VA IV Cleanroom Issue 4 Bid Drawings R2.pdf
PDF 10 MB Posted
- Solicitation number
- 36C24424B0001
About this file
This document provides details for a federal contract opportunity to replace an IV cleanroom at the Coatesville VA Medical Center. The solicitation number is 36C24424B0001 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4. The opportunity type is a solicitation for the contract named Z2DA--542-22-133. The solicitation is seeking bids to replace the IV cleanroom facility with new construction in order to meet updated standards for sterile compounding. Bids are due by June 15th, 2022 and the contract is expected to be awarded by August 1st, 2022. The bid drawings file provided is 10MB in size and contains specifications and plans for the cleanroom replacement project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| S04 - Site Visit Sign-In.pdf | ||
| 36C24424B0001 0001.docx | DOCX document | |
| S06 - Ceiling Specs.pdf | ||
| Specifications 100_ Design R4 100323.pdf | ||
| 36C24424B0001_2.docx | DOCX document | |
| AHU Design Submittal - Coatesville VAMC 9-26-2023.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COATESVILLE VA
IV CLEAN ROOM RENOVATION
1400 BLACKHORSE HILL RD,
COATESVILLE, PA
COMBINED CONTRACT
INDEX OF DRAWINGS
10/11/2022
36C24422N0568
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Severna Park, Maryland 21146
TEL: 410.544.3570
www.LRSFederal.com
Replace IV Clean Room
VA Medical Center, Building 2 Project Director
Revisions: Date: 5/19/2023
FULLY SPRINKLERED
ISSUED FOR BID
565 Benfield Road, Suite 400
1213 West Morehead St. Ste. 210 Charlotte, NC 28208
704.594.5335 www.dlrgroup.com
© DLR Group
COVER SHEET
A000
MDISEC
53-23171-00
.ARCHITECTURAL.
A000 COVER SHEET
A001 APPENDIX B
A002 PROJECT STANDARDS
A011 LIFE SAFETY PLAN - LEVEL 01
A102 LEVEL 02 - DEMOLITION & NEW FLOOR PLAN
A103 LEVEL 02 - NEW EQUIPMENT PLAN
A112 LEVEL 02 -DEMOLITION & NEW REFLECTED CEILING PLAN
.MECHANICAL.
M-001 SYMBOLS, ABBREVIATIONS, NOTES AND SCHEDULES
MD-101 HVAC, PIPING AND FIRE PROTECTION - DEMOLITION
MP-101 PARTS PLANS - BASEMENT, FIRST FLOOR AND SECOND FLOOR - NEW WORK
MP-102 PARTS PLANS - IV CLEAN ROOM - HVAC, PIPING AND FIRE PROTECTION - NEW WORK
MP-103 PARTS PLANS - ATTIC - DEMOLITION AND NEW WORK
MP-104 SECTIONS AND RISER DIAGRAMS
MP-105 DETAILS AND DIAGRAMS
MP-106 DETAILS AND DIAGRAMS
MP-107 MECHANICAL CONTROLS DIAGRAM, POINTS LIST, AND SEQUENCE OF OPERATIONS
MP-108 MECHANICAL CONTROLS DIAGRAM, POINTS LIST AND SEQUIENCE OF OPERATION
MP-109 AIR HANDLING UNIT INSTALLATION
MP-110 AIR HANDLING UNIT INSTALLATION
.ELECTRICAL.
E-001 SYMBOLS, ABBREVIATIONS, NOTES AND SCHEDULE
E-101 CLEAN ROOM PART PLANS - LIGHTING AND POWER CONNECTION - NEW WORK
E-102 CLEAN ROOM - ATTIC AND BASEMENT PLANS - EQUIPMENT POWER
E-103 SCHEDULES
ED-101 CLEAN ROOM PARTS PLANS - LIGHTING AND EQUIPMENT POWER - DEMOLITION
.HAZARDOUS MATERIAL REMEDIATION.
H-101 PART PLAN - IV CLEAN ROOM - HAZARDOUS MATERIALS
U P
R
IS
E R
S
2 HR FIRE/SMOKE BARRIER (NCBC SECTION 407.5/709)
RGB
111-063-127
1 HR FIRE BARRIER (NCBC SECTION 707)
RGB
000-000-255
2 HR FIRE BARRIER (NCBC SECTION 707)
RGB
255-127-191
3 HR & 4 HR FIRE WALL SEPARATION (NCBC SECTION 706)
RGB
255-000-000
BUILDING SEPARATION
RGB
000-000-000
1 HR FIRE/SMOKE BARRIER (NCBC SECTION 407.5/709)
RGB
165-145-082
1 HR FIRE PARTITION (NCBC SECTION 708)
RGB
000-255-255
SMOKE TIGHT PARTITION (CORRIDOR) (NCBC SECTION 407.3/710)
RGB
000-255-000
SUITE PERIMETER WALLS (NCBC SECTION 407.4.4.2)
(BUILT AS 407.3/710 SMOKE TIGHT CORRIDOR)RGB
255-127-000
EXIT
NOT INCLUDED IN SOC
CHUTES/ACCESS/DISCHARGE
HAZARDOUS AREA (NFPA 101 18.3.2.1)
SLEEPING SUITE
NON-SLEEPING SUITE
NON-PATIENT SUITE
2 HR FLOOR/CEILING ABOVE
1 HR FLOOR/CEILING ABOVE
NOTE:
1. THIS SHEET VOID UNLESS PRINTED IN COLOR.
2. THIS SHEET HAS BEEN CREATED FROM THE OWNERS
BARRIER MANAGEMENT PLANS AND HAS BEEN MODIFIED ONLY
FOR THE SCOPE OF THIS PROJECT. ALL DIFFERENCES FOR
AREAS NIC SHALL BE REPORTED TO THE ARCHITECT AND
OWNER.
EXIT PATH
FIRE WALL - A FIRE RESISTANCE-RATED WALL HAVING PROTECTED OPENINGS, WHICH
RESTRICTS THE SPREAD OF FIRE AND EXTENDS CONTINUOUSLY FROM THE
FOUNDATION TO OR THROUGH THE ROOF, WITH SUFFICIENT STRUCTURAL
STABILITY UNDER FIRE CONDITIONS TO ALLOW COLLAPSE OF CONSTRUCTION ON
EITHER SIDE WITHOUT COLLAPSE OF THE WALL.
FIRE BARRIER - A FIRE RESISTANCE RATED WALL ASSEMBLY OF MATERIALS DESIGNED
TO RESTRICT THE SPREAD OF FIRE IN WHICH CONTINUITY IS
MAINTAINED.
FIRE PARTITION - A VERTICAL ASSEMBLY OF MATERIALS DESIGNED TO
RESTRICT THE SPREAD OF FIRE IN WHICH OPENINGS ARE
PROTECTED.
2HRS
1HR
2HR
3HR/4HR
BLDG
1HRS
1HR ATRIUM
SMOKE
SUITE
CODE
TEMPORARY PARTITION
PROJECT AREA
SQ FT 650
MAX TRAVEL DISTANCE
60' - 8"
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Severna Park, Maryland 21146
TEL: 410.544.3570
www.LRSFederal.com
Replace IV Clean Room
VA Medical Center, Building 2 Project Director
Revisions: Date: 5/19/2023
FULLY SPRINKLERED
ISSUED FOR BID
565 Benfield Road, Suite 400
1213 West Morehead St. Ste. 210 Charlotte, NC 28208
704.594.5335 www.dlrgroup.com
© DLR Group
LIFE SAFETY PLAN - LEVEL 01
A011
MDISEC
53-23171-00
2018 LIFE SAFETY LEGEND
SCALE: 1/8" = 1'-0"
LEVEL 02 - LIFE SAFETY PLAN - NEW
DEMOLITION GENERAL NOTES
THE CONTRACTOR SHALL:
A. COORDINATE ALL DEMOLITION AND PHASING EFFORTS WITH THE
ARCHITECT AND OWNER’S REPRESENTATIVE. EVERY EFFORT
SHALL BE MADE TO MINIMIZE DISRUPTION OF OWNER’S
OPERATIONS. EXCESSIVE NOISE OR VIBRATION SHALL BE PRE-
APPROVED AND COORDINATED WITH THE OWNER’S
REPRESENTATIVE. IN ALL CASES, PROVISIONS SHALL BE MADE
FOR USER’S SAFETY.
B. COORDINATE ANY DISRUPTION OF UTILITY SERVICES WITH THE
OWNER AND AS SPECIFIED.
C. CONSTRUCT TEMPORARY CONSTRUCTION PARTITIONS WITHIN
THE EXISTING BUILDING WHICH OFFER A ONE-HOUR ENCLOSURE
TO ISOLATE ANY DEMOLITION/CONSTRUCTION WORK FROM THE
GENERAL PUBLIC AND AS DEEMED NECESSARY BY THE OWNER
AND CODE OFFICIAL HAVING JURISDICTION. COORDINATE
LOCATIONS WITH THE OWNER AND MAINTAIN MEANS OF EGRESS
THROUGHOUT THE WORK.
D. MAINTAIN A SECURE, WEATHER-TIGHT ENCLOSURE AT ALL
TIMES.
E. VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND
ELEVATIONS AND NOTIFY THE ARCHITECT OF ANY
DISCREPANCIES.
F. REMOVE IN THEIR ENTIRETY ALL EXISTING WALLS, DOORS,
MILLWORK, PLUMBING FIXTURES, CEILINGS, SOFFITS,
MARKERBOARDS, AND OTHER ITEMS, AS REQUIRED TO EXECUTE
THE DEMOLITION/CONSTRUCTION WORK DESCRIBED BY THE
DRAWINGS.
G. THE OWNER SHALL RESERVE THE RIGHT TO SALVAGE ANY
MATERIALS.
H. PROVIDE PROTECTION FOR ALL EXISTING BUILDING MATERIALS
AND EQUIPMENT FROM DAMAGE DUE TO ANY DEMOLITION OR
CONSTRUCTION-RELATED INCIDENT PERFORMED UNDER THIS
CONTRACT.
