This document contains mechanical schedules for the renovation of Building 58 at the Coatesville VA Medical Center. Key details include specifications for air handling units to serve the first and second floors, including air flow rates, fan schedules, coil schedules, and other component details. Filter schedules, air device schedules for supply, return, and exhaust, and schedules for other mechanical equipment such as pumps, humidifiers, and expansion tanks are also included.

The related federal contract opportunity is for the renovation of Building 58's first and second floors at the Coatesville VA Medical Center. The solicitation number is 36C24423R0083 and is set aside 100% for SDVOSB contractors. The opportunity type is a solicitation from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4. The mechanical schedules provide specifications for the mechanical systems and components required to complete the renovation of Building 58's first and second floors.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Engineers Architects

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/4

/2

:1 :0

P

M

M-601

MECHANICAL SCHEDULES

26 28AV

BUILDING 58 FIRST &

SECOND FLOOR

RENOVATION

1400 BLACKHORSE HILL ROAD

COATESVILLE, PA 19320

SEPTEMBER 26, 2022

CONSTRUCTION DOCUMENTS

542-19-11319-045

BLDG 58

PLH

AIR FILTER SCHEDULE

LOCATION MERV RATING

APD

HOUSING TYPE # - CARTRIDGES

CARTRIDGES

REMARKSINITIAL CHANGEOVER SIZE ARRANGEMENT

AHU PRE-FILTER 8 0.31 in-wg 0.62 in-wg SIDE LOAD PER AHU MANUF. 2" THICK PER AHU MANUF. 1

AHU PRE-FILTER 11 0.34 in-wg 0.68 in-wg SIDE LOAD PER AHU MANUF. 4" THICK PER AHU MANUF. 1

ENERGY REOCVERY MODULE OUTSIDE AIR

STREAM

8 0.31 in-wg 0.62 in-wg SIDE LOAD PER UNIT MANUF 2" THICK PER UNIT MANUF. 1

ENERGY REOCVERY MODULE EXHAUST AIR

STREAM

8 0.31 in-wg 0.62 in-wg SIDE LOAD PER UNIT MANUF 2" THICK PER UNIT MANUF. 1

REMARKS:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

2. PROVIDE SLEEVED UV-C LIGHTS DOWNSTREAM OF COOLING COIL WITH VIEWING WINDOW AND DOOR INTERLOCK SWITCH.

3. PROVIDE WITH (4) POWER CIRCUITS: (1) 208V/3Ph CIRCUIT FOR SUPPLY FAN ARRAY AND CONTROLS; (1) 120V/1Ph CIRCUIT FOR UV LIGHTS; (1) 120V/1Ph CIRCUIT FOR INTERIOR LIGHTS; (1) 120V CIRCUIT FOR CONVENIENCE RECEPTACLE.

4. BALANCE AIRFLOWS PER THE FLOOR PLANS. SCHEDULED AIRFLOWS ARE NOMINAL FOR SIZING EQUIPMENT.

5. MAXIMUM ALLOWABLE UNIT WEIGHT: 3,900 LBS. MAXIMUM ALLOWABLE UNIT DIMENSIONS: 215" LONG, 72" WIDE 49" HIGH. PROVIDE WITH 2.5" INTEGRAL BASE RAIL.

6. PROVIDE SHIPPING SPLITS TO ALLOW UNIT TO BE BROUGHT INTO THE ATTIC THROUGH OPENING BEING CUT IN THE ROOF. PRIOR TO ORDERING UNIT, CONFIRM MAXIMUM ALLOWABLE SIZE OF A SHIPPING SPLIT THAT WILL FIT THROUGH THE

OPENING BEING CUT. ASSEMBLE UNIT IN THE ATTIC.

