VA_WAC Fire Alarm - Bid Set Drawings.pdf

PDF 35 MB Posted

Attached to
1230--674A4-21-108 Upgrade Fire Alarm System Campus Wide - Waco
Solicitation number
36C25722B0003
Issued by

About this file

This document provides details for a federal contract opportunity to upgrade the fire alarm system at the Central Texas Veterans Health Care System campus in Waco, Texas. The solicitation number is 36C25722B0003 and will require replacing the existing fire alarm system in its entirety across 25 buildings. A 100% Service-Disabled Veteran-Owned Small Business set-aside will be in place. The procurement is estimated between $5 million to $10 million and have a one year period of performance once a notice to proceed is issued. Interested parties must obtain verification from the Department of Veterans Affairs Center for Verification and Evaluation as a Service-Disabled Veteran-Owned Small Business prior to proposal submission to be considered for this opportunity from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17. The point of contact is Gaila P. Lowe and she can be reached by email.

View the file

Other files

File Type Posted
36C25722B0003 A00003.docx DOCX document
36C25722B0003 A00002.docx DOCX document
36C25722B0003 A00001.docx DOCX document
VA_WAC Fire Alarm - Bid Set Specifications.pdf PDF
36C25722B0003.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Above finished floor AFF Acoustic ACST Acoustic Panel Ceiling APC Addendum ADD Alternate ALT Aluminum AL Angle L Approximate APPROX Architecture, architectural ARCH Asbestos ASB Asphalt ASPH Assistant ASST Association ASSN Automatic AUTO Average AVG Base plate BP Basement BSMT Beam BM Bearing BRG Bedroom BR Benchmark BM Board BD Boiler BLR Bottom BOT Brick BRK Building line BL Building BLDG Built-up-roof BUR Cabinet CAB Carpet CPT Catalog CAT Ceiling height CH Ceiling CLG Center CTR Centerline CL Ceramic Tile CT Ceramic CER Chalkboard CB Clear CLR Closet CLO Coated CTD Cold rolled CR Column COL Company CO Composition COMP Concrete Masonry Unit CMU Concrete CONC Construction joint CJ Construction CONSTR "Continue, Continuous" CONT Corridor CORR Countersink CSK Cubic CU Curve(d) CRV Dampproofing DP Degree DEG Department(al) DEPT Detail DET Diagonal DIAG Diameter DIA Dimension DIM Dishwasher DW Dispenser DISP Door DR Double DBL Double-hung DH Down DN Downspout DS Drain DR Drawing DWG Each EA East E Electric Water Cooler EWC "Electric, electrical" ELEC Elevation EL Elevator ELEV Engineer ENGR Entrance ENTR Equal EQ Equipment EQUIP Exhaust EXH Existing EXIST Expansion joint EXP JT Exposed EXP Exterior EXT Fabricate FAB Face of Stud F. OF S.

Fan Coil Unit FCU Fiberglass-reinforced plastics FRP Finish FIN Finished Floor FF Fire Extinguisher FE Fire Extinguisher & Cabinet FEC Fire Retardant Treated FRT Fireproof FPRF Fixture FXTR Flange FLG Flashing FL Floor FL Floor drain FD Flooring FLG Fluorescent FLUOR

Footing FTG Foundation FDN Furnish(ed), furniture FURN Furring FURR Gage (gauge) GA Galvanize(d) GALV Galvanized Iron GALVI Glazed Wall Tile GWT Grab Bar GB Grade GR Gravel GVL Gypsum Wallboard GWB Gypsum GYP Handicapped HC Hardware HDW Heating ventilating and HVAC air conditioning Height HGT High Point HPT High Performance HP High Performance Coating HPC Hollow Metal HM Horizontal HORIZ Include(d), inclusive INCL Incorporated INC Information INFO Inside diameter ID Install(ed), installation INSTL Insulation INSUL Interior INT Janitor JAN Joint JT Joist J, JST Junction box JB Knock down KD Laboratory LAB Lavatory LAV Left Hand LH Left L Length LG Level LVL Light LT Machine MACH Maintenance MAINT Manager MGR Manual MNL Manufacturing MFG Markerboard MB Masonry opening MO Masonry MSNRY Master bedroom MBR Material MATL Maximum MAX Mechanical MECH Membrane MEMB Men M Metal MET, MTL Mezzanine MEZZ Minimum MIN Mirror MIR Miscellaneous MISC Mounted MTD Mounting MTG Necessary NEC Noise-reduction coefficient NRC Nominal NOM Non Combustible NC, NONCOM North N Not in Contract NIC Not to scale NTS Not available NA Number NO Office OFF On center OC Opening OPNG Opposite OPP Outside diameter OD Overall OA Overhead OVHD Page P Painted PTD Pair PR Panel PNL Partition PTN Percent PCT Perforate(d) PERF Permanent PERM Perpendicular PERP Piece PC Plastic Laminate PLAM Plastic Laminate PLAS.LAM Plate PL Plumbing PLMB Plywood PLYWD Point PT Polyvinyl chloride PVC Precast PRCST Prefabricated PREFAB Preliminary PRELIM Preparation, prepare PREP Program PRGM Projection Screen PS

Project PROJ Property PROP Public Address PA Quality control QC Quality QUAL Quantity QTY Quarry Tile QT Radius RAD Rain Leader RL Received RCVD Receptacle RCPT Receptionist RECPT Recess(ed) REC Refer, reference REF Refrigerate, refrigerator REFR Reinforce REINF Reinforced concrete RC Remove RMV Repair RPR Required REQD Revise, revision REV Right hand RH Road RD Roof Drain RD Roof RF Roofing RFG Room RM Rubber tile floor RTF Rubber RBR Schedule SCHED Schematic SCHEM Section SECT Service SVCE "Sheet, sheeting" SHT Shower SH Siding SDG Similar SIM Slope SL Sound-transmission class STC South S Speaker SPKR Specification SPEC Sprinkler SPR Square SQ Stainless steel SS Standard STD Standpipe SP Steel STL Storage STOR Structural Glazed Facing Tile SGFT Structural, structure STRUCT Substitute SUBST Surface SURF Suspend(ed) SUSP Switch SW Symmetrical SYM System SYS Tackboard TB Tackstrip TS Telephone TEL Television TV Temporary TEMP Terrazzo TER Thick THK Through THRU Toilet T Tongue and groove T&G Top and bottom T&B Top chord TC Top of Masonry Parapet TMP Top of Bearing TOFB Top of Steel T.O.S.

Topping TOPG Total TOT Transformer XFMR Transom TR Transparent TRANS Tread TRD Threshold THRESH Typical TYP Underground UG Underwriters Laboratories UL Unfinished UNF Unit Ventilator UV Unless Otherwise Noted UON Urinal UR US Gypsum Company USG Vertical VERT Vestibule VEST, V Vinyl Reducing Strip VRS Vinyl Composite Tile VCT Vinyl asbestos tile VAT Wardrobe WARD Water closet WC Waterproof WP Weight WT Welded WLD Welded Wire Mesh WWM With W/ Without W/O Women W Wood WD Wrought Iron WI

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR.

