6/26/2020 OP AIR MEASURING STATIONS
Room Service System Width Height Relocate Cables I Note
1 J1 301 Return AHU-2 24 12 20' 1
1 J1 Return AHU-2 46 20 accept 2 above clg 1 J1 Exhaust AHU-1A 22 16 accept 1 above clg
2 J1 301 Return AHU-2 22 14 20' 1
2 J1 307 Return AHU-2 42 14 20' 2
2 J1 301 Exhaust AHU-1A 24 12 20' 1
2J1 Exhaust AHU-1A ? ? accept 1 above clg 2 J1 Exhaust AHU-1A ? - ? accept 1 above clg
3 J1 301 Return AHU-2 22 14 20' 1
3 J1 246 ' Return AHU-2 38 22 40' 2 above clg 3 J1 301 Exhaust AHU-1A 20 14 20' 1
4 J1 301 Return AHU-2 22 14 20' 1
4 J1 236 Return AHU-2 42 18 40' 2 above clg 4 J1 301 Exhaust AHU-1A 20 14 20' 1
5 J1 301 Return AHU-2 22 14 20' 1
5 J1 236 Return AHU-2 44 18 40' 2 above clg 5 J1 301 Exhaust AHU-1A 20 14 20' 1
6 J1 301 Return AHU-2 22 14 20' 1
6 J1 246 Return AHU-2 44 22 40' 2 above clg 6 J1 301 Exhaust AHU-1A 20 14 20' 1
7 J1 301 Return AHU-2 22 14 20' 1
7 J1 236 Return AHU-2 44 22 40' 2 above clg 7 J1 301 Exhaust AHU-1A 20 14 20' 1
1 J2 338 Return AHU-3 . 30 42 40' 2 above clg 1 J2 291 Exhaust AHU-2A 12 10 40' 1 above clg
2 J2 338 Return AHU-3 46 24 20'
2 J2 338 Exhaust AHU-2A 12 12 40' 1 above clg
3 J2 338 Return AHU-3 46 24 20' 1
3 J2 338 Exhaust AHU-2A 12 12 40' 1 above clg
4 J2 338 Return AHU-3 46 26 20' 2
4 J2 338 Exhaust AHU-2A 34 12 40' 1 above clg
5 J2 338 Return AHU-3 46 28 20' 1
5 J2 338 Exhaust AHU-2A 18 8 40' 1 above clg
6 J2 338 Return AHU-3 46 26 20' 1
6 J2 338 Exhaust AHU-2A 18 8 40' 1 above clg
7 J2 338
Return AHU-3 46 28 move
7 J2 338 Exhaust AHU-2A 12 8 40' above clg
8 J1 Supply AHU-2 122 50 20' 2
8 J1 Return AHU-2 80 66 move 4
8 J1 Outside AHU-1A 64 36 20' 2
8 J1 Exhaust AHU-1A 48 42 20' 2
6/26/2020 OP AIR MEASURING STATIONS
8J2 Supply AHU-3 114 60 20'
8J2 Return AHU-3 132 44 20' 2
8 J2 Outside AHU-2A 96 24 move 2
8 J2 Exhaust AHU-2A 76 24 20'
1 H Exhaust
18 24 accept 2 above clg
2 H 102 Return AHU-1 46 18 accept 2 above clg 2 H 102 Return AHU-1 38 34 accept 2
2 H 102 Exhaust
18 24 accept 2 above clg
3 H C05 Return AHU-1 24 20 accept 2 above clg 3 H C05 Return AHU-1 28 14 accept 2 above clg
3 H Exhaust
? ? accept 2 above clg
4 H 108 Return AHU-1 26 16 accept 2 above clg 4 H 108 Return AHU-1 26 14 accept 2 above clg
4 H Exhaust
? accept 2 above clg
5H Supply AHU-1 accept not found 5H Return AHU-1
5H 5H
Outside AHU-1
Exhaust AHU-1 on roof
Notes
Number of cables equal quantity of extensions requied.
Relocate with equal cable extension length of 20 feet unless noted otherwise.
