VAV CEP 120-7MH613z.pdf

PDF 154 KB Posted

Attached to
Z2DA--CFM - Rebalance HVAC System Federal contract opportunity
Solicitation number
36C256
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--CFM - Rebalance HVAC System, newest first.
File Type Posted
DNT L02i F-Gz.pdf PDF
TLR L03z.pdf PDF
TLR L01z.pdf PDF
TLR L05z.pdf PDF
DNT L01 F-Gz.pdf PDF
13 Results.docx DOCX document
DNT L03i F-Gz.pdf PDF
TLR L04z.pdf PDF
OUT L01 J2z.pdf PDF
DNT L02i D-E.pdf PDF
VAV OP 03038-3MH615z.pdf PDF
DNT L04 D-Ez.pdf PDF
RESEARCH East Mechanicalz.pdf PDF
AHU capacitiesz.pdf PDF
INP L03z.pdf PDF
230593 Testing Adjusting and Balancing for HVAC 7 22 20.pdf PDF
DNT L05 Fz.pdf PDF
DNT L03i D-Ez.pdf PDF
DNT L03 F-Gz.pdf PDF
OUT L01 Hz.pdf PDF
DNT L05 Gz.pdf PDF
VAV IP 01422-1MH612z.pdf PDF
INP L02z.pdf PDF
CEP L03z.pdf PDF
DNT L03 D-Ez.pdf PDF
Campus AMS inventory 06262020z.pdf PDF
230923 DDC Control Revised 7 24 20.pdf PDF
DNT L02i D-Ez.pdf PDF
VAV DNT 02302-2MH627z.pdf PDF
TLR L02z.pdf PDF
DNT L04i F-Gz.pdf PDF
INP L01z.pdf PDF
VAV DNT 02301-2MH626z.pdf PDF
OUT L01 J1z.pdf PDF
DNT L02 F-Gz.pdf PDF
S06- Amendment- 0002.pdf PDF
DNT L01i D-Ez.pdf PDF
Site Plan-AIR HANDLERS LOCATIONSz.pdf PDF
DNT L04 F-Gz.pdf PDF
Existing Ceiling Grille Inventoryz.pdf PDF
RESEARCH West Mechanicalz.pdf PDF
DNT L05 Dz.pdf PDF
VAV IP 01421-1MH611z.pdf PDF
Show all 43

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

7MH613

BLDG 07 HVAC SINGLE DUCT AIR TERMINAL

UNIT SCHEDULE

KJS PDHOctober 31,2011

07629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

EWP-07

CONSTRUCTION DOCUMENTS 1

SUPPLY � SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (Area 1N1)

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 07�1N1 E1 1250 CFM 1250 2.0 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�2 07�1N1 H1 2500 CFM 2500 4.1 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�3 07�1N1 C1 450 CFM 0 0 VV DETAIL 5 ON 7MH812 NO COIL/ATTENUATOR

S�4 07�1N1 E2 1200 CFM 1200 1.9 CV DETAIL 5 ON 7MH812

S�5 07�1N1 F1 1600 CFM 1600 2.6 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�6 07�1N1 D2 700 CFM 350 VCV DETAIL 5 ON 7MH812

S�7 07�1N1 C1 550 CFM 550 0.9 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�8 07�1N1 H1 2400 CFM 1950 3.2 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�9 07�1N1 E1 1100 CFM 1100 1.8 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�10 07�1N1 E1 1100 CFM 1100 1.8 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�11 07�1N1 A1 150 CFM 150 0.5 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�12 07�1N1 E2 1050 CFM 1050 1.7 CV DETAIL 5 ON 7MH812

SUPPLY � SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (Area 1N2)

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 07�1N2 G2 1900 CFM 600 1.0 VCV DETAIL 6 ON 7MH812