I. REPAIR OR REPLACE ITEMS THAT ARE DAMAGED AS A RESULT
OF DEMOLITION OR CONSTRUCTION TO MATCH EXISTING FINISH
AND/OR CONDITION.
J. EXISTING MATERIALS SHALL NOT BE REUSED UNLESS NOTED
OTHERWISE OR AS AUTHORIZED BY ARCHITECT.
K. VERIFY AND MAINTAIN THE LOCATION OF EXISTING POWER,
COMMUNICATION AND DATA CABLES TO PREVENT
INTERRUPTION OF THEIR SERVICE.
L. PATCH FLOOR, WALL AND CEILING PENETRATIONS RESULTING
FROM REMOVAL OR RE-ROUTING OF NEW OR EXISTING PIPING,
DUCTWORK, CONDUIT, AND OTHER ITEMS, AS REQUIRED TO
MAINTAIN FIRE-RESISTANCE-RATED SEPARATIONS. FINISH AS
REQUIRED FOR NEW OR EXISTING ADJACENT SURFACES.
M. CAP ALL DISCONNECTED MECHANICAL PIPING LINES WITHIN THE
WALL OR FLOOR. PATCH AND FINISH AS REQUIRED TO MATCH
NEW OR EXISTING ADJACENT SURFACES.
N. SEE MECHANICAL AND ELECTRICAL DRAWINGS AND NOTES FOR
FURTHER SEQUENCING AND SCOPE OF WORK.
O. AVOID ANY DISTURBANCE OF SOILS WITHIN THE ZONE OF
INFLUENCE AROUND EXISTING FOOTINGS AND FLOOR SLABS AS
DIRECTED BY GEOTECHNICAL ENGINEER.
P. WHERE CMU WALLS ARE INDICATED TO BE REMOVED, PREPARE
ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY REMOVING
CMU IN TOOTH-IN PATTERN BOTH SIDES OF DEMOLITION FOR
CONTRACTOR TO TOOTH-IN NEW CMU PATCHES.
Q. WHERE PLASTER/STUD WALLS ARE INDICATED TO BE REMOVED,
PREPARE ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY
SAWCUTTING ADJACENT PLASTER FINISH A MINIMUM OF 1'-0"
BEYOND DEMOLITION.
R. CONTRACTOR TO REMOVE EXISTING FURNITURE AND
EQUIPMENT AND STORE AS DIRECTED BY COR.
DEMOLITION NOTES APPLY TO ALL DEMOLITION SHEETS.
COORD. OFFICE
212A
CORRIDOR
VIST. COORD.
OFFICE
DOCTOR
OFFICE
EXAM ROOM
206MENS TLT
CORRIDOR
STAIR
IV STORAGE
IV ROOM
JAN.
CLOSET
209A
DOCTOR
OFFICE
D-4
D-2
D-2
D-2
D-4
D-4
D-4
D-1
D-1 D-3
D -5D-6
COORD. OFFICE
212A
CORRIDOR
VIST. COORD.
OFFICE
DOCTOR
OFFICE
EXAM ROOM
206MENS TLT
CORRIDOR
STAIR
DOCTOR
OFFICE
V
IF
" 2"
JAN.
CLOSET
209A
ANTE
ROOM - ISO
CLASS 8
IV ROOM -
ISO CLASS
LINE OF
DEMARCATION
VIF
+/- 1' - 0"
PREFABRICATED
PANEL SYSTEM
1 1
/2
10' - 4"
/8
SX. 4. 20
211X 211Y
X
3' - 5 1/2"
4' - 4"
GENERAL ARCHITECTURAL NOTES
1. PARTITION TYPES SHALL BE DESIGNATED ON FLOOR PLANS
THUS: SEE SHEET A102 FOR TYPES. ALL INTERIOR
PARTITIONS ARE TYPE SX.4.20 UNLESS NOTED OTHERWISE.
2. FURNISH AND INSTALL FIRE-TREATED WOOD BLOCKING OR
METAL BACKING PLATE IN METAL STUD PARTITIONS FOR THE
PROPER ANCHORAGE OF ALL WALL ATTACHED ITEMS; I.E.
TOILET ACCESSORIES, CASEWORK, MILLWORK, WALL-
MOUNTED FIXTURES, MARKER BOARDS, TACK BOARDS, DOOR
STOPS, AUDIO VISUAL BRACKETS, AND OTHER WALL ATTACHED
ITEMS.
XX. X. XX
DEMOLITION KEYED NOTES
THE CONTRACTOR SHALL:
1. REMOVE EXISTING PREFABRICATED CLEAN ROOM IN ITS
ENTIRETY.
2. REMOVE EXISTING RADIATORS. PTM WALL CONSTRUCTION.
3. REMOVE EXISTING FLOORING.
4. REMOVE EXISTING DOOR & FRAME.
5. REMOVE PORTION OF EXISTING WALL AS REQUIRED TO
ACCOMODATE NEW DOOR.
6. REMOVE EXISTING PLUMBING FIXTURE FOR STORAGE AND
REINSTALLATION.
D-#
KEYED NOTES
THE CONTRACTOR SHALL:
1. PATCH TO MATCH WALL AND FLOORING AS REQUIRED.
2. PATCH TO MATCH EXISTING FINISHES AS REQUIRED TO INSTALL
NEW UTILITIES. PAINT WALL TO MATCH EXISTING. PROVIDE NEW
BASE TO MATCH EXISTING.
3. PREPARE SLAB TO RECIEVE NEW WSV FLOORING. SEE SPECS.
GYPSUM WALL BOARD
METAL FRAMING
SOUND ATTENUATION
BLANKET INSULATION
WHERE OCCURS BY
UNIQUE CONDITION
CHARACTER
T H
K
R O
U G
H
MATERIAL DESCRIPTION
S = STEEL (METAL STUDS)
W = WOOD STUDS
H = SHAFT WALLS
M = MASONRY
C = CONCRETE
RATING / HEIGHT
A = FULL HEIGHT / UNDERSIDE OF STRUCT (NOT RATED)
B = 6" ABOVE CEILING (NOT RATED)
C = UNDERSIDE OF CEILING (NOT RATED)
D = PARTIAL HEIGHT (NOT RATED)
X = VARIABLE HEIGHT (NOT RATED)
S = SMOKE PARTITON (NOT RATED)
0 = 0 HOUR RATED (CORRIDOR)
5 = 0.5 HOUR RATED
1 = 1 HOUR RATED
2 = 2 HOUR RATED
3 = 3 HOUR RATED
4 = 4 HOUR RATED
UNIT WIDTH / CONFIGURATION
F = FURRING STRIPS / CHANNELS
1 = 1 5/8" METAL
2 = 2 1/2" METAL / 1 1/2" WOOD
3 = 3 5/8" METAL
4 = 4" METAL / 3 1/2 WOOD / 3 5/8" CMU
6 = 6" METAL / 5 1/2" WOOD / 5 5/8" CMU / 6" CONC
8 = 8" METAL / 7 1/4" WOOD / 7 5/8" CMU / 8" CONC
10 = 10" CONC
12 = 11 5/8" CMU / 12" CONC
X = NON-STANDARD WIDTH, SEE DETAILS
D = DOUBLE STUD FRAMING
S = STAGGERED STUD FRAMING
GYPSUM WALLBOARD INDICATOR
(NOT INCLUDING SHAFT LINER)
0 = NO GWB
1 = ONE LAYER, TAG SIDE
2 = ONE LAYER, EACH SIDE
3 = TWO LAYERS TAG SIDE, ONE LAYER OTHER
4 = TWO LAYERS, EACH SIDE
5 = TWO LAYERS TAG SIDE, NO GWB OTHER
6 = THREE LAYERS, EACH SIDE
SA.3.10
MATERIAL
RATING / HEIGHT
UNIT WIDTH
GWB INDICATOR
UNIQUE CONDITION
WALL TYPE TAG
PARTITION TYPES
DESCRIPTIONS
DOOR AND FRAME SCHEDULE
GENERAL NOTES
A. ALL EXTERIOR HOLLOW METAL FRAMES SHALL BE FILLED WITH
INSULATION.
B. ALL INTERIOR HOLLOW METAL FRAMES SET IN MASONRY AND
CONCRETE WALLS SHALL BE GROUTED SOLID.
C. ALL HOLLOW METAL FRAMES SET IN METAL STUD WALLS
SHALL BE FILLED WITH MINERAL WOOL BLANKET INSULATION.
D. ALL EXTERIOR FRAMES SHALL BE INSTALLED WITH 1/4" SHIM
AND SEALANT AROUND PERIMETER OF FRAME.
E. MASONRY LINTELS AND STEEL LINTELS ARE SHOWN ON
STRUCTURAL DRAWINGS.
F. GLASS TYPES FOR DOORS ARE INDICATED IN THE DOOR
GLAZING COLUMN OF THE DOOR AND FRAME SCHEDULE.
GLASS TYPES FOR FRAMES ARE INDICATED ON THE FRAME
ELEVATIONS.
G. FOR COILING DOORS, GRILLES AND SECTIONAL DOORS, WIDTH
AND HEIGHT DIMENSIONS SHOWN IN DOOR AND FRAME
SCHEDULE REPRESENT FINISHED OPENING SIZE.
CONTRACTOR TO COORDINATE EXACT SIZE OF DOOR WITH
MANUFACTURER.
H. FRAME MANUFACTURER SHALL COORDINATE LOCATIONS OF
ALL CONCEALED CONDUIT AND J-BOXES REQUIRED FOR
SECURITY SYSTEM HARDWARE PRIOR TO MANUFACTURING OF
HOLLOW METAL FRAMES AND COORDINATE WITH SECURITY
HARDWARE AND DEVICES.
I. PROVIDE HEAD RECEIVERS AT ALUMINUM STOREFRONTS AND
CURTAIN WALLS AS REQUIRED FOR STRUCTURAL DEFLECTION
ALLOWANCE.