SUITE 350

CALVERTON, MD 20705

443-388-7351

Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

6/25/2021

100% BID SET 4800 MEMORIAL DRIVE, WACO, TX

76711

674A4-21-108

JLHMAR

COVER SHEET

G001

A

-2

-1

G

/2

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

ALARM CAMPUS UPGRADE

Fire Alarm Campus Upgrade

100% BID SET

674A4-21-108

Waco VA Medical Center 4800 Memorial Drive

Waco, TX 76711

Volume 1

226-E101 BUILDING 226 - ELECTRICAL PLAN – LEVEL 1 X

225-E101 BUILDING 225 - ELECTRICAL PLAN – LEVEL 1 X X

224-E101 BUILDING 224 - ELECTRICAL PLAN – LEVEL 1 X X

222-E101 BUILDING 222 - ELECTRICAL PLAN – LEVEL 1 X X

219-E101 BUILDING 219 - ELECTRICAL PLAN – BASEMENT LEVEL X X

216-E101 BUILDING 216 - ELECTRICAL PLAN – LEVEL 1 X X

202-E101 BUILDING 202 - ELECTRICAL PLAN – LEVEL 1 X X

99-E101 BUILDING 99 - ELECTRICAL PLAN – BASEMENT LEVEL X X

94-E101 BUILDING 94 - ELECTRICAL PLAN – BASEMENT LEVEL X X

93-E101 BUILDING 93 - ELECTRICAL PLAN – BASEMENT LEVEL X X

92-E101 BUILDING 92 - ELECTRICAL PLAN – BASEMENT LEVEL X X

90-E101 BUILDING 90 - ELECTRICAL PLAN – BASEMENT LEVEL X X

24-E101 BUILDING 24 - ELECTRICAL PLAN – LEVEL 1 X X

18-E101 BUILDING 18 - ELECTRICAL PLAN – LEVEL 1 X X

17-E101 BUILDING 17 - ELECTRICAL PLAN – LEVEL 1 X X

16-E101 BUILDING 16 - ELECTRICAL PLAN – LEVEL 1 X X

15-E101 BUILDING 15 - ELECTRICAL PLAN – LEVEL 1 X X

8-E101 BUILDING 8 - ELECTRICAL PLAN – LEVEL 1 X X

7-E101 BUILDING 7 - ELECTRICAL PLAN – BASEMENT AREA X X

6-E101 BUILDING 6 - ELECTRICAL PLAN – LEVEL 1 X X

5-E101 BUILDING 5 - ELECTRICAL PLAN – BASEMENT LEVEL X X

4-E101 BUILDING 4 - ELECTRICAL PLAN – BASEMENT LEVEL X X

2-E101 BUILDING 2 - ELECTRICAL PLAN – BASEMENT LEVEL X X

ELECTRICAL: X

X X

226-FA102 BUILDING 226 - FIRE ALARM PLAN - MEZZANINE LEVEL X X

226-FA101 BUILDING 226 - FIRE ALARM PLAN - LEVEL 1 X X

226-FA001 BUILDING 226 - FIRE ALARM GENERAL NOTES AND DETAILS X X

225-FA102 BUILDING 225 - FIRE ALARM PLAN – LEVEL 2 X X

225-FA101 BUILDING 225 - FIRE ALARM PLAN – LEVEL 1 X X

225-FA100 BUILDING 225 - FIRE ALARM PLAN – BASEMENT X X

224-FA101 BUILDING 224 - FIRE ALARM PLAN - LEVEL 1 X X

222-FA101 BUILDING 222 - FIRE ALARM PLAN - LEVEL 1 X X

219-FA101 BUILDING 219 - FIRE ALARM PLAN - BASEMENT LEVEL X X

216-FA101 BUILDING 216 - FIRE ALARM PLAN - BASEMENT & LEVEL 1 X X

202-FA101 BUILDING 202 - FIRE ALARM PLAN - LEVEL 1 X X

99-FA101 BUILDING 99 - FIRE ALARM PLAN - BASEMENT LEVEL & LEVEL 1 X X

94-FA102 BUILDING 94 - FIRE ALARM PLAN - LEVEL 1 X X

94-FA101 BUILDING 94 - FIRE ALARM PLAN - BASEMENT LEVEL X X

94-FA001 BUILDING 94 - FIRE ALARM GENERAL NOTES AND DETAILS X X

93-FA103 BUILDING 93 - FIRE ALARM PLAN - LEVEL 2 X X

93-FA102 BUILDING 93 - FIRE ALARM PLAN - LEVEL 1 X X

93-FA101 BUILDING 93 - FIRE ALARM PLAN - BASEMENT LEVEL X X

93-FA001 BUILDING 93 - FIRE ALARM GENARL NOTES AND DETAILS X X

92-FA103 BUILDING 92 - FIRE ALARM PLAN - LEVEL 2 X X

92-FA102 BUILDING 92 - FIRE ALARM PLAN - LEVEL 1 X X

92-FA101 BUILDING 92 - FIRE ALARM PLAN - BASEMENT LEVEL X X

92-FA001 BUILDING 92 - FIRE ALARM GENERAL NOTES AND DETAILS X X

90-FA103 BUILDING 90 - FIRE ALARM PLAN - LEVEL 2 X X

90-FA102 BUILDING 90 - FIRE ALARM PLAN - LEVEL 1 X X

90-FA101 BUILDING 90 - FIRE ALARM PLAN - BASEMENT LEVEL X X

90-FA001 BUILDING 90 - FIRE ALARM GENERAL NOTES AND DETAILS X X

24-FA101 BUILDING 24 - FIRE ALARM PLAN - LEVEL 1 X X

18-FA101 BUILDING 18 - FIRE ALARM PLANS X X

17-FA101 BUILDING 17 - FIRE ALARM PLAN - LEVEL 1 X X

16-FA101 BUILDING 16 - FIRE ALARM PLAN - LEVEL 1 X X

15-FA101 BUILDING 15 - FIRE ALARM PLAN - LEVEL 1 X X

8-FA103 BUILDING 8 - FIRE ALARM PLAN – LEVEL 2 X X

8-FA102 BUILDING 8 - FIRE ALARM PLAN – LEVEL 1 X X

8-FA101 BUILDING 8 - FIRE ALARM PLAN – BASEMENT LEVEL X X

8-FA001 BUILDING 8 - FIRE ALARM GENERAL NOTES AND DETAILS X X

7-FA103-C BUILDING 7 - FIRE ALARM PLAN - LEVEL 2 AREA C X X

7-FA103-A&B BUILDING 7 - FIRE ALARM PLAN - LEVEL 2 AREA A&B X

7-FA102-C BUILDING 7 - FIRE ALARM PLAN - LEVEL 1 AREA C X

7-FA102-A&B BUILDING 7 - FIRE ALARM PLAN - LEVEL 1 AREA A&B X

7-FA101-C BUILDING 7 - FIRE ALARM PLAN - BASEMENT AREA C X X

7-FA101-A&B BUILDING 7 - FIRE ALARM PLAN - BASEMENT AREA A&B X X

7-FA001 BUILDING 7 - FIRE ALARM GENERAL NOTES AND DETAILS X X

6-FA103 BUILDING 6 - FIRE ALARM PLAN - LEVEL 3 X X

6-FA102 BUILDING 6 - FIRE ALARM PLAN - LEVEL 2 X X

6-FA101 BUILDING 6 - FIRE ALARM PLAN - LEVEL 1 X X

6-FA100 BUILDING 6 - FIRE ALARM PLAN - BASEMENT LEVEL X X

5-FA103 BUILDING 5 - FIRE ALARM PLAN - LEVEL 2 X X

5-FA102 BUILDING 5 - FIRE ALARM PLAN - LEVEL 1 X X

5-FA101 BUILDING 5 - FIRE ALARM PLAN - BASEMENT LEVEL X X

5-FA001 BUILDING 5 - FIRE ALARM GENERAL NOTES AND DETAILS X X X

4-FA102 BUILDING 4 - FIRE ALARM PLAN - LEVEL 1 X X X

4-FA101 BUILDING 4 - FIRE ALARM PLAN - BASEMENT LEVEL X X X

4-FA001 BUILDING 4 - FIRE ALARM GENERAL NOTES AND DETAILS X X X

2-FA103 BUILDING 2 - FIRE ALARM PLAN - LEVEL 2 X X X

2-FA102 BUILDING 2 - FIRE ALARM PLAN - LEVEL 1 X X X

2-FA101 BUILDING 2 - FIRE ALARM PLAN - BASEMENT LEVEL X X X

FIRE PROTECTION:

GI003 PENETRATION DETAILS X

GI002 SITE ORIENTATION PLAN X X

GI001 COVER SHEET X X X

GENERAL:

SHEET NUMBER SHEET NAME 35% 65% 100% 100% FINAL

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

G A T E

G A T E

G A T E

M A

IN

G A T E

G A T E

OLD FARM ROAD

OLD FARM ROAD

DORIS MILLER CIRCLE

DORIS MILLER CIRCLE

D O R

IS

M

IL

LE

R C

IR

CL

E

DOR

IS M

ILLE

R C

IRCL

E

O U T E R

L O O P

R O A D

O U T E R

L O O P

R O A D

O U T E R

L O O P

R O A D

O U

TE

R

LO

O P

R O A D

OUTER LOOP ROAD

OUTER LOOP ROAD

OU

TE

R

LO

OP

C

IR

CL

E

MEMORIAL BLVD.

MEMORIAL BLVD.

QUARTERS DRIVE

C

IR

C

LE

D R

IV

E

BEVERLY DRIVE

BEVERLY DRIVE

BEVERLY DRIVE

N E W

R O A D

N E W

R O A D

H C

V A N

H C

CO

UR

T

CO

UR

T

C O U R T

V A N

9' - 5 7/8"

MAIN GRAPHIC

ANNUNCIATOR

PANELS IN

BUILDINGS 225

AND 18

FACP RM BA139

BUILDING 4

FACP RM BA104

BUILDING 6

FACP RM BC112

BUILDING 7

FACP RM 8A

BUILDING 5

FACP COR CB1-1

BUILDING 2

FACP RM BB127

BUILDING 94

FACP 3RD FLR

BUILDING 92

FACP RM 101

BUILDING 90

FACP RM BA110

BUILDING 93

FACP RM 3

BUILDING 99

FACP RM 103M

BUILDING 15

FACP COR 221

BUILDING 8

FACP RM 101

BUILDING 226

FACP RM 105

BUILDING 225

FACP RM 106

BUILDING 224

FACP RM 1A-100

BUILDING 216

FACP RM 127

BUILDING 202

BUILDING 16

FACP RM 112

BUILDING 18

FACP COR 21

BUILDING 24

NOTE: CONTRACTOR TO VERIFY PANEL LOCATION

ON SITE AND COORDINATE LOCATION OF THE NEW

PANEL WITH EXISTING IN BUILDING 17.

FACP RM 1A-107

BUILDING 219

FACP

BUILDING 17

BUILDING 222

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

ARCHITECT:

CB DESIGN GROUP

11720 BELTSVILLE DR.

SUITE 350

CALVERTON, MD 20705

443-388-7351

Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

6/25/2021

100% BID SET 4800 MEMORIAL DRIVE, WACO, TX

76711

674A4-21-108

JLHMAR

SITE ORIENTATION PLAN

G002

A

-2

-1

G

/2

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

ALARM CAMPUS UPGRADE

N TRUE

NORTH

226 LAUNDRY

225 ENERGY PLANT

224 SAFETY

222 RADIO EQUIPMENT

219 PHYSICAL THERAPY

216 CENTRAL CHILLER

202 DIETETICS

99 FMS SHOPS

94 INPATIENT PSYCH

93 FUTURE CENTER OF EXCELLENCE

92 VA FINANCIAL CENTER

90 PHARMACY CALL CENTER

24 F.M.S./SHOPS

18 POLICE

17 CONSOLIDATED LAUNDRY/FUTURE A&MM/VACANT

16 GARAGE MISC.

15 VBA

8 FUTURE ACUTE MENTAL HEALTH/PARTIAL OCCUPANCY

7 BLIND REHAB UNIT/VACANT

6 AUDITORIUM

5 PHARMACY/EDUCATION

4 OUTPATIENT CLINIC/LAB CLINIC

2 ADMINISTRATIVE

Building # Building Name

SCALE: NTS

A5

CAMPUS RISER DIAGRAM

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

FIRE RESISTANT RATED WALL CONSTRUCTION

THROUGH PENETRATION FIRESTOPPING SYSTEM

PROVIDE SYSTEM IN ACCORDANCE WITH FIRESTOPPING SCHEDULE

WALL PENETRATION - SEE DRAWINGS

SLAB PENETRATION - SEE DRAWINGS

THROUGH PENETRATION FIRESTOPPING SYSTEM

PROVIDE SYSTEM IN ACCORDANCE WITH

FIRESTOPPING SCHEDULE

FIRE RESISTANCE RATED FLOOR CONSTRUCTION

FLOOR PIPE PENETRATION

UL No: F-L-1020

JOINT SEALANT APPLIED

WITHIN OPENING

METAL PIPE

CONCRETE OVER COMPOSITE

STEEL DECK

MINERAL WOOL INSULATION

JOINT SEALANT

JOINT SEALANT

MINERAL WOOL

INSULATION

METAL PIPE

FLOOR PIPE PENETRATION

UL No: F-L-5014

JOINT SEALANT APPLIED

WITHIN OPENING

METAL PIPE

CONCRETE OVER COMPOSITE

STEEL DECK

MINERAL WOOL INSULATION

JOINT SEALANT

JOINT SEALANT

MINERAL WOOL

INSULATION

GLASS FIBER INSULATION

GLASS FIBER

INSULATION

METAL PIPE

SINGLE CONDUIT/PIPE PENETRATION

UL No: W-L-1063

JOINT SEALANT

PIPE / CONDUIT

JOINT SEALANT

RATED WALL ASSEMBLY - VERIFY

WALL TYPE IN FIELD

48" MAX

V A

R

IE

S

6" M

A X

2" MAX, 1" MIN

1" M

A X

MULTIPLE CONDUIT/PIPE PENETRATIONS

UL No: W-L-1063

MINERAL WOOL INSULATION

WALL TYPE, SEE PLAN

MINERAL WOOD INSULATION

MINERAL WOOL INSULATION

WALL TYPE, SEE PLAN

WALL TYPE, SEE PLAN

SINGLE CONDUIT/PIPE PENETRATION

UL No: W-L-5044

PIPE/CONDUIT

FORMING MATERIAL

JOINT SEALANT

VERIFY WALL TYPE IN FIELD

JOINT SEALANT

PIPE / CONDUIT

WALL TYPE

SMALL PENETRATIONS IN PARTITIONS

RATED UP TO 2 HOURS

NO TREATMENT REQUIRED FOR UP

TO 1/8" GAP

MAXIMUM GAP 1/4"

MAXIMUM GAP 1/2", FILL TO FULL DEPTH

OF DRYWALL AND STRIKE OFF AT FACE

OF DRYWALL, DO NOT SPREAD BEYOND

OPENING

2'-0" (PER UL)

SHALLOW FIVE SIDED BOX

RATED WALL ASSEMBLY-

SEE PARTITION TYPES FOR

NUMBER OF LAYERS OF

GYPSUM BOARD

ELECTRICAL JUNCTION BOX

16 SQ INCH MAX OPENING

MAX 100 SQ INCHES IN 100 SQ FEET

LAMINATE BACK PIECE

TO WALLBOARD

REQUIRED BOX EXCEEDS 16 SQ INCHES

OR AGGREGATE SUM OF BOXES

EXCEEDS 100 SQ INCHES IN 100 SQ

FEET OF WALL AREA

ADJACENT ELECTRICAL BOXES

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

6/25/2021

100% BID SET 4800 MEMORIAL DRIVE, WACO, TX

76711

674A4-21-108

EWMDLO

PENETRATION DETAILS

GI003

A

-2

-1

G I0

/1

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

ALARM CAMPUS UPGRADE

SCALE: NTS

A5

THROUGH PENETRATION FIRESTOP SYSTEM KEY

SCALE: NTS

F6

PENETRATION DETAIL

SCALE: NTS

F3

PENETRATION DETAIL

SCALE: NTS

A9

PENETRATION DETAIL

SCALE: NTS

D9

PENETRATION DETAIL

SCALE: NTS

D6

PENETRATION DETAIL

SCALE: NTS

D3

PENETRATIONS

SCALE: NTS

F9

ELECTRICAL JUNCTION BOX DETAIL

F

S

S C

M

C

CO

H R

S

ID

S P

WF

PS

VS

FAA

FACP

FATC

C S C CS C

F

S CC

F

F

F

F

S P

FACP

C C

C

H R

WF

VS

WF

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

VS

1. PROVIDE AND INSTALL A NEW FIRE ALARM SYSTEM THROUGHOUT THE BUILDING

PER THE VA DESIGN GUIDE AND NFPA 72. REFER TO SPEC SECTION 28 31 00

INTERIOR FIRE ALARM SYSTEM. FIRE ALARM SYSTEM WILL BE ZONED PER FLOOR.

2. ALL EXISTING FIRE ALARM DEVICES, PANELS AND RELATED EQUIPMENT ARE TO

BE DEMOLISHED. EXISTING ALARM SYSTEMS MUST REMAIN IN-SERVICE AND

FUNCTIONAL WHILE NEW ALARM SYSTEM IS INSTALLED. FOLLOW ILSM

PROTOCOLS FOR SHUTDOWN AND PHASE DEMO OF EXISTING ALARM SYSTEM SO

THAT REMOVAL ONLY OCCURS ONCE NEW ALARM SYSTEM IS FULLY INSTALLED

AND FUNCTIONAL.

3. ALL EXISTING INTERFACING DEVICES (TAMPERS, FLOWS, PRESSURE SWITCHES,

ETC) WILL BE CONNECTED TO THE NEW FA SYSTEM AND REPORT TO THE MAIN

GRAPHIC ANNUNCIATORS IN BUILDING 225. A SECONDARY MONITORY STATION

SHALL BE LOCATED IN BUILDING 18. INTERFACING DEVICES ARE SHOWN WHEN

LOCATIONS ARE KNOWN, HOWEVER THE DRAWINGS SHOULD NOT BE USED AS

EXHAUSTIVE LIST. THE EXISTING CAMPUS FIRE ALARM SYSTEM WILL NOT BE

REUSED AND A NEW CAMPUS WIDE SYSTEM IS TO BE PROVIDED, SEE FIRE ALARM

SITE PLAN.

4. COORDINATE FIRE ALARM SYSTEM DEVICE LOCATIONS WITH LIGHT FIXTURES,

STRUCTURAL MEMBERS, SPRINKLER HEADS AND PIPING, HVAC EQUIPMENT AND

DUCTWORK. CONTRACTOR TO VERIFY LOCATIONS OF DUCT SMOKE DETECTORS

AND CONNECT TO NEW FIRE ALARM SYSTEM.

5. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE AND

SATISFACTORILY OPERATING SYSTEMS AS INDICATED ON THE CONTRACT

DOCUMENTS AND AS EVIDENTLY INTENDED. IT IS NOTED THAT THE DRAWINGS

ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENTS OF SYSTEMS AND

WORK. INTERCONNECTIONS HAVE BEEN SHOWN, AND THE CONTRACTOR SHALL

FURNISH AND INSTALL CONDUIT AND WIRING AS REQUIRED TO ACCOMPLISH THE

FUNCTIONS INDICATED. ADDITIONALLY, FIRE ALARM SYSTEMS HAVE BEEN

SHOWN AND THE CONTRACTOR SHALL FURNISH AND INSTALL THE REQUIRED

QUANTITIES AND TYPES OF CABLES, CONDUCTORS, RACEWAYS, REMOTE POWER

SUPPLIES AND CONNECTIONS, SHIELDING REQUIREMENTS, ETC., AS REQUIRED

BY THE SYSTEM MANUFACTURER, THE SPECIFICATIONS, AND ANY APPLICABLE

CODES. ALL WIRING SHOWN ON RISER DIAGRAMS SHALL ALSO BE FURNISHED

AND INSTALLED REGARDLESS OF WHETHER THESE ITEMS ARE SHOWN ON THE

FLOOR PLANS.

6. THE CONTRACTOR SHALL COORDINATE THE ELECTRICAL WORK WITH THE WORK

OF ALL OTHER TRADES AND EXISTING CONDITIONS SO AS TO AVOID CONFLICTS.

RESOLVE ALL CONFLICTS THROUGH THE A/E PRIOR TO ROUGH-IN. FAILURE TO

PROVIDE SUCH COORDINATION PRIOR TO WORK BEING INSTALLED SHALL NOT BE

CAUSE FOR ADDITIONAL COMPENSATION TO THE CONTRACTOR, AND MAY

RESULT IN REJECTION OF THE WORK.

7. ADDITIONAL DEVICES MAY BE REQUIRED. DO NOT USE THESE DRAWINGS FOR

DEVICE COUNTS.

8. ALL MATERIALS SHALL BE NEW, SHALL BE SUITABLE FOR THE APPLICATION

INTENDED, AND SHALL BEAR LABELS OR MARKINGS INDICATING THIRD PARTY

TESTING LABORATORY LISTINGS ACCEPTABLE TO THE AUTHORITY HAVING

JURISDICTION.

9. EXISTING CONDUIT IN GOOD CONDITION THAT HAS BEEN SALVAGED FROM OTHER

BUILDINGS MAY BE REUSED IF POSSIBLE AND SHALL BE STRIPED IN PATIENT

AREAS. NEW CONDUIT SHALL BE MARKED WITH RED COUPLINGS. ALL OTHER

MATERIALS SHALL BE NEW, SHALL BE SUITABLE FOR THE APPLICATION INTENDED,

AND SHALL BEAR LABELS OR MARKINGS INDICATING THIRD PARTY TESTING

LABORATORY LISTINGS ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.

10. ALL FIRE ALARM CABLES SHOULD BE INSTALLED IN METAL RACEWAYS.

11. ALL RACEWAY AND WIRING SHALL BE CONCEALED IN FINISHED SPACES AND MAY

BE EXPOSED IN UNFINISHED SPACES SUCH AS MECHANICAL AND ELECTRICAL

ROOMS. ALL RACEWAY AND WIRING SHALL BE ROUTED EITHER PERPENDICULAR

OR PARALLEL TO THE BUILDING'S STRUCTURAL COMPONENTS.

12. PROVIDE PULL AND JUNCTION BOXES AS REQUIRED TO MEET CODE AND

INSTALLATION REQUIREMENTS. PULL AND JUNCTION BOXES SHALL BE

CONCEALED IN FINISHED SPACES AND LOCATIONS SHALL BE COORDINATED WITH

THE WORK OF ALL OTHER TRADES SO AS TO AVOID CONFLICTS.

