This document provides details for a federal contract opportunity to upgrade the fire alarm system at the Central Texas Veterans Health Care System campus in Waco, Texas. The solicitation number is 36C25722B0003 and will require replacing the existing fire alarm system in its entirety across 25 buildings. A 100% Service-Disabled Veteran-Owned Small Business set-aside will be in place. The procurement is estimated between $5 million to $10 million and have a one year period of performance once a notice to proceed is issued. Interested parties must obtain verification from the Department of Veterans Affairs Center for Verification and Evaluation as a Service-Disabled Veteran-Owned Small Business prior to proposal submission to be considered for this opportunity from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 17. The point of contact is Gaila P. Lowe and she can be reached by email.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25722B0003 A00003.docx | DOCX document | |
| 36C25722B0003 A00002.docx | DOCX document | |
| 36C25722B0003 A00001.docx | DOCX document | |
| VA_WAC Fire Alarm - Bid Set Specifications.pdf | ||
| 36C25722B0003.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Above finished floor AFF Acoustic ACST Acoustic Panel Ceiling APC Addendum ADD Alternate ALT Aluminum AL Angle L Approximate APPROX Architecture, architectural ARCH Asbestos ASB Asphalt ASPH Assistant ASST Association ASSN Automatic AUTO Average AVG Base plate BP Basement BSMT Beam BM Bearing BRG Bedroom BR Benchmark BM Board BD Boiler BLR Bottom BOT Brick BRK Building line BL Building BLDG Built-up-roof BUR Cabinet CAB Carpet CPT Catalog CAT Ceiling height CH Ceiling CLG Center CTR Centerline CL Ceramic Tile CT Ceramic CER Chalkboard CB Clear CLR Closet CLO Coated CTD Cold rolled CR Column COL Company CO Composition COMP Concrete Masonry Unit CMU Concrete CONC Construction joint CJ Construction CONSTR "Continue, Continuous" CONT Corridor CORR Countersink CSK Cubic CU Curve(d) CRV Dampproofing DP Degree DEG Department(al) DEPT Detail DET Diagonal DIAG Diameter DIA Dimension DIM Dishwasher DW Dispenser DISP Door DR Double DBL Double-hung DH Down DN Downspout DS Drain DR Drawing DWG Each EA East E Electric Water Cooler EWC "Electric, electrical" ELEC Elevation EL Elevator ELEV Engineer ENGR Entrance ENTR Equal EQ Equipment EQUIP Exhaust EXH Existing EXIST Expansion joint EXP JT Exposed EXP Exterior EXT Fabricate FAB Face of Stud F. OF S.
Fan Coil Unit FCU Fiberglass-reinforced plastics FRP Finish FIN Finished Floor FF Fire Extinguisher FE Fire Extinguisher & Cabinet FEC Fire Retardant Treated FRT Fireproof FPRF Fixture FXTR Flange FLG Flashing FL Floor FL Floor drain FD Flooring FLG Fluorescent FLUOR
Footing FTG Foundation FDN Furnish(ed), furniture FURN Furring FURR Gage (gauge) GA Galvanize(d) GALV Galvanized Iron GALVI Glazed Wall Tile GWT Grab Bar GB Grade GR Gravel GVL Gypsum Wallboard GWB Gypsum GYP Handicapped HC Hardware HDW Heating ventilating and HVAC air conditioning Height HGT High Point HPT High Performance HP High Performance Coating HPC Hollow Metal HM Horizontal HORIZ Include(d), inclusive INCL Incorporated INC Information INFO Inside diameter ID Install(ed), installation INSTL Insulation INSUL Interior INT Janitor JAN Joint JT Joist J, JST Junction box JB Knock down KD Laboratory LAB Lavatory LAV Left Hand LH Left L Length LG Level LVL Light LT Machine MACH Maintenance MAINT Manager MGR Manual MNL Manufacturing MFG Markerboard MB Masonry opening MO Masonry MSNRY Master bedroom MBR Material MATL Maximum MAX Mechanical MECH Membrane MEMB Men M Metal MET, MTL Mezzanine MEZZ Minimum MIN Mirror MIR Miscellaneous MISC Mounted MTD Mounting MTG Necessary NEC Noise-reduction coefficient NRC Nominal NOM Non Combustible NC, NONCOM North N Not in Contract NIC Not to scale NTS Not available NA Number NO Office OFF On center OC Opening OPNG Opposite OPP Outside diameter OD Overall OA Overhead OVHD Page P Painted PTD Pair PR Panel PNL Partition PTN Percent PCT Perforate(d) PERF Permanent PERM Perpendicular PERP Piece PC Plastic Laminate PLAM Plastic Laminate PLAS.LAM Plate PL Plumbing PLMB Plywood PLYWD Point PT Polyvinyl chloride PVC Precast PRCST Prefabricated PREFAB Preliminary PRELIM Preparation, prepare PREP Program PRGM Projection Screen PS
Project PROJ Property PROP Public Address PA Quality control QC Quality QUAL Quantity QTY Quarry Tile QT Radius RAD Rain Leader RL Received RCVD Receptacle RCPT Receptionist RECPT Recess(ed) REC Refer, reference REF Refrigerate, refrigerator REFR Reinforce REINF Reinforced concrete RC Remove RMV Repair RPR Required REQD Revise, revision REV Right hand RH Road RD Roof Drain RD Roof RF Roofing RFG Room RM Rubber tile floor RTF Rubber RBR Schedule SCHED Schematic SCHEM Section SECT Service SVCE "Sheet, sheeting" SHT Shower SH Siding SDG Similar SIM Slope SL Sound-transmission class STC South S Speaker SPKR Specification SPEC Sprinkler SPR Square SQ Stainless steel SS Standard STD Standpipe SP Steel STL Storage STOR Structural Glazed Facing Tile SGFT Structural, structure STRUCT Substitute SUBST Surface SURF Suspend(ed) SUSP Switch SW Symmetrical SYM System SYS Tackboard TB Tackstrip TS Telephone TEL Television TV Temporary TEMP Terrazzo TER Thick THK Through THRU Toilet T Tongue and groove T&G Top and bottom T&B Top chord TC Top of Masonry Parapet TMP Top of Bearing TOFB Top of Steel T.O.S.
Topping TOPG Total TOT Transformer XFMR Transom TR Transparent TRANS Tread TRD Threshold THRESH Typical TYP Underground UG Underwriters Laboratories UL Unfinished UNF Unit Ventilator UV Unless Otherwise Noted UON Urinal UR US Gypsum Company USG Vertical VERT Vestibule VEST, V Vinyl Reducing Strip VRS Vinyl Composite Tile VCT Vinyl asbestos tile VAT Wardrobe WARD Water closet WC Waterproof WP Weight WT Welded WLD Welded Wire Mesh WWM With W/ Without W/O Women W Wood WD Wrought Iron WI
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
FIRE PROTECTION:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR.
SUITE 350
CALVERTON, MD 20705
443-388-7351
Drawing of
ELECTRICAL:
HUITT-ZOLLARS
500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts
6/25/2021
100% BID SET 4800 MEMORIAL DRIVE, WACO, TX
76711
674A4-21-108
JLHMAR
COVER SHEET
G001
A
-2
-1
G
/2
/2
.p d f
WACO VA MEDICAL CENTER - FIRE
ALARM CAMPUS UPGRADE
Fire Alarm Campus Upgrade
