VAV CEP 120-7MH613z.pdf

PDF 154 KB Posted

Attached to
Z2DA--CFM - Rebalance HVAC System
Solicitation number
36C256
Issued by

View the file

Other files

File Type Posted
INP L01z.pdf PDF
DNT L05 Dz.pdf PDF
DNT L03i F-Gz.pdf PDF
DNT L02i F-Gz.pdf PDF
RESEARCH West Mechanicalz.pdf PDF
VAV IP 01421-1MH611z.pdf PDF
230923 DDC Control Revised 7 24 20.pdf PDF
CEP L03z.pdf PDF
DNT L03 D-Ez.pdf PDF
INP L03z.pdf PDF
DNT L03i D-Ez.pdf PDF
DNT L02i D-Ez.pdf PDF
TLR L04z.pdf PDF
DNT L01 F-Gz.pdf PDF
VAV OP 03038-3MH615z.pdf PDF
TLR L03z.pdf PDF
TLR L01z.pdf PDF
INP L02z.pdf PDF
AHU capacitiesz.pdf PDF
VAV IP 01422-1MH612z.pdf PDF
Campus AMS inventory 06262020z.pdf PDF
DNT L05 Gz.pdf PDF
RESEARCH East Mechanicalz.pdf PDF
TLR L05z.pdf PDF
VAV DNT 02302-2MH627z.pdf PDF
TLR L02z.pdf PDF
DNT L04i F-Gz.pdf PDF
DNT L05 Fz.pdf PDF
OUT L01 Hz.pdf PDF
DNT L03 F-Gz.pdf PDF
230593 Testing Adjusting and Balancing for HVAC 7 22 20.pdf PDF
13 Results.docx DOCX document
DNT L02i D-E.pdf PDF
OUT L01 J2z.pdf PDF
DNT L04 D-Ez.pdf PDF
DNT L04 F-Gz.pdf PDF
S06- Amendment- 0002.pdf PDF
DNT L02 F-Gz.pdf PDF
DNT L01i D-Ez.pdf PDF
Site Plan-AIR HANDLERS LOCATIONSz.pdf PDF
OUT L01 J1z.pdf PDF
VAV DNT 02301-2MH626z.pdf PDF
Existing Ceiling Grille Inventoryz.pdf PDF
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DATE

LOCATION

CHECKED DRAWN

PROJECT TITLE PROJECT NUMBER

DOCUMENT SET PACKAGE

DRAWING NUMBERAPPROVED: PROJECT DIRECTOR

DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:

REVISIONS: DATE

B

A

D

C

E

VA FORM 08-6231

O N

E

EI

G H

T

IN

C H

O

N E

FO

O

T O

N E

Q U

AR

TE

R

IN

C H

O

N E

FO

O

T O

N E

H A L

F

IN

C H

O

N E

FO

O

T

TH

R

EE

Q U

AR

TE

R S

IN

C

H

O N

E

FO

O T

TH

R

EE

IN

C H

ES

O N

E

FO

O T

O N

E

IN

C H

F

O R

TY

F

E E T

(1

0'

6"

6"

0'

0'

123456

F

B

A

D

C

E

F

O N

E

SI

X T

EE

N

TH

IN

C

H

O N

E

FO

O T

O N

E

AN

D O

N E

H

AL

F

IN

C H

ES

O N

E

FO

O T

6"

BUILDING NUMBER

NEW ORLEANS, LOUISIANA

7MH613

BLDG 07 HVAC SINGLE DUCT AIR TERMINAL

UNIT SCHEDULE

KJS PDHOctober 31,2011

07629-HS2-401SLVHCS REPLACEMENT MEDICAL

CENTER PROJECT

SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL

KORDA/NEMETH ENGINEERING / STRUCTURAL

BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE

SCALES ASSOCIATES / FIRE PROTECTION

DESMAN ASSOCIATES / PARKING

CODE CONSULTANTS, INC. / CODE CONSULTANT

THE SEXTANT GROUP / AV & ACOUSTICAL

HAMMER DESIGN ASSOCIATES / FOOD SERVICE

PYBURN & ODOM / ABATEMENT

TATA & HOWARD / TANK CONSULTANT Department of

Veterans Affairs

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

EWP-07

CONSTRUCTION DOCUMENTS 1

SUPPLY � SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (Area 1N1)

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 07�1N1 E1 1250 CFM 1250 2.0 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�2 07�1N1 H1 2500 CFM 2500 4.1 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�3 07�1N1 C1 450 CFM 0 0 VV DETAIL 5 ON 7MH812 NO COIL/ATTENUATOR

S�4 07�1N1 E2 1200 CFM 1200 1.9 CV DETAIL 5 ON 7MH812

S�5 07�1N1 F1 1600 CFM 1600 2.6 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�6 07�1N1 D2 700 CFM 350 VCV DETAIL 5 ON 7MH812

