 3C2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 11 3C C02 1 01 3C2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 12 3C C02 1 01 3C2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 13 3C C02 1 01 3C2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 14 3C C02 1 01 3C2 C3 650 CFM 650 1.25 CV DETAIL 2/MH821 NOTE (1)

S 15 3C C02 1 01 3C2 B2 275 CFM 275 0.5 CV DETAIL 1/MH821 NOTE (1)

S 16 3C C02 1 01 3C2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 17 3C166 01 3C2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

EXHAUST TERMINAL UNIT SCHEDULE � FOURTH FLOOR B1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

E 1 4B C02 01 4B1 C3 750 CFM 750 CV DETAIL 2/MH821 NOTE (1)

E 2 4B C02 01 4B1 D3 750 CFM 750 CV DETAIL 2/MH821 NOTE (1)

FAN COIL UNIT SCHEDULE � FOURTH FLOOR B1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC 1 4B116 01 4B1 E NOTE (2),(3)

FCU 1 01 4B1 4F4 DETAIL 2/MH820 NOTE (2)

FCU 2 STB 1 3 01 4B1 4C1 DETAIL 2/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE � FOURTH FLOOR AREA B2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 4BC03 01 4B2 E2 1200 CFM 1200 2.25 CV DETAIL 1/MH821 NOTE (1)

S 2 4BC03 01 4B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 3 4BC03 01 4B2 A3 200 CFM 100 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 4 4BC03 01 4B2 B2 350 CFM 175 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 5 4BC03 01 4B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 6 4BC03 01 4B2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 7 4BC03 01 4B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 8 4BC03 01 4B2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 9 4BC03 01 4B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 10 4BC03 01 4B2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 11 4BC03 01 4B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 12 4BC03 01 4B2 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 13 4BC03 01 4B2 C2 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 14 4BC03 01 4B2 C3 650 CFM 650 1.25 CV DETAIL 2/MH821 NOTE (1)

S 15 4BC03 01 4B2 B2 300 CFM 300 0.5 CV DETAIL 1/MH821 NOTE (1)

S 16 4BC03 01 4B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 17 4B166 01 4B2 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

SUPPLY TERMINAL UNIT SCHEDULE � FOURTH FLOOR AREA C1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 4C C02 01 4C1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 2 4C C02 01 4C1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 3 4C C02 01 4C1 C2 450 CFM 450 1.0 CV DETAIL 1/MH821 NOTE (1)

S 4 4C C04 01 4C1 D2 900 CFM 900 1.75 CV DETAIL 1/MH821 NOTE (1)

S 5 4C122B 01 4C1 A3 250 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 6 4C126 01 4C1 B3 300 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 7 4C126 01 4C1 B3 375 CFM 375 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 8 4C C04 01 4C1 B3 300 CFM 150 0.5 CV DETAIL 2/MH821 NOTE (1)

S 9 4C110 01 4C1 B2 350 CFM 200 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 10 4C110 01 4C1 C2 500 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 11 4C C05 01 4C1 A2 150 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 12 4C138 01 4C1 C1 625 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 13 4C106 01 4C1 A3 125 CFM 125 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 14 4C104 01 4C1 A3 125 CFM 125 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 15 4C C06 01 4C1 A2 150 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 16 4C107 01 4C1 A3 125 CFM 125 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 17 4C105 01 4C1 A3 125 CFM 125 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 18 01 4C1 A3 125 CFM 125 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 19 4C103 01 4C1 A3 125 CFM 125 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 20 4C102 01 4C1 B1 400 CFM 400 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 21 4B C01 01 4C1 B2 450 CFM 450 1.0 CV DETAIL 1/MH821 NOTE (1)

FAN COIL UNIT SCHEDULE � FOURTH FLOOR C1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

CAC 1 4C C02 01 4C1 E NOTE (2),(3)

FCU 1 01 4C1 4F4 DETAIL 2/MH820 NOTE (2)

FCU 2 STC 4 3 01 4C1 4C3 DETAIL 2/MH820 NOTE (2)

FAN COIL UNIT SCHEDULE � FIFTH FLOOR B1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU 1 01 5B1 4F7 DETAIL 2/MH820 NOTE (2)

FCU 2 01 5B1 4F7 DETAIL 2/MH820 NOTE (2)

FCU 3 01 5B1 4F7 DETAIL 2/MH820 NOTE (2)

FAN COIL UNIT SCHEDULE � FIFTH FLOOR C1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU 1 01 5C1 2D2 DETAIL 1/MH820 NOTE (2)

FCU 2 01 5C1 2H8 DETAIL 1/MH820 NOTE (2)

FCU 3 01 5C1 2H8 DETAIL 1/MH820 NOTE (2)

FCU 4 01 5C1 4F4 DETAIL 2/MH820 NOTE (2)

FCU 5 01 5C1 4F4 DETAIL 2/MH820 NOTE (2)

FCU 6 01 5C1 4F4 DETAIL 2/MH820 NOTE (2)