100% BID SET
674A4-21-108
Waco VA Medical Center 4800 Memorial Drive
Waco, TX 76711
Volume 1
226-E101 BUILDING 226 - ELECTRICAL PLAN – LEVEL 1 X
225-E101 BUILDING 225 - ELECTRICAL PLAN – LEVEL 1 X X
224-E101 BUILDING 224 - ELECTRICAL PLAN – LEVEL 1 X X
222-E101 BUILDING 222 - ELECTRICAL PLAN – LEVEL 1 X X
219-E101 BUILDING 219 - ELECTRICAL PLAN – BASEMENT LEVEL X X
216-E101 BUILDING 216 - ELECTRICAL PLAN – LEVEL 1 X X
202-E101 BUILDING 202 - ELECTRICAL PLAN – LEVEL 1 X X
99-E101 BUILDING 99 - ELECTRICAL PLAN – BASEMENT LEVEL X X
94-E101 BUILDING 94 - ELECTRICAL PLAN – BASEMENT LEVEL X X
93-E101 BUILDING 93 - ELECTRICAL PLAN – BASEMENT LEVEL X X
92-E101 BUILDING 92 - ELECTRICAL PLAN – BASEMENT LEVEL X X
90-E101 BUILDING 90 - ELECTRICAL PLAN – BASEMENT LEVEL X X
24-E101 BUILDING 24 - ELECTRICAL PLAN – LEVEL 1 X X
18-E101 BUILDING 18 - ELECTRICAL PLAN – LEVEL 1 X X
17-E101 BUILDING 17 - ELECTRICAL PLAN – LEVEL 1 X X
16-E101 BUILDING 16 - ELECTRICAL PLAN – LEVEL 1 X X
15-E101 BUILDING 15 - ELECTRICAL PLAN – LEVEL 1 X X
8-E101 BUILDING 8 - ELECTRICAL PLAN – LEVEL 1 X X
7-E101 BUILDING 7 - ELECTRICAL PLAN – BASEMENT AREA X X
6-E101 BUILDING 6 - ELECTRICAL PLAN – LEVEL 1 X X
5-E101 BUILDING 5 - ELECTRICAL PLAN – BASEMENT LEVEL X X
4-E101 BUILDING 4 - ELECTRICAL PLAN – BASEMENT LEVEL X X
2-E101 BUILDING 2 - ELECTRICAL PLAN – BASEMENT LEVEL X X
ELECTRICAL: X
X X
226-FA102 BUILDING 226 - FIRE ALARM PLAN - MEZZANINE LEVEL X X
226-FA101 BUILDING 226 - FIRE ALARM PLAN - LEVEL 1 X X
226-FA001 BUILDING 226 - FIRE ALARM GENERAL NOTES AND DETAILS X X
225-FA102 BUILDING 225 - FIRE ALARM PLAN – LEVEL 2 X X
225-FA101 BUILDING 225 - FIRE ALARM PLAN – LEVEL 1 X X
225-FA100 BUILDING 225 - FIRE ALARM PLAN – BASEMENT X X
224-FA101 BUILDING 224 - FIRE ALARM PLAN - LEVEL 1 X X
222-FA101 BUILDING 222 - FIRE ALARM PLAN - LEVEL 1 X X
219-FA101 BUILDING 219 - FIRE ALARM PLAN - BASEMENT LEVEL X X
216-FA101 BUILDING 216 - FIRE ALARM PLAN - BASEMENT & LEVEL 1 X X
202-FA101 BUILDING 202 - FIRE ALARM PLAN - LEVEL 1 X X
99-FA101 BUILDING 99 - FIRE ALARM PLAN - BASEMENT LEVEL & LEVEL 1 X X
94-FA102 BUILDING 94 - FIRE ALARM PLAN - LEVEL 1 X X
94-FA101 BUILDING 94 - FIRE ALARM PLAN - BASEMENT LEVEL X X
94-FA001 BUILDING 94 - FIRE ALARM GENERAL NOTES AND DETAILS X X
93-FA103 BUILDING 93 - FIRE ALARM PLAN - LEVEL 2 X X
93-FA102 BUILDING 93 - FIRE ALARM PLAN - LEVEL 1 X X
93-FA101 BUILDING 93 - FIRE ALARM PLAN - BASEMENT LEVEL X X
93-FA001 BUILDING 93 - FIRE ALARM GENARL NOTES AND DETAILS X X
92-FA103 BUILDING 92 - FIRE ALARM PLAN - LEVEL 2 X X
92-FA102 BUILDING 92 - FIRE ALARM PLAN - LEVEL 1 X X
92-FA101 BUILDING 92 - FIRE ALARM PLAN - BASEMENT LEVEL X X
92-FA001 BUILDING 92 - FIRE ALARM GENERAL NOTES AND DETAILS X X
90-FA103 BUILDING 90 - FIRE ALARM PLAN - LEVEL 2 X X
90-FA102 BUILDING 90 - FIRE ALARM PLAN - LEVEL 1 X X
90-FA101 BUILDING 90 - FIRE ALARM PLAN - BASEMENT LEVEL X X
90-FA001 BUILDING 90 - FIRE ALARM GENERAL NOTES AND DETAILS X X
24-FA101 BUILDING 24 - FIRE ALARM PLAN - LEVEL 1 X X
18-FA101 BUILDING 18 - FIRE ALARM PLANS X X
17-FA101 BUILDING 17 - FIRE ALARM PLAN - LEVEL 1 X X
16-FA101 BUILDING 16 - FIRE ALARM PLAN - LEVEL 1 X X
15-FA101 BUILDING 15 - FIRE ALARM PLAN - LEVEL 1 X X
8-FA103 BUILDING 8 - FIRE ALARM PLAN – LEVEL 2 X X
8-FA102 BUILDING 8 - FIRE ALARM PLAN – LEVEL 1 X X
8-FA101 BUILDING 8 - FIRE ALARM PLAN – BASEMENT LEVEL X X
8-FA001 BUILDING 8 - FIRE ALARM GENERAL NOTES AND DETAILS X X
7-FA103-C BUILDING 7 - FIRE ALARM PLAN - LEVEL 2 AREA C X X
7-FA103-A&B BUILDING 7 - FIRE ALARM PLAN - LEVEL 2 AREA A&B X
7-FA102-C BUILDING 7 - FIRE ALARM PLAN - LEVEL 1 AREA C X
7-FA102-A&B BUILDING 7 - FIRE ALARM PLAN - LEVEL 1 AREA A&B X
7-FA101-C BUILDING 7 - FIRE ALARM PLAN - BASEMENT AREA C X X
7-FA101-A&B BUILDING 7 - FIRE ALARM PLAN - BASEMENT AREA A&B X X
7-FA001 BUILDING 7 - FIRE ALARM GENERAL NOTES AND DETAILS X X
6-FA103 BUILDING 6 - FIRE ALARM PLAN - LEVEL 3 X X
6-FA102 BUILDING 6 - FIRE ALARM PLAN - LEVEL 2 X X
6-FA101 BUILDING 6 - FIRE ALARM PLAN - LEVEL 1 X X
6-FA100 BUILDING 6 - FIRE ALARM PLAN - BASEMENT LEVEL X X
5-FA103 BUILDING 5 - FIRE ALARM PLAN - LEVEL 2 X X
5-FA102 BUILDING 5 - FIRE ALARM PLAN - LEVEL 1 X X
5-FA101 BUILDING 5 - FIRE ALARM PLAN - BASEMENT LEVEL X X
5-FA001 BUILDING 5 - FIRE ALARM GENERAL NOTES AND DETAILS X X X
4-FA102 BUILDING 4 - FIRE ALARM PLAN - LEVEL 1 X X X
4-FA101 BUILDING 4 - FIRE ALARM PLAN - BASEMENT LEVEL X X X
4-FA001 BUILDING 4 - FIRE ALARM GENERAL NOTES AND DETAILS X X X
2-FA103 BUILDING 2 - FIRE ALARM PLAN - LEVEL 2 X X X
2-FA102 BUILDING 2 - FIRE ALARM PLAN - LEVEL 1 X X X
2-FA101 BUILDING 2 - FIRE ALARM PLAN - BASEMENT LEVEL X X X
FIRE PROTECTION:
GI003 PENETRATION DETAILS X
GI002 SITE ORIENTATION PLAN X X
GI001 COVER SHEET X X X
GENERAL:
SHEET NUMBER SHEET NAME 35% 65% 100% 100% FINAL
ARCHITECT:
CB DESIGN GROUP
421 KING ST., SUITE 301
ALEXANDRIA, VA 22314
POC: WES BRIDGES
703.772.4213
G A T E
G A T E
G A T E
M A
IN
G A T E
G A T E
OLD FARM ROAD
OLD FARM ROAD
DORIS MILLER CIRCLE
DORIS MILLER CIRCLE
D O R
IS
M
IL
LE
R C
IR
CL
E
DOR
IS M
ILLE
R C
IRCL
E
O U T E R
L O O P
R O A D
O U T E R
L O O P
R O A D
O U T E R
L O O P
R O A D
O U
TE
R
LO
O P
R O A D
OUTER LOOP ROAD
OUTER LOOP ROAD
OU
TE
R
LO
OP
C
IR
CL
E
MEMORIAL BLVD.
MEMORIAL BLVD.
QUARTERS DRIVE
C
IR
C
LE
D R
IV
E
BEVERLY DRIVE
BEVERLY DRIVE
BEVERLY DRIVE
N E W
R O A D
N E W
R O A D
H C
V A N
H C
CO
UR
T
CO
UR
T
C O U R T
V A N
9' - 5 7/8"
MAIN GRAPHIC
ANNUNCIATOR
PANELS IN
BUILDINGS 225
AND 18
FACP RM BA139
BUILDING 4
FACP RM BA104
BUILDING 6
FACP RM BC112
BUILDING 7
FACP RM 8A
BUILDING 5
FACP COR CB1-1
BUILDING 2
FACP RM BB127
BUILDING 94
FACP 3RD FLR
BUILDING 92
FACP RM 101
BUILDING 90
FACP RM BA110
BUILDING 93
FACP RM 3
BUILDING 99
FACP RM 103M
BUILDING 15
FACP COR 221
BUILDING 8
FACP RM 101
BUILDING 226
FACP RM 105
BUILDING 225
FACP RM 106
BUILDING 224
FACP RM 1A-100
BUILDING 216
FACP RM 127
BUILDING 202
BUILDING 16
FACP RM 112
BUILDING 18
FACP COR 21
BUILDING 24
NOTE: CONTRACTOR TO VERIFY PANEL LOCATION
ON SITE AND COORDINATE LOCATION OF THE NEW
PANEL WITH EXISTING IN BUILDING 17.
FACP RM 1A-107
BUILDING 219
FACP
BUILDING 17
BUILDING 222
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
FIRE PROTECTION:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
ARCHITECT:
CB DESIGN GROUP
11720 BELTSVILLE DR.
SUITE 350
CALVERTON, MD 20705
443-388-7351
Drawing of
ELECTRICAL:
HUITT-ZOLLARS
500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts
6/25/2021
100% BID SET 4800 MEMORIAL DRIVE, WACO, TX
76711
674A4-21-108
JLHMAR
SITE ORIENTATION PLAN
G002
A
-2
-1
G
/2
/2
.p d f
WACO VA MEDICAL CENTER - FIRE
ALARM CAMPUS UPGRADE
N TRUE
NORTH
226 LAUNDRY
225 ENERGY PLANT
224 SAFETY
222 RADIO EQUIPMENT
219 PHYSICAL THERAPY
216 CENTRAL CHILLER
202 DIETETICS
99 FMS SHOPS
94 INPATIENT PSYCH
93 FUTURE CENTER OF EXCELLENCE
92 VA FINANCIAL CENTER
90 PHARMACY CALL CENTER
24 F.M.S./SHOPS
18 POLICE
17 CONSOLIDATED LAUNDRY/FUTURE A&MM/VACANT
16 GARAGE MISC.
15 VBA
8 FUTURE ACUTE MENTAL HEALTH/PARTIAL OCCUPANCY
7 BLIND REHAB UNIT/VACANT
6 AUDITORIUM
5 PHARMACY/EDUCATION
4 OUTPATIENT CLINIC/LAB CLINIC
2 ADMINISTRATIVE
Building # Building Name
SCALE: NTS
A5
CAMPUS RISER DIAGRAM
ARCHITECT:
CB DESIGN GROUP
421 KING ST., SUITE 301
ALEXANDRIA, VA 22314
POC: WES BRIDGES
703.772.4213
FIRE RESISTANT RATED WALL CONSTRUCTION
THROUGH PENETRATION FIRESTOPPING SYSTEM
PROVIDE SYSTEM IN ACCORDANCE WITH FIRESTOPPING SCHEDULE
WALL PENETRATION - SEE DRAWINGS
SLAB PENETRATION - SEE DRAWINGS
THROUGH PENETRATION FIRESTOPPING SYSTEM
PROVIDE SYSTEM IN ACCORDANCE WITH
FIRESTOPPING SCHEDULE
FIRE RESISTANCE RATED FLOOR CONSTRUCTION
FLOOR PIPE PENETRATION
UL No: F-L-1020
JOINT SEALANT APPLIED
WITHIN OPENING
METAL PIPE
CONCRETE OVER COMPOSITE
STEEL DECK
MINERAL WOOL INSULATION
JOINT SEALANT
JOINT SEALANT
MINERAL WOOL
INSULATION
METAL PIPE
FLOOR PIPE PENETRATION
UL No: F-L-5014
JOINT SEALANT APPLIED
WITHIN OPENING
METAL PIPE
CONCRETE OVER COMPOSITE
STEEL DECK
MINERAL WOOL INSULATION
JOINT SEALANT
JOINT SEALANT
MINERAL WOOL
INSULATION
GLASS FIBER INSULATION
GLASS FIBER
INSULATION
METAL PIPE
SINGLE CONDUIT/PIPE PENETRATION
UL No: W-L-1063
JOINT SEALANT
PIPE / CONDUIT
JOINT SEALANT
RATED WALL ASSEMBLY - VERIFY
WALL TYPE IN FIELD
48" MAX
V A
R
IE
S
6" M
A X
2" MAX, 1" MIN
1" M
A X
MULTIPLE CONDUIT/PIPE PENETRATIONS
UL No: W-L-1063
MINERAL WOOL INSULATION
WALL TYPE, SEE PLAN
MINERAL WOOD INSULATION
MINERAL WOOL INSULATION
WALL TYPE, SEE PLAN
WALL TYPE, SEE PLAN
SINGLE CONDUIT/PIPE PENETRATION
UL No: W-L-5044
PIPE/CONDUIT
FORMING MATERIAL
JOINT SEALANT
VERIFY WALL TYPE IN FIELD
JOINT SEALANT
PIPE / CONDUIT
WALL TYPE
SMALL PENETRATIONS IN PARTITIONS
RATED UP TO 2 HOURS
NO TREATMENT REQUIRED FOR UP
TO 1/8" GAP
MAXIMUM GAP 1/4"
MAXIMUM GAP 1/2", FILL TO FULL DEPTH
OF DRYWALL AND STRIKE OFF AT FACE
OF DRYWALL, DO NOT SPREAD BEYOND
OPENING
2'-0" (PER UL)
SHALLOW FIVE SIDED BOX
RATED WALL ASSEMBLY-
SEE PARTITION TYPES FOR
NUMBER OF LAYERS OF
GYPSUM BOARD
ELECTRICAL JUNCTION BOX
16 SQ INCH MAX OPENING
MAX 100 SQ INCHES IN 100 SQ FEET
LAMINATE BACK PIECE
TO WALLBOARD
REQUIRED BOX EXCEEDS 16 SQ INCHES
OR AGGREGATE SUM OF BOXES
EXCEEDS 100 SQ INCHES IN 100 SQ
FEET OF WALL AREA
ADJACENT ELECTRICAL BOXES
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
FIRE PROTECTION:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
ARCHITECT:
CB DESIGN GROUP
421 KING ST., SUITE 301
ALEXANDRIA, VA 22314
POC: WES BRIDGES
703.772.4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
Drawing of
ELECTRICAL:
HUITT-ZOLLARS
500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts
6/25/2021
100% BID SET 4800 MEMORIAL DRIVE, WACO, TX
76711
674A4-21-108
EWMDLO
PENETRATION DETAILS
GI003
A
-2
-1
G I0
/1
/2
.p d f
WACO VA MEDICAL CENTER - FIRE
ALARM CAMPUS UPGRADE
SCALE: NTS
A5
THROUGH PENETRATION FIRESTOP SYSTEM KEY
SCALE: NTS
F6
PENETRATION DETAIL
SCALE: NTS
F3
PENETRATION DETAIL
SCALE: NTS
A9
PENETRATION DETAIL
SCALE: NTS
D9
PENETRATION DETAIL
SCALE: NTS
D6
PENETRATION DETAIL
SCALE: NTS
D3
PENETRATIONS
SCALE: NTS
F9
ELECTRICAL JUNCTION BOX DETAIL
F
S
S C
M
C
CO
H R
S
ID
S P
WF
PS
VS
FAA
FACP
FATC
C S C CS C
F
S CC
F
F
F
F
S P
FACP
C C
C
H R
WF
VS
WF
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
VS
1. PROVIDE AND INSTALL A NEW FIRE ALARM SYSTEM THROUGHOUT THE BUILDING
PER THE VA DESIGN GUIDE AND NFPA 72. REFER TO SPEC SECTION 28 31 00
INTERIOR FIRE ALARM SYSTEM. FIRE ALARM SYSTEM WILL BE ZONED PER FLOOR.
2. ALL EXISTING FIRE ALARM DEVICES, PANELS AND RELATED EQUIPMENT ARE TO
BE DEMOLISHED. EXISTING ALARM SYSTEMS MUST REMAIN IN-SERVICE AND
FUNCTIONAL WHILE NEW ALARM SYSTEM IS INSTALLED. FOLLOW ILSM
PROTOCOLS FOR SHUTDOWN AND PHASE DEMO OF EXISTING ALARM SYSTEM SO
THAT REMOVAL ONLY OCCURS ONCE NEW ALARM SYSTEM IS FULLY INSTALLED
AND FUNCTIONAL.
3. ALL EXISTING INTERFACING DEVICES (TAMPERS, FLOWS, PRESSURE SWITCHES,
ETC) WILL BE CONNECTED TO THE NEW FA SYSTEM AND REPORT TO THE MAIN
GRAPHIC ANNUNCIATORS IN BUILDING 225. A SECONDARY MONITORY STATION
SHALL BE LOCATED IN BUILDING 18. INTERFACING DEVICES ARE SHOWN WHEN
LOCATIONS ARE KNOWN, HOWEVER THE DRAWINGS SHOULD NOT BE USED AS
EXHAUSTIVE LIST. THE EXISTING CAMPUS FIRE ALARM SYSTEM WILL NOT BE
REUSED AND A NEW CAMPUS WIDE SYSTEM IS TO BE PROVIDED, SEE FIRE ALARM
SITE PLAN.
4. COORDINATE FIRE ALARM SYSTEM DEVICE LOCATIONS WITH LIGHT FIXTURES,
STRUCTURAL MEMBERS, SPRINKLER HEADS AND PIPING, HVAC EQUIPMENT AND
DUCTWORK. CONTRACTOR TO VERIFY LOCATIONS OF DUCT SMOKE DETECTORS
AND CONNECT TO NEW FIRE ALARM SYSTEM.
5. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE AND
SATISFACTORILY OPERATING SYSTEMS AS INDICATED ON THE CONTRACT
DOCUMENTS AND AS EVIDENTLY INTENDED. IT IS NOTED THAT THE DRAWINGS
ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENTS OF SYSTEMS AND
WORK. INTERCONNECTIONS HAVE BEEN SHOWN, AND THE CONTRACTOR SHALL
FURNISH AND INSTALL CONDUIT AND WIRING AS REQUIRED TO ACCOMPLISH THE
FUNCTIONS INDICATED. ADDITIONALLY, FIRE ALARM SYSTEMS HAVE BEEN
SHOWN AND THE CONTRACTOR SHALL FURNISH AND INSTALL THE REQUIRED
QUANTITIES AND TYPES OF CABLES, CONDUCTORS, RACEWAYS, REMOTE POWER
SUPPLIES AND CONNECTIONS, SHIELDING REQUIREMENTS, ETC., AS REQUIRED
BY THE SYSTEM MANUFACTURER, THE SPECIFICATIONS, AND ANY APPLICABLE
CODES. ALL WIRING SHOWN ON RISER DIAGRAMS SHALL ALSO BE FURNISHED
AND INSTALLED REGARDLESS OF WHETHER THESE ITEMS ARE SHOWN ON THE
FLOOR PLANS.
6. THE CONTRACTOR SHALL COORDINATE THE ELECTRICAL WORK WITH THE WORK
OF ALL OTHER TRADES AND EXISTING CONDITIONS SO AS TO AVOID CONFLICTS.
RESOLVE ALL CONFLICTS THROUGH THE A/E PRIOR TO ROUGH-IN. FAILURE TO
PROVIDE SUCH COORDINATION PRIOR TO WORK BEING INSTALLED SHALL NOT BE
CAUSE FOR ADDITIONAL COMPENSATION TO THE CONTRACTOR, AND MAY
RESULT IN REJECTION OF THE WORK.
7. ADDITIONAL DEVICES MAY BE REQUIRED. DO NOT USE THESE DRAWINGS FOR
DEVICE COUNTS.
8. ALL MATERIALS SHALL BE NEW, SHALL BE SUITABLE FOR THE APPLICATION
INTENDED, AND SHALL BEAR LABELS OR MARKINGS INDICATING THIRD PARTY
TESTING LABORATORY LISTINGS ACCEPTABLE TO THE AUTHORITY HAVING
JURISDICTION.
9. EXISTING CONDUIT IN GOOD CONDITION THAT HAS BEEN SALVAGED FROM OTHER
BUILDINGS MAY BE REUSED IF POSSIBLE AND SHALL BE STRIPED IN PATIENT
AREAS. NEW CONDUIT SHALL BE MARKED WITH RED COUPLINGS. ALL OTHER
MATERIALS SHALL BE NEW, SHALL BE SUITABLE FOR THE APPLICATION INTENDED,
AND SHALL BEAR LABELS OR MARKINGS INDICATING THIRD PARTY TESTING
LABORATORY LISTINGS ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.
10. ALL FIRE ALARM CABLES SHOULD BE INSTALLED IN METAL RACEWAYS.
11. ALL RACEWAY AND WIRING SHALL BE CONCEALED IN FINISHED SPACES AND MAY
BE EXPOSED IN UNFINISHED SPACES SUCH AS MECHANICAL AND ELECTRICAL
ROOMS. ALL RACEWAY AND WIRING SHALL BE ROUTED EITHER PERPENDICULAR
OR PARALLEL TO THE BUILDING'S STRUCTURAL COMPONENTS.
12. PROVIDE PULL AND JUNCTION BOXES AS REQUIRED TO MEET CODE AND
INSTALLATION REQUIREMENTS. PULL AND JUNCTION BOXES SHALL BE
CONCEALED IN FINISHED SPACES AND LOCATIONS SHALL BE COORDINATED WITH
THE WORK OF ALL OTHER TRADES SO AS TO AVOID CONFLICTS.
13. ALL CONDUCTORS SHALL BE IDENTIFIED AT EACH JUNCTION BOX, OUTLET BOX,
CABINET, PULL BOX, ETC., WITH VINYL SELF-ADHESIVE TAGS INDICATING PANEL
AND CIRCUIT NUMBER, CONTROL WIRE IDENTIFICATION NUMBER, OR OTHER
APPROPRIATE INFORMATION. ALL PULL AND JUNCTION BOXES SHALL BE LABELED
AS TO FUNCTION.