S�7 07�1N1 C1 550 CFM 550 0.9 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�8 07�1N1 H1 2400 CFM 1950 3.2 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�9 07�1N1 E1 1100 CFM 1100 1.8 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�10 07�1N1 E1 1100 CFM 1100 1.8 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�11 07�1N1 A1 150 CFM 150 0.5 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�12 07�1N1 E2 1050 CFM 1050 1.7 CV DETAIL 5 ON 7MH812

SUPPLY � SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (Area 1N2)

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 07�1N2 G2 1900 CFM 600 1.0 VCV DETAIL 6 ON 7MH812

S�2 07�1N2 H1 2400 CFM 1200 1.9 VCV DETAIL 6 ON 7MH812 NO ATTENUATOR

S�3 07�1N2 G2 1725 CFM 600 1.0 VCV DETAIL 6 ON 7MH812

S�4 07�1N2 E2 1040 CFM 1040 1.7 CV DETAIL 5 ON 7MH812

S�5 07�1N2 C2 630 CFM 630 1.0 CV DETAIL 5 ON 7MH812

S�6 07�1N2 C2 550 CFM 550 0.9 CV DETAIL 5 ON 7MH812

S�7 07�1N2 G1 2000 CFM 1000 1.6 VCV DETAIL 6 ON 7MH812 NO ATTENUATOR

S�8 07�1N2 F1 1600 CFM 800 1.3 VCV DETAIL 6 ON 7MH812 NO ATTENUATOR

S�9 07�1N2 G1 1000 1.6 VCV DETAIL 6 ON 7MH812 NO ATTENUATOR

S�10 07�1N2 F1 827 1.3 VCV DETAIL 6 ON 7MH812 NO ATTENUATOR

S�11 07�1N2 G2 2300 CFM 600 1.0 VCV DETAIL 6 ON 7MH812

S�12 07�1N2 C1 1900 CFM 600 1.0 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

SUPPLY � SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (Area 2N1)

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 07�2N1 D2 800 CFM 800 1.3 CV DETAIL 5 ON 7MH812

S�2 07�2N1 B2 300 CFM 300 0.5 CV DETAIL 5 ON 7MH812

S�3 07�2N1 D2 925 CFM 925 1.5 CV DETAIL 5 ON 7MH812

S�4 07�2N1 E2 1000 CFM 1000 1.6 CV DETAIL 5 ON 7MH812

S�5 07�2N1 B2 300 CFM 300 0.5 CV DETAIL 5 ON 7MH812

S�6 07�2N1 B2 200 CFM 200 0.5 CV DETAIL 5 ON 7MH812

S�7 07�2N1 D2 925 CFM 925 1.5 CV DETAIL 5 ON 7MH812

S�8 07�2N1 F2 1500 CFM 750 1.2 VCV DETAIL 6 ON 7MH812

S�9 07�2N1 C2 500 CFM 500 0.8 CV DETAIL 5 ON 7MH812

S�10 07�2N1 G2 2000 CFM 1000 1.6 VCV DETAIL 6 ON 7MH812

S�11 07�2N1 C2 450 CFM 450 0.7 CV DETAIL 5 ON 7MH812

S�12 07�2N1 C2 600 CFM 600 1.0 CV DETAIL 5 ON 7MH812

S�13 07�2N1 C1 0 0 VV DETAIL 6 ON 7MH812 NO COIL/ATTENUATOR

SUPPLY � SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (Area 2N2)

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 07�2N2 F2 1500 CFM 500 0.8 VCV DETAIL 6 ON 7MH812

S�2 07�2N2 D2 825 CFM 825 1.3 CV DETAIL 5 ON 7MH812

S�3 07�2N2 C2 675 CFM 525 0.9 CV DETAIL 5 ON 7MH812

S�4 07�2N2 F1 1500 CFM 0 0 VV DETAIL 6 ON 7MH812 NO COIL/ATTENUATOR

S�5 07�2N2 G1 2000 CFM 2000 3.2 CV DETAIL 5 ON 7MH812 NO ATTENUATOR

S�6 07�2N2 E1 1400 CFM 500 0.8 VCV DETAIL 6 ON 7MH812 NO ATTENUATOR

S�7 07�2N2 E2 1100 CFM 550 0.9 CV DETAIL 5 ON 7MH812

S�8 07�2N2 B1 400 CFM 0 0 VV DETAIL 6 ON 7MH812 NO COIL/ATTENUATOR

SUPPLY � SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (Area 3.5N2)

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 07�3.5N2 G2 1800 CFM 600 1.0 VCV DETAIL 6 ON 7MH812

S�2 07�3.5N2 H2 3200 CFM 3200 5.2 CV DETAIL 5 ON 7MH812

S�3 07�3.5N2 G2 1800 CFM 600 1.0 VCV DETAIL 6 ON 7MH812

S�4 07�3.5N2 C2 450 CFM 450 0.7 CV DETAIL 5 ON 7MH812

S�5 07�3.5N2 G2 1800 CFM 600 1.0 VCV DETAIL 6 ON 7MH812

SUPPLY � SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (Area 3N1)

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 07�3N1 C2 600 CFM 300 0.5 VCV DETAIL 6 ON 7MH812

