VA CWM UTILITY SHUTDOWN REQUEST 2025 fillable form.pdf
PDF 320 KB Posted
- Solicitation number
- 36C24126Q0601
About this file
This document is a VA CWM Utility Shutdown Request form and instructions for managing utility interruptions at VA Medical Center facilities.
The form requires contractors to submit shutdown requests with specific information including project number, company name, shutdown point of contact and phone number, requested shutdown date(s) and times, locations of shutdown and work, LOTO (Lock Out Tag Out) location, competent person(s) performing the work, required PPE, reason for shutdown, work description, and all impacted buildings and areas including downstream and upstream systems. Contractors must identify which utilities will be shut down and which will be affected, selecting from Steam, HVAC, Normal Power, Domestic Cold Water, Domestic Hot Water, Heating Hot Water, Chilled Water, Sanitary System, Nurse Call, Fire Alarm, Sprinkler System, Emergency Power, IT, and Other. Minor shutdowns require 7 calendar days' written notification, while major shutdowns affecting Medical Center operations require 21 calendar days' notification. All Fire Alarm and Sprinkler shutdowns must be coordinated with the VA Fire Alarm Technician. Contractors must have all required LOTO equipment and mandatory PPE on site or the shutdown will be cancelled.
The instructions delineate responsibilities for contractors, VA Contracting Officer Representatives (CORs), and M&O (Maintenance and Operations) Shops. VA M&O shops require 72-hour notice from VA CORs for all shutdowns. Contractors must provide panel photos and schedules with the request and involve the COR early for system investigation. The COR reviews accuracy, notifies relevant parties to prevent conflicting shutdowns, confirms affected systems and critical functions, communicates with supervisors and staff, ensures temporary measures maintain operations, and provides final notification upon approval. M&O Shops review accuracy, report known issues, specify required support, and return completed forms to the COR. A fully executed copy of the request form is required before shutdown can proceed.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24126Q0601_3.docx | DOCX document | |
| Site Visit Sign-in Sheet.pdf | ||
| VHA ICRA-1.5 July 2 2026.pdf | ||
| Appendix A - Sample Forms.pdf | ||
| Floor Plan Attachment_20250127_NH-02.pdf | ||
| 36C24126Q0601_2.docx | DOCX document | |
| 36C24126Q0601_1.docx | DOCX document | |
| 36C24126Q0601.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA CWM UTILITY SHUTDOWN REQUEST
Project Number: Company/Name:
Shutdown POC: POC Phone Number:
Requested Shutdown Date(s):
Expected Start Time:
Expected Stop Time:
Location of Shutdown:
Location of Work:
Location of
LOTO:
Competent Person(s):
PPE
Required:
Reason for Shutdown:
Description of Work:
All Building(s)/Area(s) Impacted (include downstream and upstream systems affected):
SERVICES AFFECTED BY SHUTDOWN
Service(s) being shut down during the requested work period: ✔ Service(s) affected during the requested work period: X ☐ Steam ☐ Domestic Cold Water ☐ Chilled Water ☐ Fire Alarm ☐ IT ☐ HVAC ☐ Domestic Hot Water ☐ Sanitary System ☐ Sprinkler System ☐ Other:
☐ Normal Power ☐ Heating Hot Water ☐ Nurse Call ☐ Emergency Power
WRITTEN NOTIFCATION REQUIRED
• Requests for utility shutdown must be conducted per 01 00 00 GENERAL REQUIREMENTS. Type of shutdown (major/minor) are the discretion of COR.
• Minor shutdowns require a 7-calendar day notification.
• Major shutdowns require a 21-calendar day notification. Major shutdowns are any interruptions that affect Medical Center operations.
• All Fire Alarm and Sprinkler shutdowns and outages require coordination with VA Fire Alarm Technician.
• All LOTO (Lock Out Tag Out) equipment and mandatory PPE must be on site and is required to shut down utilities. Failure to have proper
PPE and equipment will result in the shutdown being cancelled.
Requestor (Signature and Date):
VA ONLY-COR COMMENTS AND CONSIDERATIONS
Is shop support required for the shutdown? (i.e. investigating systems) YES NO If yes, specify support needed for shutdown:
Additional Comments:
COR Acknowledged (Signature and Date): APPROVED DENIED
VA ONLY-OPERATIONS AND MAINTENANCE
Is shop presence support required for the shutdown? YES NO Comments:
O&M Shop Acknowledged (Signature and Date):
VA CWM UTILITY SHUTDOWN REQUEST INSTRUCTIONS
CONTRACTORS RESPONIBILTIES
1. Requests need to be made in enough advance for investigation of affected systems by VA.
2. VA M&O shops require 72-hour notice from VA CORs for all shutdowns.
3. The below needs to be provided for the corresponding section:
• Shutdown POC/POC Phone Number: Provide the person onsite for the shutdown that will be coordinating all work and communicating with VA and appropriate parties. This contact will be provided to appropriate VA parties.