13. ALL CONDUCTORS SHALL BE IDENTIFIED AT EACH JUNCTION BOX, OUTLET BOX,

CABINET, PULL BOX, ETC., WITH VINYL SELF-ADHESIVE TAGS INDICATING PANEL

AND CIRCUIT NUMBER, CONTROL WIRE IDENTIFICATION NUMBER, OR OTHER

APPROPRIATE INFORMATION. ALL PULL AND JUNCTION BOXES SHALL BE LABELED

AS TO FUNCTION.

14. ALL EQUIPMENT SHALL BE SECURELY FASTENED BY MEANS OF ANCHORS, RODS,

HANGERS, SUPPORTS, GUIDES, SWAY BRACES, ETC., TO MAINTAIN ALIGNMENT

AND PREVENT EQUIPMENT MOVEMENT. ALL EQUIPMENT LOCATED IN SEISMIC

ZONES SHALL BE SECURED WITH MEANS APPROVED FOR THE SEISMIC

CLASSIFICATION ENCOUNTERED.

15. ALL PENETRATIONS OF FIRE OR SMOKE RATED CONSTRUCTION SHALL BE SEALED

WITH FIRESTOPPING MATERIALS APPROVED AND LISTED FOR THE RATING OF THE

CONSTRUCTION TO BE PENETRATED. PROVIDE DOCUMENTATION ON ALL SUCH

PENETRATION SEALING SYSTEMS FOR VERIFICATION OF PROPER INSTALLATION.

16. ALL PENETRATIONS OF ROOFS, EXTERIOR WALLS, FOUNDATIONS, OR OTHER

WATER OR MOISTURE PROOF CONSTRUCTION SHALL BE SEALED WITH

APPROPRIATE SEALING FITTINGS OR SEALED CONSTRUCTION TO PREVENT THE

INTRODUCTION OF MOISTURE INTO THE BUILDING.

17. WHERE EMPTY RACEWAYS ARE INSTALLED, THEY SHALL BE LABELED AT BOTH

ENDS AND FITTED WITH NYLON PULLSTRINGS FOR FUTURE USE.

18. ELECTRICAL WORK SHALL BE PERFORMED ON DE-ENERGIZED SYSTEMS ONLY TO

PREVENT PERSONNEL INJURY AND POTENTIAL SYSTEM FAILURE. WHERE WORK

ON EXISTING SYSTEMS WILL REQUIRE INTERRUPTION OF ELECTRICAL SERVICE,

THEN TEMPORARY PROVISIONS ACCEPTABLE TO THE OWNER FOR TEMPORARY

POWER SHALL BE UTILIZED UNTIL THE WORK IS COMPLETE.

19. THE FIRE ALARM SYSTEM SHALL COMPLY WITH ALL RELATED NFPA, BUILDING

CODES AND LOCAL FIRE DEPARTMENT REGULATIONS.

20. WALL MOUNTED FIRE ALARM PULL STATIONS ARE TO BE LOCATED 46" A.F.F. AND

WITHIN 5' OF THE NEAREST ADJACENT EXIT DOOR FROM THE FLOOR OR

BUILDING.

21. WALL MOUNTED FIRE ALARM NOTIFICATION APPLIANCES, EITHER VISUAL, OR

COMBINATION AUDIO/VISUAL, SHALL BE LOCATED SUCH THAT THE ENTIRE LENS

OF THE VISUAL PORTION IS BETWEEN 80" AND 96" A.F.F. AUDIO ONLY APPLIANCES

SHALL BE LOCATED, NOT LESS THAN 90" A.F.F. TO TOP OF APPLIANCE, OR 6"

BELOW CEILING.

FIRE ALARM GENERAL NOTES

DUCT SMOKE DETECTOR

AREA SMOKE DETECTOR

DOOR RELEASE SMOKE DETECTOR

S O

U N

D G

E N

E R

A L

B U

IL

D

IN

LA

R

M

X

X

N O

T

IF

Y N

E C

E S

S A

R Y

S

TA

FF

X

INPUT

OUTPUT

N O

T

IF

Y F

IR

E

D E

P A

R M

E N

T

IN

IT

IA

T

E S

U P

E R

V

IS

O R

Y S

IG

N

A L

T O

A

4- H

O U

R M

A N

N E

D P

O

IN

T F

O R

IM

M

E D

IA

TE

R E

S P

O N

S E

X

C

LO

S E

A S

S O

C

IA

T E

S M

O K

E

B

R R

IE

R

D O

O R

S O

N T

H

LO

O

R

X

MANUAL PULL STATION

ELEVATOR MACHINE ROOM HEAT DETECTOR

SPRINKLER WATERFLOW / PRESSURE SWITCH

X

X

X

X

X

X

X

X

X

ELEVATOR SMOKE DETECTOR X X X

X

X

C

LO

S E

D A

M P

E R

S O

N F

P

R O

X

IM

A T

E T

O D

E T

E C

TO

R

X

X

S H

U T

D O

W N

A U

R H

A N

D

LE

S

R V

E D

B Y

T H

E D

E T

E C

T O

R

X1

1. DO NOT PROVIDE DUCT DETECTORS IN DEDICATED (100%) EXHAUST FANS, THEY SHOULD CONTINUE TO RUN.

R E

C A

LL

E

LE

V

A T

O R

X

IN

IT

IA

T

E E

LE

V

A T

O R

S H

U

D

O W

N A

N D

D

IS

C O

N N

E C

V A

T O

R P

O W

E R

X

O P

E N

L O

C K

E D

E G

R E

O

R S

O N

F

LO

O R

O F

F

IR

IG

IN

X

X

X

X

FIRE ALARM MATRIX

WATER CONTROL VALVE TAMPER SWITCH X

FIRE ALARM SYMBOLS

DEVICES

EXTERIOR BELL

SYMBOL DESCRIPTION

DETECTORS

MANUAL PULL STATION

SPEAKER ONLY CEILING MOUNTED

COMBINATION OF SPEAKER/STROBE WALL MOUNTED

SPEAKER ONLY WALL MOUNTED

STROBE ONLY CEILING MOUNTED

STROBE ONLY WALL MOUNTED

MNS SPEAKER/STROBE CEILING MOUNTED

GAS DETECTOR - CARBON MONOXIDE

HEAT DETECTOR - RATE OF RISE

SMOKE DETECTOR - IN DUCT

SMOKE DETECTOR - PHOTOELECTRIC

SWITCHES

FLOW DETECTOR/SWITCH

PRESSURE DETECTOR/SWITCH

VALVE SUPERVISORY SWITCH

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

FIRE ALARM TERMINAL CABINET

PANELS

LINE TYPES

SMOKE/ALARM ZONE BOUNDARY LINES

CODE DATA

OCCUPANCY BUSINESS

SPRINKLERS PARTIALLY SPRINKLERED

NOTIFICATION SPEAKERS, STROBES AND COMBINATION SPEAKER-STROBES IN

NORMALLY OCCUPIED AREAS

DETECTION MANUAL PULL-STATIONS, SPRINKLERS, SMOKE DETECTION

THROUGHOUT*, CO DETECTOR AT FUEL FIRED EQUIPMENT

FIRE ALARM

ZONING

FIRE ALARM SYSTEM TO BE ZONED PER FLOOR

* SMOKE DETECTION IS SHOWN THROUGHOUT BUILDING BUT NEED ONLY BE INSTALLED

WHERE THERE IS NO SPRINKLER DETECTION. ADDITIONALLY, IF FULL SPRINKLERED

PROTECTION IS PROVIDED AS PART OF A SEPARATE PROJECT, SMOKE DETECTION

DEVICES MAY BE REDUCED PER NFPA 72.

ELE. EQPT.

B1A100

OFFICE

B1A101

HRMS OFFICE

B1A102

OFFICE

B1A103

OFFICE

B1A104

OFFICE

B1A105

MECHANICAL

B1A106

HRMS

CONFERENCE

STORAGE

B1A107

HRMS OFFICE

B1A108

OFFICE

B1A105A

OFFICE

B1A105B

SERVICE

ROOM

B1B100

WOMEN

B1B101

MEN

B1B102

XEROX/ E-QUIP

B1B104

SWING ROOM

B1B105

HRMS

OFFICE

B1B106

PIV

B1B107

HRMS

CONFERENCE

B1B108

HRMS

OFFICE

B1B109

HRMS

OFFICE

B1B110

ELE. CLO.

B1B111

TEL.

B1B108A

IDF

B1B108B

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12

FA05

FA01

ELEVATOR PUMP

ROOM

B1A100A

VESTIBULE

B1B103A

VESTIBULE

B1B102A

CORRIDOR

CB1-1

CORRIDOR

CB1-2

FIRE ALARM

CONTROL PANEL

CORRIDOR CB1-1

NOTIFICATION APPLIANCES

GROUND LEVEL FIRE/SMOKE

INITIATING DEVICES GROUND LEVEL

FIRE/SMOKE

GROUND LEVEL

NOTE: CONTRACTOR SHALL

VERIFY ALL NECESSARY DEVICE

COUNTS

NOTIFICATION APPLIANCES

LEVEL 1 FIRE/SMOKE

INITIATING DEVICES

LEVEL 1 FIRE/SMOKE

LEVEL 1

NOTIFICATION APPLIANCES

LEVEL 2 FIRE/SMOKE

INITIATING DEVICES

LEVEL 2 FIRE/SMOKE

LEVEL 2

MAIN GRAPHIC ANNUCIATOR IN

BUILDINGS 225 AND 18

KEYNOTE LEGEND

FA01 EXISTING FIRE ALARM CONTROL PANEL.

FA05 HEAT DETECTOR IN ELEVATOR MACHINE ROOM MAY BE OMITTED IF NO SPRINKLER

IS PRESENT.

