Tucson_CMOP_Code_Compliance-1-20-2023.xlsx
XLSX spreadsheet 12 KB Posted
- Attached to
- Z1AZ--PROPERTY MGT SERVICES Federal contract opportunity
- Solicitation number
- 36C77024Q0068
About this file
This document contains a spreadsheet listing code compliance activities required at the Tucson Clinical Resource and Management Center of Excellence property and a solicitation notice for property management services at that location.
The spreadsheet details required inspection and testing frequencies for various building systems and safety equipment according to National Fire Protection Association and other standards. Items addressed include emergency power supplies, fire extinguishers, sprinklers, fire alarms, backflow preventers, and eyewash stations. It specifies that the contractor will be responsible for conducting and documenting the activities monthly and submitting documentation to the Clinical Resource and Management Center of Excellence. The solicitation seeks property management services and lists the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 as the agency and 36C77024Q0068 as the solicitation number.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C77024Q0068 0001.docx | DOCX document | |
| 36C77024Q0068.pdf | ||
| Roof-HVAC-Identified.pdf | ||
| 36C77024Q0068.docx | DOCX document | |
| QASP-Maint Sched and calendar Table-1-20-2023.xlsx | XLSX spreadsheet | |
| P07 DOL Wage Det 2015-5473 Rev 20 dtd 07.21.2023.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| Electrical System | |||
| Item / Activity | Frequency | Code Reference | |
| Battery Powered Lights tested for 30 Seconds | Every 30 Days | NFPA 101 Chapter 7 | |
| Battery Powered Lights tested for 90 Minutes | Annual | NFPA 101 Chapter 7 | |
| GFCI Testing per Manufacturer | Monthly | NFPA 70 Article 110 | |
| Emergency Power Supply System Inspection | Weekly | NFPA 110 Chapter 8 | |
| Emergency Power Supply System exercised under load | |||
| (rotate ATSs if applicable), and Battery Testing | Monthly | NFPA 110 Chapter 8 | |
| If monthly load of 30% of the nameplate KW rating is not met, then the system shall be load tested | Annual | NFPA 110 Chapter 8 | |
| Emergency Power Supply System tested for 4 continuous hours at a load minimum of 30% of the nameplate KW rating | Three Years | NFPA 110 Chapter 8 | |
| Fuel Quality Test per ASTM | Annual | NFPA 110 Chapter 8 | |
| Portable Fire Extinguishers | |||
| Item / Activity | Frequency | Code Reference | |
| Portable Fire Extinguishers are Inventoried and Inspected | Monthly | NFPA 10 Chapters 4 & 7 | |
| Portable Fire Extinguishers are Inventoried and Maintained | Annual | NFPA 10 Chapters 4 & 7 | |
| Portable Fire Extinguisher Hydrostatic Testing | Five or Twelve Years | NFPA 10 Table 8.3.1 | |
| Fire Suppression and Standpipe Systems | |||
| Item / Activity | Frequency | Code Reference | |
| Sprinkler System Inspection and Main Drain Test on All Risers | Annual | NFPA 25 Chapter 13 | |
| Fire Department Connection Inspection | Quarterly | NFPA 25 Chapter 23 | |
| Auto Standpipe Systems Tested with Water Flow | Five Years | NFPA 25 Chapter 6 | |
| Fire Detection and Alarm System | |||
| Item / Activity | Frequency | Code Reference | |
| Emergency Services Notification Transmission Equipment | Annual (Test), Semiannual (Visual) | NFPA 72 Chapter 14 | |
| Secondary Power Supply, UPS, Batteries | Annual (Test), Semiannual (Visual) | NFPA 72 Chapter 14 | |
| Supervisory Signal Devices | Annual (Test), Quarterly (Visual) | NFPA 72 Chapter 14 | |
| Valve Tamper Switches and Water Flow Devices | Semiannual (Test), Quarterly (Visual) | NFPA 72 Chapter 14 | |
| Duct Detectors, Heat Detectors, Smoke Detectors, Pull Boxes | Annual (Test), Semiannual (Visual) | NFPA 72 Chapter 14 | |
| Door Releasing Devices, Notification Devices (Visual and Audio) | Annual (Test), Semiannual (Visual) | NFPA 72 Chapter 14 | |
| Backflow Prevention | |||
| Item / Activity | Frequency | Code Reference | |
| Test and maintenance of backflow preventers | Annual | City of Tucson | |
| Eyewash Stations and Emergency Drench Showers | |||
| Item / Activity | Frequency | Code Reference | |
| Testing of Eyewash Stations and Emergency Drench Showers | Weekly | ANSI Z358.1 & |
VHA Directive 7704
| Flow rate Testing of Eyewash Stations and Emergency Drench Showers | Annual |
| Notes: |
1) Code reference is current edition at the time of contract award.
2) If an item is the responsibility of CMOP it shall be annotated at time of contract award.
3) Contractor is responsible for confirming frequencies.
4) Contractor is responsible for submitting documentation to CMOP on a monthly basis in accordance with the contract. The documentation shall have the name of the activity, date of activity, inventory, required frequency, name and contact info of person who performed activity, NFPA standard referenced, and results. Any failures shall be tracked until resolution with a follow up report to CMOP for each activity.
&"-,Bold"&12SOUTHWEST (TUCSON) CMOP PROPERTY MANAGEMENT CODE COMPLIANCE
March 5, 2021