7. PROVIDE A BLANK SECTION TO ALLOW FOR INSTALLATION OF A FUTURE HUMIDIFIER DISPERSION RACK. PROVIDE 36" LONG SECTION WITH ACCESS DOOR DOWNSTREAM OF HUMIDIFIER BLANK SECTION TO ALLOW FOR HUMIDIFIER ABSORPTION

DISTANCE. HUMIDIFIER SECTION AND ABSORPTION SECTION SHALL HAVE A STAINLESS STEEL DRAIN PAN. PROVIDE THESE SECTIONS BETWEEN PREHEAT COIL AND COOLING COIL. PROVIDE ACCESS SECTION BETWEEN PREHEAT COIL AND

HUMIDIFIER SECTION.

REMARKS:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

REMARKS:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

2. SUPPLY FANS SHALL BE ABLE TO DELIVER 105% OF THE AIRFLOW SCHEDULED. EXTERNAL STATIC PRESSURE INCLUDES 1.7" ON SUCTION SIDE FOR PRESSURE DROP THROUGH OUTSIDE AIR DUCTWORK AND ENERGY RECOVERY MODULE.

3. PROVIDE A SEPARATE VFD FOR EACH FAN IN PLENUM FAN ARRAYS. VFDs SHALL BE MOUNTED EXTERNALLY ON THE SIDE OF AIR HANDLING UNIT.

4. PROVIDE MOTOR OVERLOAD PANEL AND SHAFT GROUNDING RINGS FOR PLENUM DIRECT DRIVE FANS.

5. BALANCE AIRFLOWS PER THE FLOOR PLANS. SCHEDULED AIRFLOWS ARE NOMINAL FOR SIZING EQUIPMENT.

6. FLOOR MOUNT 58-EF-1 AND 58-EF-2 ON A NEW 4" CONCRETE PAD AND 1" DEFLECTION SPRING VIBRATION ISOLATORS. MAXIMUM ALLOWABLE WEIGHT OF EACH FAN IS 500 LBS.

7. RETURN FANS SHALL BE SUSPENDED FROM ROOF STRUCTURE ABOVE ON 1" DEFLECTION SPRING ISOLATION HANGERS. MAXIMUM ALLOWABLE WEIGHT OF EACH FAN IS 400 LBS. MAXIMUM ALLOWABLE INLET SOUND LEVEL IS 74 dBA.

REMARKS:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

2. PROVIDE CONTROLLERS AS REQUIRED TO INTEGRATE INTO DDC BUILDING AUTOMATION SYSTEM.

3. PROVIDE PREMIUM EFFICIENCY MOTOR AND VARIABLE FREQUENCY DRIVE (VFD).

4. FLOW RATE IS HEATING HOT WATER PUMPS IS BASED ON DESIGN FLOW RATE THROUGH THE EXISTING HEAT EXCHANGERS.

5. PROVIDE SUCTION DIFFUSER WITH STAINLESS STEEL START-UP STRAINER.

REMARKS:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

REMARKS:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

REMARKS:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

REMARKS:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

2. PROVIDE WITH MANUFACTURER'S PROGRAMMABLE WALL THERMOSTAT AND WASHABLE FILTER.

3. INSTALL DDC TEMPERATURE SENSOR IN EACH ROOM FOR DDC MONITORING.

4. PROVIDE CONDENSING UNIT WITH WIND BAFFLE AND ACCESSORIES FOR COOLING OPERATION DOWN TO 0 DEGREES F OUTDOOR AIR TEMPERATURE.

5. SIZE, ROUTE AND INSTALL REFRIGERANT PIPING TO INDOOR UNIT PER MANUFACTURER'S INSTRUCTIONS.

REMARKS:

1. INSTALL PER MANUFACTERER'S RECOMMENDATIONS.

2. PROVIDE 2" MERV 8 FILTERS IN OUTSIDE AIR AND EXHAUST AIR STREAMS.

3. MAXIMUM UNIT SIZE: 73.5" L x 37.25" W x 86" H; 700 LBS. PROVIDE WITH KNOCKDOWN CONFIGURATION TO ALLOW UNIT TO BE BROUGHT INTO ATTIC IN PIECES. ASSEMBLE

UNIT IN THE ATTIC. COORDINATION MAXIMUM ALLOWABLE SIZE OF LARGEST COMPONENT WITH NEW OPENING BEING CUT IN ROOF.