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

PARTIALLY

SPRINKLERED Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

6/25/2021

100% BID SET BUILDING 2 - ADMINISTRATIVE

4800 MEMORIAL DRIVE

WACO, TX 76711

024-10122-000

JLHMAR

FIRE ALARM PLAN - BASEMENT

LEVEL

2-FA101

2 83

-1

-0

F A

/3

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

ALARM CAMPUS UPGRADE

NTRUE

NORTH

SCALE: 1/8" = 1'-0"

A13

BUILDING 2 - FIRE ALARM PLAN - BASEMENT LEVEL

SCALE: NTS

F11

BUILDING 2 - FIRE ALARM RISER DIAGRAM

VA Project Number:

674A4-21-108

S

S C

M

C

CO

H R

S

ID

S P

WF

PS

VS

FAA

FACP

FATC

C S C CS C

F

C

S C

F

C

S P

WF

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P S

P S

P

S P

S P

S P

S P

S P

VS

FIRE ALARM SYMBOLS

DEVICES

EXTERIOR BELL

SYMBOL DESCRIPTION

DETECTORS

MANUAL PULL STATION

SPEAKER ONLY CEILING MOUNTED

COMBINATION OF SPEAKER/STROBE WALL MOUNTED

SPEAKER ONLY WALL MOUNTED

STROBE ONLY CEILING MOUNTED

STROBE ONLY WALL MOUNTED

MNS SPEAKER/STROBE CEILING MOUNTED

GAS DETECTOR - CARBON MONOXIDE

HEAT DETECTOR - RATE OF RISE

SMOKE DETECTOR - IN DUCT

SMOKE DETECTOR - PHOTOELECTRIC

SWITCHES

FLOW DETECTOR/SWITCH

PRESSURE DETECTOR/SWITCH

VALVE SUPERVISORY SWITCH

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

FIRE ALARM TERMINAL CABINET

PANELS

LINE TYPES

SMOKE/ALARM ZONE BOUNDARY LINES

MHBM

1A100

MHBM

1A101

OFFICE

1A102C

MHBM

1A103

BREAK ROOM

1A104

NURSING

1A105

NURSING

1B100

HAC

1B101

WOMENS

1B102

MENS

1B103

DIRECTOR'S

CONFERENCE

ROOM

1B104

NURSING

CONFERENCE

ROOM

1B105

NURSING

1B106

NURSING

1B107

NURSING

1B108WORK ROOM

1B108A

OFFICE

1A102A

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12

OFFICE

1A102

OFFICE

1A102E

OFFICE

1A102F

CORRIDOR

C1-3

TOILET

1A102B

ELEVATOR

VESTIBULE

1B102A

VESTIBULE

1B103A

STAIR 2

CORRIDOR

C1-1

CORRIDOR

C1-2

STAIR 1

KEYNOTE LEGEND

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1 /2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

PARTIALLY

SPRINKLERED Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

6/25/2021

100% BID SET BUILDING 2 - ADMINISTRATIVE

4800 MEMORIAL DRIVE

WACO, TX 76711

024-10122-000

JLHMAR

FIRE ALARM PLAN - LEVEL 1

2-FA102

2 3

-1

-0

F A

/2

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

ALARM CAMPUS UPGRADE

NTRUE

NORTH

SCALE: 1/8" = 1'-0"

A13

BUILDING 2 - FIRE ALARM PLAN - LEVEL 1

VA Project Number:

S

S C

M

C

CO

H R

S

ID

S P

WF

PS

VS

FAA

FACP

FATC

C S C CC

F

C

C

F

S P

C S C

C

S P

H R

WF

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

VS

FIRE ALARM SYMBOLS

DEVICES

EXTERIOR BELL

SYMBOL DESCRIPTION

DETECTORS

MANUAL PULL STATION

SPEAKER ONLY CEILING MOUNTED

COMBINATION OF SPEAKER/STROBE WALL MOUNTED

SPEAKER ONLY WALL MOUNTED

STROBE ONLY CEILING MOUNTED

STROBE ONLY WALL MOUNTED

MNS SPEAKER/STROBE CEILING MOUNTED

GAS DETECTOR - CARBON MONOXIDE

HEAT DETECTOR - RATE OF RISE

SMOKE DETECTOR - IN DUCT

SMOKE DETECTOR - PHOTOELECTRIC

SWITCHES

FLOW DETECTOR/SWITCH

PRESSURE DETECTOR/SWITCH

VALVE SUPERVISORY SWITCH

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

FIRE ALARM TERMINAL CABINET

PANELS

LINE TYPES

SMOKE/ALARM ZONE BOUNDARY LINES

EQUIPMENT

2A100

MAS

2A101

MAS

2A102

MAS

2A103

CONFERENCE

ROOM

2A104

MAS

2A105A

BREAK ROOM

2A106

WACO

COMPUTER

TRAINING

2A107

RESTROOM

2B100

QS&V (OFF. OF

DIRECTOR)

2B101

NURSING

EDUCATION

ROOM

2B102

QS&V (OFF OF

DIRECTOR)

2B103

QS&V (OFF. OF

DIRECTOR)

2B104

NURSING

2B105

MAS

2A105

NURSING

2A108

NURSING

2A109

QS&V (OFF. OF

DIRECTOR)

2A110

QS&V (OFF. OF

DIRECTOR)

2A111

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9 10 11 12

FA04

KEYNOTE LEGEND

FA04 SMOKE AND HEAT DETECTION AT TOP OF ELEVATOR SHAFT MAY BE OMITTED IF NO

SPRINKLER IS PRESENT. DEVICES THAT ARE INSTALLED WILL BE INSTALLED PER

NFPA 72 REQUIREMENTS

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1 /2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

PARTIALLY

SPRINKLERED Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

6/25/2021

100% BID SET BUILDING 2 - ADMINISTRATIVE

4800 MEMORIAL DRIVE

WACO, TX 76711

024-10122-000

JLHMAR

FIRE ALARM PLAN - LEVEL 2

2-FA103

2 3

-1

-0

F A

/2

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

ALARM CAMPUS UPGRADE

NTRUE

NORTH

SCALE: 1/8" = 1'-0"

A13

BUILDING 2 - FIRE ALARM PLAN - LEVEL 2

VA Project Number:

S

S C

M

C

CO

H R

S

ID

S P

WF

PS

VS

FAA

FACP

FATC

1. PROVIDE AND INSTALL A NEW FIRE ALARM SYSTEM THROUGHOUT THE BUILDING

PER THE VA DESIGN GUIDE AND NFPA 72. REFER TO SPEC SECTION 28 31 00

INTERIOR FIRE ALARM SYSTEM. FIRE ALARM SYSTEM WILL BE ZONED PER FLOOR.

2. ALL EXISTING FIRE ALARM DEVICES, PANELS AND RELATED EQUIPMENT ARE TO

BE DEMOLISHED. EXISTING ALARM SYSTEMS MUST REMAIN IN-SERVICE AND

FUNCTIONAL WHILE NEW ALARM SYSTEM IS INSTALLED. FOLLOW ILSM

PROTOCOLS FOR SHUTDOWN AND PHASE DEMO OF EXISTING ALARM SYSTEM SO

THAT REMOVAL ONLY OCCURS ONCE NEW ALARM SYSTEM IS FULLY INSTALLED

AND FUNCTIONAL.

3. ALL EXISTING INTERFACING DEVICES (TAMPERS, FLOWS, PRESSURE SWITCHES,

ETC) WILL BE CONNECTED TO THE NEW FA SYSTEM AND REPORT TO THE MAIN

GRAPHIC ANNUNCIATORS IN BUILDING 225. A SECONDARY MONITORY STATION

SHALL BE LOCATED IN BUILDING 18. INTERFACING DEVICES ARE SHOWN WHEN

LOCATIONS ARE KNOWN, HOWEVER THE DRAWINGS SHOULD NOT BE USED AS

EXHAUSTIVE LIST. THE EXISTING CAMPUS FIRE ALARM SYSTEM WILL NOT BE

REUSED AND A NEW CAMPUS WIDE SYSTEM IS TO BE PROVIDED, SEE FIRE ALARM

SITE PLAN.

4. COORDINATE FIRE ALARM SYSTEM DEVICE LOCATIONS WITH LIGHT FIXTURES,

STRUCTURAL MEMBERS, SPRINKLER HEADS AND PIPING, HVAC EQUIPMENT AND

DUCTWORK. CONTRACTOR TO VERIFY LOCATIONS OF DUCT SMOKE DETECTORS

AND CONNECT TO NEW FIRE ALARM SYSTEM.

5. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE AND

SATISFACTORILY OPERATING SYSTEMS AS INDICATED ON THE CONTRACT

DOCUMENTS AND AS EVIDENTLY INTENDED. IT IS NOTED THAT THE DRAWINGS

ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENTS OF SYSTEMS AND

WORK. INTERCONNECTIONS HAVE BEEN SHOWN, AND THE CONTRACTOR SHALL

FURNISH AND INSTALL CONDUIT AND WIRING AS REQUIRED TO ACCOMPLISH THE

FUNCTIONS INDICATED. ADDITIONALLY, FIRE ALARM SYSTEMS HAVE BEEN

SHOWN AND THE CONTRACTOR SHALL FURNISH AND INSTALL THE REQUIRED

QUANTITIES AND TYPES OF CABLES, CONDUCTORS, RACEWAYS, REMOTE POWER

SUPPLIES AND CONNECTIONS, SHIELDING REQUIREMENTS, ETC., AS REQUIRED

BY THE SYSTEM MANUFACTURER, THE SPECIFICATIONS, AND ANY APPLICABLE

CODES. ALL WIRING SHOWN ON RISER DIAGRAMS SHALL ALSO BE FURNISHED

AND INSTALLED REGARDLESS OF WHETHER THESE ITEMS ARE SHOWN ON THE

FLOOR PLANS.

6. THE CONTRACTOR SHALL COORDINATE THE ELECTRICAL WORK WITH THE WORK

OF ALL OTHER TRADES AND EXISTING CONDITIONS SO AS TO AVOID CONFLICTS.

RESOLVE ALL CONFLICTS THROUGH THE A/E PRIOR TO ROUGH-IN. FAILURE TO

PROVIDE SUCH COORDINATION PRIOR TO WORK BEING INSTALLED SHALL NOT BE

CAUSE FOR ADDITIONAL COMPENSATION TO THE CONTRACTOR, AND MAY

RESULT IN REJECTION OF THE WORK.

7. ADDITIONAL DEVICES MAY BE REQUIRED. DO NOT USE THESE DRAWINGS FOR

DEVICE COUNTS.

