Troup Co FS 1 Construction Documents.pdf
PDF 38 MB Posted
- Attached to
- Construction of Troup County Fire Station #1
- Solicitation number
- PE-77030-NONST-2027-000000029
- Issued by
- Terrell County, Georgia
About this file
This document comprises the 100% construction documents for Troup County Fire Station #1, located at Burkes Chapel Road in Troup County, Georgia, prepared by 2WR + Partners Architects in collaboration with structural, mechanical/plumbing, civil, and engineering consultants. The project involves construction of a new single-story fire station comprising approximately 7,496 square feet of enclosed area with 8,801 square feet total including covered areas. The facility will serve as a mixed-occupancy building classified as both Group R-3 (lodging/rooming house) and Group S-2 (low-hazard storage), featuring a two-bay or optional three-bay apparatus bay, dormitory facilities for five transient residents, administrative offices, kitchen, day room, and support spaces. The construction documents include comprehensive architectural, structural, mechanical, plumbing, electrical, civil, and erosion/sediment control plans. A mandatory pre-bid meeting is scheduled for August 27, 2026, at 2:00 PM at the jobsite. Sealed proposals are due October 1, 2026, at 2:00 PM at the Troup County Purchasing Department. The project must be substantially completed within 300 consecutive calendar days, with an anticipated start date in November 2026.
The contract will be awarded on a lump-sum basis to a single general contractor responsible for all trades and coordination. A 5% bid bond is required with proposal submission, which must include two hard copies and one digital copy. Troup County will be responsible for submitting plans to the local fire marshal and building inspection department, paying all water and sewer tap fees, providing and installing the water meter, and furnishing landscaping and signage (except for the 48-inch numeral "1"). The general contractor is not responsible for permit fees. The project assumes favorable soil conditions absent a geotechnical report, incorporates a well water system and septic tank for on-site sewage management, and includes a civil-designed storm drainage system with detention pond and outlet control structure. The design incorporates both sprinklered and unsprinklered areas, fire-rated partitions, life safety systems including fire alarm and emergency lighting, and construction materials and methods compliant with 2024 International Building Code and current Georgia amendments.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Troup County BOC _ Invitation To Bid Bid For.pdf | ||
| TC Fire Station1 Project Manuel.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project No.:
Date:
Drawn by:
Checked by:
Revisions:
PR
IN
TE
D:
FI
LE
P
AT
H:
11 Ninth Street, Suite 120 Columbus, GA 31901 P. (706) 571-6923
8/
/2
4:
:3
PM
C :\U se rs
\A le xG rig gs _r m ud ak 7\
Ap pD at a\
Lo ca l\A ut od es k\ R ev it\
Au to de sk
R ev it
\C ol la bo ra tio nC ac he
\Q 2G
2D
JC
C L7
R D
H U
\3 e7
8-
5e db
-4
2-a3
-8
7d
2\
9a
7e 2b
-1 d6 c-a6 -a b7 c-f1 b5
.rv t
T1.1
COVER SHEET
B
U R
KE
S
C H
AP
EL
R O
AD
TR
O U
P C
O U
N
TY
, G
EO
R G
IA
TR
OU
P
CO
UN
TY
F
IR
E
ST
AT
IO
N #1
WAG
8/18/2026 26-00013
0%
C
ON
ST
RU
CT
IO
N
DO
CU
ME
NT
S
WAG
TROUP COUNTY FIRE STATION #1
@ BURKES CHAPEL ROAD
TROUP COUNTY, GEORGIA
100% CONSTRUCTION DOCUMENTS
8/18/2026
2WR # 26-00013
T1.1 COVER SHEET
T1.2 GENERAL NOTES &
LEGENDS
LS1.1 LIFE SAFETY PLAN
GENERAL ARCHITECTURAL STRUCTURAL MECHANICAL / PLUMBING ELECTRICAL
OWNER REPRESENTATIVE
JAMES (JAY) ANDERSON
ASSISTANT COUNTY MANAGER
TROUP COUNTY BOARD OF COMMISSIONERS
100 RIDLEY AVENUE
LAGRANGE, GA 30240
P (706) 298-3792
MOBILE: (706) 298-1883
ARCHITECT
ALEX GRIGGS
2WR + PARTNERS
11 9TH STREET, SUITE 120
COLUMBUS, GA 31901
P (706) 571-6923
E: ALEX@2WRARCH.COM
MEP ENGINEER
MARK LEVERETT
PEACH ENGINEERING
1214 1ST AVE,
COLUMBUS, GA 31901
P (706) 596-1840
E: MLEVERETT@PEACHENGINEERING.COM
STRUCTURAL ENGINEER
MATT PEARSON
WRIGHT ENGINEERING
7413 WHITESVILLE RD STE 800
COLUMBUS, GA 31904
P (706) 507-0232
E: MPEARSON@WRIGHTENG.NET
CIVIL ENGINEER
SCOTT HARRIS
HARRIS-GRAY, LLC
824 3RD AVENUE,
WEST POINT, GA 31833
P (706) 645-5885
E: SHARRIS@HARRIS-GRAY.COM
SP1.2 SITE DETAILS
A1.1 2-BAY FLOOR PLAN
A1.1A 3-BAY FLOOR PLAN
A2.1 ENLARGED TOILET PLANS AND
DETAILS
A3.1 ROOF PLAN
A3.2 ROOF DETAILS
A4.1 EXTERIOR ELEVATIONS
A5.1 BUILDING SECTIONS
A6.1 WALL SECTIONS
A6.2 WALL SECTIONS
A6.3 WALL SECTIONS
A7.1 SECTION DETAILS
A7.2 SECTION / PLAN DETAILS
A8.1 DOORS, SIGNS & WINDOW
SCHEDULES & DETAILS
A8.2 DOOR & WINDOW DETAILS
A9.1 REFLECTED CEILING PLAN
A10.1 FINISH PLAN
A12.1 MILLWORK PLANS & DETAILS
A12.2 MILLWORK DETAILS
S0.1 GENERAL NOTES
S0.2 SPECIAL INSPECTIONS
S1.1 FOUNDATION & SLAB PLANS
S1.1A FOUNDATION & SLAB PLANS (ALTERNATE)
S2.1 ROOF FRAMING PLAN
S2.1A ROOF FRAMING PLAN (ALTERNATE)
S4.0 GENERAL BLOCK DETAILS
S4.1 FOUNDATION SECTIONS
S5.1 FRAMING SECTIONS
S5.2 FRAMING SECTIONS
M1.1 FLOOR PLAN W/ ALT. 1 MECHANICAL
M1.1A FLOOR PLAN ALTERNATES MECHANICAL
M2.0 MECHANICAL SCHEDULES AND DETAILS
FS1.0 FLOOR PLANS - SPRINKLER
P1.0 FLOOR PLAN - PLUMBING - WASTE & VENT PIPING
P1.1A FLOOR PLAN ALTERNATES - WASTE & VENT PIPING
P1.2 FLOOR PLAN - PLUMBING - COLD & HOT WATER PIPING
P1.3 FLOOR PLAN ALTERNATES - COLD & HOT WATER PIPING
P1.4 FLOOR PLAN - PLUMBING - LP GAS PIPING (10/22/25)
P1.5 FLOOR PLAN - PLUMBING - LP GAS PIPING (10/22/25)
P2.0 PLUMBING SCHEDULE & DETAILS
E1.0 FLOOR PLAN W/ ALT. 1 LIGHTING
E1.1 FLOOR PLAN W/ ALT. 2-4 LIGHTING
E2.0 FLOOR PLAN W/ ALT. 1 POWER & AUXILIARIES
E2.1 FLOOR PLAN W/ ALT. 2-4 POWER & AUXILIARIES
E3.0 FLOOR PLAN W/ ALT. 1 FIRE ALARM
E3.1 FLOOR PLAN W/ ALT. 2-4 FIRE ALARM
E4.0 DETAILS
CIVIL
01 COVER SHEET
02 GSWCC CHECKLIST & INFO
03 CONSTRUCTION NOTES
04 EXISTING CONDITIONS
05 SITE PLAN
06 GRADING & DRAINAGE PLAN
07 STORM PROFILES & DETAILS
08 STORM DETAILS
09 UTILITY PLAN
10 E.S.& P.C. NOTES
11 E.S.& P.C. NOTES
12 E.S.& P.C. PLAN INITIAL PHASE
13 E.S.& P.C. PLAN INTERMEDIATE PHASE
14 E.S.& P.C. PLAN FINAL PHASE
15 GSWCC DETAILS
16 GSWCC DETAILS
17 CONSTRUCTION DETAILS
18 CONSTRUCTION DETAILS
19 CONSTRUCTION DETAILS
CIVIL DOCUMENTS PREPARED BY OTHERS UNDER
SEPARATE CONTRACT
(TO BE INCLUDED IN BASE BID)
REVISED 26-0211
No. Date Description
A101
SIM
Room name
150 SF
SA-1
/1 A101
1 View Name 1/8" = 1'-0"A101
W25
A
10'-0" A
A1.1
A101
SIM
R ef
EXTERIOR ELEVATION
DRAWING TITLE
DRAWING NUMBER
DRAWING SCALE
SHEET NUMBER
SIM = SIMILAR TO VIEW
OPP = MIRRORED VIEW
SECTION
VIEW DIRECTION
COLUMN GRIDLINE
ELEVATION POINT10'-3"
DRAWING REFERENCE
DRAWING NUMBER
SHEET NUMBER
ENLARGED DETAIL
INTERIOR ELEVATION
CENTER LINE
NORTH ARROW
SLOPE DOWN
DIRECTION
ROOM LABEL
AREA
ROOM NUMBER
ROOM NAME
CEILING LABEL
KEYED NOTE
TOILET ACCESSORY
REVISION
WALL TYPE
WINDOW TYPE
HOLLOW METAL
FRAME TYPE
101A DOOR NUMBER
CEILING TYPE
HEIGHT AFF
4:12
DRAINAGE SLOPE
A101
SIM
DN
DEMOLISHED
EXISTING
NEW STUD PARTITION
1.