14. ALL EQUIPMENT SHALL BE SECURELY FASTENED BY MEANS OF ANCHORS, RODS,
HANGERS, SUPPORTS, GUIDES, SWAY BRACES, ETC., TO MAINTAIN ALIGNMENT
AND PREVENT EQUIPMENT MOVEMENT. ALL EQUIPMENT LOCATED IN SEISMIC
ZONES SHALL BE SECURED WITH MEANS APPROVED FOR THE SEISMIC
CLASSIFICATION ENCOUNTERED.
15. ALL PENETRATIONS OF FIRE OR SMOKE RATED CONSTRUCTION SHALL BE SEALED
WITH FIRESTOPPING MATERIALS APPROVED AND LISTED FOR THE RATING OF THE
CONSTRUCTION TO BE PENETRATED. PROVIDE DOCUMENTATION ON ALL SUCH
PENETRATION SEALING SYSTEMS FOR VERIFICATION OF PROPER INSTALLATION.
16. ALL PENETRATIONS OF ROOFS, EXTERIOR WALLS, FOUNDATIONS, OR OTHER
WATER OR MOISTURE PROOF CONSTRUCTION SHALL BE SEALED WITH
APPROPRIATE SEALING FITTINGS OR SEALED CONSTRUCTION TO PREVENT THE
INTRODUCTION OF MOISTURE INTO THE BUILDING.
17. WHERE EMPTY RACEWAYS ARE INSTALLED, THEY SHALL BE LABELED AT BOTH
ENDS AND FITTED WITH NYLON PULLSTRINGS FOR FUTURE USE.
18. ELECTRICAL WORK SHALL BE PERFORMED ON DE-ENERGIZED SYSTEMS ONLY TO
PREVENT PERSONNEL INJURY AND POTENTIAL SYSTEM FAILURE. WHERE WORK
ON EXISTING SYSTEMS WILL REQUIRE INTERRUPTION OF ELECTRICAL SERVICE,
THEN TEMPORARY PROVISIONS ACCEPTABLE TO THE OWNER FOR TEMPORARY
POWER SHALL BE UTILIZED UNTIL THE WORK IS COMPLETE.
19. THE FIRE ALARM SYSTEM SHALL COMPLY WITH ALL RELATED NFPA, BUILDING
CODES AND LOCAL FIRE DEPARTMENT REGULATIONS.
20. WALL MOUNTED FIRE ALARM PULL STATIONS ARE TO BE LOCATED 46" A.F.F. AND
WITHIN 5' OF THE NEAREST ADJACENT EXIT DOOR FROM THE FLOOR OR
BUILDING.
21. WALL MOUNTED FIRE ALARM NOTIFICATION APPLIANCES, EITHER VISUAL, OR
COMBINATION AUDIO/VISUAL, SHALL BE LOCATED SUCH THAT THE ENTIRE LENS
OF THE VISUAL PORTION IS BETWEEN 80" AND 96" A.F.F. AUDIO ONLY APPLIANCES
SHALL BE LOCATED, NOT LESS THAN 90" A.F.F. TO TOP OF APPLIANCE, OR 6"
BELOW CEILING.
FIRE ALARM GENERAL NOTES
DUCT SMOKE DETECTOR
AREA SMOKE DETECTOR
DOOR RELEASE SMOKE DETECTOR
S O
U N
D G
E N
E R
A L
B U
IL
D
IN
LA
R
M
X
X
N O
T
IF
Y N
E C
E S
S A
R Y
S
TA
FF
X
INPUT
OUTPUT
N O
T
IF
Y F
IR
E
D E
P A
R M
E N
T
IN
IT
IA
T
E S
U P
E R
V
IS
O R
Y S
IG
N
A L
T O
A
4- H
O U
R M
A N
N E
D P
O
IN
T F
O R
IM
M
E D
IA
TE
R E
S P
O N
S E
X
C
LO
S E
A S
S O
C
IA
T E
S M
O K
E
B
R R
IE
R
D O
O R
S O
N T
H
LO
O
R
X
MANUAL PULL STATION
ELEVATOR MACHINE ROOM HEAT DETECTOR
SPRINKLER WATERFLOW / PRESSURE SWITCH
X
X
X
X
X
X
X
X
X
ELEVATOR SMOKE DETECTOR X X X
X
X
C
LO
S E
D A
M P
E R
S O
N F
P
R O
X
IM
A T
E T
O D
E T
E C
TO
R
X
X
S H
U T
D O
W N
A U
R H
A N
D
LE
S
R V
E D
B Y
T H
E D
E T
E C
T O
R
X1
1. DO NOT PROVIDE DUCT DETECTORS IN DEDICATED (100%) EXHAUST FANS, THEY SHOULD CONTINUE TO RUN.
R E
C A
LL
E
LE
V
A T
O R
X
IN
IT
IA
T
E E
LE
V
A T
O R
S H
U
D
O W
N A
N D
D
IS
C O
N N
E C
V A
T O
R P
O W
E R
X
O P
E N
L O
C K
E D
E G
R E
O
R S
O N
F
LO
O R
O F
F
IR
IG
IN
X
X
X
X
FIRE ALARM MATRIX
WATER CONTROL VALVE TAMPER SWITCH X
FIRE ALARM SYMBOLS
DEVICES
EXTERIOR BELL
SYMBOL DESCRIPTION
DETECTORS
MANUAL PULL STATION
SPEAKER ONLY CEILING MOUNTED
COMBINATION OF SPEAKER/STROBE WALL MOUNTED
SPEAKER ONLY WALL MOUNTED
STROBE ONLY CEILING MOUNTED
STROBE ONLY WALL MOUNTED
MNS SPEAKER/STROBE CEILING MOUNTED
GAS DETECTOR - CARBON MONOXIDE
HEAT DETECTOR - RATE OF RISE
SMOKE DETECTOR - IN DUCT
SMOKE DETECTOR - PHOTOELECTRIC
SWITCHES
FLOW DETECTOR/SWITCH
PRESSURE DETECTOR/SWITCH
VALVE SUPERVISORY SWITCH
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
PANELS
LINE TYPES
SMOKE/ALARM ZONE BOUNDARY LINES
CODE DATA
OCCUPANCY BUSINESS
SPRINKLERS PARTIALLY SPRINKLERED
NOTIFICATION SPEAKERS, STROBES AND COMBINATION SPEAKER-STROBES IN
NORMALLY OCCUPIED AREAS
DETECTION MANUAL PULL-STATIONS, SPRINKLERS, SMOKE DETECTION
THROUGHOUT*, CO DETECTOR AT FUEL FIRED EQUIPMENT
FIRE ALARM
ZONING
FIRE ALARM SYSTEM TO BE ZONED PER FLOOR
* SMOKE DETECTION IS SHOWN THROUGHOUT BUILDING BUT NEED ONLY BE INSTALLED
WHERE THERE IS NO SPRINKLER DETECTION. ADDITIONALLY, IF FULL SPRINKLERED
PROTECTION IS PROVIDED AS PART OF A SEPARATE PROJECT, SMOKE DETECTION
DEVICES MAY BE REDUCED PER NFPA 72.
ELE. EQPT.
B1A100
OFFICE
B1A101
HRMS OFFICE
B1A102
OFFICE
B1A103
OFFICE
B1A104
OFFICE
B1A105
MECHANICAL
B1A106
HRMS
CONFERENCE
STORAGE
B1A107
HRMS OFFICE
B1A108
OFFICE
B1A105A
OFFICE
B1A105B
SERVICE
ROOM
B1B100
WOMEN
B1B101
MEN
B1B102
XEROX/ E-QUIP
B1B104
SWING ROOM
B1B105
HRMS
OFFICE
B1B106
PIV
B1B107
HRMS
CONFERENCE
B1B108
HRMS
OFFICE
B1B109
HRMS
OFFICE
B1B110
ELE. CLO.
B1B111
TEL.
B1B108A
IDF
B1B108B
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 12
FA05
FA01
ELEVATOR PUMP
ROOM
B1A100A
VESTIBULE
B1B103A
VESTIBULE
B1B102A
CORRIDOR
CB1-1
CORRIDOR
CB1-2
FIRE ALARM
CONTROL PANEL
CORRIDOR CB1-1
NOTIFICATION APPLIANCES
GROUND LEVEL FIRE/SMOKE
INITIATING DEVICES GROUND LEVEL
FIRE/SMOKE
GROUND LEVEL
NOTE: CONTRACTOR SHALL
VERIFY ALL NECESSARY DEVICE
COUNTS
NOTIFICATION APPLIANCES
LEVEL 1 FIRE/SMOKE
INITIATING DEVICES
LEVEL 1 FIRE/SMOKE
LEVEL 1
NOTIFICATION APPLIANCES
LEVEL 2 FIRE/SMOKE
INITIATING DEVICES
LEVEL 2 FIRE/SMOKE
LEVEL 2
MAIN GRAPHIC ANNUCIATOR IN
BUILDINGS 225 AND 18
KEYNOTE LEGEND
FA01 EXISTING FIRE ALARM CONTROL PANEL.
FA05 HEAT DETECTOR IN ELEVATOR MACHINE ROOM MAY BE OMITTED IF NO SPRINKLER
IS PRESENT.
