Tucson_CMOP_Code_Compliance-1-20-2023.xlsx

XLSX spreadsheet 12 KB Posted

Attached to
Z1AZ--PROPERTY MGT SERVICES Federal contract opportunity
Solicitation number
36C77024Q0068
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15

About this file

This document contains a spreadsheet listing code compliance activities required at the Tucson Clinical Resource and Management Center of Excellence property and a solicitation notice for property management services at that location.

The spreadsheet details required inspection and testing frequencies for various building systems and safety equipment according to National Fire Protection Association and other standards. Items addressed include emergency power supplies, fire extinguishers, sprinklers, fire alarms, backflow preventers, and eyewash stations. It specifies that the contractor will be responsible for conducting and documenting the activities monthly and submitting documentation to the Clinical Resource and Management Center of Excellence. The solicitation seeks property management services and lists the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 as the agency and 36C77024Q0068 as the solicitation number.

View the file

Other files for this federal contract opportunity

Other files attached to Z1AZ--PROPERTY MGT SERVICES, newest first.
File Type Posted
36C77024Q0068 0001.docx DOCX document
36C77024Q0068.pdf PDF
Roof-HVAC-Identified.pdf PDF
36C77024Q0068.docx DOCX document
QASP-Maint Sched and calendar Table-1-20-2023.xlsx XLSX spreadsheet
P07 DOL Wage Det 2015-5473 Rev 20 dtd 07.21.2023.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

Electrical System
Item / ActivityFrequencyCode Reference
Battery Powered Lights tested for 30 SecondsEvery 30 DaysNFPA 101 Chapter 7
Battery Powered Lights tested for 90 MinutesAnnualNFPA 101 Chapter 7
GFCI Testing per ManufacturerMonthlyNFPA 70 Article 110
Emergency Power Supply System InspectionWeeklyNFPA 110 Chapter 8
Emergency Power Supply System exercised under load
(rotate ATSs if applicable), and Battery TestingMonthlyNFPA 110 Chapter 8
If monthly load of 30% of the nameplate KW rating is not met, then the system shall be load testedAnnualNFPA 110 Chapter 8
Emergency Power Supply System tested for 4 continuous hours at a load minimum of 30% of the nameplate KW ratingThree YearsNFPA 110 Chapter 8
Fuel Quality Test per ASTMAnnualNFPA 110 Chapter 8
Portable Fire Extinguishers
Item / ActivityFrequencyCode Reference
Portable Fire Extinguishers are Inventoried and InspectedMonthlyNFPA 10 Chapters 4 & 7
Portable Fire Extinguishers are Inventoried and MaintainedAnnualNFPA 10 Chapters 4 & 7
Portable Fire Extinguisher Hydrostatic TestingFive or Twelve YearsNFPA 10 Table 8.3.1
Fire Suppression and Standpipe Systems
Item / ActivityFrequencyCode Reference
Sprinkler System Inspection and Main Drain Test on All RisersAnnualNFPA 25 Chapter 13
Fire Department Connection InspectionQuarterlyNFPA 25 Chapter 23
Auto Standpipe Systems Tested with Water FlowFive YearsNFPA 25 Chapter 6
Fire Detection and Alarm System
Item / ActivityFrequencyCode Reference
Emergency Services Notification Transmission EquipmentAnnual (Test), Semiannual (Visual)NFPA 72 Chapter 14
Secondary Power Supply, UPS, BatteriesAnnual (Test), Semiannual (Visual)NFPA 72 Chapter 14
Supervisory Signal DevicesAnnual (Test), Quarterly (Visual)NFPA 72 Chapter 14
Valve Tamper Switches and Water Flow DevicesSemiannual (Test), Quarterly (Visual)NFPA 72 Chapter 14
Duct Detectors, Heat Detectors, Smoke Detectors, Pull BoxesAnnual (Test), Semiannual (Visual)NFPA 72 Chapter 14
Door Releasing Devices, Notification Devices (Visual and Audio)Annual (Test), Semiannual (Visual)NFPA 72 Chapter 14
Backflow Prevention
Item / ActivityFrequencyCode Reference
Test and maintenance of backflow preventersAnnualCity of Tucson
Eyewash Stations and Emergency Drench Showers
Item / ActivityFrequencyCode Reference
Testing of Eyewash Stations and Emergency Drench ShowersWeeklyANSI Z358.1 &

VHA Directive 7704

Flow rate Testing of Eyewash Stations and Emergency Drench ShowersAnnual
Notes:

1) Code reference is current edition at the time of contract award.

2) If an item is the responsibility of CMOP it shall be annotated at time of contract award.

3) Contractor is responsible for confirming frequencies.

4) Contractor is responsible for submitting documentation to CMOP on a monthly basis in accordance with the contract. The documentation shall have the name of the activity, date of activity, inventory, required frequency, name and contact info of person who performed activity, NFPA standard referenced, and results. Any failures shall be tracked until resolution with a follow up report to CMOP for each activity.

&"-,Bold"&12SOUTHWEST (TUCSON) CMOP PROPERTY MANAGEMENT CODE COMPLIANCE

March 5, 2021