58-AS-2 SUB-BASEMENT HEATING HOT WATER FULL FLOW TANGENTIAL 4 290 2 NO 1

58-AS-1 SUB-BASEMENT CHILLED WATER FULL FLOW TANGENTIAL 5 335 1 NO 1

IN GPM FT

SIZE FLOW WPD BUILT-IN STRAINER

REQ'D

MARK LOCATION SYSTEM TYPE

AIR SEPARATOR

REMARKS

AIR SEPARATOR SCHEDULE

STEAM TRAP SCHEDULE

SYSTEM AND/OR SERVICE TYPE

MIN. DIFF.

PRESSURE

MIN. INLET

PRESSURE REMARKS

AHU PREHEAT COILS FLOAT AND THERMOSTATIC 1/4 psi 5 psi 1

LPS DRIP LEGS - MAINS INVERTED BUCKET 12 psi 15 psi 1

LPS DRIP LEG - PREHEAT COILS INVERTED BUCKET 1 psi 5 psi 1

REMARKS:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

58-RF-6 ATTIC 58-AHU-6 RETURN 7000 MIXED FLOW INLINE MIXED FLOW 1.5 1.5 20 57% DIRECT 1,497 2.9 5 3 208 1800 VFD 1, 7

58-RF-5 ATTIC 58-AHU-5 RETURN 5800 MIXED FLOW INLINE MIXED FLOW 1.5 1.5 18 57% DIRECT 1,654 2.4 5 3 208 1800 VFD 1, 7

58-RF-4 ATTIC 58-AHU-4 RETURN 5700 MIXED FLOW INLINE MIXED FLOW 1.5 1.5 18 58% DIRECT 1,635 2.3 5 3 208 1800 VFD 1, 7

58-RF-3 ATTIC 58-AHU-3 RETURN 7700 MIXED FLOW INLINE MIXED FLOW 1.5 1.5 20 55% DIRECT 1,555 3.3 5 3 208 1800 VFD 1, 7

58-SF-6 ATTIC 58-AHU-6 SUPPLY 7500 PLENUM FAN ARRAY AIRFOIL 3.5 6.1 16.5 69% DIRECT 2,888 9.9 (2) AT 7.5 HP EACH 3 208 1800 VFD 1, 2, 3, 4, 5

58-SF-5 ATTIC 58-AHU-5 SUPPLY 6300 PLENUM FAN ARRAY AIRFOIL 3.2 5.4 16.5 68% DIRECT 2,863 7.8 (2) @ 5 HP EACH 3 208 1800 VFD 1, 2, 3, 4, 5

58-SF-4 ATTIC 58-AHU-4 SUPPLY 6200 PLENUM FAN ARRAY AIRFOIL 3.2 5.3 16.5 68% DIRECT 2,839 7.6 (2) @ 5 HP EACH 3 208 1800 VFD 1, 2, 3, 4, 5

58-SF-3 ATTIC 58-AHU-3 SUPPLY 8200 PLENUM FAN ARRAY AIRFOIL 3.9 6.8 16.5 68% DIRECT 3,029 11.5 (2) @ 7.5 HP EACH 3 208 1800 VFD 1, 2, 3, 4, 5

58-EF-3 ATTIC ATTIC VENTILATION 2000 SQUARE INLINE BI CENTRIFUGAL 0.25 0.25 18 46% BELT 629 0.2 1/3 1 115 1725 CONSTANT 1

58-EF-2 ATTIC N/A EXHAUST 5785 SW UTILITY VENT SET AF CENTRIFUGAL 3.7 3.7 22 70% DIRECT 1,469 4.4 5 3 208 1800 CONSTANT 1, 6

58-EF-1 ATTIC N/A EXHAUST 5165 SW UTILITY VENT SET AF CENTRIFUGAL 2.5 2.5 22 73% DIRECT 1,671 2.8 5 3 208 1770 CONSTANT 1, 6

CFM INCHES BHP HP

TYPE WHEEL TYPE ESP (IN WG) TSP (IN WG)