S�2 07�3N1 C2 450 CFM 450 0.7 CV DETAIL 5 ON 7MH812

S�3 07�3N1 B2 300 CFM 150 0.5 VCV DETAIL 6 ON 7MH812

S�4 07�3N1 D2 750 CFM 375 0.6 VCV DETAIL 6 ON 7MH812

S�5 07�3N1 B2 325 CFM 200 0.5 VCV DETAIL 6 ON 7MH812

S�6 07�3N1 C2 425 CFM 475 0.8 CV DETAIL 6 ON 7MH812

S�7 07�3N1 B2 400 CFM 200 1.5 VCV DETAIL 6 ON 7MH812

S�8 07�3N1 D2 700 CFM 350 0.6 VCV DETAIL 6 ON 7MH812

S�9 07�3N1 C2 525 CFM 300 0.5 VCV DETAIL 6 ON 7MH812

S�10 07�3N1 D2 900 CFM 900 1.6 CV DETAIL 5 ON 7MH812

S�11 07�3N1 D2 750 CFM 375 0.6 VCV DETAIL 6 ON 7MH812

S�12 07�3N1 C1 450 CFM 0 0 VV DETAIL 6 ON 7MH812 NO COIL/ATTENUATOR

SUPPLY � SINGLE DUCT AIR TERMINAL UNIT SCHEDULE (Area 4N1)

MARK LOCATION

AREA AND/OR

BLDG SERVED SIZE Max CFM Min CFM GPM (Flow)

CONTROL

TYPE

CONTROL

SEQUENCE Remarks

S�1 4N111 07�4N1 E2 1100 CFM 1100 1.8 CV DETAIL 5 ON 7MH812

S�2 4N111 07�4N1 G2 2000 CFM 1000 1.6 VCV DETAIL 6 ON 7MH812

S�3 4N111 07�4N1 D2 700 CFM 700 1.1 CV DETAIL 5 ON 7MH812

S�4 07�4N1 G2 2000 CFM 1000 1.6 VCV DETAIL 6 ON 7MH812

S�5 07�4N1 F2 1500 CFM 750 1.2 VCV DETAIL 6 ON 7MH812

S�6 07�4N1 E2 1000 CFM 625 1.0 VCV DETAIL 6 ON 7MH812

S�7 07�4N1 C1 450 CFM 0 0 VV DETAIL 6 ON 7MH812 NO COIL/ATTENUATOR

S�8 07�4N1 B2 300 CFM 150 0.5 VCV DETAIL 6 ON 7MH812

S�9 07�4N1 C2 500 CFM 250 0.5 VCV DETAIL 6 ON 7MH812

S�10 07�4N1 B2 200 CFM 200 0.5 CV DETAIL 5 ON 7MH812

GENERAL NOTES:

1. FOR SYMBOL LISTS, ABBREVIATIONS, AND GENERAL

NOTES THAT APPLY TO ALL DRAWINGS SEE THE

7MH�0 SERIES OF DRAWINGS.

2. FOR GENERAL DETAILS SEE THE 7MH�5 SERIES OF

DRAWINGS.

3. FOR CONTROL DIAGRAMS SEE THE 7MH�8 SERIES OF

DRAWINGS.

NOTE: (1) FOR GENERAL TERMINAL BOX SCHEDULE DRAWING 7MH612

(2) REFER TO DRAWING 7MH607

NOTE: (1) FOR GENERAL TERMINAL BOX SCHEDULE DRAWING 7MH612

(2) REFER TO DRAWING 7MH607

NOTE: (1) FOR GENERAL TERMINAL BOX SCHEDULE DRAWING 7MH612

(2) REFER TO DRAWING 7MH607

NOTE: (1) FOR GENERAL TERMINAL BOX SCHEDULE DRAWING 7MH612

(2) REFER TO DRAWING 7MH607

NOTE: (1) FOR GENERAL TERMINAL BOX SCHEDULE DRAWING 7MH612

(2) REFER TO DRAWING 7MH607

NOTE: (1) FOR GENERAL TERMINAL BOX SCHEDULE DRAWING 7MH612

(2) REFER TO DRAWING 7MH607

NOTE: (1) FOR GENERAL TERMINAL BOX SCHEDULE DRAWING 7MH612

(2) REFER TO DRAWING 7MH607

1 Addendum 1 12/2/11

Pre-bid RFI 088: See Drawing 7MH815

Pre-bid RFI 088: See Drawing 7MH815

Pre-bid RFI 088: See Drawing 7MH815

Pre-bid RFI 088: See Drawing 7MH815

Pre-bid RFI 088: See Drawing 7MH815

Pre-bid RFI 088: See Drawing 7MH815

Pre-bid RFI 088: See Drawing 7MH815

RFI 01856: Provide terminal box size based on the connected air flows shown on the plan drawing. Refer to 7MH612 for terminal box capacity.

RFI 07289.1: VAV S-2 CFM to be readjusted to cover the CFM from deleted VAV on Level 4i (in area A7)