J. SEE SPECIFICATIONS HARDWARE SECTION FOR HARDWARE
SETS NOTED IN DOOR AND FRAME SCHEDULE.
EQ EQ
/8
1/2" 1/2"
H1
MTL STUDS
AT 16" OC
GYPSUM BOARD
CAULK
HM FRAME
VIF
MATCH EXISTING
EQ EQ
/8
1/2" 1/2"
J1
VIF
MATCH EXISTING
MTL STUDS
AT 16" OC
GYPSUM BOARD
CAULK
HM FRAME
DG DUAL LITE GLASS
F FLUSH PANEL
FG FULL LITE GLASS
FL FULL LOUVERED
G HALF LITE GLASS
GL HALF LITE GLASS & LOUVERED
L LOUVERED (BOTTOM)
LL LOUVERED (TOP & BOTTOM)
N NARROW LITE GLASS
NL NARROW LITE GLASS & LOUVERED
TL LOUVERED (TOP)
V VISION LITE GLASS (10" SQUARE)
VL VISION LITE GLASS & LOUVERED
DOOR PANEL TYPE DESCRIPTIONS
G
HALF LIGHT
S E
E S
C H
E D
U L
E
SCHEDULE
SEE
2"
2"
SCHEDULE
SEE
S E
E S
C H
E D
U L
E
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Severna Park, Maryland 21146
TEL: 410.544.3570
www.LRSFederal.com
Replace IV Clean Room
VA Medical Center, Building 2 Project Director
Revisions: Date: 5/19/2023
FULLY SPRINKLERED
ISSUED FOR BID
565 Benfield Road, Suite 400
1213 West Morehead St. Ste. 210 Charlotte, NC 28208
704.594.5335 www.dlrgroup.com
© DLR Group
LEVEL 02 - DEMOLITION & NEW FLOOR PLAN
A102
MDISEC
53-23171-00
SCALE: 1/4" = 1'-0"
DEMOLITION FLOOR PLAN - LEVEL 02
SCALE: 1/4" = 1'-0"
NEW FLOOR PLAN - LEVEL 02
SCALE: 1 1/2" = 1'-0"
Wall Type SX.4.20
S_-_-2_ NON-RATED STUD PARTITION
MARK
ROUGH
THICKNESS
FIRE/SMOKE SOUND
T.O. WALL
DETAIL
B.O. WALL
DETAIL COMMENTSRATING TESTED ASSEMBLIES
STC
RATING TESTED ASSEMBLIES
SX 4 20 6" NR
SCALE: 1 1/2" = 1'-0"
DOOR HEAD AND JAMB TYPES
SCALE: 1/4" = 1'-0"
DOOR PANEL TYPES
SCALE: 1/4" = 1'-0"
INTERIOR FRAME TYPES
DOOR AND FRAME SCHEDULE
NUMBER
PANEL FRAME
FIRE
RATING HARDWARE SET
DETAILS
COMMENTS
NO. OF
PANELS WIDTH HEIGHT THICKNESS MATERIAL GLASS TYPE MATERIAL TYPE HEAD JAMB
210X Doors to be provided with panel system. Hand wave activation. Interlocking.
211X Doors to be provided with panel system. Hand wave activation. Interlocking.
211Y
GLAZING TYPE DESCRIPTIONS
CG CLEAR FLOAT GLASS
CIG CLEAR INSULATING GLASS
CTG CLEAR TEMPERED FLOAT GLASS
CTIG CLEAR TEMPERED INSULATING GLASS
GL GLASS
IIP INSULATED INFILL PANEL GLASS
LG LAMINATED GLASS
PG PATTERN GLASS
PIG PATTERN INSULATING GLASS
SG SPANDREL GLASS
TFG TINTED FLOAT GLASS
TG TEMPERED GLASS
TIG TINTED INSULATING GLASS
TTG TINTED TEMPERED FLOAT GLASS
TTIG TINTED TEMPERED INSULATING GLASS
WG POLISHED WIRE GLASS
1 3' - 6"
7' - 0"
7' - 0"
7' - 0"
2"
2"
2"
G
G
G HM
NR
NR
NR
ALUM
ALUM
WOOD
3' - 6"
3' - 6"
HW-SH-3
ALUM
ALUM BY VENDOR
BY VENDOR
H1 J1
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Card Reader
E5
E8
E3
E2
E1
E1E1
E4E6
E7
IV ROOM -
ISO CLASS
ANTE
ROOM - ISO
CLASS 8
JAN.
CLOSET
209A
DOCTOR
OFFICE
COORD. OFFICE
212A
CORRIDOR
VIST. COORD.
OFFICE
DOCTOR
OFFICE
EXAM ROOM
206MENS TLT
CORRIDOR
STAIR
A1035
CONTRACTOR TO REMOVE
EXISTING FURNITURE AND
EQUIPMENT AND STORE AS
DIRECTED BY COR.
Level 02 14' - 0"
Level 03 28' - 0"
REMOVE AND DEMOLISH LOUVERED
ATTIC VENT FOR EQUIPMENT
INSTALLATION. DEMOLISH EXTERIOR
WALL TO ACCOMODATE NEW 3'-6" X
3'-6" LOUVERED ATTIC VENT. PATCH
WALL AS REQUIRED. MATCH
EXISTING CONSTRUCTION. SEE A002
FOR LOOSE LINTEL SIZING.
EQ EQ
5' - 5"
E Q
E Q
Level 02 14' - 0"
Level 03 28' - 0"
REMOVE LOUVERED ATTIC VENT
FOR EQUIPMENT INSTALLATION.
DEMOLISH EXTERIOR WALL TO
ACCOMODATE NEW 3'-6" X 3'-6"
LOUVERED ATTIC VENT. PATCH
WALL AS REQUIRED. MATCH
EXISTING CONSTRUCTION. SEE A002
FOR LOOSE LINTEL SIZING.
EQ EQ
3' - 6"
A103
" E
Q E
Q
PTM BRICK
PTM EXISTING WALL
CONSTRUCTION. ENSURE
NEW VAPOR BARRIER
OVERLAPS EXISTING 0'-8".
LOOSE LINTEL STEEL ANGLE
(SEE A002 FOR SIZING)
FACE TRIM
LOUVER BOX
BRACE WHEN NEEDED
GALV. BIRD SCREEN
SEALANT OV/BACKER
ROD - TYP. ALL AROUND
PTD. MTL. FLASHING
S E
E E
L E
V A
T
IO
N
4' - 6"
A103
Sim
2 1/2" DUAL SIDED
PLASTIC GROMMET ONE
IN EACH COUNTER
SUPPORT
1' - 11 15/16" U.N.O
1" R.
/2
/2
S E
E E
L E
V A
T
IO
N
1" R.
1'-2" R.
UNDER COUNTER SUPPORTS
SEE ELEVATION FOR
LOCATION
2" DIAMETER GROMMET
AT ALL LOCATIONS WITH
WORKSTATIONS
3/4" PLYWOOD REQUIRED
UNDER COUNTERTOP AT
ALL OVERHANGS AND
KNEE SPACES
BACKSPLASH
SEE INTERIOR FINISH
SCHEDULE FOR
COUNTERTOP MATERIAL
SIDESPLASH
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Severna Park, Maryland 21146
TEL: 410.544.3570
www.LRSFederal.com
Replace IV Clean Room
VA Medical Center, Building 2 Project Director
Revisions: Date: 5/19/2023
FULLY SPRINKLERED
ISSUED FOR BID
565 Benfield Road, Suite 400
1213 West Morehead St. Ste. 210 Charlotte, NC 28208
704.594.5335 www.dlrgroup.com
© DLR Group
LEVEL 02 - NEW EQUIPMENT PLAN
A103
MDISEC
53-23171-00
SCALE: 1/4" = 1'-0"
NEW EQUIPMENT PLAN - LEVEL 02
SCALE: 1/4" = 1'-0"
EQUIPMENT ENTRANCE ELEVATION - DEMOLITION
EQUIPMENT SCHEDULE
OWNER EQ.
NO. EQUIPMENT NAME MANUFACTURER MODEL PROVIDED BY INSTALLED BY FIXED
POWER
DATA PLUMB COMMENTS (W x D x H)NORMAL EMERGENCY
E1 Stool TBD TBD OWNER OWNER No No No No No
E2 Storage, Metal Shelving TBD TBD OWNER OWNER No No No No No
E3 Through Wall Pass Thru W/ Hepa Filtration Terra Universal 2634-80A CONTRACTOR CONTRACTOR Yes No No No No 18" x 18" x 18"
E4 Pharmaceutical Hood TBD TBD OWNER VENDOR Yes Yes No No No
E5 Bin, Waste TBD TBD OWNER OWNER No No No No No
E6 Table, 2X4 TBD TBD OWNER OWNER No No No No No
E7 Table, 2X3 TBD TBD OWNER OWNER No No No No No
E8 Glove Box Holder - Triple TBD TBD OWNER OWNER No No No No No
E9 Access Panel, Ceiling Acudor AD WT CONTRACTOR CONTRACTOR Yes No No No No 24 X 24, Stainless Steel.
SCALE: 1/4" = 1'-0"
EQUIPMENT ENTRANCE ELEVATION - NEW
SCALE: 1 1/2" = 1'-0"A103
4 EXTERIOR WALL SECTION @ LOUVERED ATTIC VENT
SCALE: 3/8" = 1'-0"A103
5 IV ROOM PASS THROUGH WORK COUNTER
SCALE: 1" = 1'-0"A103
6 COUNTERTOP WITH SUPPORT
DEMOLITION GENERAL NOTES
THE CONTRACTOR SHALL:
A. COORDINATE ALL DEMOLITION AND PHASING EFFORTS WITH THE
ARCHITECT AND OWNER’S REPRESENTATIVE. EVERY EFFORT
SHALL BE MADE TO MINIMIZE DISRUPTION OF OWNER’S
OPERATIONS. EXCESSIVE NOISE OR VIBRATION SHALL BE PRE-
APPROVED AND COORDINATED WITH THE OWNER’S
REPRESENTATIVE. IN ALL CASES, PROVISIONS SHALL BE MADE
FOR USER’S SAFETY.