WHEEL DIAMETER

MIN % EFF DRIVE FAN MAX RPM

NOMINAL POWER

PHASE VOLT RPM

SPEED

CONTROL

MARK LOCATION

BUILDING/AREA

SERVED

SERVICE

AIR FLOW

FAN MOTOR ELECTRICAL

REMARKS

FAN SCHEDULE

58-CC-6 ATTIC 58 58-AHU-6 7500 446 0.725 80.9 67.6 53 52.8 341 231 68 45 55 7.0 1

58-CC-5 ATTIC 58 58-AHU-5 6300 375 0.481 80.7 67.4 53 52.8 281 192 56 45 55 6.2 1

58-CC-4 ATTIC 58 58-AHU-4 6200 369 0.460 80 66.8 53 52.8 264 184 53 45 55 5.5 1

58-CC-3 ATTIC 58 58-AHU-3 8200 488 0.917 79.6 68.1 53 52.8 387 241 77 45 55 8.8 1

CFM FPM IN WG °F °F °F °F MBH MBH GPM °F °F FT

Db Wb Db Wb FLOW EWT LWT WPDMARK LOCATION

AREA AND/OR

BLDG SERVED

SYSTEM AIR

HANDLING

AIR FLOW

MAX FACE

VELOCITY

APD

EAT LAT

TOTAL CAPACITY

SENSIBLE

CAPACITY

CHILLED WATER

REMARKS

CHILLED WATER COOLING COIL SCHEDULE

58-PHC-6 ATTIC 58 58-AHU-6 4000 291 0.027 40 79 169 5 176 352 1

58-PHC-5 ATTIC 58 58-AHU-5 3400 247 0.020 40 80.9 151 5 157 314 1

58-PHC-4 ATTIC 58 58-AHU-4 3200 233 0.018 40 82 144 5 150 300 1

58-PHC-3 ATTIC 58 58-AHU-3 4400 320 0.032 40 77.8 180 5 187 374 1

CFM FPM IN WG °F °F MBH PSIG LBS/HR CAPACITY (LBS/HR)