2.
NOTE:
SEE WALL TYPES FOR DETAILED DESIGNATIONS.
SEE LIFE SAFETY PLAN FOR FIRE SEPARATIONS.
NEW MASONRY PARTITION
SMOKE PARTITION
1 HR RATED PARTITION
2 HR RATED PARTITION
3 HR RATED PARTITION
GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
NEW CONSTRUCTION
ALL WOOD IN CONTACT WITH MASONRY OR CONCRETE SHALL BE PRESSURE TREATED WITH AN
APPROVED PRESERVATIVE.
ALL INSULATIONS NOTED ON PLANS SHALL BE NONCOMBUSTIBLE AND MAINTAIN THERMAL AND MOISTURE
PROTECTION AS NOTED IN THE SPECIFICATIONS.
CONTRACTOR SHALL COORDINATE THE INSTALLATION OF THE VARIOUS TRADE ITEMS WITHIN THE SPACE ABOVE ALL CEILINGS (INCLUDING, BUT NOT LIMITED TO: STRUCTURAL MEMBERS, MECHANICAL DUCTS AND INSULATION, CONDUITS, RACEWAYS, SPRINKLER SYSTEM, LIGHT FIXTURES, CEILING SYSTEMS, AND ANY SPECIAL STRUCTURAL SUPPORTS REQUIRED) AND SHALL BE RESPONSIBLE FOR MAINTAINING THE FINISH CEILING HEIGHT ABOVE THE FINISH FLOOR INDICATED IN THE DRAWINGS AND THE FINISH SCHEDULE. (CEILING HEIGHT DIMENSIONS ARE TO THE FINISH SURFACE OF CEILING.) CONTRACTOR SHALL NOTIFY ARCHITECT IN WRITING OF ANY CONFLICTS PRIOR TO PROCEEDING WITH THE WORK.
ACCESS PANELS SHALL BE PROVIDED AND INSTALLED WHEREVER REQUIRED BY BUILDING CODE OR FOR THE PROPER OPERATION OR MAINTENANCE OF MECHANICAL OR ELECTRICAL EQUIPMENT, WHETHER OR NOT INDICATED ON THE DRAWINGS. CONTRACTOR SHALL COORDINATE SIZE, LOCATION, AND TYPE OF
ACCESS PANEL WITH OTHER CONTRACTORS' WORK AND RECEIVE APPROVAL OF THE ARCHITECT.
ACCESS PANEL SHALL BE AS SPECIFIED. NO ACCESS PANEL SHALL BE LOCATED, FRAMED OR INSTALLED
WITHOUT THE EXPRESSED APPROVAL OF THE ARCHITECT.
ALL DUCT PENETRATIONS THROUGH PARTITIONS AND CEILINGS SHALL BE PROVIDED WITH NECESSARY FRAMES AND BRACING AROUND THE OPENING AND SHALL BE PROVIDED WITH AUTOMATIC FIRE DAMPERS
AS REQUIRED BY THE BUILDING DEPARTMENT FOR FIRE-RATED PENETRATIONS.
HORIZONTAL JOINT REINFORCEMENT IS GENERALLY NOT SHOWN FOR REASONS OF CLARITY. TIES AND ANCHORS SPECIFICALLY NOTED ON DETAILS ARE IN ADDITION TO HORIZONTAL JOINT REINFORCEMENT
UNLESS SPECIFICALLY NOTED OTHERWISE.
SIZE OF MECHANICAL AND ELECTRICAL EQUIPMENT PADS AND BASES ARE APPROXIMATE ONLY.
CONTRACTOR SHALL VERIFY DIMENSIONS WITH RESPECTIVE EQUIPMENT MANUFACTURER.
CONTRACTOR SHALL PROVIDE AND INSTALL ALL STIFFENERS, BRACING, BACK-UP PLATES, BLOCKING, AND SUPPORTING BRACKETS REQUIRED FOR THE INSTALLATION OF ALL CASEWORK, TOILET
ACCESSORIES AND ALL FLOOR-MOUNTED OR SUSPENDED MECHANICAL AND ELECTRICAL EQUIPMENT.
ALL DISSIMILAR METALLIC MATERIALS SHALL BE EFFECTIVELY ISOLATED FROM EACH OTHER TO PREVENT
GALVANIC ACTION.
FILLED CMU CELLS ON ARCHITECTURAL DRAWINGS ARE IN ADDITION TO THOSE SHOWN ON STRUCTURAL
DRAWINGS AND SHALL BE REINFORCED AS INDICATED THEREIN.
1.
2.
3.
4.
5.
6.
FIRE RATED CONSTRUCTION
ALL DUCT PENETRATIONS THROUGH PARTITIONS AND CEILINGS SHALL BE PROVIDED WITH NECESSARY
FRAMES AND BRACING AROUND THE OPENING.
DUCT PENETRATIONS THROUGH FIRE RATED PARTITIONS SHALL BE PROVIDED WITH AUTOMATIC FIRE DAMPERS AS REQUIRED BY CURRENT FIRE CODE AND THE LOCAL AUTHORITY HAVING JURISDICTION.
THE CONTRACTOR SHALL PROVIDE A COMPLETE FIRE SAFE BARRIER SEALING ALL AIR SPACES AND
OPENINGS IN FIRE PROTECTED WALLS.
ALL FIRE AND/OR SMOKE BARRIERS OR WALLS SHALL BE EFFECTIVELY AND PERMENANTLY IDENTIFIED WITH SIGNS OR STENCILING ABOVE A DECORATIVE CEILING AND/OR IN CONCEALED SPACES WITH LETTERS A MINIMUM OF (2) INCHES HIGH ON A CONTRASTING BACKGROUND SPACED A MAXIMUM OF (12) FEET ON CENTER WITH A MINIMUM OF (1) PER WALL OR BARRIER IN ACCORDANCE WITH MODIFICATIONS OF THE 2006 STANDARD FIRE PREVENTION CODE, 120-3-3, CHAPTER 5 OF THE RULES AND REGULATIONS OF THE FIRE SAFETY COMMISIONER. THE HOURLY RATING SHALL BE INCLUDED ON ALL RATED BARRIERS
OR WALLS IN FORMAT: "-- HOUR FIRE AND SMOKE BARRIER. PROTECT ALL OPENINGS."
ALL PENETRATIONS THROUGH FIRE RATED SYSTEMS (WALLS, FLOORS, CEILINGS, ETC.) SHALL BE SEALED WITH 3M BRAND FIRE BARRIER CAULK CP25N/S NO-SAG OR CP25S/L SELF-LEVELING OR EQUAL. DEPTH OF CAULK SHALL BE AS REQUIRED TO ACHIEVE THE REQUIRED FIRE RATING FOR THAT SYSTEM. PROVIDE BACKER ROD AS NECESSARY FOR BACK UP MATERIAL. NOTE BOTH SIDES OF RATED SYSTEMS SHALL BE
CAULKED.
FIRESTOPPING REQUIREMENT: PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALL BE SEALED
WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOT GASES WHEN
SUBJECTED TO THE REQUIREMENTS OF TEST STANDARD SPECIFICS FOR FIRESTOPS, ASTM E814.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
USE OF CONTRACT DOCUMENTS
DRAWINGS AND SPECIFICATIONS OF ALL DISCIPLINES INCLUDED HEREIN CONSTITUTE THE FULL SCOPE OF THIS PROJECT. THESE DOCUMENTS ARE INTENDED TO ESTABLISH THE FULL CONTRACTUAL OBLIGATION OF THE GENERAL CONTRACTOR TO COMPLETE THE WORK SHOWN AND SPECIFIED. IT SHALL BE THE GENERAL CONTRACTOR'S ULTIMATE RESPONSIBILITY TO COORDINATE THE PROPOSALS AND WORK OF
ALL TRADES.