8. ALL MATERIALS SHALL BE NEW, SHALL BE SUITABLE FOR THE APPLICATION

INTENDED, AND SHALL BEAR LABELS OR MARKINGS INDICATING THIRD PARTY

TESTING LABORATORY LISTINGS ACCEPTABLE TO THE AUTHORITY HAVING

JURISDICTION.

9. EXISTING CONDUIT IN GOOD CONDITION THAT HAS BEEN SALVAGED FROM OTHER

BUILDINGS MAY BE REUSED IF POSSIBLE AND SHALL BE STRIPED IN PATIENT

AREAS. NEW CONDUIT SHALL BE MARKED WITH RED COUPLINGS. ALL OTHER

MATERIALS SHALL BE NEW, SHALL BE SUITABLE FOR THE APPLICATION INTENDED,

AND SHALL BEAR LABELS OR MARKINGS INDICATING THIRD PARTY TESTING

LABORATORY LISTINGS ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.

10. ALL FIRE ALARM CABLES SHOULD BE INSTALLED IN METAL RACEWAYS.

11. ALL RACEWAY AND WIRING SHALL BE CONCEALED IN FINISHED SPACES AND MAY

BE EXPOSED IN UNFINISHED SPACES SUCH AS MECHANICAL AND ELECTRICAL

ROOMS. ALL RACEWAY AND WIRING SHALL BE ROUTED EITHER PERPENDICULAR

OR PARALLEL TO THE BUILDING'S STRUCTURAL COMPONENTS.

12. PROVIDE PULL AND JUNCTION BOXES AS REQUIRED TO MEET CODE AND

INSTALLATION REQUIREMENTS. PULL AND JUNCTION BOXES SHALL BE

CONCEALED IN FINISHED SPACES AND LOCATIONS SHALL BE COORDINATED WITH

THE WORK OF ALL OTHER TRADES SO AS TO AVOID CONFLICTS.

13. ALL CONDUCTORS SHALL BE IDENTIFIED AT EACH JUNCTION BOX, OUTLET BOX,

CABINET, PULL BOX, ETC., WITH VINYL SELF-ADHESIVE TAGS INDICATING PANEL

AND CIRCUIT NUMBER, CONTROL WIRE IDENTIFICATION NUMBER, OR OTHER

APPROPRIATE INFORMATION. ALL PULL AND JUNCTION BOXES SHALL BE LABELED

AS TO FUNCTION.

14. ALL EQUIPMENT SHALL BE SECURELY FASTENED BY MEANS OF ANCHORS, RODS,

HANGERS, SUPPORTS, GUIDES, SWAY BRACES, ETC., TO MAINTAIN ALIGNMENT

AND PREVENT EQUIPMENT MOVEMENT. ALL EQUIPMENT LOCATED IN SEISMIC

ZONES SHALL BE SECURED WITH MEANS APPROVED FOR THE SEISMIC

CLASSIFICATION ENCOUNTERED.

15. ALL PENETRATIONS OF FIRE OR SMOKE RATED CONSTRUCTION SHALL BE SEALED

WITH FIRESTOPPING MATERIALS APPROVED AND LISTED FOR THE RATING OF THE

CONSTRUCTION TO BE PENETRATED. PROVIDE DOCUMENTATION ON ALL SUCH

PENETRATION SEALING SYSTEMS FOR VERIFICATION OF PROPER INSTALLATION.

16. ALL PENETRATIONS OF ROOFS, EXTERIOR WALLS, FOUNDATIONS, OR OTHER

WATER OR MOISTURE PROOF CONSTRUCTION SHALL BE SEALED WITH

APPROPRIATE SEALING FITTINGS OR SEALED CONSTRUCTION TO PREVENT THE

INTRODUCTION OF MOISTURE INTO THE BUILDING.

17. WHERE EMPTY RACEWAYS ARE INSTALLED, THEY SHALL BE LABELED AT BOTH

ENDS AND FITTED WITH NYLON PULLSTRINGS FOR FUTURE USE.

18. ELECTRICAL WORK SHALL BE PERFORMED ON DE-ENERGIZED SYSTEMS ONLY TO

PREVENT PERSONNEL INJURY AND POTENTIAL SYSTEM FAILURE. WHERE WORK

ON EXISTING SYSTEMS WILL REQUIRE INTERRUPTION OF ELECTRICAL SERVICE,

THEN TEMPORARY PROVISIONS ACCEPTABLE TO THE OWNER FOR TEMPORARY

POWER SHALL BE UTILIZED UNTIL THE WORK IS COMPLETE.

19. THE FIRE ALARM SYSTEM SHALL COMPLY WITH ALL RELATED NFPA, BUILDING

CODES AND LOCAL FIRE DEPARTMENT REGULATIONS.

20. WALL MOUNTED FIRE ALARM PULL STATIONS ARE TO BE LOCATED 46" A.F.F. AND

WITHIN 5' OF THE NEAREST ADJACENT EXIT DOOR FROM THE FLOOR OR

BUILDING.

21. WALL MOUNTED FIRE ALARM NOTIFICATION APPLIANCES, EITHER VISUAL, OR

COMBINATION AUDIO/VISUAL, SHALL BE LOCATED SUCH THAT THE ENTIRE LENS

OF THE VISUAL PORTION IS BETWEEN 80" AND 96" A.F.F. AUDIO ONLY APPLIANCES

SHALL BE LOCATED, NOT LESS THAN 90" A.F.F. TO TOP OF APPLIANCE, OR 6"

BELOW CEILING.

FIRE ALARM GENERAL NOTES

DUCT SMOKE DETECTOR

AREA SMOKE DETECTOR

DOOR RELEASE SMOKE DETECTOR

S O

U N

D G

E N

E R

A L

B U

IL

D

R

M

X

X

N O

T

IF

Y N

E C

E S

S A

R Y

S

INPUT

OUTPUT

N O

T

IF

Y F

IR

E

D E

P A

R M

E

IN

IT

IA

T

E S

U P

E R

V

IS

O R

Y S

IG

N

A L

T O

A

4- H

O U

R M

A N

N E

D P

O

IN

T F

O R

IM

M

E D

IA

TE

R E

S P

O N

S E

X

C

LO

S E

A S

S O

C

IA

T E

S M

O

R R

IE

R

D O

O R

S O

N T

O

R

X

MANUAL PULL STATION

ELEVATOR MACHINE ROOM HEAT DETECTOR

SPRINKLER WATERFLOW / PRESSURE SWITCH

X

X

X

X

X

X

X

X

X

ELEVATOR SMOKE DETECTOR X X X

X

X

C

LO

S E

D A

M P

E R

S O

N F

O

X

IM

A T

E T

O D

E T

E C

TO

R

X

X

S H

U T

D O

W N

A U

R H

A N

D

R V

E D

B Y

T H

E D

E T

E C

T O

R

X1

R E

C A

LL

E

LE

V

A T

O R

X

IN

IT

IA

T

E E

LE

V

A T

O R

S H

W

N A

N D

D

IS

C O

N N

E

V A

T O

R P

O W

E R

X

O P

E N

L O

C K

E D

E G

R E

O

R S

O N

F

LO

O R

O F

F

IG

IN

X

X

X

X

FIRE ALARM MATRIX

WATER CONTROL VALVE TAMPER SWITCH

1. DO NOT PROVIDE DUCT DETECTORS IN DEDICATED (100%) EXHAUST FANS, THEY SHOULD CONTINUE TO RUN.

X

FIRE ALARM SYMBOLS

DEVICES

EXTERIOR BELL

SYMBOL DESCRIPTION

DETECTORS

MANUAL PULL STATION

SPEAKER ONLY CEILING MOUNTED

COMBINATION OF SPEAKER/STROBE WALL MOUNTED

SPEAKER ONLY WALL MOUNTED

STROBE ONLY CEILING MOUNTED

STROBE ONLY WALL MOUNTED

MNS SPEAKER/STROBE CEILING MOUNTED

GAS DETECTOR - CARBON MONOXIDE

HEAT DETECTOR - RATE OF RISE

SMOKE DETECTOR - IN DUCT

SMOKE DETECTOR - PHOTOELECTRIC

SWITCHES

FLOW DETECTOR/SWITCH

PRESSURE DETECTOR/SWITCH

VALVE SUPERVISORY SWITCH

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

FIRE ALARM TERMINAL CABINET

PANELS

LINE TYPES

SMOKE/ALARM ZONE BOUNDARY LINES

CODE DATA

OCCUPANCY BUSINESS

SPRINKLERS FULLY SPRINKLERED

NOTIFICATION SPEAKERS, STROBES AND COMBINATION SPEAKER-STROBES IN

NORMALLY OCCUPIED AREAS

DETECTION MANUAL PULL-STATIONS, SPRINKLERS, SMOKE DETECTOR AT

FACP, CO DETECTOR AT FUEL FIRED EQUIPMENT

FIRE ALARM

ZONING

FIRE ALARM SYSTEM TO BE ZONED PER FLOOR

* SMOKE DETECTION IS SHOWN THROUGHOUT BUILDING BUT NEED ONLY BE INSTALLED

WHERE THERE IS NO SPRINKLER DETECTION. ADDITIONALLY, IF FULL SPRINKLERED

PROTECTION IS PROVIDED AS PART OF A SEPARATE PROJECT, SMOKE DETECTION

DEVICES MAY BE REDUCED PER NFPA 72.

FIRE ALARM

CONTROL PANEL

RM BA139

NOTIFICATION APPLIANCES

GROUND LEVEL FIRE/SMOKE

INITIATING DEVICES GROUND LEVEL

FIRE/SMOKE

GROUND LEVEL

NOTE: CONTRACTOR SHALL

VERIFY ALL NECESSARY DEVICE

COUNTS

NOTIFICATION APPLIANCES

LEVEL 1 FIRE/SMOKE

INITIATING DEVICES

LEVEL 1 FIRE/SMOKE

LEVEL 1

MAIN GRAPHIC ANNUCIATOR IN

BUILDINGS 225 AND 18

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

FULLY

SPRINKLERED Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

6/25/2021

100% BID SET BLDG 4 - OPC / PHARM. / LAB / RAD.