B. COORDINATE ANY DISRUPTION OF UTILITY SERVICES WITH THE
OWNER AND AS SPECIFIED.
C. CONSTRUCT TEMPORARY CONSTRUCTION PARTITIONS WITHIN
THE EXISTING BUILDING WHICH OFFER A ONE-HOUR ENCLOSURE
TO ISOLATE ANY DEMOLITION/CONSTRUCTION WORK FROM THE
GENERAL PUBLIC AND AS DEEMED NECESSARY BY THE OWNER
AND CODE OFFICIAL HAVING JURISDICTION. COORDINATE
LOCATIONS WITH THE OWNER AND MAINTAIN MEANS OF EGRESS
THROUGHOUT THE WORK.
D. MAINTAIN A SECURE, WEATHER-TIGHT ENCLOSURE AT ALL
TIMES.
E. VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND
ELEVATIONS AND NOTIFY THE ARCHITECT OF ANY
DISCREPANCIES.
F. REMOVE IN THEIR ENTIRETY ALL EXISTING WALLS, DOORS,
MILLWORK, PLUMBING FIXTURES, CEILINGS, SOFFITS,
MARKERBOARDS, AND OTHER ITEMS, AS REQUIRED TO EXECUTE
THE DEMOLITION/CONSTRUCTION WORK DESCRIBED BY THE
DRAWINGS.
G. THE OWNER SHALL RESERVE THE RIGHT TO SALVAGE ANY
MATERIALS.
H. PROVIDE PROTECTION FOR ALL EXISTING BUILDING MATERIALS
AND EQUIPMENT FROM DAMAGE DUE TO ANY DEMOLITION OR
CONSTRUCTION-RELATED INCIDENT PERFORMED UNDER THIS
CONTRACT.
I. REPAIR OR REPLACE ITEMS THAT ARE DAMAGED AS A RESULT
OF DEMOLITION OR CONSTRUCTION TO MATCH EXISTING FINISH
AND/OR CONDITION.
J. EXISTING MATERIALS SHALL NOT BE REUSED UNLESS NOTED
OTHERWISE OR AS AUTHORIZED BY ARCHITECT.
K. VERIFY AND MAINTAIN THE LOCATION OF EXISTING POWER,
COMMUNICATION AND DATA CABLES TO PREVENT
INTERRUPTION OF THEIR SERVICE.
L. PATCH FLOOR, WALL AND CEILING PENETRATIONS RESULTING
FROM REMOVAL OR RE-ROUTING OF NEW OR EXISTING PIPING,
DUCTWORK, CONDUIT, AND OTHER ITEMS, AS REQUIRED TO
MAINTAIN FIRE-RESISTANCE-RATED SEPARATIONS. FINISH AS
REQUIRED FOR NEW OR EXISTING ADJACENT SURFACES.
M. CAP ALL DISCONNECTED MECHANICAL PIPING LINES WITHIN THE
WALL OR FLOOR. PATCH AND FINISH AS REQUIRED TO MATCH
NEW OR EXISTING ADJACENT SURFACES.
N. SEE MECHANICAL AND ELECTRICAL DRAWINGS AND NOTES FOR
FURTHER SEQUENCING AND SCOPE OF WORK.
O. AVOID ANY DISTURBANCE OF SOILS WITHIN THE ZONE OF
INFLUENCE AROUND EXISTING FOOTINGS AND FLOOR SLABS AS
DIRECTED BY GEOTECHNICAL ENGINEER.
P. WHERE CMU WALLS ARE INDICATED TO BE REMOVED, PREPARE
ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY REMOVING
CMU IN TOOTH-IN PATTERN BOTH SIDES OF DEMOLITION FOR
CONTRACTOR TO TOOTH-IN NEW CMU PATCHES.
Q. WHERE PLASTER/STUD WALLS ARE INDICATED TO BE REMOVED,
PREPARE ADJACENT WALLS TO RECEIVE NEW PATCH/FINISH BY
SAWCUTTING ADJACENT PLASTER FINISH A MINIMUM OF 1'-0"
BEYOND DEMOLITION.
R. CONTRACTOR TO REMOVE EXISTING FURNITURE AND
EQUIPMENT AND STORE AS DIRECTED BY COR.
DEMOLITION NOTES APPLY TO ALL DEMOLITION SHEETS.
COORD. OFFICE
212A
CORRIDOR
VIST. COORD.
OFFICE
DOCTOR
OFFICE
EXAM ROOM
206MENS TLT
CORRIDOR
STAIR
ANTE ROOM
IV ROOM
JAN.
CLOSET
209A
DOCTOR
OFFICE
CD-1
CD-2
CD-1
CD-1
CD-3
CD-3
CD-3
GENERAL ARCHITECTURAL NOTES
1. PARTITION TYPES SHALL BE DESIGNATED ON FLOOR PLANS
THUS: SEE SHEET A102 FOR TYPES. ALL INTERIOR
PARTITIONS ARE TYPE SX.4.20 UNLESS NOTED OTHERWISE.
2. FURNISH AND INSTALL FIRE-TREATED WOOD BLOCKING OR
METAL BACKING PLATE IN METAL STUD PARTITIONS FOR THE
PROPER ANCHORAGE OF ALL WALL ATTACHED ITEMS; I.E.
TOILET ACCESSORIES, CASEWORK, MILLWORK, WALL-
MOUNTED FIXTURES, MARKER BOARDS, TACK BOARDS, DOOR
STOPS, AUDIO VISUAL BRACKETS, AND OTHER WALL ATTACHED
ITEMS.
XX. X. XX
COORD. OFFICE
212A
CORRIDOR
VIST. COORD.
OFFICE
DOCTOR
OFFICE
EXAM ROOM
206MENS TLT
CORRIDOR
STAIR
DOCTOR
OFFICE
JAN.
CLOSET
209A
ANTE
ROOM - ISO
CLASS 8
IV ROOM -
ISO CLASS
GWB
9' - 0"
GWB
9' - 0"
APC-1
8' - 0"
GWB
8' - 0"
E9
E9
DEMOLITION RCP KEYED NOTES
THE CONTRACTOR SHALL:
1. REMOVE EXISTING CEILING IN ITS ENTIRETY.
2. REMOVE PORTION OF EXISTING CEILING AS REQUIRED TO INSTALL
NEW UTILITIES. SEE ENGINEERING DRAWINGS. PATCH TO MATCH
EXISTING FINISHES.
3. CONTRACTOR SHALL DEMOLISH THE DRYWALL CEILING AND WIRE
MESH ABOVE THE DROP CEILING IN ROOM 210 AND 211. FOLLOWING
DEMOLITION, THE CONTRACTOR WILL COORDINATE WITH THE
CONTRACTING OFFICER'S REPRESENTATIVE TO DETERMINE IF
THERE AR EANY OBSTRUCTRIONS, SUCH AS EXISTING PIPING OR
DUCTWORK, THAT MAY INTERFERE WITH FUTURE OPERATIONS OF
THE CLEAN ROOM PRIOR TO REPLACEMENT OF CEILING.
CD-#
NEW RCP KEYED NOTES
THE CONTRACTOR SHALL:
1. ADD NEW DROPPED CEILING TO NEAREST WHOLE TILE. MINIMUM
AREA NEEDED IS 4'-0" X 10'-0". LOCATION TO BE COORDINATED WITH
MECHANICAL WORK. SEE ENGINEERING SHEETS.
2. PATCH TO MATCH EXISTING FINISHES AS REQUIRED TO INSTALL
NEW UTILITIES.
3. CEILING ETR. PATCH TO MATCH AS REQUIRED.
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Severna Park, Maryland 21146
TEL: 410.544.3570
www.LRSFederal.com
Replace IV Clean Room
VA Medical Center, Building 2 Project Director
Revisions: Date: 5/19/2023
FULLY SPRINKLERED
ISSUED FOR BID
565 Benfield Road, Suite 400
1213 West Morehead St. Ste. 210 Charlotte, NC 28208
704.594.5335 www.dlrgroup.com
© DLR Group
LEVEL 02 -DEMOLITION & NEW REFLECTED
CEILING PLAN
A112
MDISEC
53-23171-00
SCALE: 1/4" = 1'-0"A112
D1 DEMOLITION REFLECTED CEILING PLAN - LEVEL 02
SCALE: 1/4" = 1'-0"A112
D6 NEW REFLECTED CEILING PLAN - LEVEL 02
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Severna Park, Maryland 21146
TEL: 410.544.3570
www.LRSFederal.com
Replace IV Clean Room
VA Medical Center, Building 2 Project Director
Revisions: Date: 5/19/2023
FULLY SPRINKLERED
ISSUED FOR BID
565 Benfield Road, Suite 400
1213 West Morehead St. Ste. 210 Charlotte, NC 28208
704.594.5335 www.dlrgroup.com
© DLR Group
APPENDIX B
A001
MDISEC
53-23171-00
2018 APPENDIX B
BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS
(EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES)
Owner/Authorized Agent: Phone #: E-mail:
Owned By:
Code Enforcement Jurisdiction:
City/County
City
State
County
Private
State
CONTACT:
DESIGNER
Architectural
FIRM NAME LICENSE # TELEPHONE # E-MAIL
Civil
Electrical
Fire Alarm
Plumbing
Mechanical
Sprinkler-Standpipe
Structural
Retaining Walls > 5' High
Other
BASIC BUILDING DATA
NoSprinklers: Partial NFPA 13 NFPA 13R NFPA 13D
Standpipes: Class:
Fire District: Flood Hazard Area: No Yes
Gross Building Area:
Accessory
Occupancies:
Special Uses: 402 403 404 405 406 407 408 409 410 411 412
416 417 418 419 420 421 422 423
Special Provisions: 510.2 510.3 510.4 510.5 510.6 510.7 510.8
Mixed Occupancy/Use: No Yes Separation: Hr. Exception:
Non-Separated Use (508.3) The required type of construction for the building shall be determined by applying the height and area limitations for each of the applicable occupancies to the entire building. The most restrictive type of construction, so determined, shall apply to the entire building.