ARCHITECTURAL AND ENGINEERING DRAWINGS ARE COMPLIMENTARY. ITEMS INDICATED ON
ARCHITECTURAL DRAWINGS SHALL BE PROVIDED WHETHER OR NOT THEY ARE INDICATED ON AND/OR
COORDINATED WITH CONSULTANTS' DRAWINGS. ANY CONFLICTS BETWEEN ARCHITECTURAL AND
ENGINEERING WORK SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO
PROCEEDING WITH THE WORK.
CONTRACTORS SHALL COORDINATE THE SCOPE OF THEIR WORK WITH THE CONTRACT DOCUMENTS.
PLANS AND SPECIFICATIONS SHALL NOT BE SEPARATED. NO CLAIMS FOR EXTRAS WILL BE CONSIDERED
DUE TO SUB-CONTRACTOR NOT RELATING SCOPE OF WORK TO CONTRACT DOCUMENTS.
ALL WORK IS TO BE IN STRICT COMPLIANCE WITH ALL STATE LAWS AND CODES WHICH APPLY TO THIS
USE AND TO GENERALLY ACCEPTED CONSTRUCTION TRADE PRACTICES.
THE ARCHITECT WAIVES ANY AND ALL RESPONSIBILITY AND LIABILITY FOR PROBLEMS WHICH ARISE FROM FAILURE TO FOLLOW THESE PLANS, SPECIFICATIONS AND THE DESIGN INTENT THEY CONVEY, OR FOR
PROBLEMS WHICH ARISE FROM OTHERS' FAILURE TO OBTAIN AND/OR FOLLOW THE DESIGN
PROFESSIONAL'S GUIDANCE WITH RESPECT TO ANY ERRORS, OMISSIONS, INCONSISTENCIES,
AMBIGUITIES OR CONFLICTS WHICH ARE ALLEGED.
SECTIONS AND DETAILS CONTAINED IN THE CONTRACT DOCUMENTS ARE TYPICAL. CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPONENTS AND/OR CONSTRUCTION NOTED OR INDICATED IN OTHER SIMILAR AREAS OF THE PROJECT IF THEY CAN BE REASONABLY INFERRED TO BE A PART OF THE
ASSEMBLY BASED ON OTHER SIMILAR SECTIONS AND DETAILS CONTAINED IN THE CONTRACT
DOCUMENTS.
NOT ALL COMPONENTS IN EACH DETAIL MAY BE SPECIFICALLY CALLED OUT ON THAT PARTICULAR ARCHITECTURAL DETAIL. CONTRACTOR SHALL STILL BE RESPONSIBLE FOR PROVIDING THESE ITEMS IF THEY CAN BE REASONABLY INFERRED TO BE A PART OF THE ASSEMBLY BASED ON OTHER SIMILAR
DETAILS CONTAINED WITHIN THE CONTRACT DOCUMENTS.
DO NOT SCALE ANY DRAWINGS TO DETERMINE DIMENSIONS. RELY ONLY ON FIELD MEASUREMENT AND
WRITTEN DIMENSIONS FOR NEW WORK.
ALL DIMENSIONS ARE FROM FACE OF STUD OR FACE OF MASONRY (UNO).
ALL DIMENSIONS AND CONDITIONS SHALL BE FIELD VERIFIED PRIOR TO PROCEEDING WITH THE WORK OF THIS CONTRACT. ANY DISCREPANCIES BETWEEN FIELD CONDITIONS AND CONTRACT DOCUMENTS SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE
WORK.
"SCALE" INDICATED ON THE ELEVATIONS MAY NOT BE REPRESENTATIVE OF A SCALED DRAWING. THE
CONTRACTOR SHALL MAKE FIELD MEASUREMENTS AS REQUIRED TO ASCERTAIN THE EXTENT AND
QUANTITY OF WORK TO BE PERFORMED.
SUBCONTRACTORS SHALL INVESTIGATE ALL EXISTING CONDITIONS ASSOCIATED WITH THEIR SCOPE OF WORK AND VERIFY REQ'D QUANTITIES OF MATERIALS PRIOR TO PROVIDING A BID TO THE GENERAL CONTRACTOR. NO CHANGE ORDERS WILL BE GRANTED FOR ADDITIONAL WORK REQ'D WHICH IS EVIDENT
FROM FIELD INVESTIGATION AND IS CONSISTENT WITH THE REQUIREMENTS OF THE CONTRACT
DOCUMENTS.
SUBCONTRACTORS SHALL VERIFY REQ'D QUANTITIES OF MATERIALS WITH THE GENERAL CONTRACTOR PRIOR TO PURCHASING. NO CHANGE ORDERS WILL BE GRANTED FOR ADDITIONAL QUANTITIES OR DETAIL WORK REQ'D WHICH IS EVIDENT FROM FIELD CONDITIONS AND IS CONSISTENT WITH THE REQUIREMENTS
OF THE CONTRACT DOCUMENTS.
ANY WORK INSTALLED IN CONFLICT WITH THE CONTRACT DOCUMENTS SHALL BE CORRECTED BY THE CONTRACTOR AT HIS EXPENSE AND AT NO ADDITIONAL EXPENSE TO THE OWNER, ARCHITECT, OR
CONSULTANTS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
CONTRACTOR RESPONSIBILITY
THE CONTRACTOR SHALL PROVIDE ALL NECESSARY PERMITS AND INSPECTIONS
CONTRACTOR AND SUBCONTRACTORS SHALL BE RESPONSIBLE FOR OBTAINING AND PAYING FOR ALL
PERMITS AND FEES REQUIRED, NOT NORMALLY COVERED BY THE BUILDING PERMIT.
THE CONTRACTOR SHALL FILE ALL NECESSARY CERTIFICATES OF INSURANCE, PAY ALL FEES, AND
OBTAIN ANY AND ALL BONDS REQUIRED BY ANY AGENCY IN ORDER TO DO THE WORK HEREIN
DESCRIBED.
THE CONTRACTOR SHALL VERIFY THE LOCATION OF ALL EXISTING UTILITIES BELOW GRADE AND
RELATED SERVICE CONNECTIONS WITH THE RESPECTIVE UTILITY COMPANIES.
THE CONTRACTOR SHALL REMOVE FROM THE SITE AND DISPOSE OF ALL TRASH, DEBRIS AND
CONSTRUCTION MATERIALS DUE TO CONSTRUCTION OR DEMOLITION PRIOR TO COMPLETION OF THE WORK. THE CONTRACTOR SHALL LEAVE THE SITE IN A CONDITION EQUAL TO OR BETTER THAN IT WAS BEFORE COMMENCEMENT OF WORK ON THIS CONTRACT. THE CONTRACTOR SHALL ALSO ENSURE THAT TRASH AND DEBRIS ARE NOT BLOWN OR SPREAD ON OR OFF SITE DURING PERFORMANCE OF THE WORK.
THE CONTRACTOR SHALL RESTRICT ACCESS TO THE ROOF TO ONLY THOSE FORCES NEEDING ACCESS
TO THE ROOF IN ORDER TO COMPLETE THEIR WORK. FINISHED ROOF SURFACES ARE TO BE
PROTECTED AT ALL TIMES.
THE CONTRACTOR SHALL LIMIT HIS WORK AND FORCES UNDER HIS CONTROL TO ONLY THOSE AREAS OF
WORK AS DEFINED BY THE CONTRACT DOCUMENTS.
THE CONTRACTOR SHALL PROVIDE CRAFTSMAN-LIKE INSTALLATION AND FINISH OF ALL EXPOSED
CONSTRUCTION SYSTEMS.
PAINT ALL EXPOSED SCHEDULED PIPING, CONDUIT AND MECHANICAL EQUIPMENT IN AREAS NOTED TO BE
PAINTED.
THE CONTRACTOR SHALL REPAIR AT HIS EXPENSE DAMAGE TO ANY FINISHES TO REMAIN WHICH ARE
INCURRED DURING WORK ON THIS CONTRACT.
THE CONTRACTOR SHALL PROVIDE ADEQUATE WEATHER PROTECTION FOR THE BUILDING AND ITS CONTENTS DURING THE COURSE OF THE WORK. ALL OPENINGS IN ANY WALL OR ROOF SHALL BE
PROTECTED FROM ALL FORMS OF WEATHER OR WATER.
1.
2.
SITE WORK
SOD, LANDSCAPING, SIDEWALKS, CURBS OR ANY OTHER SITE APPURTENANCES DAMAGED DURING DEMOLITION OR CONSTRUCTION SHALL BE REPLACED OR REPAIRED TO PRE-CONSTRUCTION CONDITIONS
AT THE CONTRACTOR'S EXPENSE PRIOR TO COMPLETION OF THIS PROJECT.
WHERE CONC. WALKWAYS ABUT EXTERIOR MASONRY WALLS, CONTRACTOR SHALL ADJUST THE HEIGHT OF WEEPS AND BASE FLASHING AS NECESSARY TO PROVIDE CAVITY DRAINAGE ABOVE ADJACENT
SURFACES, TYP.
1.
2.
3.
4.
5.
6.
7.
8.