S�2 07�1N2 H1 2400 CFM 1200 1.9 VCV DETAIL 6 ON 7MH812 NO ATTENUATOR

S�3 07�1N2 G2 1725 CFM 600 1.0 VCV DETAIL 6 ON 7MH812

S�4 07�1N2 E2 1040 CFM 1040 1.7 CV DETAIL 5 ON 7MH812

S�5 07�1N2 C2 630 CFM 630 1.0 CV DETAIL 5 ON 7MH812

S�6 07�1N2 C2 550 CFM 550 0.9 CV DETAIL 5 ON 7MH812

S�7 07�1N2 G1 2000 CFM 1000 1.6 VCV DETAIL 6 ON 7MH812 NO ATTENUATOR

S�8 07�1N2 F1 1600 CFM 800 1.3 VCV DETAIL 6 ON 7MH812 NO ATTENUATOR

S�9 07�1N2 G1 1000 1.6 VCV DETAIL 6 ON 7MH812 NO ATTENUATOR

S�10 07�1N2 F1 827 1.3 VCV DETAIL 6 ON 7MH812 NO ATTENUATOR

S�11 07�1N2 G2 2300 CFM 600 1.0 VCV DETAIL 6 ON 7MH812

S�12 07�1N2 C1 1900 CFM 600 1.0 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

SUPPLY � SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (Area 2N1)

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 07�2N1 D2 800 CFM 800 1.3 CV DETAIL 5 ON 7MH812

S�2 07�2N1 B2 300 CFM 300 0.5 CV DETAIL 5 ON 7MH812

S�3 07�2N1 D2 925 CFM 925 1.5 CV DETAIL 5 ON 7MH812

S�4 07�2N1 E2 1000 CFM 1000 1.6 CV DETAIL 5 ON 7MH812

S�5 07�2N1 B2 300 CFM 300 0.5 CV DETAIL 5 ON 7MH812

S�6 07�2N1 B2 200 CFM 200 0.5 CV DETAIL 5 ON 7MH812

S�7 07�2N1 D2 925 CFM 925 1.5 CV DETAIL 5 ON 7MH812

S�8 07�2N1 F2 1500 CFM 750 1.2 VCV DETAIL 6 ON 7MH812

S�9 07�2N1 C2 500 CFM 500 0.8 CV DETAIL 5 ON 7MH812

S�10 07�2N1 G2 2000 CFM 1000 1.6 VCV DETAIL 6 ON 7MH812

S�11 07�2N1 C2 450 CFM 450 0.7 CV DETAIL 5 ON 7MH812

S�12 07�2N1 C2 600 CFM 600 1.0 CV DETAIL 5 ON 7MH812

S�13 07�2N1 C1 0 0 VV DETAIL 6 ON 7MH812 NO COIL/ATTENUATOR

SUPPLY � SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (Area 2N2)

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 07�2N2 F2 1500 CFM 500 0.8 VCV DETAIL 6 ON 7MH812

S�2 07�2N2 D2 825 CFM 825 1.3 CV DETAIL 5 ON 7MH812

S�3 07�2N2 C2 675 CFM 525 0.9 CV DETAIL 5 ON 7MH812

S�4 07�2N2 F1 1500 CFM 0 0 VV DETAIL 6 ON 7MH812 NO COIL/ATTENUATOR

S�5 07�2N2 G1 2000 CFM 2000 3.2 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�6 07�2N2 E1 1400 CFM 500 0.8 VCV DETAIL 6 ON 7MH812 NO ATTENUATOR

S�7 07�2N2 E2 1100 CFM 550 0.9 CV DETAIL 5 ON 7MH812

S�8 07�2N2 B1 400 CFM 0 0 VV DETAIL 6 ON 7MH812 NO COIL/ATTENUATOR

SUPPLY � SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (Area 3.5N2)

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 07�3.5N2 G2 1800 CFM 600 1.0 VCV DETAIL 6 ON 7MH812

S�2 07�3.5N2 H2 3200 CFM 3200 5.2 CV DETAIL 5 ON 7MH812

S�3 07�3.5N2 G2 1800 CFM 600 1.0 VCV DETAIL 6 ON 7MH812

S�4 07�3.5N2 C2 450 CFM 450 0.7 CV DETAIL 5 ON 7MH812

S�5 07�3.5N2 G2 1800 CFM 600 1.0 VCV DETAIL 6 ON 7MH812

SUPPLY � SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (Area 3N1)

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 07�3N1 C2 600 CFM 300 0.5 VCV DETAIL 6 ON 7MH812