• Shutdown Date and Times: These times are a reflection of the time the utility will be shutdown which may differ from the overall time for the rest of the work to be completed.
• Location of Shutdown: Building(s), Floor(s), and Room Numbers(s), directly affected by the shutdown.
• Location of Work: Building(s), Floor(s), and Room Numbers(s) where the work is being performed.
• Location of LOTO: Include a Primary Panel Number(s)/Circuit Number(s) or Pipe(s) Tagged.
• Competent Person(s): Provide the name of the CP that will be performing the shutdown & LOTO for the shutdown.
• PPE Required: List all PPE required for shutdown. Failure to have proper PPE and equipment will result in the shutdown being cancelled.
• Reason for Shutdown: Specify work being performed that requires the shutdown.
• Description of Work: Provide all work to be completed during the shutdown. Ensure required permits are obtained as applicable.
• Impacted Area(s): All impacted/affected areas are determined by investigating panel schedules, tracing down stream piping, etc. VA COR assistance may be necessary to determine impacts, so it is recommended to involve the COR as early as possible to investigate the shutdown. Submit a photo of all panels and panel schedules affected by the shut down with this request form.
• Services Affected by Shutdown: Mark both the utility being shut down as well as utilities impacted by the shutdown.
(i.e. electrical shut downs may affect HVAC, IT Systems, Nurse Call)
• A copy of the fully executed request form is required for shutdown.
VA (COR) RESPONIBILTIES
1. Review request for accuracy. In the comments, specify whether an investigation will need to occur to ensure all interrupted services are listed. Email request to Greg and applicable M&O Shop Supervisor(s).
2. Notify the M&O Shops and Projects Team of shutdown to avoid conflicting shutdowns or interrupt work on other projects.
3. Review shutdown with Shops. Confirm what systems will be affected and ensure critical functions (phone, medication fridges, etc.) are not interrupted or have a contingency plan.
4. Communicate with affected Supervisors and Staff to ensure Medical Center operations can be maintained. Address concerns as necessary.
5. Meet with the Contractor to confirm shutdown schedule, duration and ensure VA is prepared for additional investigation if required.
6. Ensure that adequate temporary measures are in place that Medical Center Operations remain unaffected/mitigated.
7. Ensure if shop presence is required that shop personnel is available and present for shutdown.
8. Once request has been signed by all parties, provide general notification including End Users, Engineering, Police, and
Greg. Return completed form to the Contractor.
M&O (SHOPS) RESPONIBILTIES
1. Review request for accuracy-ensure all impacted systems are listed. If impacted systems are missing, notify COR.
2. Report any known issues to COR, ensure to provide follow-up tasks/actions if needed. (i.e. checking breakers after shutdown, checking specific affected systems etc.)
3. If shop support is required for shutdown, specify in the “Comments” section. Notify COR to coordinate. Communicate all
Shop requirements to COR.
4. Return completed form to COR.
| Project Number: |
| Additional Comments: |
| Comments: |
| COMPANY: |
| SHUTDOWN LOCATION: |
| LOTO LOCATION: |
| WORK LOCATION: |
| CP: |
| PPE: |
| REASON FOR SHUTDOWN: |
| DESCRIPTION OF WORK: |
| EXPECTED START: |
| EXPECTED STOP: |
| POC PHONE NUMBER: |
| SHUTDOWN POC: |
| EXPECTED DATES: |
| ALL BLDs/AREAs IMPACTED: |
| COR SHOP SUPPORT: |
| OTHER DESCRIPTION: |
| CORSHOPSUPPORT: Off |
| FORMAPPROVED: Off |
| SHOPPRESENCE: Off |
| HVAC: [nothing selected] |
| STEAM: [nothing selected] |
| NORMAL POWER: [nothing selected] |
| DOMESTIC COLD WATER: [nothing selected] |
| DOMESTIC HOT WATER: [nothing selected] |
| HEATING HOT WATER: [nothing selected] |
| CHILLED WATER: [nothing selected] |
| SANITARY SYSTEM: [nothing selected] |
| NURSE CALL: [nothing selected] |
| FIRE ALARM: [nothing selected] |
| SPRINKLER SYSTEM: [nothing selected] |
| EMERGENCY POWER: [nothing selected] |
| IT: [nothing selected] |
| OTHER: [nothing selected] |