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
FIRE PROTECTION:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
ARCHITECT:
CB DESIGN GROUP
421 KING ST., SUITE 301
ALEXANDRIA, VA 22314
POC: WES BRIDGES
703.772.4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
PARTIALLY
SPRINKLERED Drawing of
ELECTRICAL:
HUITT-ZOLLARS
500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts
6/25/2021
100% BID SET BUILDING 2 - ADMINISTRATIVE
4800 MEMORIAL DRIVE
WACO, TX 76711
024-10122-000
JLHMAR
FIRE ALARM PLAN - BASEMENT
LEVEL
2-FA101
2 83
-1
-0
F A
/3
/2
.p d f
WACO VA MEDICAL CENTER - FIRE
ALARM CAMPUS UPGRADE
NTRUE
NORTH
SCALE: 1/8" = 1'-0"
A13
BUILDING 2 - FIRE ALARM PLAN - BASEMENT LEVEL
SCALE: NTS
F11
BUILDING 2 - FIRE ALARM RISER DIAGRAM
VA Project Number:
674A4-21-108
S
S C
M
C
CO
H R
S
ID
S P
WF
PS
VS
FAA
FACP
FATC
C S C CS C
F
C
S C
F
C
S P
WF
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P S
P S
P
S P
S P
S P
S P
S P
VS
FIRE ALARM SYMBOLS
DEVICES
EXTERIOR BELL
SYMBOL DESCRIPTION
DETECTORS
MANUAL PULL STATION
SPEAKER ONLY CEILING MOUNTED
COMBINATION OF SPEAKER/STROBE WALL MOUNTED
SPEAKER ONLY WALL MOUNTED
STROBE ONLY CEILING MOUNTED
STROBE ONLY WALL MOUNTED
MNS SPEAKER/STROBE CEILING MOUNTED
GAS DETECTOR - CARBON MONOXIDE
HEAT DETECTOR - RATE OF RISE
SMOKE DETECTOR - IN DUCT
SMOKE DETECTOR - PHOTOELECTRIC
SWITCHES
FLOW DETECTOR/SWITCH
PRESSURE DETECTOR/SWITCH
VALVE SUPERVISORY SWITCH
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
PANELS
LINE TYPES
SMOKE/ALARM ZONE BOUNDARY LINES
MHBM
1A100
MHBM
1A101
OFFICE
1A102C
MHBM
1A103
BREAK ROOM
1A104
NURSING
1A105
NURSING
1B100
HAC
1B101
WOMENS
1B102
MENS
1B103
DIRECTOR'S
CONFERENCE
ROOM
1B104
NURSING
CONFERENCE
ROOM
1B105
NURSING
1B106
NURSING
1B107
NURSING
1B108WORK ROOM
1B108A
OFFICE
1A102A
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 12
OFFICE
1A102
OFFICE
1A102E
OFFICE
1A102F
CORRIDOR
C1-3
TOILET
1A102B
ELEVATOR
VESTIBULE
1B102A
VESTIBULE
1B103A
STAIR 2
CORRIDOR
C1-1
CORRIDOR
C1-2
STAIR 1
KEYNOTE LEGEND
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1 /2
FIRE PROTECTION:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
ARCHITECT:
CB DESIGN GROUP
421 KING ST., SUITE 301
ALEXANDRIA, VA 22314
POC: WES BRIDGES
703.772.4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
PARTIALLY
SPRINKLERED Drawing of
ELECTRICAL:
HUITT-ZOLLARS
500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts
6/25/2021
100% BID SET BUILDING 2 - ADMINISTRATIVE
4800 MEMORIAL DRIVE
WACO, TX 76711
024-10122-000
JLHMAR
FIRE ALARM PLAN - LEVEL 1
2-FA102
2 3
-1
-0
F A
/2
/2
.p d f
WACO VA MEDICAL CENTER - FIRE
ALARM CAMPUS UPGRADE
NTRUE
NORTH
SCALE: 1/8" = 1'-0"
A13
BUILDING 2 - FIRE ALARM PLAN - LEVEL 1
VA Project Number:
S
S C
M
C
CO
H R
S
ID
S P
WF
PS
VS
FAA
FACP
FATC
C S C CC
F
C
C
F
S P
C S C
C
S P
H R
WF
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
VS
FIRE ALARM SYMBOLS
DEVICES
EXTERIOR BELL
SYMBOL DESCRIPTION
DETECTORS
MANUAL PULL STATION
SPEAKER ONLY CEILING MOUNTED
COMBINATION OF SPEAKER/STROBE WALL MOUNTED
SPEAKER ONLY WALL MOUNTED
STROBE ONLY CEILING MOUNTED
STROBE ONLY WALL MOUNTED
MNS SPEAKER/STROBE CEILING MOUNTED
GAS DETECTOR - CARBON MONOXIDE
HEAT DETECTOR - RATE OF RISE
SMOKE DETECTOR - IN DUCT
SMOKE DETECTOR - PHOTOELECTRIC
SWITCHES
FLOW DETECTOR/SWITCH
PRESSURE DETECTOR/SWITCH
VALVE SUPERVISORY SWITCH
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
PANELS
LINE TYPES
SMOKE/ALARM ZONE BOUNDARY LINES
EQUIPMENT
2A100
MAS
2A101
MAS
2A102
MAS
2A103
CONFERENCE
ROOM
2A104
MAS
2A105A
BREAK ROOM
2A106
WACO
COMPUTER
TRAINING
2A107
RESTROOM
2B100
QS&V (OFF. OF
DIRECTOR)
2B101
NURSING
EDUCATION
ROOM
2B102
QS&V (OFF OF
DIRECTOR)
2B103
QS&V (OFF. OF
DIRECTOR)
2B104
NURSING
2B105
MAS
2A105
NURSING
2A108
NURSING
2A109
QS&V (OFF. OF
DIRECTOR)
2A110
QS&V (OFF. OF
DIRECTOR)
2A111
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9 10 11 12
FA04
KEYNOTE LEGEND
FA04 SMOKE AND HEAT DETECTION AT TOP OF ELEVATOR SHAFT MAY BE OMITTED IF NO
SPRINKLER IS PRESENT. DEVICES THAT ARE INSTALLED WILL BE INSTALLED PER
NFPA 72 REQUIREMENTS
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1 /2
FIRE PROTECTION:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
ARCHITECT:
CB DESIGN GROUP
421 KING ST., SUITE 301
ALEXANDRIA, VA 22314
POC: WES BRIDGES
703.772.4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
PARTIALLY
SPRINKLERED Drawing of
ELECTRICAL:
HUITT-ZOLLARS
500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts
6/25/2021
100% BID SET BUILDING 2 - ADMINISTRATIVE
4800 MEMORIAL DRIVE
WACO, TX 76711
024-10122-000
JLHMAR
FIRE ALARM PLAN - LEVEL 2
2-FA103
2 3
-1
-0
F A
/2
/2
.p d f
WACO VA MEDICAL CENTER - FIRE
ALARM CAMPUS UPGRADE
NTRUE
NORTH
SCALE: 1/8" = 1'-0"
A13
BUILDING 2 - FIRE ALARM PLAN - LEVEL 2
VA Project Number:
S
S C
M
C
CO
H R
S
ID
S P
WF
PS
VS
FAA
FACP
FATC
1. PROVIDE AND INSTALL A NEW FIRE ALARM SYSTEM THROUGHOUT THE BUILDING
PER THE VA DESIGN GUIDE AND NFPA 72. REFER TO SPEC SECTION 28 31 00
INTERIOR FIRE ALARM SYSTEM. FIRE ALARM SYSTEM WILL BE ZONED PER FLOOR.
2. ALL EXISTING FIRE ALARM DEVICES, PANELS AND RELATED EQUIPMENT ARE TO
BE DEMOLISHED. EXISTING ALARM SYSTEMS MUST REMAIN IN-SERVICE AND
FUNCTIONAL WHILE NEW ALARM SYSTEM IS INSTALLED. FOLLOW ILSM
PROTOCOLS FOR SHUTDOWN AND PHASE DEMO OF EXISTING ALARM SYSTEM SO
THAT REMOVAL ONLY OCCURS ONCE NEW ALARM SYSTEM IS FULLY INSTALLED
AND FUNCTIONAL.
3. ALL EXISTING INTERFACING DEVICES (TAMPERS, FLOWS, PRESSURE SWITCHES,
ETC) WILL BE CONNECTED TO THE NEW FA SYSTEM AND REPORT TO THE MAIN
GRAPHIC ANNUNCIATORS IN BUILDING 225. A SECONDARY MONITORY STATION
SHALL BE LOCATED IN BUILDING 18. INTERFACING DEVICES ARE SHOWN WHEN
LOCATIONS ARE KNOWN, HOWEVER THE DRAWINGS SHOULD NOT BE USED AS
EXHAUSTIVE LIST. THE EXISTING CAMPUS FIRE ALARM SYSTEM WILL NOT BE
REUSED AND A NEW CAMPUS WIDE SYSTEM IS TO BE PROVIDED, SEE FIRE ALARM
SITE PLAN.
4. COORDINATE FIRE ALARM SYSTEM DEVICE LOCATIONS WITH LIGHT FIXTURES,
STRUCTURAL MEMBERS, SPRINKLER HEADS AND PIPING, HVAC EQUIPMENT AND
DUCTWORK. CONTRACTOR TO VERIFY LOCATIONS OF DUCT SMOKE DETECTORS
AND CONNECT TO NEW FIRE ALARM SYSTEM.
5. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE AND
SATISFACTORILY OPERATING SYSTEMS AS INDICATED ON THE CONTRACT
DOCUMENTS AND AS EVIDENTLY INTENDED. IT IS NOTED THAT THE DRAWINGS
ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENTS OF SYSTEMS AND
WORK. INTERCONNECTIONS HAVE BEEN SHOWN, AND THE CONTRACTOR SHALL
FURNISH AND INSTALL CONDUIT AND WIRING AS REQUIRED TO ACCOMPLISH THE
FUNCTIONS INDICATED. ADDITIONALLY, FIRE ALARM SYSTEMS HAVE BEEN
SHOWN AND THE CONTRACTOR SHALL FURNISH AND INSTALL THE REQUIRED
QUANTITIES AND TYPES OF CABLES, CONDUCTORS, RACEWAYS, REMOTE POWER
SUPPLIES AND CONNECTIONS, SHIELDING REQUIREMENTS, ETC., AS REQUIRED
BY THE SYSTEM MANUFACTURER, THE SPECIFICATIONS, AND ANY APPLICABLE
CODES. ALL WIRING SHOWN ON RISER DIAGRAMS SHALL ALSO BE FURNISHED
AND INSTALLED REGARDLESS OF WHETHER THESE ITEMS ARE SHOWN ON THE
FLOOR PLANS.
6. THE CONTRACTOR SHALL COORDINATE THE ELECTRICAL WORK WITH THE WORK
OF ALL OTHER TRADES AND EXISTING CONDITIONS SO AS TO AVOID CONFLICTS.
RESOLVE ALL CONFLICTS THROUGH THE A/E PRIOR TO ROUGH-IN. FAILURE TO
PROVIDE SUCH COORDINATION PRIOR TO WORK BEING INSTALLED SHALL NOT BE
CAUSE FOR ADDITIONAL COMPENSATION TO THE CONTRACTOR, AND MAY
RESULT IN REJECTION OF THE WORK.