WALL TYPES ARE GENERIC IN NATURE AND DO NOT SHOW
EVERY POSSIBLE CONFIGURATION OR CONDITION. REFER
TO PLANS, ELEVATIONS, SECTIONS, AND DETAILS FOR
SPECIFIC DESIGN INFORMATION AND ELEMENTS WHICH
MAY ALTER INFORMATION CONTAINED IN WALL TYPES.
NEW EXTERIOR WALLS ARE DETAILED IN BUILDING AND
WALL SECTIONS.
SEE STRUCTURAL PLANS FOR ADDITIONAL FRAMING
INFORMATION AND REINFORCING.
COORDINATE SEALING OF PENETRATIONS AT RATED
WALLS WITH MEP DRAWINGS AND SPECIFICATIONS.
REFER TO NOTED UL ASSEMBLY FOR ADDITIONAL
CONSTRUCTION INFORMATION.
ALL FIRE WALLS, SMOKE WALLS, AND WALLS REQUIRED
TO HAVE PROTECTED OPENINGS OR PENETRATIONS ARE
TO BE PERMANENTLY STENCIL LABELED ACCORDING TO
FIRE CODE REQUIREMENTS IN ACCESSIBLE CONCEALED
FLOOR, CEILING OR ATTIC SPACES.
REFER TO LIFE SAFETY PLANS FOR CONTINUITY OF ALL
RATED PARTITIONS.
A FINISH OR FIRE RATING INDICATION ON A WALL SHALL
MEAN THE ENTIRE LENGTH IS TO BE FINISHED OR FIRE
RATED.
WALL TYPE GENERAL NOTES
M W U
2 1 5/8"
1x
(FURRING
STRIPS)
3 2 1/2" 2x3 -
4 3 5/8" 2x4 4"
6 6" 2x6 6"
8 8" 2x8 8"
10 10" 2x10 10"
12 12" 2x12 12"
METAL
STUD
WOOD
STUD CMU BRICK CONCRETE
B C
- N
O M
IN
AL
C O
R E
SI
ZE
CORE COMPOSITION
(HAT
CHANNEL)
2x2
4"
6"
8"
10"
12"
1 WYTHE
2 WYTHE
3 WYTHE
WALL TYPE NOMINAL SIZING
WALL TAG LEGEND
W 4 F-2
CORE COMPOSITION
(SEE SIZING CHART)
SUBTYPE
NOMINAL CORE SIZE
(SEE SIZING CHART)
TYPICAL:
A FURRING
B NON RATED PARTITION
C NON RATED FULL-HEIGHT
D-Z PROJECT SPECIFIC
F-(HOURS) FIRE RATED (SEE DETAILS)
S-(HOURS) SMOKE RATED (SEE DETAILS)
X-(STC) SOUND RATED (SEE DETAILS)
SEE WALL TYPE DETAILS FOR WALL ASSEMBLIES USED IN THIS
PROJECT AND ADDITIONAL INFORMATION.
CMU RUNNING BOND - REFER TO
STRUCTURAL DRAWINGS AND
SPECIFICATIONS FOR
REINFORCING AND ADDTIONAL
INFORMATION INCLUDING
THICKENED SLABS OR STRIP
FOOTINGS
UNIT MASONRY WALL - BOTH FINISH SIDES
BASE AS SPECIFIED IN
FINISH PLANS
U#F-2
TOP OF CMU
FINISH CEILING AS
SPECIFIED IN RCP
UL U914 : 2 HOUR MINIMUM FIRE RATING
50-59 STC RATING
FIRE SEAL BASE OF WALL
FIRE CAULK ALL
PENETRATIONS.
CMU WALLU#A
8 x 8 x 16 CMU. SEE STRUCTURAL
FOR REINFORCING
USE CLASS D-2 FIRE RATED UNITS
AT ALL RATED LOCATIONS (AS
SHOWN ON LS1.1)
TOP OF CMU
WOOD WALL - STRUCTURAL, UL RATEDW#F-2
BOT. OF STRUCTURE/DECK
(2) LAYERS 5/8" GWB
FINISH CEILING AS
SPECIFIED IN RCP
EXTEND SHEATHING TO
STRUCTURE AND SOUND SEAL
ALL EDGES.
• UL U301 : 2 - HR MINIMUM FIRE RATING
R-13 BATT INULATION
CONTINUOUS FIRE SEAL
AT BASE OF WALL
2 x WOOD STUDS @ 16" O.C. - SEE PLAN
FOR SIZE
CMU RUNNING BOND - REFER TO
STRUCTURAL DRAWINGS AND
SPECIFICATIONS FOR
REINFORCING AND ADDTIONAL
INFORMATION INCLUDING
THICKENED SLABS OR STRIP
FOOTINGS
UNIT MASONRY WALL - BOTH FINISH SIDES
BASE AS SPECIFIED IN
FINISH PLANS
U#F-1
TOP OF CMU
FINISH CEILING AS
SPECIFIED IN RCP
UL U913 : 1 HOUR MINIMUM FIRE RATING
50-59 STC RATING
FIRE SEAL BASE OF WALL
FIRE CAULK ALL
PENETRATIONS.
BOND BEAM, SEE
STRUCTURAL DRAWINGS FOR
REINFORCEMENT
BOND BEAM, SEE
STRUCTURAL DRAWINGS FOR
REINFORCEMENT
BOND BEAM, SEE
STRUCTURAL DRAWINGS FOR
REINFORCEMENT
CMU RUNNING BOND - REFER TO
STRUCTURAL DRAWINGS AND
SPECIFICATIONS FOR
REINFORCING AND ADDTIONAL
INFORMATION INCLUDING
THICKENED SLABS OR STRIP
FOOTINGS
FINISH CEILING AS
SPECIFIED IN RCP
USE CLASS D-2 FIRE RATED UNITS
AT ALL RATED LOCATIONS (AS
SHOWN ON LS1.1)
ABOVE (2) HR RATED CMU - SEE
LIFE SAFETY PLAN AND BUILDING
SECTIONS FOR SPECIFIC LOCATION
Project No.:
Date:
Drawn by:
Checked by:
Revisions:
PR
IN
TE
D:
FI
LE
P
AT
H:
11 Ninth Street, Suite 120 Columbus, GA 31901 P. (706) 571-6923
8/
/2
4:
:3
PM
C :\U se rs
\A le xG rig gs _r m ud ak 7\
Ap pD at a\
Lo ca l\A ut od es k\ R ev it\
Au to de sk
R ev it
\C ol la bo ra tio nC ac he
\Q 2G
2D
JC
C L7
R D
H U
\3 e7
8-
5e db
-4
2-a3
-8
7d
2\
9a
7e 2b
-1 d6 c-a6 -a b7 c-f1 b5
.rv t
T1.2
GENERAL
NOTES &
LEGENDS
B
U R
KE
S
C H
AP
EL
R O
AD
TR
O U
P C
O U
N
TY
, G
EO
R G
IA
TR
OU
P
CO
UN
TY
F
IR
E
ST
AT
IO
N #1
WAG
8/18/2026 26-00013
0%
C
ON
ST
RU
CT
IO
N
DO
CU
ME
NT
S
EF
@ At ABV Above ACT Acoustic Ceiling Tile ADJ Adjacent AFF Above Finished Floor ALT Alternate ALUM Aluminum APPROX Approximately ARCH Architect/Architectural AVG Average BD Board BLDG Building BLKG Blocking B.O. Bottom of BOS Bottom of Step BOT Bottom BSMT Basement CAB Cabinet CF Cubic Feet CG Corner Guard CIP Cast In Place CJ Control Joint
Construction Joint CL Center Line CLG Ceiling CLR Clear CM Construction Manager CMU Cement Masonry Unit COL Column CONC Concrete CONST Construction CONT Continuous COORD Coordinate CPT Carpet CT Ceramic Tile CTR Center D Deep or Depth DBL Double DEMO Demolish DEPT Department DET Detail DIA Diameter DIAG Diagonal DIM Dimension DN Down DWG Drawing EA Each EJ Expansion Joint EL Elevation ELEC Electric or Electrical ELEV Elevator ENG Engineer EQ Equal EQUIP Equipment EXIST Existing EW Equal Width EXT Exterior FA Fire Alarm FDN Foundation FEC Fire Extinguisher Cab FFE Finished Floor Elevation FIN Finish FLR Floor FT Foot or Feet FUR Furred or Furring FURN Furnished GA Gauge GALV Galvanize(d) GC General Contractor GEN General GWB Gypsum Wall Board GYP Gypsum HC Hollow Core H/C Handicap Accessible HDW Hardware HM Hollow Metal HOR Horizontal HR Hour H Height HVAC Heating, Vent. & A/C IN Inch INCL Included/ing INFO Information INSUL Insulation INT Interior JC Janitor’s Closet JST Joist JT Joint LAM Laminate LAV Lavatory LBS Pounds LF Linear Feet LOC Location MACH Machine MAINT Maintenance MAT Material MAX Maximum MECH Mechanical MFR Manufacturer MIN Minimum or Minute MISC Miscellaneous M.O. Masonry Opening MTD Mounted MTL Metal N/A Not Applicable N.I.C. Not in Contract NOM Nominal NO. Number NTS Not to Scale O.C. On Center OD Outside Diameter OFCI Owner Furnished
Contractor Installed OPP Opposite OZ Ounce PERF Perforated PERIM Perimeter PH Partial Height PLAM Plastic Laminate PLUM Plumbing PLWD Plywood PREFAB Prefabricated PSF Pounds Per Square Foot PSI Pounds Per Square Inch PT Pressure Treated PTD Painted PVC Poly Vinyl Chloride QTY Quantity QT Quarry Tile R Radius RD Roof Drain, Road REBAR Reinforcing Bar REF Refrigerator REINF Reinforced REQ'D Required REV Revision RM Room R.O. Rough Opening SC Solid Core SCHED Schedule SEC Section SF Square Feet SHT Sheet SIM Similar SPEC Specification SS Stainless Steel SQ Square STC Sound Transmission Class STD Standard STOR Storage STRUCT Structural SV Sheet Vinyl SYS System T&G Tongue and Groove TEL Telephone THRU Through THK Thick T.O.S. Top of Steel TLT Toilet TYP Typical U.N.O. Unless Noted
Otherwise UTIL Utility VAR Variable VCT Vinyl Composite Tile VERT Vertical VEST Vestibule V.I.F. Verify in Field VOL Volume VWC Vinyl Wall Covering W/ With W/O With Out WC Water Closet WD Wood WNDW Window WF Wide Flange WT Weight WWF Welded Wire Fabric
ABBREVIATIONS ARCHITECTURAL SYMBOLS
WALL LEGEND
GC NOTE:
THESE DOCUMENTS WERE ORIGINALLY PREPARED FOR A PROTOTYPICAL FIRE STATION WITHOUT AN
EXACT SITE.