EAT LAT ENT. PRESSURE FLOW TRAPMARK LOCATION

AREA AND/OR

BLDG SERVED

SYSTEM

AND/OR

SERVICE

AIR FLOW

MAX FACE

VELOCITY

APD

TEMPERATURES TOTAL MIN

CAPACITY

STEAM

REMARKS

STEAM PREHEAT COIL SCHEDULE

58-AHU-6 ATTIC 58 MODULAR 7500 2805 4750 58-SF-6 58-RF-6 58-PF-6 58-PHC-6 58-CC-6 1, 2, 3, 4, 5, 6, 7

58-AHU-5 ATTIC 58 MODULAR 6300 2250 3300 58-SF-5 58-RF-5 58-PF-5 58-PHC-5 58-CC-5 1, 2, 3, 4, 5, 6, 7

58-AHU-4 ATTIC 58 MODULAR 6200 1950 6000 58-SF-4 58-RF-4 58-PF-4 58-PHC-4 58-CC-4 1, 2, 3, 4, 5, 6, 7

58-AHU-3 ATTIC 58 MODULAR 8200 1950 5000 58-SF-3 58-RF-3 58-PF-3 58-PHC-3 58-CC-3 1, 2, 3, 4, 5, 6, 7

CFM CFM CFM

SUPPLY MIN OA RETURNMARK LOCATION

AREA AND/OR BLDG

SERVED

TYPE

AIR FLOW

SUPPLY FAN

MARK

RETURN OR

RELIEF FAN MARK

PREFILTER MARK

PREHEAT COIL

MARK

COOLING COIL

MARK

REMARKS

AIR HANDLING UNIT SCHEDULE

HEATING 55% 7000 1.55 10.1 5.6 46.2 36.7 5425 1.11 70 54.3 --- --- 1, 2, 3

58-ERM-2 ATTIC 58-AHU-1

COOLING 45% 7000 1.55 90.9 75 81.3 69.8 5425 1.11 75 62 --- --- 1, 2, 3

HEATING 54% 7000 1.55 10.1 5.6 45.3 36 5165 1.05 70 54.3 --- --- 1, 2, 3

58-ERM-1 ATTIC 58-AHU-1

COOLING 44% 7000 1.55 90.9 75 81.6 69.9 5165 1.05 75 62 --- --- 1, 2, 3

CFM IN °F °F °F °F CFM IN °F °F °F °F

Db Wb Db Wb Db Wb Db Wb

SUPPLY AIR

FLOW

APD

EAT LAT EXHAUST

AIR FLOW

APD

EAT LAT

MARK LOCATION

SYSTEM AND/OR

SERVICE

MODE

MIN SUPPLY AIR

EFF %

SUPPLY AIR EXHAUST AIR

REMARKS

CROSSFLOW AIR-TO-AIR HEAT EXCHANGER ENERGY RECOVERY MODULES

58-DAC-3/58-CU-3 GRADE IT WALL-MOUNTED 635 24 17.6 80 67 95 N/A N/A N/A 0.6 208/1/60 15 16.5 208/1/60 25 1, 2, 3, 4, 5

58-DAC-2/58-CU-2 GRADE IT WALL-MOUNTED 635 24 17.6 80 67 95 27 70 47 0.6 208/1/60 15 16.5 208/1/60 25 1, 2, 3, 4, 5

58-DAC-1/58-CU-1 GRADE SPD CEILING CASSETTE 335 11.1 19.4 80 67 95 14 70 47 n/a 208/1/60 n/a 12.3 208/1/60 15 1, 2, 3, 4, 5

CFM MBH °F °F °F MBH °F °F MCA V/PH/HZ MOP MCA V/PH/HZ MOP

Db Wb

MIN TOTAL

CAPACITY

MIN

SEER

EAT OSA DESIGN

TEMP

MIN. HEAT

CAPACITY

EAT DB

OSA DESIGN

TEMP

INDOOR UNIT OUTDOOR UNITMARK LOCATION

AREA AND/OR

BLDG SERVED

TYPE

TOTAL SUPPLY

AIR FLOW

COOLING CAPACITY HEATING CAPACITY ELECTRICAL

REMARKS

SPLIT SYSTEM AIR CONDITIONER HEAT PUMP SCHEDULE

58-HWP-2 SUB-BASEMENT HOT WATER HEATING BASE MOUNTED END SUCTION WATER 145 40 60 73 5 3 208 1800 VFD 1, 2, 3, 4, 5

58-HWP-1 SUB-BASEMENT HOT WATER HEATING BASE MOUNTED END SUCTION WATER 145 40 60 73 5 3 208 1800 VFD 1, 2, 3, 4, 5

58-CWP-2 SUB-BASEMENT CHILLED WATER BASE MOUNTED END SUCTION WATER 375 60 65 71 10 3 208 1800 VFD 1, 2, 3, 5

58-CWP-1 SUB-BASEMENT CHILLED WATER BASE MOUNTED END SUCTION WATER 375 60 65 71 10 3 208 1800 VFD 1, 2, 3, 5

GPM GPM FT HP

FLUID

FLOW MIN FLOW HEAD NOMINAL POWER

PHASE VOLT MAX RPM

SPEED

CONTROL

MARK LOCATION SYSTEM TYPE

CIRCULATING FLUID

MIN % EFF

ELECTRICAL MOTOR

REMARKS

HYDRONIC PUMP SCHEDULE

REMARKS:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

2. PROVIDE DAMPER IN BRANCH DUCT TO AIR DEVICE, EVEN IF DAMPER IS NOT SHOWN ON FLOOR PLANS.

3. HIGH SECURITY RISK RESISTANT GRILLE. BASIS OF DESIGN: PRICE MSRRP (OR EQUAL).

REMARKS:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

2. PROVIDE DAMPER IN BRANCH DUCT TO AIR DEVICE, EVEN IF DAMPER IS NOT SHOWN ON FLOOR PLANS.

3. HIGH SECURITY RISK RESISTANT DIFFUSER. BASIS OF DESIGN: PRICE MSRRCD (OR EQUAL).

REMARKS:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

2. PROVIDE DAMPER IN BRANCH DUCT TO AIR DEVICE, EVEN IF DAMPER IS NOT SHOWN ON

FLOOR PLANS.