Accept requires no relocation to AMS. Calibration and verification only.
Move requires no cable extensions but electrical wiring and control extensions.
Duct sizes shown are based off existing plans, which need to be field verified.
Locate centerline of all transmitter display boxes at 60" above finished floor.
Relocate those noted above ceiling to adjacent service bay or janitor closet.
OP 1J1 and 2J1 noted above ceiling can remain at existing location.
OP 1H, 2H, 3H and 4H noted above ceiling can remain at existing location.
6/19/2020 IP AIR MEASURING STATIONS
Room Service System Width Height Relocate Cables Note
1B114 Return AHU-1 68 28 20' 2
113114 Exhaust AHU-1A 12 12 20' 1
1A104 Exhaust AHU-2A 20 18 20' 2
1A104 Return AHU-2 66 22 20' 2
2B110 Return AHU-1 64 30 20' 2
2B110 Exhaust AHU-1A 22 16 20' 2
20114 Exhaust AHU-2A 18 18 20' 2
20114 Return AHU-2 56 30 20' 2
3B110 Return AHU-1 64 30 20' 2
3B110 Exhaust AHU-1A 22 16 20' 2
30114 Exhaust AHU-2A 18 18 20' 2
3C114 Return AHU-2 56 30 20' 2
413114 Return AHU-1 64 26 move 2 down 413114 Exhaust AHU-1A 22 16 move 2 down 4C132 Exhaust AHU-2A 24 24 20' 2
40132 Return AHU-2 34 24 20' 2
513121 Return AHU-1 66 54 accept 2 ok 5B121 Supply AHU-1 102 48 ? ? not found
5B121 Exhaust AHU-1A 30 30 move 2 down 5B121 Outside AHU-1A 51 32 move 2 down 5B121 Outside AHU-1A 50 30 20' 2
513121 Exhaust AHU-1A 24 30 20' 2 not found
5C110 Return AHU-2 95 44 20' 2
50110 Supply AHU-2 76 78 ? ? not found
50110 Exhaust AHU-2A 40 24 20' 1
5C110 Outside AHU-2A 42 48 move 2 down 50110 Outside AHU-2A 68 26 move 2 down 50110 Exhaust AHU-2A 24 34 ? ? not found
Number of cables equal quantity of extensions.
Relocate with equal extension length of 20 feet unless noted otherwise.
6/19/2020 RESEARCH AIR MEASURING STATIONS
5P Supply AHU-1 ? ? 20' 4 louver 5P Supply AHU-2 ? ? 20' 4 louver
5P Exhaust EF-1 EAHU-1 ? ? accept 4 ok 5P Exhaust EF-2 EAHU-2 ? ? accept 4 ok
5P Supply AHU-3 72 36 20' 4
5P Exhaust EF-3 ? ? accept 4 ok
5P Supply AHU-4 96 36 20' 3
5P Exhaust EF-4 72 36 accept 4 ok
5P Supply AHU-5 96 36 accept 4 ok 5P Outside AHU-5 ? ? 20' 4
5P Return AHU-5 42 60 accept 2 ok
5P Supply AHU-6 96 36 accept 4 ok 5P Outside AHU-6 ? ? accept 4 ok 5P Return AHU-6 42 60 accept 2 ok
5P Supply AHU-7 26 16 accept 1 ok 5P Outside AHU-7 36 16 accept 1 ok 5P Return AHU-7 28 14 20' 1
1P R-1 Return AHU-5 40 16
0 above clg 1P R-2 Return AHU-5 36 24
1P R-3 Return AHU-6 36 16
1P R-4 Return AHU-6 24 12
2P R-1 Return AHU-5 40 14
2P R-2 Return AHU-6 40 16
3P R-1 Return AHU-5 30 14
3P R-2 Return AHU-6 40 16
3P R-3 Return AHU-6 32 20
4P R-1 Return AHU-5 22 12
4P R-2 Return AHU-6 40 16
Return/damper above ceiling in Corridor. Verify flow and damper.