Separated Use (508.4) - See below for area calculations For each story, the area of the occupancy shall be such that the sum of the ratios of the actual floor area of each use divided by the allowable floor area for each use shall not exceed 1.
Actual Area of Occupancy A + Actual Area of Occupancy B Allowable Area of Occupancy A Allowable Area of Occupancy B
< 1
< 1.00
1Frontage area increases from Section 506.3 are computed thus:
a. Perimeter which fronts a public way or open space having 20 feet minimum width = _______ (F)
b. Total Building Perimeter = _________ (P)
c. Ratio (F/P) = ___________ (F/P)
d. W = Minimum width of public way = _________ (W)
e. Percent of frontage increase If = [ F/P - 0.25] x W/30 = _______
2Unlimited area applicable under conditions of Section 507.
3Maximum Building Area = total number of stories in the building x D (maximum 3 stories) (506.2) 4The maximum area of open parking garages must comply with Table 406.5.4. The maximum area of air traffic control towers must comply with Table 412.3.1.
5Frontage increase is based on the unsprinklered area value in Table 506.2.
ALLOWABLE HEIGHT
LIFE SAFETY SYSTEM REQUIREMENTS
Emergency Lighting:
Exit Signs:
Fire Alarm:
Smoke Detection Systems:
Carbon Monoxide Detection:
STORY
NO.
DESCRIPTION AND
USE
(A)
BLDG AREA PER
STORY (ACTUAL)
(B)
TABLE 506.24
AREA
(C)
AREA FOR FRONTAGE
INCREASE1,5
(D)
ALLOWABLE AREA PER
STORY OR UNLIMITED2,3
ALLOWABLE SHOWN ON PLANS CODE REFERENCE1
Building Height in Feet (Table 504.3) 2
Building Height in Stories (Table 504.4) 3
ACCESSIBLE PARKING
(SECTION 1106)
LOT OR
PARKING AREA
TOTAL # OF PARKING SPACES
REQUIRED
# OF ACCESSIBLE SPACES PROVIDED
VAN SPACES WITH
TOTAL #
ACCESSIBLE
PROVIDEDPROVIDED REGULAR WITH
5' ACCESS AISLE
TOTAL
SPECIAL APPROVALS
Special approval: (Local Jurisdiction, Department of Insurance, OSC, DPI, DHHS, ICC, etc., describe below)
ENERGY SUMMARY
ENERGY REQUIREMENTS:
The following data shall be considered minimum and any special attribute required to meet the energy code shall also be provided.
Each Designer shall furnish the required portions of the project information for the plan data sheet. If performance method, state the annual energy cost for the standard reference design vs annual energy cost for the proposed design.
THERMAL ENVELOPE (Prescriptive method only)
Method of Compliance:
Performance
Roof/ceiling Assembly (each assembly)
Description of assembly
U-Value of total assembly
R-Value of insulation
Skylights in each assembly
U-Value of skylight total square footage of skylights in each assembly
Exterior Walls (each assembly)
Description of assembly
U-Value of total assembly
R-Value of insulation
Openings (windows or doors with glazing)
U-Value of assembly
Solar heat gain coefficient projection factor
Door R-Values
Walls below grade (each assembly)
Description of assembly
U-Value of total assembly
R-Value of insulation
Floors over unconditioned space (each assembly)
Description of assembly
U-Value of total assembly
R-Value of insulation
Floors slab on grade
Description of assembly
U-Value of total assembly
R-Value of insulation
Horizontal/vertical requirement slab heated
2018 NC BUILDING CODE:
New Construction
Addition
1st Time Interior Completion
Renovation
424 425 426 427
Incidental Uses (Table 509):
Furnace room where any piece of equipment is over 400,000 Btu per hour input
Rooms with boilers where the largest piece of equipment is over 15 psi and 10 horsepower
Refrigerant machine room
Hydrogen cutoff rooms, not classified as Group H
Incinerator rooms
Paint shops, not classified as Group H, located in occupancies other than Group F
Laboratories and vocational shops, not classified as Group H. located in a Group E or I-2 occupancy
Laundry rooms over 100 square feet
Group I-3 cells equipped with padded surfaces
Group I-2 waste and linen collection rooms
Waste and linen collection rooms over 100 square feet
Stationary storage battery systems having a liquid electrolyte capacity of more than 50 gallons, or a lithiumion capacity of 1,000 pounds used for facility standby power, emergency power or uninterrupted power supplies
Rooms containing fire pumps Rooms containing Life-Safety generator Rooms containing primary transformers
Group I-2 storage rooms over 100 square feet
Group I-2 commercial kitchens
Group I-2 laundries equal to or less than 100 square feet
Group I-2 rooms or spaces that contain fuel-fired heating equipment
Fire and/or smoke rated wall locations (Chapter 7)
Assumed and real property line locations (if not on the site plan)
Exterior wall opening area with respect to distance to assumed property lines (705.8)
Occupancy Use for each area as it relates to occupant load calculation (Table 1004.1.2)
Occupant loads for each area
Exit Sign Locations (1013)
Exit access travel distances (1017)
Common path of travel distances (1006.2.1 & 1006.3(1))
Dead end lengths (1018.4)
Clear exit widths for each exit door
Maximum calculated occupant load capacity each exit door can accommodate based on egress width (1005.3)
Actual occupant load for each exit door
A separate schematic plan indicating where fire rated floor/ceiling and/or roof structure is provided for purposes of occupancy separation
Location of doors with panic hardware (1010.1.10)
Location of doors with delayed egress locks and the amount of delay (1010.1.9.7)
Location of doors with electromagnetic egress locks (1010.1.9.9)
Location of doors equipped with hold-open devices
Location of emergency escape windows (1030)
The square footage of each fire area (202)
The square footage of each smoke compartment for Occupancy Classification I-2 (407.5)
Note any code exceptions or table notes that may have been utilized regarding the items above
LIFE SAFETY PLAN REQUIREMENTS
Life Safety Plan Sheet #
OCCUPANCY
Primary
Occupancy:
Assembly (303) A-1 A-2 A-3 A-4 A-5
Business (304)
Factory (306) F-1 Moderate F-2 Low
Hazardous (307) H-2 Deflagrate H-3 Combust H-5 HPMH-1 Detonate H-4 Health
Institutional (308) 1 2I-1
R-1 R-2 R-3 R-4
S-1 Moderate S-2 Low High Piled
Parking Garage Open Enclosed Repair Garage
Educational (305)
Mercantile (309)
Residential (310)
Storage (311)
Utility and Miscellaneous (312)
(< 10%)
ACCESSIBLE DWELLING UNITS AND SLEEPING UNITS
(SECTION 1107)
Climate Zone: 3A 4A 5A
Energy Code
510.9
Shell/Core - Contact the local inspection jurisdiction for possible additional procedures and requirements
Phased Construction - Shell/Core - Contact the local inspection jurisdiction for possible additional procedures and requirements
2018 NC EXISTING BUILDING CODE:
N/A
Prescriptive Chapter 14
Repair Alteration Level I
Alteration Level II
Alteration Level III
Historic Property
Change of Use
CONSTRUCTED:
RENOVATED:
CURRENT OCCUPANCY(S) (Ch.3):
PROPOSED OCCUPANCY(S) (Ch. 3):
Special Inspections Required:
ALLOWABLE AREA
428 429
1Provide code reference if the "Shown on Plans" quantity is not based on Table 504.3 or 504.4.
2The maximum height of air traffic control towers must comply with Table 412.3.1.
3The maximum height of open parking garages must comply with Table 406.5.4.
TOTAL
UNITS
ACCESSIBLE
UNITS
REQUIRED
ACCESSIBLE
UNITS
PROVIDED
TYPE A
UNITS
REQUIRED
TYPE A
UNITS
PROVIDED
TYPE B
UNITS
REQUIRED
TYPE B
UNITS
PROVIDED
TOTAL
ACCESSIBLE UNITS
PROVIDED
132" ACCESS
AISLE
8' ACCESS
AISLE
PLUMBING FIXTURE REQUIREMENTS
(TABLE 2902.1)
USE WATERCLOSETS URINALS
MALE FEMALE
LAVATORIES SHOWERS/
TUBS
DRINKING FOUNTAINS
NEW
ETR
RQD
SPACE
UNISEX MALE FEMALE UNISEX REGULAR ACCESSIBLE
Existing building envelope complies with code: Yes (The remainder of this section is not applicable) No
Exempt Building: Yes No Provide code or statutory reference:
(If "Other" specify source here)
("Other" should include firms and individuals such as truss, precast, pre-engineered, interior designers, etc.)