4800 MEMORIAL DRIVE

WACO, TX 76711

024-10122-000

JLHMAR

FIRE ALARM GENERAL NOTES AND

DETAILS

4-FA001

4 1 3

-1

-0

F A

/2

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

ALARM CAMPUS UPGRADE

SCALE: NTS

A6

BUILDING 4 - FIRE ALARM RISER DIAGRAM

VA Project Number:

UP

UP

UP

UP

C

C

C C S C

C

S C

S C

S C

C

CC

C

C S C M

C

S C

C C

F

F

F

F

F

F

F FF

C

S P

CO

C

S C

C

S C

C

F

C

C

C

S C

C

C

S CC

CS C

C

C

S C C

S C

C

S C

C

PSVSWF

WF VS

VS

VS

PS

M

C

C

C

C

F

S C

C

S C

S P

H R

F F A C P

S P

F

F A A

F

F

S

S C

M

C

CO

H R

S

ID

S P

WF

PS

VS

FAA

FACP

FATC

ELECTRICAL

BA130

WOMEN

RESTROOM

BA125B

NURSING OFFICE

CB15

MENS

RESTROOM

BA125A

WAITING AREA

CB2B

CORRIDOR

CB5

HOUSEKEEPING

BA166

WOMEN

RESTROOM

BA164

ESCORT

BB103-D

CORRIDOR

CB23

STORAGE,

GENERAL

BA139

COFFEE BAR

BA173

CONTROLLED

NARCOTICS

BB104

ELECTRICAL

ROOM

BA172

PHARMACIST

BA169

PHARMACY

BB104A

EXAM ROOM

BA117

DIABETICS/

TELERETINAL

IMAGING

BA112

EXAM ROOM

BA109

HAC

BB102

PHARMACY

BREAK ROOM

BB103

PATIENT REP

BA170

MECHANICAL

ROOM

BA171

EMS STORAGE

BB100

MED SUPPLY

STORAGE

BA115

AMBULANCE

ENTRANCE

CB2C

RESTROOM

BA110

TREATMENT

ROOM

BA106

TREATMENT

ROOM

BA107

EXAM ROOM

BA111

EXAM ROOM

BA113

AMBULATORY

CARE DESK

BA114

EXAM ROOM

BA153

MEANS TEST

BA101B

PROCESSING/REGISTRATION

BA101C

VET ID CARD

BA101A

WAITING AREA

CB2A

MENS

RESTROOM

BA168

PRIMARY CARE

OFFICE

BA163

CAFE

BB101

CLEAN LINEN

CB-18A

SOILED LINEN

CB-18B

TELEHEALTH

BB103-F

PHARMACY HELP

LINE

BB103B

PHARMACY

WAITING

BB103-C

TELEHEALTH

BB103-E

EXAM ROOM

BA161

PHARMACY

BA162

CORRIDOR

CB2

CORRIDOR

CB20

CORRIDOR

CB10

CORRIDOR

CB17

CORRIDOR

CB11

CORRIDOR

CB8

CORRIDOR

CB16

CORRIDOR

ELEVATOR

LOBBY

CB-18

ELEVATOR

MACHINE ROOM

BA100

STAIR 2

BAS2

STORAGE

NO

LABEL

SUB BSMT

ACCESS

VIDEO ROOM

BA105

CHASE

BB100A

STAIR 6

BAS6

STAIR 5

BAS5

TREATMENT

ROOM

BA157

EXAM ROOM

BA160

EXAM ROOM

BA156

EXAM ROOM

BA159

DISPOSITION

AREA

BA123

SOCIAL WORKER

BA129

OFFICE

BA124

EXAM ROOM

BA121

MAROON TEAM

CHECK-IN DESK

BA122

WAITING AREA

BA149

NURSING

INTERVEIW

ROOM

BA152

UNISEX

RESTROOM

BA145B

CORRIDOR

CB14

IMAGING

RECEPTION

BA146

EXAM ROOM

BA155

WAITING AREA

2 EXAM ROOM

BA154

FORM STORAGE

SUPERVISOR

BA103

OFFICE

BA116

INFORMATION

RECEPTIONIST

BA101

ELECTRICAL

BA119

COMMUNICATIONS

CLOSET

BA120

CLINIC MANAGER

BA118

CLEAN LINEN

ROOM

BA103-3

EXAM ROOM

BA104

SOILED UTILITY

BA103-2

STORAGE,

EQUIPMENT

BA103-1OXYGEN

BA103-4

EXAM ROOM

BA167

HOUSEKEEPING

BA127

NURSE

BA126

STAFF LOUNGE

BA125

VESTIBULE

CB1

MULTI PURPOSE

ROOM

BA165

CORRIDOR

CB3

NURSE LOCKER

ROOM

BA128

WAITING AREA

CORRIDOR

XXX

PROGRAM CLERK

BA132

NURSE MANAGER

BA131

MENS

RESTROOM

BA137

OFFICE

BA133

NUTRITION

CLINIC DIETITION

BA129A

WAITING AREA

B13A

CORRIDOR

CB12

PATIENT FUNDS

BA138

TRAVEL

BA134

WOMENS

RESTROOM

BA136

STAIR 1

BAS1

SUB BASEMENT

ACCESS

AGENT CASHIER

BA135

CORRIDOR

CB13

ULTRASOUND

BA147A

IMAGING

EDUCATION

BA144 STORAGE,

GENERAL

TECH OFFICE

BA143

CT SCAN

BA145

IMAGING

MANAGEMENT

BA148

CT CONTROL

BA145A

IMAGING OFFICE

BA142

X-RAY IMAGING

BA140

VESTIBULE

9 DIGITAL

PROCESSING

BA141A

X-RAY IMAGING

BA141

RESTROOM

BA140A

TOILET

BA163A

1 2 3 5

6 7 8 9 10 11 12

13 14 15

A

B

C

D

E

F

G

H

I

J

K

L

BUILDING 4 BUILDING 202

FA05

FA01

FA03

FIRE ALARM SYMBOLS

DEVICES

EXTERIOR BELL

SYMBOL DESCRIPTION

DETECTORS

MANUAL PULL STATION

SPEAKER ONLY CEILING MOUNTED

COMBINATION OF SPEAKER/STROBE WALL MOUNTED

SPEAKER ONLY WALL MOUNTED

STROBE ONLY CEILING MOUNTED

STROBE ONLY WALL MOUNTED

MNS SPEAKER/STROBE CEILING MOUNTED

GAS DETECTOR - CARBON MONOXIDE

HEAT DETECTOR - RATE OF RISE

SMOKE DETECTOR - IN DUCT

SMOKE DETECTOR - PHOTOELECTRIC

SWITCHES

FLOW DETECTOR/SWITCH

PRESSURE DETECTOR/SWITCH

VALVE SUPERVISORY SWITCH

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

FIRE ALARM TERMINAL CABINET

PANELS

LINE TYPES

SMOKE/ALARM ZONE BOUNDARY LINES

SCALE: 1/8" = 1'-0"

A12

BUILDING 4 - FIRE ALARM PLAN - BASEMENT LEVEL

KEYNOTE LEGEND

FA01 EXISTING FIRE ALARM CONTROL PANEL.

FA03 EXISTING ANNUNCIATOR LOCATION

FA05 HEAT DETECTOR IN ELEVATOR MACHINE ROOM MAY BE OMITTED IF NO SPRINKLER

IS PRESENT.

NTRUE

NORTH

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1 /2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

FULLY

SPRINKLERED Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

6/25/2021

100% BID SET BLDG 4 - OPC / PHARM. / LAB / RAD.

4800 MEMORIAL DRIVE

WACO, TX 76711

024-10122-000

JLHMAR

FIRE ALARM PLAN - BASEMENT

LEVEL

4-FA101

4 2 3

-1

-0

F A

/3

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

ALARM CAMPUS UPGRADE

VA Project Number:

DN

DN

DN

DN

DN

DN

DN

DN

UP

UP

F

F

F

F

F

C

C S C C

C

C

C

S C

C S C C

S C

C

C

C

S P

S CC

C

C

C

S CC

C

S C

C

H R

VS WF

WFVS

C C

F

C

C

C

C

C

C C

C

CC

C

C

S P

H R

S P

C C C

C

F

F

S

S C

M

C

CO

H R

S

ID

S P

WF

PS

VS

FAA

FACP

FATC

MEN'S LOCKER

1A100A

MEN'S

RESTROOM

1A100B

OFFICE

1A107A

OFFICE

1A104

CORRIDOR

1A106C

OFFICE

1A107

OFFICE

1A104A

BIOSAFETY

LOUNGE

1A100

PHLEBOTOMY

SUPPLY ROOM

1A-157A

ELEVATOR MACH.

ROOM

1A156

HEMATOLOGY

1A157F

WOMEN'S

LOCKER

1A100CWOMEN'S

RESTROOM

1A100D

SERVER ROOM

1A106

HOUSEKEEPING

1A128

EXAM ROOM

1A114

SERVER ROOM

FOYER

OFFICE/EXAM

1A103A

SPD CLOSET

1A129

LIQUID NITROGEN

1A151

SERVER ROOM

1A105

STORAGE

STORAGE

CHEMISTRY

1A157E

URINALYSIS

1A157H

LEVEL 3 LAB

SUITE

1A157

PCR LAB

1A157I

LAB OFFICE

1A157L

DECONTAMINATION

ROOM

1A157K

COPY/STORAGE

1A126A

CLINIC

RECEPTION

1A126

ELECTRICAL

CLOSET

1A109

CORRIDOR

C1-7

STAIR 4

1S4

GLUCOSE METER

CLINIC

1A122

OFFICE/EXAM

1A103

SECRETARY

1A-157C

TOXICOLOGY

1A157G

CORRIDOR

DEIONIZED

WATER

1A-157B

HOUSEKEEPING

1A157R

ANCILLARY

TESTING OFFICE

1A157P

ANCILLARY

TESTING

1A157N STAIR 2

1S2

LIFT

MANAGER'S

OFFICE

1A157D

VIEWING ROOM

1A157J1

STERILE/SOLUTION

PREP

1A157M

MYCOBACTERIOLOGY

ROOM

1A157J2

MYCOLOGY

1A157J3

CORRIDOR

C1 10

CORRIDOR

C1 12

WAITING

C1 1C

WAITING

C1 8A

CORRIDOR

C1 8

STAIR 3

1S3

CORRIDOR

C1 13

WAITING

C1

11D

WORKROOM

1A145C

CORRIDOR

C1 11

COMMUNICATIONS

CLOSET

1A134A

EXAM ROOM

1A135

TELEPHONE

CLOSET

1A110A

EXAM ROOM

1A149

SOILED

UTILITY/LINEN

1A150

CLEAN LINEN

1A130

OFFICE/EXAM

1A146

RESTROOM

1A148

GROUP

CLINIC/EXAM

1A152

LAB COLLECTION

AREA

1A127

CORRIDOR

RESTROOM

1A127A

EXAM ROOM

1A152A

STORAGE

CLOSET

1A145A

HEALTH

TECHNICIAN

1A144

SPEECH/LANGUAGE

PATHOLOGIST

1A143

WAITING ROOM

C1

13A

HEARING AID

REPAIR

1A140

HEARING

AID/EVOKED

RESPONSE

TESTING

1A142

CLINICAL

AUDIOLOGIST

1A141

OFFICE/EXAM

1A147

PULMONARY

FUNCTION

1A145

OFFICE/EQUPT.