7. ADDITIONAL DEVICES MAY BE REQUIRED. DO NOT USE THESE DRAWINGS FOR
DEVICE COUNTS.
8. ALL MATERIALS SHALL BE NEW, SHALL BE SUITABLE FOR THE APPLICATION
INTENDED, AND SHALL BEAR LABELS OR MARKINGS INDICATING THIRD PARTY
TESTING LABORATORY LISTINGS ACCEPTABLE TO THE AUTHORITY HAVING
JURISDICTION.
9. EXISTING CONDUIT IN GOOD CONDITION THAT HAS BEEN SALVAGED FROM OTHER
BUILDINGS MAY BE REUSED IF POSSIBLE AND SHALL BE STRIPED IN PATIENT
AREAS. NEW CONDUIT SHALL BE MARKED WITH RED COUPLINGS. ALL OTHER
MATERIALS SHALL BE NEW, SHALL BE SUITABLE FOR THE APPLICATION INTENDED,
AND SHALL BEAR LABELS OR MARKINGS INDICATING THIRD PARTY TESTING
LABORATORY LISTINGS ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.
10. ALL FIRE ALARM CABLES SHOULD BE INSTALLED IN METAL RACEWAYS.
11. ALL RACEWAY AND WIRING SHALL BE CONCEALED IN FINISHED SPACES AND MAY
BE EXPOSED IN UNFINISHED SPACES SUCH AS MECHANICAL AND ELECTRICAL
ROOMS. ALL RACEWAY AND WIRING SHALL BE ROUTED EITHER PERPENDICULAR
OR PARALLEL TO THE BUILDING'S STRUCTURAL COMPONENTS.
12. PROVIDE PULL AND JUNCTION BOXES AS REQUIRED TO MEET CODE AND
INSTALLATION REQUIREMENTS. PULL AND JUNCTION BOXES SHALL BE
CONCEALED IN FINISHED SPACES AND LOCATIONS SHALL BE COORDINATED WITH
THE WORK OF ALL OTHER TRADES SO AS TO AVOID CONFLICTS.
13. ALL CONDUCTORS SHALL BE IDENTIFIED AT EACH JUNCTION BOX, OUTLET BOX,
CABINET, PULL BOX, ETC., WITH VINYL SELF-ADHESIVE TAGS INDICATING PANEL
AND CIRCUIT NUMBER, CONTROL WIRE IDENTIFICATION NUMBER, OR OTHER
APPROPRIATE INFORMATION. ALL PULL AND JUNCTION BOXES SHALL BE LABELED
AS TO FUNCTION.
14. ALL EQUIPMENT SHALL BE SECURELY FASTENED BY MEANS OF ANCHORS, RODS,
HANGERS, SUPPORTS, GUIDES, SWAY BRACES, ETC., TO MAINTAIN ALIGNMENT
AND PREVENT EQUIPMENT MOVEMENT. ALL EQUIPMENT LOCATED IN SEISMIC
ZONES SHALL BE SECURED WITH MEANS APPROVED FOR THE SEISMIC
CLASSIFICATION ENCOUNTERED.
15. ALL PENETRATIONS OF FIRE OR SMOKE RATED CONSTRUCTION SHALL BE SEALED
WITH FIRESTOPPING MATERIALS APPROVED AND LISTED FOR THE RATING OF THE
CONSTRUCTION TO BE PENETRATED. PROVIDE DOCUMENTATION ON ALL SUCH
PENETRATION SEALING SYSTEMS FOR VERIFICATION OF PROPER INSTALLATION.
16. ALL PENETRATIONS OF ROOFS, EXTERIOR WALLS, FOUNDATIONS, OR OTHER
WATER OR MOISTURE PROOF CONSTRUCTION SHALL BE SEALED WITH
APPROPRIATE SEALING FITTINGS OR SEALED CONSTRUCTION TO PREVENT THE
INTRODUCTION OF MOISTURE INTO THE BUILDING.
17. WHERE EMPTY RACEWAYS ARE INSTALLED, THEY SHALL BE LABELED AT BOTH
ENDS AND FITTED WITH NYLON PULLSTRINGS FOR FUTURE USE.
18. ELECTRICAL WORK SHALL BE PERFORMED ON DE-ENERGIZED SYSTEMS ONLY TO
PREVENT PERSONNEL INJURY AND POTENTIAL SYSTEM FAILURE. WHERE WORK
ON EXISTING SYSTEMS WILL REQUIRE INTERRUPTION OF ELECTRICAL SERVICE,
THEN TEMPORARY PROVISIONS ACCEPTABLE TO THE OWNER FOR TEMPORARY
POWER SHALL BE UTILIZED UNTIL THE WORK IS COMPLETE.
19. THE FIRE ALARM SYSTEM SHALL COMPLY WITH ALL RELATED NFPA, BUILDING
CODES AND LOCAL FIRE DEPARTMENT REGULATIONS.
20. WALL MOUNTED FIRE ALARM PULL STATIONS ARE TO BE LOCATED 46" A.F.F. AND
WITHIN 5' OF THE NEAREST ADJACENT EXIT DOOR FROM THE FLOOR OR
BUILDING.
21. WALL MOUNTED FIRE ALARM NOTIFICATION APPLIANCES, EITHER VISUAL, OR
COMBINATION AUDIO/VISUAL, SHALL BE LOCATED SUCH THAT THE ENTIRE LENS
OF THE VISUAL PORTION IS BETWEEN 80" AND 96" A.F.F. AUDIO ONLY APPLIANCES
SHALL BE LOCATED, NOT LESS THAN 90" A.F.F. TO TOP OF APPLIANCE, OR 6"
BELOW CEILING.
FIRE ALARM GENERAL NOTES
DUCT SMOKE DETECTOR
AREA SMOKE DETECTOR
DOOR RELEASE SMOKE DETECTOR
S O
U N
D G
E N
E R
A L
B U
IL
D
R
M
X
X
N O
T
IF
Y N
E C
E S
S A
R Y
S
INPUT
OUTPUT
N O
T
IF
Y F
IR
E
D E
P A
R M
E
IN
IT
IA
T
E S
U P
E R
V
IS
O R
Y S
IG
N
A L
T O
A
4- H
O U
R M
A N
N E
D P
O
IN
T F
O R
IM
M
E D
IA
TE
R E
S P
O N
S E
X
C
LO
S E
A S
S O
C
IA
T E
S M
O
R R
IE
R
D O
O R
S O
N T
O
R
X
MANUAL PULL STATION
ELEVATOR MACHINE ROOM HEAT DETECTOR
SPRINKLER WATERFLOW / PRESSURE SWITCH
X
X
X
X
X
X
X
X
X
ELEVATOR SMOKE DETECTOR X X X
X
X
C
LO
S E
D A
M P
E R
S O
N F
O
X
IM
A T
E T
O D
E T
E C
TO
R
X
X
S H
U T
D O
W N
A U
R H
A N
D
R V
E D
B Y
T H
E D
E T
E C
T O
R
X1
R E
C A
LL
E
LE
V
A T
O R
X
IN
IT
IA
T
E E
LE
V
A T
O R
S H
W
N A
N D
D
IS
C O
N N
E
V A
T O
R P
O W
E R
X
O P
E N
L O
C K
E D
E G
R E
O
R S
O N
F
LO
O R
O F
F
IG
IN
X
X
X
X
FIRE ALARM MATRIX
WATER CONTROL VALVE TAMPER SWITCH
1. DO NOT PROVIDE DUCT DETECTORS IN DEDICATED (100%) EXHAUST FANS, THEY SHOULD CONTINUE TO RUN.
X
FIRE ALARM SYMBOLS
DEVICES
EXTERIOR BELL
SYMBOL DESCRIPTION
DETECTORS
MANUAL PULL STATION
SPEAKER ONLY CEILING MOUNTED
COMBINATION OF SPEAKER/STROBE WALL MOUNTED
SPEAKER ONLY WALL MOUNTED
STROBE ONLY CEILING MOUNTED
STROBE ONLY WALL MOUNTED
MNS SPEAKER/STROBE CEILING MOUNTED
GAS DETECTOR - CARBON MONOXIDE
HEAT DETECTOR - RATE OF RISE
SMOKE DETECTOR - IN DUCT
SMOKE DETECTOR - PHOTOELECTRIC
SWITCHES
FLOW DETECTOR/SWITCH
PRESSURE DETECTOR/SWITCH
VALVE SUPERVISORY SWITCH
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
PANELS
LINE TYPES
SMOKE/ALARM ZONE BOUNDARY LINES
CODE DATA
OCCUPANCY BUSINESS
SPRINKLERS FULLY SPRINKLERED
NOTIFICATION SPEAKERS, STROBES AND COMBINATION SPEAKER-STROBES IN
NORMALLY OCCUPIED AREAS
DETECTION MANUAL PULL-STATIONS, SPRINKLERS, SMOKE DETECTOR AT
FACP, CO DETECTOR AT FUEL FIRED EQUIPMENT
FIRE ALARM
ZONING
FIRE ALARM SYSTEM TO BE ZONED PER FLOOR
* SMOKE DETECTION IS SHOWN THROUGHOUT BUILDING BUT NEED ONLY BE INSTALLED
WHERE THERE IS NO SPRINKLER DETECTION. ADDITIONALLY, IF FULL SPRINKLERED
PROTECTION IS PROVIDED AS PART OF A SEPARATE PROJECT, SMOKE DETECTION
DEVICES MAY BE REDUCED PER NFPA 72.
FIRE ALARM
CONTROL PANEL
RM BA139
NOTIFICATION APPLIANCES
GROUND LEVEL FIRE/SMOKE
INITIATING DEVICES GROUND LEVEL
FIRE/SMOKE
GROUND LEVEL
NOTE: CONTRACTOR SHALL
VERIFY ALL NECESSARY DEVICE
COUNTS
NOTIFICATION APPLIANCES
LEVEL 1 FIRE/SMOKE
INITIATING DEVICES
LEVEL 1 FIRE/SMOKE
LEVEL 1
MAIN GRAPHIC ANNUCIATOR IN
BUILDINGS 225 AND 18
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
FIRE PROTECTION:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
ARCHITECT:
CB DESIGN GROUP
421 KING ST., SUITE 301
ALEXANDRIA, VA 22314
POC: WES BRIDGES
703.772.4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
FULLY
SPRINKLERED Drawing of
ELECTRICAL:
HUITT-ZOLLARS
500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts
6/25/2021
100% BID SET BLDG 4 - OPC / PHARM. / LAB / RAD.