No Yes
RISK CATEGORY (Table 1604.5):
Current: Proposed:N/A I II III IV N/A I II III IV
I-2
I-3
I-4
Condtion
1 2Condtion
1 2Condtion 3 4 5
Assembly (303) A-1 A-2 A-3 A-4 A-5
Business (304)
Factory (306) F-1 Moderate F-2 Low
Hazardous (307) H-2 Deflagrate H-3 Combust H-5 HPMH-1 Detonate H-4 Health
Institutional (308) 1 2I-1
R-1 R-2 R-3 R-4
S-1 Moderate S-2 Low High Piled
Parking Garage Open Enclosed Repair Garage
Educational (305)
Mercantile (309)
Residential (310)
Storage (311)
Utility and Miscellaneous (312)
I-2
I-3
I-4
Condtion
1 2Condtion
1 2Condtion 3 4 5
I-B II-B
I-A II-AConstruction Type:
(check all that apply) III-B
III-A IV
V-B
V-A
Yes
No Yes
No Yes
I II III Wet Dry
(Contact the local inspection jurisdiction for additional procedures and requirements)
No Yes
No Yes
No Yes
No Yes
No Yes
Partial
ASHRAE 90.1 Prescriptive
Performance Prescriptive
Name of Project: COATESVILLE VA IV CLEAN ROOM REPLACEMENT
Address: 1400 BLACKHORSE HILL RD, COATESVILLE, PA
DLR Group | WMBA Sara Cheikelard 14194 980-321-0047
N/A N/A N/A N/A
LRS FEDERAL Jay Malhotra 713-962-5555
N/A N/A N/A N/A
LRS FEDERAL William Wood 703-568-7630
LRS FEDERAL William Wood 703-568-7630
N/A N/A N/A N/A
N/A N/A N/A N/A
Sara Cheikelard
KEVIN URBINE
scheikelard@dlrgroup.com
N/A jmalhotra@lrsfederal.com
N/A wwood@lrsfederal.com wwood@lrsfederal.com
N/A
N/A
FLOOR EXISTING (SQ FT) RENOVATED (SQ FT) NEW (SQ FT)
SUB TOTAL (SQ FT)
(EXISTING AND NEW ONLY)
Level 03 631 SF 631 SF 0 SF 631 SF
Level 02 17361 SF 735 SF 0 SF 17361 SF
Grand total 17992 SF 1366 SF 0 SF 17992 SF
EXISTING TO REMAIN UNCHANGED
EXISTING TO REMAIN UNCHANGED
EXISTING TO REMAIN UNCHANGED
EXISTING TO REMAIN UNCHANGED
EXISTING TO REMAIN UNCHANGED
EXISTING TO REMAIN UNCHANGED
N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A
A011
610-384-7711 ext. 3505 Kevin.Urbine@va.gov
N/A
N/A - NFPA 101
EXISTING TO REMAIN UNCHANGED
N/A
1/2" MIN. GYPSUM
WALLBOARD
2 1/2" MIN. STUD
OR RUNNER
RETAINING ANGLE
DAMPER SLEEVE
M
IN
HEADER
J A
M B
J A
M B
J A
M B
D U
C T
J A
M B
J A
M B
D O
O R
J A
M B
J A
M B
HEADER
DOOR
SILL
WINDOW SIDELIGHT/KNEEWALL
FOR HEADER
AND JAMBS
HEADER
FOR SILL AND
JAMB POST
SILL
DUCT
SILL
HEADER
DUCT SILL
FOR DUCT
HEADER JAMB
AND SILL
DUCT HEADER
HEADER
FOR HEADER
AND JAMBS
FOR DOOR JAMB
DUCT ABOVE DOOR
J A
M B
J A
M B
P O
S T
JAMBSHEADERS
(W<6'-0")
STUDS (2)
TRACK, 22 GA MINTRACK,
22 GA MIN
BOX
HEADER,
22 GA MIN
JAMB @ DUCT
PENETRATION
HEADER
(W>6'-0")
M A
X
M
IN 2
" 3
/2
/1
/2
A D
A A
C C
E S
S
IB
L E
S H
O W
E R
S E
A T
B A
B Y
C H
A N
G
IN
G S
T A
T
IO
N
S A
N
IT
A R
Y N
A P
K
IN
D
IS
P O
S A
L
N U
R S
E C
A L L P
U L L A
T
S H
O W
E R
S O
A P
D
IS
H
W A
T E
R F
O U
N T
A
IN
L A
V A
T O
R Y
S
H E
L F
O U
T L E
T F
O R
M T
D T
.V
(D U
P L E
X
A N
T E
N N
A
C L O
T H
E S
/R O
B E
H O
O K
S H
O W
E R
R O
D
M E
D G
A S
O U
T L E
T
S T
A N
D A
R D
U R
IN
A
L H
E
IG
H T
A D
A U
R
IN
A L H
E
IG
H T
M A
X
M A
X
N O
T E
S
H O
W N
S
ID
E B
Y S
ID
E
IN
P L A
N V
IE
W
F O
R C
L A
R
IT
Y
F
IR
E E
X T
IN
G
U
IS
H E
R
C
B
IN
E T
H A
N D
S A
N
IT
IZ
E
R
M A
X
/2
N
U R
S E
C A
L L P
U L L
O
IL
E
T
M A
X
/1
S H
A R
P S
18" MIN.
12" MIN.
WHEN DOOR IS LOCATED AGAINST AN
OBSTRUCTION INCLUDING BUT NOT LIMITED TO
A PARTITION OR OTHER OBSTRUCTION THE MIN.
CLEARANCES SHOWN MUST BE OBSERVED.
DOOR AS
SCHEDULED
PARTITION AS
SCHEDULED
H.M. DOOR FRAME
JAMB ANCHOR
MTL. STUD
SHEET MTL
STRAP TO
DOUBLE STUD
DOOR JAMBS.
(TYP)
6"AS SCHED.
HIGHER
PRIORITY
LOWER PRIORITY
THREE AND FOUR HOUR FIRE
TWO HOUR FIRE WALL
TWO HOUR SHAFTWALL
TWO HOUR SMOKE BARRIER
TWO HOUR FIRE BARRIER
ONE HOUR SHAFTWALL
ONE HOUR SMOKE BARRIER
ONE HOUR FIRE PARTITION
ONE HOUR FIRE BARRIER
SMOKE TIGHT PARTITION
NON RATED
PRIORITY 1 (HIGHEST)
PRIORITY 2
PRIORITY 3
PRIORITY 4A
PRIORITY 4B
PRIORITY 5
PRIORITY 6A
PRIORITY 6B
PRIORITY 6C
PRIORITY 7
PRIORITY 8
m in
22"min.
m in m in
24"min.
24" min.
m in m in
24" min m in
12 min.*
22" min.
42" min. 5 m in m in
36" min.
m in
12" min 18" min.
m in
(a)Front Approach (b)Pocket or Hinge Approach (c)Stop or Latch Approach
(g)Latch Approach,Push Side
48" min.
if closer is provided
(f)Latch Approach,Pull Side
*54" min. if closer is provided
(e)Hinge Approach,Push Side
(d)Hinge Approach,Pull Side(c)Hinge Approach,Pull Side
* If both closer and latch are provided
** 48" min if both closer and latch provided
(b)Front Approach,Push Side(a)Front Approach,Pull Side
*If both closer and latch are provided.
M A
X
ADA OBSTRUCTED HIGH FORWARD REACH
FIG. 308.2.2 (ICC A117.1-2009)
20" MAX
M A
X
> 20" - 25"
M A
X
MAX
10"
ADA OBSTRUCTED HIGH SIDE REACH
FIG. 308.3.2 (ICC A117.1-2009)
M A
X 4
M A
X
>10" - 24"
M A
X
M
IN
M A
X
MAX
10"
ADA UNOBSTRUCTED SIDE REACH
FIG. 308.3.1 (ICC A117.1-2009)
M
IN
M A
X
ADA UNOBSTRUCTED FORWARD REACH
FIG. 308.2.1 (ICC A117.1-2009)
Product
WL-0010CAJ-0061CAJ-0061PillowsBlank Openings CAJ-0014CAJ-0014SSS100Blank Openings
FFD-1008ES100Floor to Floor Joint CWS-2003AS200Perimeter Joint, Spandrel Glass, Vision Glass
CWS-1002AS200
WWD-0004ES100Wall to Wall Joint
HWD-0153ES100
HWD-0099HWD-0140AS200
HWD-0043HWD-0086AS200Walls to Fluted Metal Deck HWD-0034HWD-0039ES100Walls to Fluted Metal Deck HWD-0044HWD-1005AS200Walls to Flat Concrete Deck HWD-0079HWD-1006ES100Walls to Flat Concrete Deck GWB WallsCMU WallsARCHITECTURAL WL-7028WJ-7011SSS/SSWNoNon-Dampered Insulated duct WL-7026WJ-7005SSS100NoNon-Dampered Spiral duct WL-7033WJ-7013SSS100NoNon-Dampered Flat oval duct WL-7025WJ-7007SSS100NoNon-Dampered Rectangular duct
GWB WallsCMU WallsConcrete SlabsInsulatedSleevedHVAC Penetrations CAJ-8093 CAJ-8093PillowsNoMultiple Innerduct/Tray/Cables/Pipe
WL-3136WJ-3047Putty/SSSYesSplit Sleeve WL-2178WJ-2054PillowsYesMultiple Inneduct WL-2093CAJ-2140CAJ-2140SSS100optionalInnerduct WL-4008CAJ-4029CAJ-4029PillowsNoOpen ladder cable tray WL-4029WJ-4021PillowsNoCenter hung cable tray WL-3024CAJ-3128CAJ-3128SSS/PuttyNoCable WL-3084PillowsNoCable Bundle (Gypsum Only)
CAJ-3154, WJ-3043CAJ-3154Putty/SSS100YesCable Bundle GWB WallsCMU WallsConcrete SlabsProductSleevedHIGH-TRAFFIC PENETRATIONS WL-6005CAJ-6019CAJ-6019PillowsNoBus Ducts WL-8003CAJ-8053CAJ-8053SSS100NoMultiple Metallic
CAJ-8093CAJ-8093PillowsNoMultiple Mixed Conduits and Tubing WL-1168SSS100NoMultiple Metallic (Gypsum Only)
GWB WallsCMU WallsConcrete SlabsInsulatedSleevedMECHANICAL PENETRATIONS WL-1049CAJ-1079CAJ-1079NoNoBare Metallic WL-1079CAJ-1217CAJ-1217NoYesBare Metallic WL-5014CAJ-5087CAJ-5087YesOptionalFiberglass Insulated Pipe WL-5054CAJ-5133CAJ-5133YesNoAB/PVC Foam Insulated Pipe WL-1168NoNoMultiple Metallic (Gypsum Only) WL-1127NoYesMultiple Metallic (Gypsum Only) WL-8003CAJ-8053CAJ-8053OptionalNoMultiple Mixed
CAJ-8093CAJ-8093PillowsNoMultiple Mixed Pipe WL-2114CAJ-2079CAJ-2079NoNoGlass Pipe
WL-1049
WL-1093
WL-2074
GWB Walls
CAJ-1079
CAJ-2125
CMU Walls
CAJ-1079
CAJ-2125
Concrete Slabs
SSS100
SSS100
No Product
No No
No Sleeved
Multiple Metallic (Gypsum Only) Single Conduit
ELECTRICAL PENETRATIONS
All Plastics 1.5"-6""" (Collar Device Only)
GENERAL SYMBOLS
SIM
ROOM NAME
XXX-XX
DETAIL NUMBER
SHEET NUMBER
CROSS REFERENCE
WALL SECTION
SIMILAR OR TYPICAL
REFERENCE
DETAIL REFERENCE
BUILDING SECTION
SHEET NOTE
COLUMN GRID LINE
ROOM NUMBER/NAME
REVISION NUMBER
EARTH
GRAVEL
SAND
CONCRETE
PRECAST CONCRETE
STEEL
STONE
CONCRETE MASONRY UNIT
BRICK VENEER
LEVEL XX
XXX'-XX"
LEVEL ELEVATION
GYM FLOOR
WOOD
(CONTINUOUS BLOCKING)
WOOD
(NON-CONTINUOUS BLOCKING)
WOOD (TRIM/FINISH)
GLASS
SHINGLES
PLYWOOD (LARGE SCALE)
GYPSUM WALL BOARD
BLANKET INSULATION
RIGID INSULATION
SPRAY FOAM INSULATION
MINERAL WOOL INSULATION
PROTECTION BOARD
CARPET (LARGE SCALE)
ACOUSTIC TILE (LARGE SCALE)
TILE (LARGE SCALE)
REFERENCE KEYNOTE
XX A4.XX BUILDING ELEVATION
A12.X
XX
XX XX
XX
INTERIOR ELEVATION
100'-0"
TYP FF EL=
100'-0"
FINISH FLOOR
ELEVATION
SPOT ELEVATION
X
ROUGH OPENING ANGLE SIZE
5'-0" L4 x 4 x 3/8
NOTES:
1. BEAR 8" EACH END OF OPENING.
2. ROLL ANGLE AT ARCHED OPENINGS.
3. ALL EXTERIOR LINTELS TO BE GALVANIZED.
4. USE ARC LENGTH ON CURVED LINTELS.
5’-1” – 8’-0” L6x4x3/8 (LLV)
8’-1” – 10’-0” L7x4X3/8 (LLV)
10’-1” – 12’-0” L8x4x1/2 (LLV)
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
F ile
P a th
/1
/2
:3
:0
P
M
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Severna Park, Maryland 21146
TEL: 410.544.3570
www.LRSFederal.com
Replace IV Clean Room
VA Medical Center, Building 2 Project Director
Revisions: Date: 5/19/2023
FULLY SPRINKLERED
ISSUED FOR BID
565 Benfield Road, Suite 400
1213 West Morehead St. Ste. 210 Charlotte, NC 28208
704.594.5335 www.dlrgroup.com
© DLR Group
PROJECT STANDARDS
A002
MDISEC
53-23171-00
NO SCALEA002
2 TYPICAL FRAMING
SCALE: 3/8" = 1'-0"A002
4 TYPICAL MOUNTING HEIGHTS
SCALE: 3/4" = 1'-0"A002
5 TYPICAL DOOR PLACEMENT
SCALE: 3/4" = 1'-0"A002
6 WALL PRIORITY LEGEND
SCALE: 3/16" = 1'-0"A002
9 DOORWAY AND CLEARANCE REQUIREMENTS
SCALE: 3/8" = 1'-0"A002
10 ADA REACH DIAGRAMS
SCALE: 12" = 1'-0"A002
11 PENTRATION SCHEDULE OF UL's
# NUMBER
& AND
@ AT
ADA AMERICANS WITH DISABILITY ACT
ADDN ADDITION OR ADDITIONAL
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
ALT ALTERNATE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APPROX APPROXIMATE
ARCH ARCHITECTURAL
BLDG BUILDING
BSMT BASEMENT
CL CENTER LINE
CLG CEILING
CM CENTIMETER
CONC CONCRETE
CONN(S) CONNECTION(S)
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACT(OR)
CTR CENTER
D DEPTH
DEG DEGREE
DEMO DEMOLISH OR DEMOLITION
DIA DIAMETER
DIM DIMENSION
DIV SPECIFICATION DIVISION
DN DOWN
DTL DETAIL
DWG(S) DRAWING(S)
E EAST
EA EACH
EC ELECTRICAL CONTRACTOR
EL ELEVATION
ELEC ELECTRICAL
ENG ENGINEER
EQ EQUAL
EQUIP EQUIPMENT
EQUIV EQUIVALENT
EXST EXISTING
EXT EXTERIOR
FIN FINISHED
FL FLOOR
FT FEET
FUT FUTURE
GC GENERAL CONTRACTOR
GOVT GOVERNMENT
H HEIGHT
HORIZ HORIZONTAL
HT HEIGHT
i.e. THAT IS
IBC INTERNATIONAL BUILDING CODE
IN INCH
INT INTERIOR
LB(S) POUND(S)
M METER
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MECH MECHANICAL
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MM MILLIMETER
N NORTH
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
OPP OPPOSITE
OVHD OVERHEAD
PAR PARALLEL
PENT PENTHOUSE
PLYWD PLYWOOD
QTY QUANTITY
REQ(D) REQUIRE(D)
REV REVISION(S)
RM ROOM
RND ROUND
S SOUTH
SCHED SCHEDULE
SECT SECTION
SHT SHEET
SIM SIMILAR
SPEC SPECIFICATION(S)
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SYM SYMETRICAL
TEMP TEMPORARY
TYP TYPICAL
UNEX UNEXCAVATED
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
W WEST
W/ WITH
W/O WITHOUT
GENERAL ABBREVIATIONS
LOOSE LINTEL SCHEDULE
J
CONDUIT CONCEALED IN OR BELOW FLOOR SLAB
BRANCH CIRCUIT HOMERUN - PANEL & CIRCUIT
NUMBER INDICATED
ELECTRICAL SYMBOLS AND ABBREVIATIONS LEGEND
MOTOR CONNECTION
PANELBOARD ON NORMAL POWER
FUSED DISCONNECT SWITCH
COMBINATION MOTOR STARTER AND DISCONNECT
SWITCH
DISCONNECT SWITCH PROVIDED WITH EQUIPMENT
JUNCTION BOX
EMERGENCY DUPLEX RECEPTACLE, +18"
DUPLEX RECEPTACLE, +18"
DUPLEX RECEPTACLE - MOUNT RECEPTACLE ABOVE
COUNTERTOP. REFER TO ARCHITECTURAL ELEVATIONS
24" X 48" RECESSED LIGHT TROFFER
24" X 48" RECESSED LIGHT TROFFER. SHADE PATTERN
INDICATES CONNECTED TO EMERGENCY CIRCUIT.
EMERGENCY DUPLEX RECEPTACLE - MOUNT
RECEPTACLE ABOVE COUNTERTOP. REFER TO
ARCHITECTURAL ELEVATIONS
SIMPLEX OUTLET. NEMA CONFIGURATION AS NOTED
SPECIAL PURPOSE OUTLET - MOUNT RECEPTACLE
ABOVE COUNTERTOP. REFER TO ARCHITECTURAL
ELEVATIONS. NEMA CONFIGURATION AS NOTED
NON-FUSED DISCONNECT SWITCH
M
R
MANUAL MOTOR STARTER WITH OVERLOADS, TOGGLE
OPERATED
THREE WAY SWITCH
SINGLE POLE SWITCH
3D THREE WAY DIMMER SWITCH
SINGLE POLE SWITCH ON EMERGENCY POWER.
SUBSCRIPT INDICATES DEVICE ON EMERGENCY POWER,
COLOR RED
D SINGLE POLE DIMMER SWITCH
ENCLOSED CIRCUIT BREAKER
MOTOR STARTER
PAD MOUNTED DRY TYPE TRANSFORMER
DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL
OC SINGLE POLE OCCUPANCY SENSORY SWITCH
OCR
SINGLE POLE OCCUPANCY SENSORY SWITCH ON
EMERGENCY POWER. SUBSCRIPT INDICATES DEVICE ON
EMERGENCY POWER, COLOR RED.
24" X 24" RECESSED LIGHT FIXTURE.
24" X 24" RECESSED LIGHT FIXTURE. SHADE PATTERN
INDICATES CONNECTED TO EMERGENCY CIRCUIT.
OC CEILING MOUNTED OCCUPANCY SENSOR
12" X 48" RECESSED LIGHT FIXTURE.
12" X 48" RECESSED LIGHT FIXTURE. SHADE PATTERN
INDICATES CONNECTED TO EMERGENCY CIRCUIT.
S M
DD
S
DH
F
F
ACR
AIM
AOM
S
S
S
F
HD
HD
SD
FIRE ALARM LEGEND
DESCRIPTIONSYMBOL
FIXED TEMPERATURE 200°F HEAT DETECTOR
FT/200
RATE OF RISE/135°F HEAT DETECTOR
RR/135
PHOTOELECTRIC SMOKE DETECTOR
EMERGENCY COMMUNICATIONS SPEAKER STROBE
"XX" INDICATES CANDELA RATINGXXcd
DUCT DETECTOR
S - SUPPLY, R- RETURN, E- EXHAUSTR E
FIRE ALARM DOOR HOLDER
FIRE ALARM HORN - CEILING MOUNTED
FIRE ALARM HORN - WALL MOUNTED
FIRE ALARM HORN/STROBE - CEILING MOUNTED
"XX" INDICATES CANDELA RATING
FIRE ALARM HORN/STROBE - WALL MOUNTED
"XX" INDICATES CANDELA RATING
FIRE ALARM MANUAL PULL
FIRE ALARM ADDRESSABLE CONTROL RELAY
FIRE ALARM ADDRESSABLE INPUT MODULE
FIRE ALARM ADDRESSABLE OUTPUT MODULE
FIRE ALARM SPEAKER - CEILING MOUNT
FIRE ALARM SPEAKER - WALL MOUNT
FIRE ALARM SPEAKER/STROBE - WALL MOUNT
"XX" INDICATES CANDELA RATING
FIRE ALARM STROBE - WALL MOUNT
"XX" INDICATES CANDELA RATING
FIRE ALARM SPEAKER/STROBE - CEILING MOUNT
"XX" INDICATES CANDELA RATING
FIRE ALARM STROBE - CEILING MOUNT
"XX" INDICATES CANDELA RATING
XXcd
XXcd
XXcd
XXcd
XXcd
XXcd S
F
NOTE: ALL DEVICE COLORS SHALL BE WHITE EXCEPT FOR PULL
STATIONS WHICH WILL BE RED.