THESE DOCUMENTS CONTAIN CIVIL DOCUMENTS FOR THIS PROJECT. PROJECT NORTH MAY VARY FROM
CIVIL DOCUMENTS.
PLEASE NOTE REFERENCES TO ALTERNATES THROUGHOUT THE SET, SPECIFICALLY IN THE STRUCTURAL, PLUMBING, MECHANICAL AND ELECTRICAL SETS. AS A PART OF THE BURKES CHAPEL ROAD SITE THERE IS
ONLY ONE ALTERNATE TO BE GIVEN.
ADD ALTERNATE 1 - WIDEN THE APPARATUS BAY TO ACCOMMODATE A THIRD BAY - SEE PLANS ON SHEET A1.1A AND OTHER STRUCTURAL, MECHANICAL, ELECTRICAL AND PLUMBING DOCUMENTS FOR THIS
ALTERNATE.
No. Date Description
BID NOTES:
TROUP COUNTY WILL BE RESPONSIBLE FOR SUBMITTING THE PLANS TO THE LOCAL FIRE MARSHAL AND
THE BUILDING INSPECTIONS AND CODE DEPARTMENT
THE GENERAL CONTRACTOR WILL NOT BE RESPONSIBLE FOR PAYING PERMIT FEES
TROUP COUNTY WILL PAY ALL WATER AND SEWER TAP FEES
TROUP COUNTY WILL PROVIDE AND INSTALL THE WATER METER
THERE IS NO SPEAKER/PAGING SYSTEM WITH ASSOCIATED WIRING, DEVICES, OR EQUIPMENT IN THE
GENERAL CONTRACTOR'S BASE CONTRACT
SEE SPECIFICATIONS SECTION 012100 - ALLOWANCES FOR GC SUPPLIED APPLIANCES
LANDSCAPING WILL BE FURNISHED AND INSTALLED BY THE OWNER - GC TO PROVIDE PERMANENT
GRASSING, ETC. PER ES&PC PLAN FINAL PHASE
A SUBSOIL INVESTIGATION REPORT (GEOTECH OR SOILS REPORT) IS NOT AVAILABLE AT THIS TIME;
ASSUME FAVORABLE SOIL CONDITIONS IN THE BASE BID
THE OWNER WILL BE PROVIDING ALL SIGNAGE FOR THE GC TO INSTALL, WITH THE EXCEPTION OF THE 48"
NUMERAL "1" BEING PROVIDED UNDER THE BASE BID.
FOR CLARITY, THE GENERAL CONTRACTOR SHALL CARRY THE COST OF THE EXHAUST REMOVAL SYSTEM, MATERIAL AND LABOR, PROVIDED BY THE OWNER'S VENDOR, MAGNEGRIP.
DELETE THE VOICE EVACUATION SYSTEM AS PART OF THE FIRE ALARM SYSTEM.
HB
HB
H B
HB
HB
HB
1.
2.
3.
4.
5.
6.
7.
8.
OCCUPANT LOAD OF ALL SPACES CALCULATED PER TABLE 1004.5 (IBC)
ALL SPACES NOT PROVIDED WITH A SPATIAL USE TAG OR OCCUPANT LOAD ARE
CONSIDERED INCIDENTAL USE AND/OR ARE NOT CONSIDERED NORMALLY
OCCUPIED SPACES.
ALL EXIT AND EXIT ACCESS DOORS PROVIDE 34" OF CLEAR EXIT WIDTH IF SINGLE
LEAF AND 68" IF DOUBLE LEAF UNLESS OTHERWISE NOTED. AS SUCH, EGRESS
CAPACITIES ARE 170 AND 340 OCCUPANTS RESPECTIVELY PER IBC SECTION 1005.
WHERE NON-FIRE RATED PARTITIONS INTERSECT FIRE RATED PARTITIONS THE
FIRE RATED PARTITION SHALL REMAIN INTACT AND CONTINUOUS.
INSTALL ALL SPECIFIED FIRE EXTINGUISHERS AND CABINETS WHERE REQUIRED
BY APPLICABLE CODES. PROVIDE AND INSTALL ANY ADDITIONAL CODE REQUIRED
FIRE EXTINGUISHERS AND CABINETS WHERE DIRECTED BY CODE OFFICIALS
AND/OR ARCHITECT. COORDINATE LOCATION WITH ARCHITECT PRIOR TO
INSTALLATION.
COORDINATE LOCATIONS OF ALL FIRE PULL STATIONS, EXIT, LIGHTS, STANDPIPES,
STROBES, AND EMERGENCY LIGHTING WITH ARCHITECT UNLESS OTHERWISE
INDICATED. ALL STROBE LIGHTS SHALL BE CEILING MOUNTED TYPE WHERE EVER
POSSIBLE. ANY WALL-MOUNTED STROBES SHALL BE MOUNTED AT 80" AFF
(MINIMUM) TO BOTTOM OF STROBE LIGHT, UNLESS OTHERWISE NOTED (UON).
ALL SPRINKLER HEADS OCCURRING IN ACOUSTICAL TILE TO BE CENTERED IN
ACOUSTICAL TILE UNLESS OTHERWISE NOTED. ALL SPRINKLER HEADS
OCCURRING IN GYPSUM BOARD CEILING SHALL BE LOCATED WITH RELATION TO
LIGHT FIXTURES. GENERAL CONTRACTOR TO SUBMIT SPRINKLER HEAD LOCATION
SHOP DRAWING TO: 1) FIRE MARSHALL FOR APPROVAL AND; 2) ARCHITECT FOR
COORDINATION PRIOR TO INSTALLATION OF SPRINKLERS.
INSTALL ALL SPECIFIED EXIT SIGNS IN LOCATIONS APPROVED BY LOCAL
JURISDICTIONS. PROVIDE AND INSTALL ANY ADDITIONAL EXIT SIGNS WHERE
DIRECTED BY CODE OFFICIALS. COORDINATE LOCATIONS WITH ARCHITECT PRIOR
TO INSTALLATION.