4800 MEMORIAL DRIVE
WACO, TX 76711
024-10122-000
JLHMAR
FIRE ALARM GENERAL NOTES AND
DETAILS
4-FA001
4 1 3
-1
-0
F A
/2
/2
.p d f
WACO VA MEDICAL CENTER - FIRE
ALARM CAMPUS UPGRADE
SCALE: NTS
A6
BUILDING 4 - FIRE ALARM RISER DIAGRAM
VA Project Number:
UP
UP
UP
UP
C
C
C C S C
C
S C
S C
S C
C
CC
C
C S C M
C
S C
C C
F
F
F
F
F
F
F FF
C
S P
CO
C
S C
C
S C
C
F
C
C
C
S C
C
C
S CC
CS C
C
C
S C C
S C
C
S C
C
PSVSWF
WF VS
VS
VS
PS
M
C
C
C
C
F
S C
C
S C
S P
H R
F F A C P
S P
F
F A A
F
F
S
S C
M
C
CO
H R
S
ID
S P
WF
PS
VS
FAA
FACP
FATC
ELECTRICAL
BA130
WOMEN
RESTROOM
BA125B
NURSING OFFICE
CB15
MENS
RESTROOM
BA125A
WAITING AREA
CB2B
CORRIDOR
CB5
HOUSEKEEPING
BA166
WOMEN
RESTROOM
BA164
ESCORT
BB103-D
CORRIDOR
CB23
STORAGE,
GENERAL
BA139
COFFEE BAR
BA173
CONTROLLED
NARCOTICS
BB104
ELECTRICAL
ROOM
BA172
PHARMACIST
BA169
PHARMACY
BB104A
EXAM ROOM
BA117
DIABETICS/
TELERETINAL
IMAGING
BA112
EXAM ROOM
BA109
HAC
BB102
PHARMACY
BREAK ROOM
BB103
PATIENT REP
BA170
MECHANICAL
ROOM
BA171
EMS STORAGE
BB100
MED SUPPLY
STORAGE
BA115
AMBULANCE
ENTRANCE
CB2C
RESTROOM
BA110
TREATMENT
ROOM
BA106
TREATMENT
ROOM
BA107
EXAM ROOM
BA111
EXAM ROOM
BA113
AMBULATORY
CARE DESK
BA114
EXAM ROOM
BA153
MEANS TEST
BA101B
PROCESSING/REGISTRATION
BA101C
VET ID CARD
BA101A
WAITING AREA
CB2A
MENS
RESTROOM
BA168
PRIMARY CARE
OFFICE
BA163
CAFE
BB101
CLEAN LINEN
CB-18A
SOILED LINEN
CB-18B
TELEHEALTH
BB103-F
PHARMACY HELP
LINE
BB103B
PHARMACY
WAITING
BB103-C
TELEHEALTH
BB103-E
EXAM ROOM
BA161
PHARMACY
BA162
CORRIDOR
CB2
CORRIDOR
CB20
CORRIDOR
CB10
CORRIDOR
CB17
CORRIDOR
CB11
CORRIDOR
CB8
CORRIDOR
CB16
CORRIDOR
ELEVATOR
LOBBY
CB-18
ELEVATOR
MACHINE ROOM
BA100
STAIR 2
BAS2
STORAGE
NO
LABEL
SUB BSMT
ACCESS
VIDEO ROOM
BA105
CHASE
BB100A
STAIR 6
BAS6
STAIR 5
BAS5
TREATMENT
ROOM
BA157
EXAM ROOM
BA160
EXAM ROOM
BA156
EXAM ROOM
BA159
DISPOSITION
AREA
BA123
SOCIAL WORKER
BA129
OFFICE
BA124
EXAM ROOM
BA121
MAROON TEAM
CHECK-IN DESK
BA122
WAITING AREA
BA149
NURSING
INTERVEIW
ROOM
BA152
UNISEX
RESTROOM
BA145B
CORRIDOR
CB14
IMAGING
RECEPTION
BA146
EXAM ROOM
BA155
WAITING AREA
2 EXAM ROOM
BA154
FORM STORAGE
SUPERVISOR
BA103
OFFICE
BA116
INFORMATION
RECEPTIONIST
BA101
ELECTRICAL
BA119
COMMUNICATIONS
CLOSET
BA120
CLINIC MANAGER
BA118
CLEAN LINEN
ROOM
BA103-3
EXAM ROOM
BA104
SOILED UTILITY
BA103-2
STORAGE,
EQUIPMENT
BA103-1OXYGEN
BA103-4
EXAM ROOM
BA167
HOUSEKEEPING
BA127
NURSE
BA126
STAFF LOUNGE
BA125
VESTIBULE
CB1
MULTI PURPOSE
ROOM
BA165
CORRIDOR
CB3
NURSE LOCKER
ROOM
BA128
WAITING AREA
CORRIDOR
XXX
PROGRAM CLERK
BA132
NURSE MANAGER
BA131
MENS
RESTROOM
BA137
OFFICE
BA133
NUTRITION
CLINIC DIETITION
BA129A
WAITING AREA
B13A
CORRIDOR
CB12
PATIENT FUNDS
BA138
TRAVEL
BA134
WOMENS
RESTROOM
BA136
STAIR 1
BAS1
SUB BASEMENT
ACCESS
AGENT CASHIER
BA135
CORRIDOR
CB13
ULTRASOUND
BA147A
IMAGING
EDUCATION
BA144 STORAGE,
GENERAL
TECH OFFICE
BA143
CT SCAN
BA145
IMAGING
MANAGEMENT
BA148
CT CONTROL
BA145A
IMAGING OFFICE
BA142
X-RAY IMAGING
BA140
VESTIBULE
9 DIGITAL
PROCESSING
BA141A
X-RAY IMAGING
BA141
RESTROOM
BA140A
TOILET
BA163A
1 2 3 5
6 7 8 9 10 11 12
13 14 15
A
B
C
D
E
F
G
H
I
J
K
L
BUILDING 4 BUILDING 202
FA05
FA01
FA03
FIRE ALARM SYMBOLS
DEVICES
EXTERIOR BELL
SYMBOL DESCRIPTION
DETECTORS
MANUAL PULL STATION
SPEAKER ONLY CEILING MOUNTED
COMBINATION OF SPEAKER/STROBE WALL MOUNTED
SPEAKER ONLY WALL MOUNTED
STROBE ONLY CEILING MOUNTED
STROBE ONLY WALL MOUNTED
MNS SPEAKER/STROBE CEILING MOUNTED
GAS DETECTOR - CARBON MONOXIDE
HEAT DETECTOR - RATE OF RISE
SMOKE DETECTOR - IN DUCT
SMOKE DETECTOR - PHOTOELECTRIC
SWITCHES
FLOW DETECTOR/SWITCH
PRESSURE DETECTOR/SWITCH
VALVE SUPERVISORY SWITCH
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
PANELS
LINE TYPES
SMOKE/ALARM ZONE BOUNDARY LINES
SCALE: 1/8" = 1'-0"
A12
BUILDING 4 - FIRE ALARM PLAN - BASEMENT LEVEL
KEYNOTE LEGEND
FA01 EXISTING FIRE ALARM CONTROL PANEL.
FA03 EXISTING ANNUNCIATOR LOCATION
FA05 HEAT DETECTOR IN ELEVATOR MACHINE ROOM MAY BE OMITTED IF NO SPRINKLER
IS PRESENT.
NTRUE
NORTH
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1 /2
FIRE PROTECTION:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
ARCHITECT:
CB DESIGN GROUP
421 KING ST., SUITE 301
ALEXANDRIA, VA 22314
POC: WES BRIDGES
703.772.4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
FULLY
SPRINKLERED Drawing of
ELECTRICAL:
HUITT-ZOLLARS
500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts
6/25/2021
100% BID SET BLDG 4 - OPC / PHARM. / LAB / RAD.
4800 MEMORIAL DRIVE
WACO, TX 76711
024-10122-000
JLHMAR
FIRE ALARM PLAN - BASEMENT
LEVEL
4-FA101
4 2 3
-1
-0
F A
/3
/2
.p d f
WACO VA MEDICAL CENTER - FIRE
ALARM CAMPUS UPGRADE
VA Project Number:
DN
DN
DN
DN
DN
DN
DN
DN
UP
UP
F
F
F
F
F
C
C S C C
C
C
C
S C
C S C C
S C
C
C
C
S P
S CC
C
C
C
S CC
C
S C
C
H R
VS WF
WFVS
C C
F
C
C
C
C
C
C C
C
CC
C
C
S P
H R
S P
C C C
C
F
F
S
S C
M
C
CO
H R
S
ID
S P
WF
PS
VS
FAA
FACP
FATC
MEN'S LOCKER
1A100A
MEN'S
RESTROOM
1A100B
OFFICE
1A107A
OFFICE
1A104
CORRIDOR
1A106C
OFFICE
1A107
OFFICE
1A104A
BIOSAFETY
LOUNGE
1A100
PHLEBOTOMY
SUPPLY ROOM
1A-157A
ELEVATOR MACH.