S�2 07�3N1 C2 450 CFM 450 0.7 CV DETAIL 5 ON 7MH812

S�3 07�3N1 B2 300 CFM 150 0.5 VCV DETAIL 6 ON 7MH812

S�4 07�3N1 D2 750 CFM 375 0.6 VCV DETAIL 6 ON 7MH812

S�5 07�3N1 B2 325 CFM 200 0.5 VCV DETAIL 6 ON 7MH812

S�6 07�3N1 C2 425 CFM 475 0.8 CV DETAIL 6 ON 7MH812

S�7 07�3N1 B2 400 CFM 200 1.5 VCV DETAIL 6 ON 7MH812

S�8 07�3N1 D2 700 CFM 350 0.6 VCV DETAIL 6 ON 7MH812

S�9 07�3N1 C2 525 CFM 300 0.5 VCV DETAIL 6 ON 7MH812

S�10 07�3N1 D2 900 CFM 900 1.6 CV DETAIL 5 ON 7MH812

S�11 07�3N1 D2 750 CFM 375 0.6 VCV DETAIL 6 ON 7MH812

S�12 07�3N1 C1 450 CFM 0 0 VV DETAIL 6 ON 7MH812 NO COIL/ATTENUATOR

SUPPLY � SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (Area 4N1)

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 4N111 07�4N1 E2 1100 CFM 1100 1.8 CV DETAIL 5 ON 7MH812

S�2 4N111 07�4N1 G2 2000 CFM 1000 1.6 VCV DETAIL 6 ON 7MH812

S�3 4N111 07�4N1 D2 700 CFM 700 1.1 CV DETAIL 5 ON 7MH812

S�4 07�4N1 G2 2000 CFM 1000 1.6 VCV DETAIL 6 ON 7MH812

S�5 07�4N1 F2 1500 CFM 750 1.2 VCV DETAIL 6 ON 7MH812

S�6 07�4N1 E2 1000 CFM 625 1.0 VCV DETAIL 6 ON 7MH812

S�7 07�4N1 C1 450 CFM 0 0 VV DETAIL 6 ON 7MH812 NO COIL/ATTENUATOR

S�8 07�4N1 B2 300 CFM 150 0.5 VCV DETAIL 6 ON 7MH812

S�9 07�4N1 C2 500 CFM 250 0.5 VCV DETAIL 6 ON 7MH812

S�10 07�4N1 B2 200 CFM 200 0.5 CV DETAIL 5 ON 7MH812

GENERAL NOTES:

1. FOR SYMBOL LISTS, ABBREVIATIONS, AND GENERAL

NOTES THAT APPLY TO ALL DRAWINGS SEE THE

7MH�0 SERIES OF DRAWINGS.

2. FOR GENERAL DETAILS SEE THE 7MH�5 SERIES OF

DRAWINGS.

3. FOR CONTROL DIAGRAMS SEE THE 7MH�8 SERIES OF

DRAWINGS.

NOTE: (1) FOR GENERAL TERMINAL BOX SCHEDULE DRAWING 7MH612

(2) REFER TO DRAWING 7MH607

NOTE: (1) FOR GENERAL TERMINAL BOX SCHEDULE DRAWING 7MH612

(2) REFER TO DRAWING 7MH607

NOTE: (1) FOR GENERAL TERMINAL BOX SCHEDULE DRAWING 7MH612

(2) REFER TO DRAWING 7MH607

NOTE: (1) FOR GENERAL TERMINAL BOX SCHEDULE DRAWING 7MH612

(2) REFER TO DRAWING 7MH607

NOTE: (1) FOR GENERAL TERMINAL BOX SCHEDULE DRAWING 7MH612

(2) REFER TO DRAWING 7MH607

NOTE: (1) FOR GENERAL TERMINAL BOX SCHEDULE DRAWING 7MH612

(2) REFER TO DRAWING 7MH607

NOTE: (1) FOR GENERAL TERMINAL BOX SCHEDULE DRAWING 7MH612

(2) REFER TO DRAWING 7MH607

1 Addendum 1 12/2/11

Pre-bid RFI 088: See Drawing 7MH815

Pre-bid RFI 088: See Drawing 7MH815

Pre-bid RFI 088: See Drawing 7MH815

Pre-bid RFI 088: See Drawing 7MH815

Pre-bid RFI 088: See Drawing 7MH815

Pre-bid RFI 088: See Drawing 7MH815

Pre-bid RFI 088: See Drawing 7MH815

RFI 01856: Provide terminal box size based on the connected air flows shown on the plan drawing. Refer to 7MH612 for terminal box capacity.

RFI 07289.1: VAV S-2 CFM to be readjusted to cover the CFM from deleted VAV on Level 4i (in area A7)

File details come from the government source that posted it. Updated .