STORAGE

1A145B

FIRE SIGNAL

CLOSET

1A133

RECEPTION

CUBICLE

C1

11C

RECEPTION

CUBICLE

C1-151

ELECTRICAL

CLOSET

1A134

EKG ROOM

1A132

STAIR 1

1S1

STAIR 5

1S5

STAIR 6

1S6

ATTIC ACCESS

1A108

WOMEN'S

RESTROOM

1A102

MEN'S

RESTROOM

1A101

RESTROOM

154A

PROCEDURE

ROOM

1A154

EXAM ROOM

1A153

CORRIDOR

C1

151CORRIDOR

C1 9

SOUND BOOTH

1A

SOUND BOOTH

SOUND BOOTH

CORRIDOR

ELEVATOR

LOBBY

C1 1A

ELEVATOR

LOBBY

C1 8C

CORRIDOR

C1 14

CORRIDOR

C1 6

CORRIDOR

C1 2

CORRIDOR

C1 1

STORAGE ROOM

1A117

EXAM ROOM

1A116

NURSE

1A119

PHYSICIAN

WORK/CONF

ROOM

1A121

OFFICE/EXAM

1A113

TREATMENT

ROOM

1A136

AUDIOLOGIST

BOOTH 2

1A137

PHYSICIAN EXAM

ROOM

1A118

EXAM ROOM

1A124

NURSE

1A125

EXAM ROOM

1A155

MEN'S

RESTROOM

1A123

EMPLOYEE

BREAK ROOM

1A110

EXAM ROOM

1A115

WOMEN'S

RESTROOM

1A120

OFFICE/EXAM

1A111

NURSES/TREATMENT

ROOM

1A112

1 2 3 5

6 7 8 9 10 11 12

13 14 15

A

B

C

D

E

F

G

H

I

J

K

L

FA04

FA05

FA06

FA04

FIRE ALARM SYMBOLS

DEVICES

EXTERIOR BELL

SYMBOL DESCRIPTION

DETECTORS

MANUAL PULL STATION

SPEAKER ONLY CEILING MOUNTED

COMBINATION OF SPEAKER/STROBE WALL MOUNTED

SPEAKER ONLY WALL MOUNTED

STROBE ONLY CEILING MOUNTED

STROBE ONLY WALL MOUNTED

MNS SPEAKER/STROBE CEILING MOUNTED

GAS DETECTOR - CARBON MONOXIDE

HEAT DETECTOR - RATE OF RISE

SMOKE DETECTOR - IN DUCT

SMOKE DETECTOR - PHOTOELECTRIC

SWITCHES

FLOW DETECTOR/SWITCH

PRESSURE DETECTOR/SWITCH

VALVE SUPERVISORY SWITCH

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM CONTROL PANEL

FIRE ALARM TERMINAL CABINET

PANELS

LINE TYPES

SMOKE/ALARM ZONE BOUNDARY LINES

SCALE: 1/8" = 1'-0"

A12

BUILDING 4 - FIRE ALARM PLAN - LEVEL 1 NTRUE

NORTH

KEYNOTE LEGEND

FA04 SMOKE AND HEAT DETECTION AT TOP OF ELEVATOR SHAFT MAY BE OMITTED IF NO

SPRINKLER IS PRESENT. DEVICES THAT ARE INSTALLED WILL BE INSTALLED PER

NFPA 72 REQUIREMENTS

FA05 HEAT DETECTOR IN ELEVATOR MACHINE ROOM MAY BE OMITTED IF NO SPRINKLER

IS PRESENT.

FA06 PROVIDE FIRE ALARM DEVICES IN THE CEILING SPACE

VA Project Number:

Building:

Drawing Number:

Project Title:

Project Location:

Issue Date:

Checked By: Drawn By:

Drawing Title:

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

A

Submission:

ARCHITECT / ENGINEER OF RECORD:

Revisions: Date:

CONSULTANTS:

/8

/4

/8

/2

/4

-1

/2

FIRE PROTECTION:

LEO A DALY

730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez

ARCHITECT:

CB DESIGN GROUP

421 KING ST., SUITE 301

ALEXANDRIA, VA 22314

POC: WES BRIDGES

703.772.4213

PROFESSIONAL SEAL:

2345678910111213141516

B

C

D

E

F

G

H

I

J

12345678910111213141516

FULLY

SPRINKLERED Drawing of

ELECTRICAL:

HUITT-ZOLLARS

500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts

6/25/2021

100% BID SET BLDG 4 - OPC / PHARM. / LAB / RAD.

4800 MEMORIAL DRIVE

WACO, TX 76711

024-10122-000

JLHMAR

FIRE ALARM PLAN - LEVEL 1

4-FA102

4 3 3

-1

-0

F A

/0

/2

.p d f

WACO VA MEDICAL CENTER - FIRE

ALARM CAMPUS UPGRADE

VA Project Number:

S

S C

M

C

CO

H R

S

ID

S P

WF

PS

VS

FAA

FACP

FATC

1. PROVIDE AND INSTALL A NEW FIRE ALARM SYSTEM THROUGHOUT THE BUILDING

PER THE VA DESIGN GUIDE AND NFPA 72. REFER TO SPEC SECTION 28 31 00

INTERIOR FIRE ALARM SYSTEM. FIRE ALARM SYSTEM WILL BE ZONED PER FLOOR.

2. ALL EXISTING FIRE ALARM DEVICES, PANELS AND RELATED EQUIPMENT ARE TO

BE DEMOLISHED. EXISTING ALARM SYSTEMS MUST REMAIN IN-SERVICE AND

FUNCTIONAL WHILE NEW ALARM SYSTEM IS INSTALLED. FOLLOW ILSM

PROTOCOLS FOR SHUTDOWN AND PHASE DEMO OF EXISTING ALARM SYSTEM SO

THAT REMOVAL ONLY OCCURS ONCE NEW ALARM SYSTEM IS FULLY INSTALLED

AND FUNCTIONAL.

3. ALL EXISTING INTERFACING DEVICES (TAMPERS, FLOWS, PRESSURE SWITCHES,

ETC) WILL BE CONNECTED TO THE NEW FA SYSTEM AND REPORT TO THE MAIN

GRAPHIC ANNUNCIATORS IN BUILDING 225. A SECONDARY MONITORY STATION

SHALL BE LOCATED IN BUILDING 18. INTERFACING DEVICES ARE SHOWN WHEN

LOCATIONS ARE KNOWN, HOWEVER THE DRAWINGS SHOULD NOT BE USED AS

EXHAUSTIVE LIST. THE EXISTING CAMPUS FIRE ALARM SYSTEM WILL NOT BE

REUSED AND A NEW CAMPUS WIDE SYSTEM IS TO BE PROVIDED, SEE FIRE ALARM

SITE PLAN.

4. COORDINATE FIRE ALARM SYSTEM DEVICE LOCATIONS WITH LIGHT FIXTURES,

STRUCTURAL MEMBERS, SPRINKLER HEADS AND PIPING, HVAC EQUIPMENT AND

DUCTWORK. CONTRACTOR TO VERIFY LOCATIONS OF DUCT SMOKE DETECTORS

AND CONNECT TO NEW FIRE ALARM SYSTEM.

5. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE AND

SATISFACTORILY OPERATING SYSTEMS AS INDICATED ON THE CONTRACT

DOCUMENTS AND AS EVIDENTLY INTENDED. IT IS NOTED THAT THE DRAWINGS

ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENTS OF SYSTEMS AND

WORK. INTERCONNECTIONS HAVE BEEN SHOWN, AND THE CONTRACTOR SHALL

FURNISH AND INSTALL CONDUIT AND WIRING AS REQUIRED TO ACCOMPLISH THE

FUNCTIONS INDICATED. ADDITIONALLY, FIRE ALARM SYSTEMS HAVE BEEN

SHOWN AND THE CONTRACTOR SHALL FURNISH AND INSTALL THE REQUIRED

QUANTITIES AND TYPES OF CABLES, CONDUCTORS, RACEWAYS, REMOTE POWER

SUPPLIES AND CONNECTIONS, SHIELDING REQUIREMENTS, ETC., AS REQUIRED

BY THE SYSTEM MANUFACTURER, THE SPECIFICATIONS, AND ANY APPLICABLE

CODES. ALL WIRING SHOWN ON RISER DIAGRAMS SHALL ALSO BE FURNISHED

AND INSTALLED REGARDLESS OF WHETHER THESE ITEMS ARE SHOWN ON THE

FLOOR PLANS.

6. THE CONTRACTOR SHALL COORDINATE THE ELECTRICAL WORK WITH THE WORK

OF ALL OTHER TRADES AND EXISTING CONDITIONS SO AS TO AVOID CONFLICTS.

RESOLVE ALL CONFLICTS THROUGH THE A/E PRIOR TO ROUGH-IN.