3. HIGH SECURITY RISK RESISTANT GRILLE. BASIS OF DESIGN: PRICE MSRRP (OR EQUAL)

AIR DEVICE SCHEDULE (SUPPLY)

MARK TYPE

AIRFLOW

MAX. APD MOUNTING

PANEL/FRAME

SIZE NECK SIZE MAX. NC DAMPER FINISH MATERIAL REMARKSMAX. MIN.

SD-1 SQUARE CONE ADJUSTABLE 180 80 0.08 in-wg CEILING 24x24 6"Ø 21 Yes WHITE STEEL 1, 2

SD-2 SQUARE CONE ADJUSTABLE 280 140 0.08 in-wg CEILING 24x24 8"Ø 20 Yes WHITE STEEL 1, 2

SD-3 SQUARE CONE ADJUSTABLE 380 110 0.09 in-wg CEILING 24x24 10"Ø 22 Yes WHITE STEEL 1, 2

SD-4 SQUARE CONE ADJUSTABLE 630 300 0.09 in-wg CEILING 24x24 12"Ø 24 Yes WHITE STEEL 1, 2

SD-11 SQUARE CONE ADJUSTABLE 160 40 0.08 in-wg CEILING 12x12 6"Ø 19 Yes WHITE STEEL 1, 2

SD-21 LOUVERED FACE REGISTER 100 0 0.09 in-wg WALL 8x8 6x6 - Yes WHITE ALUMINUM 1, 2

SD-31 LOUVERED FACE 50 0 0.06 in-wg CEILING 9X9 6X6 - Yes WHITE STEEL 1, 2, 3

SD-32 LOUVERED FACE 100 51 0.10 in-wg CEILING 10x10 8x8 - Yes WHITE STEEL 1, 2, 3

SD-33 LOUVERED FACE 150 101 0.12 in-wg CEILING 12x12 9x9 - Yes WHITE STEEL 1, 2, 3

SD-34 LOUVERED FACE 200 151 0.05 in-wg CEILING 15x15 12x12 21 Yes WHITE STEEL 1, 2, 3

SD-35 LOUVERED FACE 250 201 0.09 in-wg CEILING 18x18 15x15 25 Yes WHITE STEEL 1, 2, 3

AIR DEVICE SCHEDULE (RETURN)

MARK TYPE

AIRFLOW

MAX. APD MOUNTING

PANEL/FRAME

SIZE NECK SIZE MAX NC DAMPER FINISH MATERIAL REMARKSMAX. MIN.

RG-11 LOUVERED FACE 400 130 0.09 in-wg CEILING 24x24 8x8 19 Yes WHITE STEEL 1, 2

RG-12 LOUVERED FACE 555 210 0.08 in-wg CEILING 24x24 10X10 20 Yes WHITE STEEL 1, 2

RG-13 LOUVERED FACE 800 300 0.08 in-wg CEILING 24x24 12X12 23 Yes WHITE STEEL 1, 2

RG-14 LOUVERED FACE 955 410 0.06 in-wg CEILING 24x24 14x14 21 Yes WHITE STEEL 1, 2

RG-15 LOUVERED FACE 1070 530 0.05 in-wg CEILING 24x24 16x16 20 Yes WHITE STEEL 1, 2

RG-16 LOUVERED FACE 1350 675 0.05 in-wg CEILING 24x24 18x18 22 Yes WHITE STEEL 1, 2

RG-17 LOUVERED FACE 2015 1010 0.06 in-wg CEILING 24x24 20x20 24 Yes WHITE STEEL 1, 2