GENERAL CODE NOTES
LIFE SAFETY SYMBOLS LEGEND
EXIT PATH AND DIRECTION OF TRAVEL
EXIT DISCHARGE
EXIT LIGHT
P = xx OCCUPANT LOAD
FEC-# FIRE EXTINGUISHER CABINET
NUMBER OF OCCUPANTS IN EXIT PATH54
SMOKE PARTITION
TD: 90'-4"
CPT: 75'-10" COMMON PATH OF TRAVEL
BRACKET MOUNTED FIRE EXTINGUISHERFE
PROJECT SUMMARY
APPLICABLE CODES
W/ CURRENT STATE
AMENDMENTS
IBC
IBC MECHANICAL CODE
IBC PLUMBING CODE
IBC FUEL GAS CODE
NATIONAL ELECTRICAL CODE
NFPA 101
ADA
IECC
2024 EDITION
2024 EDITION
2024 EDITION
2024 EDITION
2023 EDITION
2024 EDITION
2010 EDITION
2015 EDITION
INTERNATIONAL FIRE CODE
NFPA 13R
NFPA 13D
2024 EDITION
2022 EDITION
2022 EDITION
ILLUMINATED FACE
DIRECTIONAL ARROW
S2 SPATIAL USE TAG
PATH OF TRAVEL ORIGINATION
TRAVEL DISTANCE
2 HR FIRE PARTITION
ROOM NAME
RM #
## SF/P P = #
AREA
OCCUPANT
LOAD RATIO
OCCUPANT
LOAD
OCCUPIED SPACE TAG
P = 10
NET AREA OCCUPANT LOAD
(SUBSET OF ROOM TOTAL)150 SF
WAITING AREA
OCCUPANT
LOAD
AREA NAME
UNOCCUPIED SPACE TAG
Room name
150 SF
FIRE STATION IS A SEPARATED MIXED OCCUPANCY, SINGLE STORY BUILDING - NEW
CONSTRUCTION
IBC OCCUPANCY: MIXED
TWO-BAY THREE-BAY
GROUP R-3 3,345 SF 3,345 SF
GROUP S-2 4,253 SF 5,456 SF
7,598 SF ENCLOSED AREA 8,801 SF
COVERED 400 @ 1/2 200 SF
NFPA 101 OCCUPANCY : MIXED
LODGING / ROOMING HOUSE
2 HOUR OCCUPANCY SEPARATION
LOW HAZARD STORAGE WITH INCIDENTAL BUSINESS
OCCUPANT LOAD TOTAL : PER LIFE SAFETY PLAN = 53
5 TRANSIENT RESIDENTS + 2 OFFICES
CONSTRUCTION TYPE : TYPE VB UNSPRINKLERED STORAGE / SPRINKLERED NFPA 13R
LODGING
EXITS REQUIRED: 2
SEE PLAN FOR FIRE RATED PARTITION REQUIREMENTS
122 SF
DORM 3
200 SF/P P = 1
122 SF
DORM 2
200 SF/P P = 1
122 SF
DORM 1
200 SF/P P = 1
76 SF
LAUNDRY
39 SF
SHOWER 2
58 SF
RESTROOM
296 SF
GEAR ROOM
500 SF/P P = 1
76 SF
MECHANICAL
177 SF
ENTRY
131 SF
STORAGE
2685 SF
APPARATUS
BAY
500 SF/P P = 6
833 SF
DAY ROOM
15 SF/P P = 31
122 SF
SHIFT COMM.
DORM
200 SF/P P = 1
122 SF
SHIFT
COMMANDER
200 SF/P P = 1
39 SF
SHOWER 1
52 SF
CLOSET
122 SF
DORM 4
200 SF/P P = 1
46 SF
ELEC.
49 SF
IT
136 SF
OFFICE
150 SF/P P = 1
367 SF
CORRIDOR
319 SF
KITCHEN
50 SF/P P = 7
IBC 303 .1.2.1 SMALL ASSEMBLY
SPACES - A ROOM OR SPACE USED
FOR ASSEMBLY PURPOSES WITH AN
OCCUPANT LOAD OF LESS THAN 50
PERSONS AND ACCESSORY TO
ANOTHER OCCUPANCY SHALL BE
CLASSIFIED AS A GROUP B
OCCUPANCY...
456 SF
456 SF
SMOKE PARTITIONS WITH GWB CEILING
APPROVED TO STOP THE TRANSFER OF
SMOKE - NOTES LODGING / ROOMING HOUSE
NOTES FOR DOOR REQUIREMENTS
2 HOUR FIRE RESISTANCE SEPARATION -
TRAVEL DISTANCE = 44'-4"
TRAVEL DISTANCE = 41'-11"
LODGING / ROOMING HOUSE (3,345 SF)
NFPA 101 - 2018 REVIEW
DEAD END CORRIDORS - NO REQUIREMENT
TRAVEL DISTANCE - NO REQUIREMENT
COMMON PATH OF TRAVEL - NO REQUIREMENT
ALL SLEEPING ROOMS SHALL BE SEPARATED FROM ESCAPE
ROUTE CORRIDORS BY SMOKE PARTITIONS
IN ADDITION TO PRIMARY ROUTE, EACH SLEEPING ROOM AND
LIVING AREA SHALL HAVE SECOND MEANS OF ESCAPE...
TRANSFER GRILLES SHALL BE PROHIBITED IN CORRIDOR WALLS
DOORS SHALL BE PROVIDED WITH LATCHES OR OTHER
MECHANISMS SUITABLE FOR KEEPING THE DOORS CLOSED;
DOORS SHALL BE SELF-CLOSING OR AUTOMATIC CLOSING UPON
DETECTION OF SMOKE.
PROVIDE A FIRE ALARM SYSTEM IAW SECTION LSC 9.6 / INITIATION
SHALL BE BY MANUAL MEANS
PROVIDE APPROVED SMOKE ALARMS
PROVIDE CARBON MONOXIDE ALARMS OR CARBON MONOXIDE
DETECTORS / OUTSIDE EACH SEPARATE SLEEPING AREA.
PROVIDE AUTOMATIC SPRINKLER SYSTEM WITHIN LODGING AREA
IAW NFPA 13R (NFPA 101 26.3.6.2.2)
PROVIDE PORTABLE FIRE EXTINGUISHERS
266 SF
WELLNESS
150 SF/P P = 2
148 SF
DECON
64 SF
AIR LOCK
3•
S2 LOW / HAZARD STORAGE (4,253 SF)
TYPE VB UNSPRINKLERED
ALLOWABLE AREA = 13,500 SF
ALLOWABLE HEIGHT = 40'-0"
ALLOWABLE NUMBER OF STORIES = TWO
NFPA 101 - 2018
ORDINARY HAZARD STORAGE
DEAD END CORRIDOR = 50 FT
COMMON PATH OF TRAVEL = 50 FT
TRAVEL DISTANCE = 200 FT
S2
B
S2
S2
FEC
FE
FEC
FE FE
FEC
FE
C
FE
C
THESE WALLS GO TO THE DECK ABOVE
FE
GROUP R-3 IBC 2018 REVIEW (3,345 SF)
TABLE 504.3 ALLOWABLE BUILDING HEIGHT IN FEET ABOVE GRADE
PLAN FOR TYPE VB CONSTRUCTION = 60
NEW GROUP R OCCUPANCIES ARE REQUIRED TO BE PROTECTED
BY AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
SECTION 903.2.8 S13R HAS ALLOWABLE HEIGHT OF 60'
TABLE 504.4 R-1 S13R FOR TYPE V CONSTRUCTION ALLOWS 3
STORIES ABOVE THE GRADE PLAN
TABLE 506.2 ALLOWABLE AREA = 7,000 SF
DESIGN FOR A NFPA 13R/13D HYBRID SPRINKLER SYSTEM WILL BE
SUBMITTED FOR THE GROUP R-3 AREA USING AN ADDITIONAL
STORAGE INTERIOR STORAGE TANK STORING THE REQUIRED
CAPACITY OF WATER NECESSARY SINCE THERE IS NO WATER
AVAILABLE ON-SITE EXCEPT FOR WELL WATER.
THE LIGHT GRAY AREA REPRESENTS AREA
OF UNSEPARATED ATTIC SPACE OF 2,782 SF.
NO ADDITIONAL DRAFT STOP WITHIN THE
ATTIC IS REQUIRED
DRAFT STOP WITHIN THE ATTIC ABOVE CMU
PARTITIONS
R3
B
Project No.:
Date:
Drawn by:
Checked by:
Revisions:
PR
IN
TE
D:
FI
LE
P
AT
H:
11 Ninth Street, Suite 120 Columbus, GA 31901 P. (706) 571-6923
8/
/2
4:
:3
PM
C :\U se rs
\A le xG rig gs _r m ud ak 7\
Ap pD at a\
Lo ca l\A ut od es k\ R ev it\
Au to de sk
R ev it
\C ol la bo ra tio nC ac he
\Q 2G
2D
JC
C L7
R D
H U
\3 e7
8-
5e db
-4
2-a3
-8
7d
2\
9a
7e 2b
-1 d6 c-a6 -a b7 c-f1 b5
.rv t
LS1.1
LIFE SAFETY
PLAN
B
U R
KE
S
C H
AP
EL
R O
AD
TR
O U
P C
O U
N
TY
, G
EO
R G
IA
TR
OU
P
CO
UN
TY
F
IR
E
ST
AT
IO
N #1
WAG
8/18/2026 26-00013
0%
C
ON
ST
RU
CT
IO
N
DO
CU
ME
NT
S
WAG
SCALE: 1/8" = 1'-0"LS1.1
1 LIFE SAFETY PLAN
ASSUMED
PROJECT
NORTH
No. Date Description
VICINITY MAP
N.T.S
OWNER:
Troup Co. Board of Commissioners
100 Ridley Ave.,LaGrange, GA 30240 CONTACT: James Anderson
706-645-5885
ENGINEER / SURVEYOR:
HARRIS GRAY LLC
824 3RD AVENUE
WEST POINT, GA 31833
706-645-5885
CONTACT: SCOTT HARRIS, P.E.