FCU 7 01 5C1 4F4 DETAIL 2/MH820 NOTE (2)

FCU 8 01 5C1 4F4 DETAIL 2/MH820 NOTE (2)

SUPPLY TERMINAL UNIT SCHEDULE � FOURTH FLOOR AREA B1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S 1 4B120 01 4B1 B2 425 CFM 425 1.0 VCV DETAIL 3/MH821 NOTE (1)

S 2 4B C02 01 4B1 D2 800 CFM 800 1.5 CV DETAIL 1/MH821 NOTE (1)

S 3 4B116 01 4B1 A3 250 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 4 01 4B1 D2 800 CFM 400 0.7 VCV DETAIL 3/MH821 NOTE (1)

S 5 4B111 01 4B1 B2 350 CFM 350 0.75 CV DETAIL 1/MH821 NOTE (1)

S 6 4B C05 01 4B1 C3 425 CFM 225 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 7 4B104 01 4B1 C3 650 CFM 650 1.25 CV DETAIL 1/MH821 NOTE (1)

S 8 4B106 01 4B1 C3 625 CFM 150 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 9 4B106 01 4B1 C3 600 CFM 300 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 10 4B C01 01 4B1 D3 675 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 11 4B103 01 4B1 C2 600 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 12 4B107 01 4B1 E2 1150 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 13 4B C01 01 4B1 D2 900 CFM 900 1.75 CV DETAIL 1/MH821 NOTE (1)

S 14 4B118 01 4B1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 15 4B118 01 4B1 B1 300 CFM 300 CV DETAIL 5/MH821 NOTE (1)

S 16 4BC03 01 4B1 C3 550 CFM 550 1.0 CV DETAIL 2/MH821 NOTE (1)

S 17 4BC03 01 4B1 E2 1050 CFM 1050 2.0 CV DETAIL 1/MH821 NOTE (1)

S 18 4BC03 01 4B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 19 4BC03 01 4B1 C3 550 CFM 550 1.0 CV DETAIL 2/MH821 NOTE (1)

S 20 4BC03 01 4B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 21 4BC03 01 4B1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 22 4BC03 01 4B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 23 4BC03 01 4B1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 24 4BC03 01 4B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 25 4BC03 01 4B1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 26 4BC03 01 4B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

S 27 4BC03 01 4B1 C3 550 CFM 250 0.5 VCV DETAIL 3/MH821 NOTE (1)

S 28 4BC03 01 4B1 C3 650 CFM 325 0.75 VCV DETAIL 3/MH821 NOTE (1)

EXHAUST TERMINAL UNIT SCHEDULE � THIRD FLOOR B2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

E 1 3B C03 01 3B2 A3 250 CFM 250 CV DETAIL 2/MH821 NOTE (1)

EXHAUST TERMINAL UNIT SCHEDULE � THIRD FLOOR C2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

E 1 3C C02 1 01 3C2 A3 250 CFM 250 CV DETAIL 2/MH821 NOTE (1)

EXHAUST TERMINAL UNIT SCHEDULE � FOURTH FLOOR B2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

E 1 4BC03 01 4B2 A3 250 CFM 250 CV DETAIL 2/MH821 NOTE (1)

EXHAUST TERMINAL UNIT SCHEDULE � FOURTH FLOOR C1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

E 1 4C C04 01 4C1 C3 500 CFM 500 CV DETAIL 2/MH821 NOTE (1)

FAN COIL UNIT SCHEDULE � FIFTH FLOOR B1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU 1 01 5B1 4F7 DETAIL 2/MH820 NOTE (2)

FCU 2 01 5B1 4F7 DETAIL 2/MH820 NOTE (2)

FCU 3 01 5B1 4F7 DETAIL 2/MH820 NOTE (2)

FAN COIL UNIT SCHEDULE � FIFTH FLOOR C1

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU 1 01 5C1 2D2 DETAIL 1/MH820 NOTE (2)

FCU 2 01 5C1 2H8 DETAIL 1/MH820 NOTE (2)

FCU 3 01 5C1 2H8 DETAIL 1/MH820 NOTE (2)

FCU 4 01 5C1 4F4 DETAIL 2/MH820 NOTE (2)

FCU 5 01 5C1 4F4 DETAIL 2/MH820 NOTE (2)

FCU 6 01 5C1 4F4 DETAIL 2/MH820 NOTE (2)

FCU 7 01 5C1 4F4 DETAIL 2/MH820 NOTE (2)

FCU 8 01 5C1 4F4 DETAIL 2/MH820 NOTE (2)

FAN COIL UNIT SCHEDULE � THIRD FLOOR B2

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE

CONTROL

TYPE CONTROL SEQUENCE Remarks

FCU 1 STB 2 3 01 3B2 4C2 DETAIL 2/MH820 NOTE (2)

REFER TO SKETCH:

SK-8-1-NJ-1-MH-612-1

RFI 01615