ACP
CR
DR
ACCESS CONTROL LEGEND
ACCESS CONTROL PANEL
CARD READER
DOOR RELEASE BUTTON
NOTE: PROVIDE BACKBOXES AND 3/4" EMPTY CONDUIT TO
PLENUM. DEVICES & WIRING TO BE PROVIDED BY OWNER
TGB
W
TELE/DATA LEGEND
TELECOMMUNICATIONS GROUNDING BUSBAR
WALL MOUNTED DATA OUTLET - WITH 1 DATA DROP
DATA OUTLET - CEILING MOUNTED
WIRELESS ACCESS POINT - CEILING MOUNTED
WALL MOUNTED DATA OUTLET - WITH 2 DATA
DROPS
WALL MOUNTED DATA OUTLET - WITH 3 DATA
DROPS
NOTE: PROVIDE BACKBOXES AND 3/4" EMPTY CONDUIT TO
PLENUM. DEVICES & WIRING TO BE PROVIDED BY OWNER
GENERAL NOTES
1. EACH CIRCUIT SHALL HAVE AN EQUIPMENT GROUNDING CONDUCTOR, AND MULTI-WIRE
CIRCUITS OF DIFFERENT PHASES MAY SHARE EQUIPMENT GROUND CONDUCTOR.
EQUIPMENT GROUND CONDCUTOR SIZE SHALL NOT BE LESS THAN #12 AWG OR AS
INDICATED ON THE DRAWINGS.
2. ALL CONDUCTORS #10 AND SMALLER SHALL BE SOLID COPPER, AND ALL CONDUCTORS #8
AND LARGER SHALL BE STRANDED COPPER UNLESS BOLTED LUGS AT TERMINALS.
3. MINIMUM CONDUIT SIZE SHALL BE 3/4" UNLESS OTHERWISE NOTED.
4. ALL WIRING DEVICES SHALL BE INSTALLED PLUMB, SQUARE, AND TRUE; AND ALL DEVICES
INSTALLED AT A SINGLE LOCATION SHALL BE ALIGNED.
5. MINIMUM WIRE SIZE SHALL BE #12 AWG UNLESS OTHERWISE SPECIFIED.
6. ALL WORK SHALL COMPLY WITH THE CURRENT EDITION OF THE NATIONAL ELECTRICAL CODE
ADOTPED BY THE CITY OF PERRY POINT.
7. CONTRACTOR SHALL REFER TO THE ARCHITECTURAL ELEVATIONS AND MILLWORK
DETAILS FOR EXACT LOCATIONS OF ALL WIRING DEVICES.
8. CONTRACTOR SHALL REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN FOR
EXACT LOCATION OF ALL LAY-IN LIGHT FIXTURES.
9. ALL EXISTING BRANCH CIRCUITS NOT USED SHALL BE REMOVED BACK TO PANEL. THE
CIRCUIT BREAKERS SHALL BE LABELED AS SPARE, AND EXISTING CONDUIT SHALL BE
REMOVED BACK TO THE PANEL.
10. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DEMOLITION IN AREAS OF
RENOVATION. ALL WIRING DEVICES, LIGHT FIXTURES, WIRE, AND CONDUIT THAT IS TO BE
REMOVED SHALL BE STORED, AS DIRECTED BY THE OWNER, OR RELOCATED, AS SHOWN
ON THE NEW FLOOR PLANS. APPROPRIATE MEASURES SHALL BE TAKEN TO ASSURE
CONTINUITY OF EXISTING CIRCUITS WHERE REQUIRED. ALL OUTAGES WHICH MAY
RESULT SHALL BE COORDINATED WITH THE OWNER PRIOR TO THE WORK.
11. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR UPDATING SCHEDULES IN
ALL ELECTRICAL PANELS THAT ARE AFFECTED BY THIS WORK. UPDATED SCHEDULES
ARE TO BE TYPEWRITTEN.
12. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR MARKING ALL SWITCHES,
RECEPTACLES, AND FIXED EQUIPMENT WITH THE BRANCH CIRCUIT PANEL NAME AND
NUMBER SERVING EACH DEVICE.
13. ALL CONDUIT SHALL BE INSTALLED AS HIGH AS POSSIBLE (MOUNT TO BOTTOM OF
STRUCTURE) TO AVOID CONFLICTS WITH DUCTWORK AND PIPING. THE ELECTRICAL
CONTRACTOR SHALL COORDINATE INSTALLATION WITH THE MECHANICAL CONTRACTOR.
14. ON THREE PHASE, FOUR WIRE SYSTEMS, DO NOT USE A COMMON NEUTRAL FOR MORE
THAN THREE CIRCUITS. MORE THAN THREE CIRCUIT IN ANY ONE CONDUIT IS NOT
ALLOWED WITHOUT WRITTEN PERMISSION FROM THE ENGINEER.
15. ON SINGLE PHASE, THREE WIRE SYSTEMS, DO NOT USE A COMMON NEUTRAL FOR MORE
THAN TWO CIRCUITS. MORE THAN TWO CIRCUITS IN ANY ONE CONDUIT IS NOT ALLOWED
WITHOUT WRITTEN PERMISSION FROM THE ENGINEER.
RENOVATION AND DEMOLITION NOTES
1. ATTENTION IS DRAWN TO THE FACT THAT THIS PROJECT INVOLVES RENOVATION OF AN EXISTING
FACILITY.
2. CONTRACTOR SHALL VISIT THE SITE AND THOROUGHLY FAMILIARIZE HIMSELF WITH EXISTING
CONDITIONS. VERIFY LOCATIONS, CONDUIT ROUTING, SYSTEM COMPONENTS ETC. BEFORE
SUBMITTING A BID. ANY DISCREPANCIES SHALL BE REPORTED TO THE ARCHITECT BEFORE THE
BID DATE.
3. SCHEDULING FOR REQUIRED SHUTDOWNS AND OTHER DISTURBANCES TO THE BUILDING SHALL
BE COORDINATED WITH THE OWNER OR BUILDING MANAGEMENT PRIOR TO BEGINNING WORK.
4. ANY EQUIPMENT AND/OR MATERIALS REMOVED FROM SERVICE BECOMES THE PROPERTY OF
THE CONTRACTOR UNTIL IT HAS BEEN PLACED BACK INTO SERVICE OR UNTIL IT HAS BEEN
DISPOSED OF. EQUIPMENT PLACED BACK INTO SERVICE SHALL BE IN GOOD WORKING
CONDITION. TRANSPORTATION AND DISPOSAL OF DEMOLISHED EQUIPMENT AND MATERIALS
SHALL BE TO AN APPROPRIATE DISPOSAL LOCATION OFF PROJECT SITE.
5. OWNER SHALL BE GIVEN THE FIRST RIGHT OF REFUSAL FOR DEMOLISHED MATERIALS AND
EQUIPMENT.
6. CONTRACTOR SHALL PATCH AND PREPARE WALLS FOR SCHEDULED FINISH WHERE EQUIPMENT
AND DEVICES ARE REMOVED FROM WALLS THAT ARE TO BE RETAINED.
7. EXISTING CIRCUITS INDICATED ARE DIAGRAMMATIC ONLY. VERIFY EXACT ROUTING OF EXISTING
CONDUIT RUNS AND NUMBERS OF CONDUCTORS AND EXTEND EXISTING CIRCUITS TO NEW
PANELBOARD LOCATIONS AS REQUIRED TO ACCOMPLISH DESIGN INTENT.
8. PROVIDE ALL CORING, CUTTING AND PATCHING TO EXISTING WALLS, FLOORS, ETC REQUIRED
FOR THE REMOVAL OF EXISTING WORK OR THE INSTALLATION OF NEW WORK.
9. CONTRACTOR SHALL PROPERLY CAP, SEAL, OR TERMINATE EXISTING TO REMAIN SYSTEMS THAT
ARE PARTIALLY DEMOLISHED.
10. IN THE COURSE OF REMOVING EXISTING LIGHT FIXTURES, CONTRACTOR SHALL NOT DISPOSE OF
LAMPS AS GENERAL DEBRIS. SPECIAL CARE SHALL BE TAKEN NOT TO BREAK LAMPS. SPECIAL
CONTAINERS WILL BE PROVIDED FOR THE COLLECTION OF CERTAIN BALLASTS. IF A BALLAST IS LABELED INDICATING THAT IT CONTAINS NO PCB'S, THEN IT MAY BE DISPOSED OF AS GENERAL DEBRIS. OTHERWISE, THE BALLAST SHALL BE PLACED IN CONTAINERS FOR PCB'S AND SHALL BE
DISPOSED OF PROPERLY BY THE CONTRACTOR.
11. CONTRACTOR SHALL MAINTAIN CONTINUITY OF POWER CIRCUITS TO EXISTING-TO-REMAIN/IN
-USE EQUIPMENT. COORDINATE WORK WITH OWNER TO MINIMIZE IMPACT TO OWNER'S
OPERATION.
12. IN THE EVENT THERE IS REMOVAL OF EXISTING ELECTRICAL EQUIPMENT, DEVICES, CONDUIT, WIRING, ETC. THE CONTRACTOR SHALL REMOVE ASSOCIATED WIRING BACK TO THE SOURCE OF
FEED UNLESS OTHERWISE NOTED. WHERE A PORTION OF A BRANCH CIRCUIT IS TO BE
MAINTAINED, REMOVE CIRCUITING…
This is the start of the file's text. The full file is on GovTribe.