24 HOUR LOCAL CONTACT:
James Anderson @ 706-298-3792 janderson@troupco.org
PLANS PREPARED: AUGUST 17, 2026
CONSTRUCTION PLANS
TROUP COUNTY
FIRE STATION @
BURKES CHAPEL RD.
FOR STAND ALONE PROJECTS THAT BEGIN CONSTRUCTION ACTIVITY AFTER THE
EFFECTIVE DATE OF THIS PERMIT, THE PRIMARY PERMITTEE MUST RETAIN THE DESIGN
PROFESSIONAL WHO PREPARED THE EROSION, SEDIMENTATION AND POLLUTION
CONTROL PLAN, OR AN ALTERNATIVE DESIGN PROFESSIONAL APPROVED BY EPD IN
WRITING, TO INSPECT THE INSTALLATION OF THE INITIAL SEDIMENT STORAGE
REQUIREMENTS AND PERIMETER CONTROL BMPs WHICH THE DESIGN PROFESSIONAL
DESIGNED WITHIN SEVEN (7) DAYS AFTER INSTALLATION. THE DESIGN PROFESSIONAL
SHALL DETERMINE IF THESE BMPs HAVE BEEN INSTALLED AND ARE BEING MAINTAINED
AS DESIGNED. THE DESIGN PROFESSIONAL SHALL REPORT THE RESULTS OF THE
INSPECTION TO THE PRIMARY PERMITTEE WITHIN SEVEN (7) DAYS AND THE PERMITTEE
MUST CORRECT ALL DEFICIENCIES WITHIN TWO (2) BUSINESS DAYS OF RECEIPT OF THE
INSPECTION REPORT FROM THE DESIGN PROFESSIONAL UNLESS WEATHER RELATED
SITE CONDITIONS ARE SUCH THAT ADDITIONAL TIME IS REQUIRED.
REVISIONS OR AMENDMENTS TO THESE PLANS SHOULD BE SUBMITTED TO THE LOCAL
ISSUING AUTHORITY FOR REVIEW.
NPDES CERTIFICATIONS
1. I CERTIFY THAT THE PERMITTEE'S EROSION, SEDIMENTATION AND POLLUTION CONTROL PLAN
PROVIDES FOR AN APPROPRIATE AND COMPREHENSIVE SYSTEM OF BEST MANAGEMENT
PRACTICES REQUIRED BY THE GEORGIA WATER QUALITY CONTROL ACT AND THE DOCUMENT
"MANUAL FOR EROSION AND SEDIMENT CONTROL IN GEORGIA" (MANUAL) PUBLISHED BY THE
GEORGIA SOIL AND WATER CONSERVATION COMMISSION AS OF JANUARY 1 OF THE YEAR IN
WHICH THE LAND-DISTURBING ACTIVITY WAS PERMITTED, PROVIDES FOR THE SAMPLING OF
THE RECEIVING WATER(S) OR THE SAMPLING OF THE STORM WATER OUTFALLS AND THAT
THE DESIGNED SYSTEM OF BEST MANAGEMENT PRACTICES MEETS THE DESIGN
REQUIREMENTS AND SAMPLING METHODS IS EXPECTED TO MEET THE REQUIREMENTS
CONTAINED IN THE GENERAL NPDES PERMIT NO. GAR 100001.
2. "I CERTIFY UNDER PENALTY OF LAW THAT THIS PLAN PREPARED AFTER A SITE VISIT TO THE
LOCATIONS DESCRIBED HEREIN BY MYSELF OR MY AUTHORIZED AGENT, UNDER MY DIRECT
SUPERVISION."
3. GEORGIA'S 2012 OR SUBSEQUENT 305(b)/303(d) LIST DOCUMENTS HAVE BEEN CONSULTED. IT
WAS DETERMINED THAT THIS SITE DOES NOT DRAIN INTO AN IMPAIRED STREAM
SEGMENT, NOR IS WITHIN 1 LINEAR MILE UPSTREAM OF AND WITHIN THE SAME WATERSHED
AS, ANY PORTION OF A BIOTA IMPAIRED STREAM SEGMENT.
SCOTT HARRIS, P.E. # 35488, GWSCC # 4456 DATE
8-17-26
ANTICIPATED CONSTRUCTION SCHEDULE
LANDSCAPING & GRASSING
FINAL PAVING
EROSION CONTROL / BMP MAINTENANCE*
ACTIVITY
EROSION CONTROL / BMP INSTALLATION
GRADING
21 13 4 2 3 4
CLEARING & GRUBBING
MO. 1 MO. 2
1. MAINTENANCE OF EROSION AND SEDIMENT CONTROL WILL BE MONITORED DAILY AND INSPECTED WEEKLY THROUGHOUT PROJECT.
2. NOTIFY INSPECTOR 24 HOURS BEFORE BEGINNING EVERY PHASE OF CONSTRUCTION.
3. CONTRACTOR IS TO REMOVE ALL TEMPORARY SEDIMENT CONTROL AFTER FINAL STABILIZATION OF SITE.
STORM DRAINAGE
UTILITIES (WATER, SEWER, ETC.)
PARKING SUBBASE
BUILDING
1 2 3 4
MO. 3
1 2 3 4
MO. 4
1 2 3 4
MO. 5
SHEET INDEX
Sheet Number Sheet Title
01 COVER
02 GSWCC CHECKLIST & INFO
03 CONSTRUCTION NOTES
04 EXISTING CONDITIONS
05 SITE PLAN
06 GRADING & DRAINAGE PLAN
07 STORM PROFILES & DETAILS
08 STORM DETAILS
09 UTILITY PLAN
10 E.S.& P.C. NOTES
11 E.S.& P.C. NOTES
12 E.S.& P.C. PLAN INITIAL PHASE
13 E.S.& P.C. PLAN INTERMEDIATE PHASE
14 E.S.& P.C. PLAN FINAL PHASE
15 GSWCC DETAILS
16 GSWCC DETAILS
17 CONSTRUCTION DETAILS
18 CONSTRUCTION DETAILS
19 CONSTRUCTION DETAILS
GEORGIA STATE MAP
SITE
TROUP
COUNTY
Burkes Chapel Rd
W hi te sv ille R d
Wood Valley Dr
Baughs Crossroads
SAFE DIGGING PA RTNER
CO
NT
ACT 811 BEFORE YOU DIG
72 HRS NOTICE IS REQUIRED TO GEORGIA
811 UTILITY PROTECTION CENTER BEFORE
ANY PLANNED DIGGING.
w w w . G e o r g i a 8 1 1 . c o m
8-17-26J OHN S C O T T HA RR I S
R
E G I S T E R E
D
E N G I N E E R
NO. PE35488
PROFESSIONAL
G
E O R G I A
GSWCC LEVEL II # 4456
EXP. 03-27-2027
LAND LOT 160 & 181 - 4th LAND DISTRICT
TROUP COUNTY, GEORGIA
ADDRESS: ? BURKES CHAPEL RD.
GPS COORDINATES
LATITUDE N 32.9167°
LONGITUDE W 85.0187°
SITE ADDRESS: ? BURKES CHAPEL RD.
TOTAL SITE ACREAGE: 2.243 Ac.
AREA OF DISTURBANCE: 2.0 Ac.
ZONING: AGR
ENGINEERS SURVEYORS PLANNERS
HARRIS GRAY, LLC
824 THIRD AVENUE WEST POINT, GEORGIA 31833
PHONE: (706) 645 - 5885
CERTIFICATE OF AUTHORIZATION NO:PEF006540
8-17-26
SITE
SCALE IN FEET
01000 500 1000
1" = 1000'
SCALE IN FEET
01000 500 1000
1" = 1000'
SITE
E N
G
IN
E E
R S
S U
R V
E Y
O R
S P
LA
N
N E
R S
H
AR
R
IS
G R
AY
, L
LC
TH
IR
D A
V E
N U
E W
E S
T P
O
IN
T, G
E O
R G
IA
P H
O N
E
6)
C E
R
TI
FI
C
A
TE
O F
A U
TH
O
R
IZ
A
TI
O N
N O
P
E F0
CHKD BY
DRAWN BY
DATE
FILE NAME
JOB NO.
J OHN S C O T T HA RRIS
R
E G I S T E R E
D
E N G I N E E R
NO. PE35488
PROFESSIONAL
G
E O R G I A
GSWCC LEVEL II # 4456
EXP. 03-27-2027
JAM
JSH
COVER.DWG
GA260144
SHT. OF
TR
OU
P
CO
UN
TY
FI
RE
S
TA
TI
ON
B
UR
KE
S
CH
AP
EL
R D.