6/25/2020 DNT AIR MEASURING STATIONS
4D101 Exhaust AHU-2A 24 12 20' 1
4D101 Return AHU-2 26 20 20' 2
4D101 Return AHU-1 16 14 20' 1
4E201 Return AHU-3 40 20 20' 1
4E201 Exhaust AHU-3A 12 12 20' 1 high right
4F107 Exhaust AHU-4 18 14 40' 2 above clg 4F107 Return AHU-4A 26 20 40' 2 above clg 4F107 Return AHU-5 26 16 40' 2 above clg 4F107 Exhaust AHU-5A 22 14 40' 2 above clg
4G101 Return AHU-6 36 18 20' 1
4G101 Exhaust AHU-6A 14 12 20' 2 high right
4G304 Exhaust AHU-7 14 10 20' 1
4G304 Return AHU-7A 22 16 20' 2
3D101 Exhaust AHU-2A 26 18 20' 2 high left 3D101 Return AHU-2 60 24 20' 1
3D101 Return AHU-1 30 24 20' 2
3D101 Exhaust AHU-1A 12 12 20' 1
3E102 Return AHU-3 60 34 20' 2
3E102 Exhaust AHU-3A 14 12 20' 2 high right
3F113 Exhaust AHU-4 12 10 20' 1
3F113 Return AHU-4A 30 18 20' 1
3F113 Return AHU-5 36 28 20' 2
3F113 Exhaust AHU-5A 18 16 20' 2
3G116 Return AHU-6 40 18 20' 1
3G116 Exhaust AHU-6A 20 14 20' 2
3G303 Exhaust AHU-7 36 18 20' 2
3G303 Return AHU-7A 22 16 20' 1
2D100 Exhaust AHU-2A 24 14 20' 1
2D100 Return AHU-2 32 16 20' 1
2D100 Return AHU-1 30 14 20' 1
2D100 Exhaust AHU-1A 26 24 20' 2
2E108 Return AHU-3 60 22 20' 2
2E108 Exhaust (n) AHU-3A 18 12 20' 2
2E108 Exhaust (s) AHU-3A 18 12 20' 2
2F107 Exhaust AHU-4A 20 14 20' 2
2F107 Return AHU-4 46 20 20' 1
2F107 Return AHU-5 34 14 20' 1
2F107 Exhaust AHU-5A 26 14 20' 2
2G110 Return AHU-6 50 20 20' 1
2G110 Exhaust AHU-6A 20 14 20' 2
2G303 Exhaust AHU-7A 12 12 20' 1
2G303 Return AHU-7 40 18 20' 1
1D102 Return AHU-1 50 22 40' 2 above clg 1D102 Exhaust AHU-1A 24 12 40' 2 above clg
1E112 Return AHU-3 58 16 40' 1 above clg 1E110 Exhaust AHU-3A 14 22 40' 3
1F107 Return AHU-5 22 22 40' 2 above clg 1F107 Exhaust AHU-5A 20 14 40' 1 above clg
1G112 Return AHU-6 48 30 20' 2
1G112 Exhaust AHU-6A 26 18 20' 1
6D Return AHU-1 66 48 20' 2
6D Exhaust AHU-1A 48 24 20' 1
6D Outside AHU-1A 52 30 20' 2
6D Supply AHU-1 84 60 move 4 down 6D Return AHU-2 52 48 20' 2
6D Return AHU-2 (5th) 40 28 accept 2 ok 6D Supply AHU-2 80 44 20' 2
6D Supply AHU-2 (5th) 48 24 move 2 down 6D Outside AHU-2A 64 36 move 2 down 6D Exhaust AHU-2A (5th) 24 20 accept 2 ok 6D Exhaust AHU-2A 36 32 20' 2
5E Return AHU-3 66 60 20' 3
5E Exhaust AHU-3A 42 34 20' 2
5E Outside AHU-3A 83 42 accept 2 ok 5E Supply AHU-3 86 66 move 4 down
5F Return AHU-4 44 30 move 2 down 5F Exhaust AHU-4A 18 14 accept 2 ok 5F Outside AHU-4A 48 42 move 2 down 5F Supply AHU-4 60 60 move 4 down 5F Return AHU-5 48 42 20' 2
5F Exhaust AHU-5A 24 20 ? ? not found 5F Outside AHU-5A 46 44 move 2 down 5F Supply AHU-5 66 52 accept 2 ok 5F Relief AHU-5 20 10 20' 1
5G Supply AHU-6 120 48 20' 2
5G Return AHU-6 88 36 20' 2 above 5G Return AHU-6 44 36 20' 2 above 5G Outside AHU-6A 40 30 ? ? not found 5G Outside AHU-6A 66 30 20' 2
5G Exhaust AHU-6A 28 24 20' 2
5G Supply AHU-7 76 46 20' 2
5G Return AHU-7 accept 2 ok 5G Exhaust AHU-7A 24 32 20' 2
5G Outside AHU-7A 64 38 20' 1
Number of cables equal quantity of extensions requied.