RG-21 PERFORATED 80 25 0.08 in-wg CEILING 9x9 6x6 - Yes WHITE STEEL 1, 2, 3

RG-22 PERFORATED 180 56 0.08 in-wg CEILING 12x12 9x9 - Yes WHITE STEEL 1, 2, 3

RG-23 PERFORATED 175 141 0.08 in-wg CEILING 13x13 10x10 - Yes WHITE STEEL 1, 2, 3

RG-24 PERFORATED 250 176 0.08 in-wg CEILING 15x15 12x12 - Yes WHITE STEEL 1, 2, 3

RG-25 PERFORATED 340 251 0.08 in-wg CEILING 18x18 15x15 - Yes WHITE STEEL 1, 2, 3

EG-23 PERFORATED 225 70 0.08 CEILING 12x12 10x10 - YES WHITE STEEL 1, 2, 3

EG-22 PERFORATED 180 55 0.08 CEILING 10x10 8x8 - YES WHITE STEEL 1, 2, 3

EG-21 PERFORATED 80 25 0.08 CEILING 8x8 6x6 - YES WHITE STEEL 1, 2, 3

EG-11 LOUVERED FACE 955 410 0.06 CEILING 24x24 14x14 21 YES WHITE STEEL 1, 2

EG-6 LOUVERED FACE 400 130 0.09 CEILING 24x24 8x8 19 YES WHITE STEEL 1, 2

EG-3 LOUVERED FACE 240 57 0.08 CEILING 14x10 12x8 17 YES WHITE STEEL 1, 2

EG-2 LOUVERED FACE 156 57 0.08 CEILING 10x10 8x8 15 YES WHITE STEEL 1, 2

EG-1 LOUVERED FACE 72 57 0.08 WALL 8x8 6x6 - YES WHITE STEEL 1, 2

MAX. MIN.MARK TYPE

AIRFLOW

MAX. APD MOUNTING PANEL/FRAME SIZE NECK SIZE MAX NC DAMPER FINISH MATERIAL REMARKS

AIR DEVICE SCHEDULE (EXHAUST)

58-HUM-1 SPD 117 5.5 ROOM HUMIDISTAT 115/1 16.4 25 1, 2, 3

LBS/HR VOLTS/ PHASE FULL LOAD AMPS MOCP

MARK LOCATION

STEAM OUTPUT CAPACITY

CONTROL TYPE

ELETRICAL

REMARKS

ELECTRIC HUMIDIFER SCHEDULE

REMARKS:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

2. ROUTE PIPING AND ELECTRICAL CONDUIT SERVING HUMIDIFIER CONCEALED IN NEW GWB WALL ON WHICH THE UNIT IS MOUNTED.

3. BASIS OF DESIGN IS THE GENERALAIRE ELITE STEAM MODEL RS15P (OR EQUAL).

58-ET-3 SUB-BASEMENT HEATING HOT WATER BLADDER 40 190 25 57 65 57 106 106 1 0.75 1

58-ET-2 SUB-BASEMENT HEATING HOT WATER BLADDER 40 190 25 57 65 57 106 106 1 0.75 1

58-ET-1 SUB-BASEMENT CHILLED WATER BLADDER 40 100 30 69 75 69 53 53 1 0.75 1

°F °F PSIG PSIG PSIG PSIG GAL GAL IN IN

MIN MAX RELIEF VALVE AT TANKMARK LOCATION SYSTEM AND/OR SERVICE TYPE

SYSTEM TEMPERATURE RANGE INITIAL PRESSURE IN

TANK

MAX OPERATING

PRESSURE

FILL PRESSURE AT TANK MIN VOLUME

TANK

MIN BLADDER

VOLUME

PIPE SIZE TO

TANK

COLD WATER FILL

SIZE REMARKS

EXPANSION TANK SCHEDULE

REMARKS:

1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.

DocuSign Envelope ID: B15CB0F8-0C41-4627-91B4-74F90F19D279

10/5/2023

Sheets
M-601 - MECHANICAL SCHEDULES
2023-10-05T08:00:40-0700
Digitally verifiable PDF exported from www.docusign.com

File details come from the government source that posted it. Updated .