ROOM
1A156
HEMATOLOGY
1A157F
WOMEN'S
LOCKER
1A100CWOMEN'S
RESTROOM
1A100D
SERVER ROOM
1A106
HOUSEKEEPING
1A128
EXAM ROOM
1A114
SERVER ROOM
FOYER
OFFICE/EXAM
1A103A
SPD CLOSET
1A129
LIQUID NITROGEN
1A151
SERVER ROOM
1A105
STORAGE
STORAGE
CHEMISTRY
1A157E
URINALYSIS
1A157H
LEVEL 3 LAB
SUITE
1A157
PCR LAB
1A157I
LAB OFFICE
1A157L
DECONTAMINATION
ROOM
1A157K
COPY/STORAGE
1A126A
CLINIC
RECEPTION
1A126
ELECTRICAL
CLOSET
1A109
CORRIDOR
C1-7
STAIR 4
1S4
GLUCOSE METER
CLINIC
1A122
OFFICE/EXAM
1A103
SECRETARY
1A-157C
TOXICOLOGY
1A157G
CORRIDOR
DEIONIZED
WATER
1A-157B
HOUSEKEEPING
1A157R
ANCILLARY
TESTING OFFICE
1A157P
ANCILLARY
TESTING
1A157N STAIR 2
1S2
LIFT
MANAGER'S
OFFICE
1A157D
VIEWING ROOM
1A157J1
STERILE/SOLUTION
PREP
1A157M
MYCOBACTERIOLOGY
ROOM
1A157J2
MYCOLOGY
1A157J3
CORRIDOR
C1 10
CORRIDOR
C1 12
WAITING
C1 1C
WAITING
C1 8A
CORRIDOR
C1 8
STAIR 3
1S3
CORRIDOR
C1 13
WAITING
C1
11D
WORKROOM
1A145C
CORRIDOR
C1 11
COMMUNICATIONS
CLOSET
1A134A
EXAM ROOM
1A135
TELEPHONE
CLOSET
1A110A
EXAM ROOM
1A149
SOILED
UTILITY/LINEN
1A150
CLEAN LINEN
1A130
OFFICE/EXAM
1A146
RESTROOM
1A148
GROUP
CLINIC/EXAM
1A152
LAB COLLECTION
AREA
1A127
CORRIDOR
RESTROOM
1A127A
EXAM ROOM
1A152A
STORAGE
CLOSET
1A145A
HEALTH
TECHNICIAN
1A144
SPEECH/LANGUAGE
PATHOLOGIST
1A143
WAITING ROOM
C1
13A
HEARING AID
REPAIR
1A140
HEARING
AID/EVOKED
RESPONSE
TESTING
1A142
CLINICAL
AUDIOLOGIST
1A141
OFFICE/EXAM
1A147
PULMONARY
FUNCTION
1A145
OFFICE/EQUPT.
STORAGE
1A145B
FIRE SIGNAL
CLOSET
1A133
RECEPTION
CUBICLE
C1
11C
RECEPTION
CUBICLE
C1-151
ELECTRICAL
CLOSET
1A134
EKG ROOM
1A132
STAIR 1
1S1
STAIR 5
1S5
STAIR 6
1S6
ATTIC ACCESS
1A108
WOMEN'S
RESTROOM
1A102
MEN'S
RESTROOM
1A101
RESTROOM
154A
PROCEDURE
ROOM
1A154
EXAM ROOM
1A153
CORRIDOR
C1
151CORRIDOR
C1 9
SOUND BOOTH
1A
SOUND BOOTH
SOUND BOOTH
CORRIDOR
ELEVATOR
LOBBY
C1 1A
ELEVATOR
LOBBY
C1 8C
CORRIDOR
C1 14
CORRIDOR
C1 6
CORRIDOR
C1 2
CORRIDOR
C1 1
STORAGE ROOM
1A117
EXAM ROOM
1A116
NURSE
1A119
PHYSICIAN
WORK/CONF
ROOM
1A121
OFFICE/EXAM
1A113
TREATMENT
ROOM
1A136
AUDIOLOGIST
BOOTH 2
1A137
PHYSICIAN EXAM
ROOM
1A118
EXAM ROOM
1A124
NURSE
1A125
EXAM ROOM
1A155
MEN'S
RESTROOM
1A123
EMPLOYEE
BREAK ROOM
1A110
EXAM ROOM
1A115
WOMEN'S
RESTROOM
1A120
OFFICE/EXAM
1A111
NURSES/TREATMENT
ROOM
1A112
1 2 3 5
6 7 8 9 10 11 12
13 14 15
A
B
C
D
E
F
G
H
I
J
K
L
FA04
FA05
FA06
FA04
FIRE ALARM SYMBOLS
DEVICES
EXTERIOR BELL
SYMBOL DESCRIPTION
DETECTORS
MANUAL PULL STATION
SPEAKER ONLY CEILING MOUNTED
COMBINATION OF SPEAKER/STROBE WALL MOUNTED
SPEAKER ONLY WALL MOUNTED
STROBE ONLY CEILING MOUNTED
STROBE ONLY WALL MOUNTED
MNS SPEAKER/STROBE CEILING MOUNTED
GAS DETECTOR - CARBON MONOXIDE
HEAT DETECTOR - RATE OF RISE
SMOKE DETECTOR - IN DUCT
SMOKE DETECTOR - PHOTOELECTRIC
SWITCHES
FLOW DETECTOR/SWITCH
PRESSURE DETECTOR/SWITCH
VALVE SUPERVISORY SWITCH
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
FIRE ALARM TERMINAL CABINET
PANELS
LINE TYPES
SMOKE/ALARM ZONE BOUNDARY LINES
SCALE: 1/8" = 1'-0"
A12
BUILDING 4 - FIRE ALARM PLAN - LEVEL 1 NTRUE
NORTH
KEYNOTE LEGEND
FA04 SMOKE AND HEAT DETECTION AT TOP OF ELEVATOR SHAFT MAY BE OMITTED IF NO
SPRINKLER IS PRESENT. DEVICES THAT ARE INSTALLED WILL BE INSTALLED PER
NFPA 72 REQUIREMENTS
FA05 HEAT DETECTOR IN ELEVATOR MACHINE ROOM MAY BE OMITTED IF NO SPRINKLER
IS PRESENT.
FA06 PROVIDE FIRE ALARM DEVICES IN THE CEILING SPACE
VA Project Number:
Building:
Drawing Number:
Project Title:
Project Location:
Issue Date:
Checked By: Drawn By:
Drawing Title:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
Submission:
ARCHITECT / ENGINEER OF RECORD:
Revisions: Date:
CONSULTANTS:
/8
/4
/8
/2
/4
-1
/2
FIRE PROTECTION:
LEO A DALY
730 Second Avenue South Suite 1300 Minneapolis, MN 612.338.8741 POC: Melisa Rodriguez
ARCHITECT:
CB DESIGN GROUP
421 KING ST., SUITE 301
ALEXANDRIA, VA 22314
POC: WES BRIDGES
703.772.4213
PROFESSIONAL SEAL:
2345678910111213141516
B
C
D
E
F
G
H
I
J
12345678910111213141516
FULLY
SPRINKLERED Drawing of
ELECTRICAL:
HUITT-ZOLLARS
500 West 7th Street, Suite 300, Fort Worth, TX 817.335.3000, POC: Jeff Roberts
6/25/2021
100% BID SET BLDG 4 - OPC / PHARM. / LAB / RAD.
4800 MEMORIAL DRIVE
WACO, TX 76711
024-10122-000
JLHMAR
FIRE ALARM PLAN - LEVEL 1
4-FA102
4 3 3
-1
-0
F A
/0
/2
.p d f
WACO VA MEDICAL CENTER - FIRE
ALARM CAMPUS UPGRADE
VA Project Number:
S
S C
M
C
CO
H R
S
ID
S P
WF
PS
VS
FAA
FACP
FATC
1. PROVIDE AND INSTALL A NEW FIRE ALARM SYSTEM THROUGHOUT THE BUILDING
PER THE VA DESIGN GUIDE AND NFPA 72. REFER TO SPEC SECTION 28 31 00
INTERIOR FIRE ALARM SYSTEM. FIRE ALARM SYSTEM WILL BE ZONED PER FLOOR.
2. ALL EXISTING FIRE ALARM DEVICES, PANELS AND RELATED EQUIPMENT ARE TO
BE DEMOLISHED. EXISTING ALARM SYSTEMS MUST REMAIN IN-SERVICE AND
FUNCTIONAL WHILE NEW ALARM SYSTEM IS INSTALLED. FOLLOW ILSM
PROTOCOLS FOR SHUTDOWN AND PHASE DEMO OF EXISTING ALARM SYSTEM SO
THAT REMOVAL ONLY OCCURS ONCE NEW ALARM SYSTEM IS FULLY INSTALLED
AND FUNCTIONAL.
3. ALL EXISTING INTERFACING DEVICES (TAMPERS, FLOWS, PRESSURE SWITCHES,
ETC) WILL BE CONNECTED TO THE NEW FA SYSTEM AND REPORT TO THE MAIN
GRAPHIC ANNUNCIATORS IN BUILDING 225. A SECONDARY MONITORY STATION
SHALL BE LOCATED IN BUILDING 18. INTERFACING DEVICES ARE SHOWN WHEN
LOCATIONS ARE KNOWN, HOWEVER THE DRAWINGS SHOULD NOT BE USED AS
EXHAUSTIVE LIST. THE EXISTING CAMPUS FIRE ALARM SYSTEM WILL NOT BE
REUSED AND A NEW CAMPUS WIDE SYSTEM IS TO BE PROVIDED, SEE FIRE ALARM
SITE PLAN.
4. COORDINATE FIRE ALARM SYSTEM DEVICE LOCATIONS WITH LIGHT FIXTURES,
STRUCTURAL MEMBERS, SPRINKLER HEADS AND PIPING, HVAC EQUIPMENT AND
DUCTWORK. CONTRACTOR TO VERIFY LOCATIONS OF DUCT SMOKE DETECTORS
AND CONNECT TO NEW FIRE ALARM SYSTEM.
5. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE AND
SATISFACTORILY OPERATING SYSTEMS AS INDICATED ON THE CONTRACT
DOCUMENTS AND AS EVIDENTLY INTENDED. IT IS NOTED THAT THE DRAWINGS
ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENTS OF SYSTEMS AND
WORK. INTERCONNECTIONS HAVE BEEN SHOWN, AND THE CONTRACTOR SHALL
FURNISH AND INSTALL CONDUIT AND WIRING AS REQUIRED TO ACCOMPLISH THE
FUNCTIONS INDICATED. ADDITIONALLY, FIRE ALARM SYSTEMS HAVE BEEN
SHOWN AND THE CONTRACTOR SHALL FURNISH AND INSTALL THE REQUIRED
QUANTITIES AND TYPES OF CABLES, CONDUCTORS, RACEWAYS, REMOTE POWER
SUPPLIES AND CONNECTIONS, SHIELDING REQUIREMENTS, ETC., AS REQUIRED
BY THE SYSTEM MANUFACTURER, THE SPECIFICATIONS, AND ANY APPLICABLE
CODES. ALL WIRING SHOWN ON RISER DIAGRAMS SHALL ALSO BE FURNISHED
AND INSTALLED REGARDLESS OF WHETHER THESE ITEMS ARE SHOWN ON THE
FLOOR PLANS.
6. THE CONTRACTOR SHALL COORDINATE THE ELECTRICAL WORK WITH THE WORK
OF ALL OTHER TRADES AND EXISTING CONDITIONS SO AS TO AVOID CONFLICTS.
RESOLVE ALL CONFLICTS THROUGH THE A/E PRIOR TO ROUGH-IN.