This document outlines security system requirements for a USDA APHIS facility lease agreement. The government owns and operates a Lenel-based security enterprise system, and all installed devices must comply with this existing architecture. All devices will be installed by certified technicians and tied into the USDA APHIS access control infrastructure. The system requires FIPS-compliant dual technology card readers installed at minimum on the most frequently used exterior entrances, with intrusion detection devices (door contacts, glass breaks, or motion sensors) on all other exterior doors and perimeter-accessible rooms. The Federal Protective Service Megacenter will provide alarm monitoring services, while USDA APHIS retains responsibility for equipment maintenance and labor. System components remain government property and may be removed at lease end.

The lessor must prepare the space with specific infrastructure: one 4' x 8' fireproof plywood panel mounted on the wall, one dedicated 20-amp 120VAC electrical circuit at 24" above finished floor in a 1900 box for hard-wired security power, one dedicated analog POTS line for the alarm dialer, and one LAN/WAN IT drop at 54" above finished floor. At each identified card reader door, the lessor must install single gang work boxes with conduit stubbed above drop ceiling or routed to the telecommunications closet as required. Where feasible, door subcontractors should prepare doors and frames for specific security equipment applications.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

USDA APHIS Lenel Security System Requirements

LESSOR: _______ GOVERNMENT: _______

Security System – USDA, APHIS owns a security enterprise system. All devices installed must be compliant to that system. Currently LENEL is used by USDA, APHIS as a compliant system. All devices will be installed by certified technicians. All access control devices will be tied into the USDA, APHIS access control architecture. Compliant access control panels and FIPS compliant dual technology card readers will be installed at a minimum on the most frequently used exterior entrances. All other exterior doors will have intrusion detection devices; door contacts, glass breaks or motion sensors in each room accessible from the perimeter to detect intrusions into space through exterior windows and doors. Federal Protective Service (FPS) Megacenter’s, will provide alarm monitoring service. USDA, APHIS will be responsible for maintenance of equipment and labor. The system components will remain the property of USDA, APHIS, and may be removed by USDA, APHIS, at the end of the lease.

Lessor to prepare the space as follows:

- (1) 4' x 8', 5/8" fireproof plywood mounted on wall

- (1) 20 amp, 120VAC dedicated electrical circuit. Mounted on left side of security system panel plywood. 24" AFF, in 1900 box with cover. No receptacle - will be used to hard wire security power.

- (1) dedicated analog POTS line for security system alarm dialer

- (1) LAN/WAN IT drop mounted on left side of security system panel plywood. 54" AFF

- At each identified card reader door, install a single gang work box with conduit either stubbed above drop ceiling or if required a conduit path to the telco closet.

- Where possible have door sub-contractor prep doors/frames for specific security equipment application.

File details come from the government source that posted it. Updated .