Relocate with equal cable extension length of 20 feet unless noted otherwise.
Relocate those noted above ceiling to adjacent service bay or janitor closet.
6/26/2020 TLR AIR MEASURING STATIONS
1M143 Exhaust AHU-1A 22 16 accept 2 above clg 1M135 Return AHU-1 50 36 accept 2 above clg 1M165 1M157
Return AHU-2 44 20 20' 2 high Exhaust AHU-2A 18 20 accept 2 not found
2M108 Return AHU-1 30 30 accept 2 above clg 2M101 Exhaust AHU-1A 26 16 accept 2 above clg 2M099 Return AHU-1 28 22 accept 2 above clg 2M080 Return AHU-2 ? ? accept 2 above clg 2M080 Exhaust AHU-2A ? ? accept 2 above clg
3M056 Return AHU-1 24 44 accept 2 above clg 3M047 Return AHU-1 38 34 accept 2 above clg 3M049 Exhaust AHU-1A 36 16 accept 2 above clg
3Roof Exhaust AHU-2A 24 18 accept 2 ok 3Roof Outside AHU-2A 40 30 accept 2 ok 3Roof Return AHU-2 46 30 accept 2 ok 3Roof Supply AHU-2 80 34 accept 2 not found
4Roof Exhaust AHU-1A 28 38 accept 2 ok 4Roof Outside AHU-1A 89 36 accept 2 ok 4Roof Return AHU-1 66 54 accept 2 ok 4Roof Supply AHU-1 88 54 accept 2 ok
Pool Supply AHU-5 34? 34? accept 2 ok Pool Exhaust AHU-5 in fan in fan accept 2 ok
Gym 2 Supply AHU-4 64 24 accept 2 ok Gym 2 Outside AHU-4 24 18 accept 2 ok Gym 2 Return AHU-4 42 32 accept 2 ok
Gym 3 Supply AHU-3 56 32 accept 2 ok Gym 3 Outside AHU-3 42 18 accept 1 ok Gym 3 Return AHU-3 50 28 accept 2 ok extensions.
of 20 feet
Number of cables equal quantity of length
Relocate with equal extension unless noted otherwise.
TLR building noted above ceiling can remain at existing location.
6/19/2020 Pan AM CEP AIR MEASURING STATIONS
Room Service System Width Height Relocate Cables Notes
60103 Return AHU-1 at unit fan ok
60103 Supply AHU-1 at unit fan
60103 Supply AHU-1 at unit fan
60103 Outside AHU-1 accept 4 ok
60102 Return AHU-2 at unit fan
60102 Supply AHU-2 at unit fan
60102 Supply AHU-2 at unit fan
60102 Outside AHU-2 accept 4 ok
3N Return AHU-1 78 32
3N Outside AHU-1 137 46 move 4 down 3N Supply AHU-1 at unit fan
2N Return AHU-3 72 48 move 2 down 2N Outside AHU-3 48 48 move 2 down 2N Supply AHU-3 at unit fan
4.5N Outside AHU-8 96 72 move 2 down 4.5N Supply AHU-8 at unit fan
3.5N Outside AHU-5 58 14 accept 1 ok