8-17-26
-1
7-
Se pt ic S ys te m
C on du its
R ev is ed
HG
G
SW
C C
C H
EC
KL
IS
T
IN
FO
Warm Water (Supporting Warm Water Fisheries) Surface Water Drainage Area, square miles
0-4.99
1.00-10 10.01-25
Site Size, acres 25.01-50
50.01-100
100.01 +
5-9.99
10-24.99 25-49.99 50-99.99 100-249.99 250-499.99 500+
ARC
RADIUS
CHORD LENGTH
CHORD BEARING
DELTA
RIGHT OF WAY
POINT OF VERTICAL TANGENT
POINT OF VERTICAL INTERSECTION
POINT OF VERTICAL CURVE
AT
ON CENTER
ELEVATION
LENGTH
SLOPE
DIAMETER
TYPICAL
LINEAR FOOT
DEGREE
STATION
INVERT IN
INVERT OUT
SERVICE LATERAL
DOUBLE-WING INLET
SINGLE-WING INLET
MANHOLE
EDGE OF PAVEMENT
BACK OF CURB
FACE OF CURB
POLYVINYL CHLORIDE PIPE
REINFORCED CONCRETE PIPE
DUCTILE IRON PIPE
HIGH PERFORMANCE POLYPROPYLENE PIPE
HIGH DENSITY POLYETHYLENE PIPE
PROPERTY BOUNDARY LINE
RIGHT-OF-WAY LINE
LOT LINE
EASEMENT
SETBACK LINE
CENTERLINE
EXISTING FENCE LINE
PROPOSED FENCE LINE
EXISTING TREE LINE
PROPOSED TREE LINE
EXISTING WETLANDS
BORING LOCATIONS
BENCHMARK
EXISTING CONTOUR
PROPOSED CONTOUR
FLOW ARROW
WATER LINE TEE
WATER VALVE (TYPE)
GV = GATE VALVE BV = BUTTERFLY VALVE
PV = PLUG VALVE CV = CHECK VALVE
WATER LINE BLOW OFF VALVE
WATER LINE CAP
WATER LINE REDUCER
WATER LINE BEND
SINGLE WATER SERVICE
DOUBLE WATER SERVICE
EXISTING FIRE HYDRANT ASSEMBLY
PROPOSED FIRE HYDRANT ASSEMBLY
EXISTING POTABLE WATER LINE
PROPOSED POTABLE WATER LINE
EXISTING IRRIGATION MAIN
PROPOSED IRRIGATION MAIN
EXISTING FIRE PROTECTION MAIN
PROPOSED FIRE PROTECTION MAIN
STORM SEWER STRUCTURE NUMBER
STORM SEWER JUNCTION BOX
STORM SEWER FLARED END SECTION
STORM SEWER YARD DRAIN
SINGLE-WINGED INLET
DOUBLE-WINGED INLET
GRATE AND HOOD INLET
AREA/GRATE INLETS
EXISTING STORM DRAIN PIPE
PROPOSED STORM DRAIN PIPE
DIRECTION OF FLOW
SANITARY SEWER MANHOLE
SANITARY SEWER STRUCTURE NUMBER
SINGLE SANITARY SEWER SERVICE
DOUBLE SANITARY SEWER SERVICE
EXISTING SANITARY SEWER LINE
PROPOSED SANITARY SEWER LINE
EXISTING SANITARY SEWER FORCEMAIN
PROPOSED SANITARY SEWER FORCEMAIN
EXISTING GAS LINE
PROPOSED GAS LINE
EXISTING UNDERGROUND ELECTRIC LINE
PROPOSED UNDERGROUND ELECTRIC LINE
EXISTING OVERHEAD ELECTRIC LINE
PROPOSED OVERHEAD ELECTRIC LINE
EXISTING TELEPHONE LINE
PROPOSED TELEPHONE LINE
EXISTING FIBEROPTIC LINE
PROPOSED FIBEROPTIC LINE
LEGEND AND ABBREVIATIONS
A R C
CH
Δ
R.O.W
PVT
PVI
PVC
O.C.
ELE.
L S Ø
TYP.
LF
STA.
INV. IN
INV. OUT
S.L.
DW-INLET
SW-INLET
MH
EP
BC
FC
PVC
RCP
DIP
HP
HDPE
WAT WAT
IRR IRR
FP FP
FP FP
IRR IRR
WAT WAT
FM
FM
GAS GAS
GAS GAS
UE UE
UE UE
OE OE
OE OE
T
T
FO FO
FO FO
WAT
15"x12"
45°
GV
BM
TH1-102
#67 S
E N
G
IN
E E
R S
S U
R V
E Y
O R
S P
LA
N
N E
R S
H
AR
R
IS
G R
AY
, L
LC
TH
IR
D A
V E
N U
E W
E S
T P
O
IN
T, G
E O
R G
IA
P H
O N
E
6)
C E
R
TI
FI
C
A
TE
O F
A U
TH
O
R
IZ
A
TI
O N
N O
P
E F0
CHKD BY
DRAWN BY
DATE
FILE NAME
JOB NO.
JOHN S C O T T HA RRI S
R
E G I S T E R E
D
E N G I N E E R
NO. PE35488
PROFESSIONAL
G
E O R G I A
GSWCC LEVEL II # 4456
EXP. 03-27-2027
JAM
JSH
NOTES.DWG
GA260144
SHT. OF
TR
OU
P
CO
UN
TY
FI
RE
S
TA
TI
ON
B
UR
KE
S
CH
AP
EL
R D.
8-17-26
-1
7-
Se pt ic S ys te m
C on du its
R ev is ed
HG
GENERAL PROVISIONS
1. ALL WORK SHALL COMPLY WITH APPLICABLE STATE, FEDERAL AND LOCAL CODES, AND ALL NECESSARY LICENSES AND
PERMITS SHALL BE OBTAINED BY THE CONTRACTOR AT HIS EXPENSE UNLESS PREVIOUSLY OBTAINED BY THE OWNER.
CONTRACTOR SHALL ABIDE BY ALL CONDITIONS CONTAINED THEREIN.
2. ALL WORK SHALL BE PERFORMED IN A FINISHED AND WORKMAN LIKE MANNER TO THE ENTIRE SATISFACTION OF THE
OWNER AND IN ACCORDANCE WITH THE BEST RECOGNIZED TRADE PRACTICES.
3. DEVIATIONS FROM THE PLANS WITHOUT THE PRIOR CONSENT OF THE OWNER OR HIS REPRESENTATIVES MAY BE CAUSE
FOR THE WORK TO BE UNACCEPTABLE.
4. A PRE-CONSTRUCTION MEETING WILL BE REQUIRED. CONTRACTOR SHALL CONTACT TROUP COUNTY TO SCHEDULE A
MEETING.
5. THE DRAWINGS AND TROUP COUNTY STANDARD FOR DESIGN AND CONSTRUCTION SPECIFICATIONS ARE INTENDED TO COVER A COMPLETE PROJECT READY FOR USE, AND ALL ITEMS NECESSARY FOR A COMPLETE AND WORKABLE JOB SHALL
BE FURNISHED AND INSTALLED.
6. ALL MATERIALS SHALL BE NEW, UNLESS USED OR SALVAGED MATERIALS ARE AUTHORIZED BY THE OWNER AND APPROPRIATE AUTHORITIES. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR ENGINEER AND CITY APPROVAL PRIOR TO
PROCUREMENT OF MATERIALS.
7. THE CONTRACTOR SHALL FURNISH AND MAINTAIN ALL NECESSARY BARRICADES AROUND THE WORK AND SHALL PROVIDE
PROTECTION AGAINST WATER DAMAGE AND SOIL EROSION.
8. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE THE LOCATION OF ALL EXISTING UNDERGROUND UTILITIES AND TO TAKE WHATEVER STEPS NECESSARY TO PROVIDE FOR THEIR PROTECTION. THE ENGINEER HAS DILIGENTLY ATTEMPTED TO LOCATE AND INDICATE ALL EXISTING FACILITIES ON THESE PLANS; HOWEVER, THIS INFORMATION IS SHOWN FOR THE CONTRACTOR'S CONVENIENCE ONLY AND IS NOT OWNER GUARANTEED. IN THE EVENT OF DAMAGE TO EXISTING UTILITIES, THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL REPAIRS AND RELATED EXPENSES.
9. THE CONTRACTOR IS TO CONTACT THE UTILITY COMPANIES FOR EXACT LOCATION OF THEIR UTILITIES PRIOR TO STARTING CONSTRUCTION. THE CONTRACTOR SHALL NOTIFY THE GEORGIA UTILITIES PROTECTION CENTER (1-800-282-7411) AND THE
TROUP COUNTY FOR LOCATION OF EXISTING UNDERGROUND UTILITIES.
10. CONTRACTOR SHALL COORDINATE LOCATION AND INSTALLATION OF ALL UNDERGROUND UTILITIES AND APPURTENANCES TO MINIMIZE DISTURBING CURBING, PAVING, AND COMPACTED SUB-GRADE. ALL UNDERGROUND UTILITIES, INCLUDING THOSE INSTALLED BY OTHERS (ELECTRICAL CONDUIT, GAS, TELEPHONE, WATER, SANITARY, SEWER AND ANY OTHER MISCELLANEOUS) SHALL BE IN-PLACE PRIOR TO THE PLACEMENT OF BASE COURSE MATERIAL IF POSSIBLE.
11. IF THE CONTRACTOR, IN THE COURSE OF WORK, FINDS ANY DISCREPANCY BETWEEN THE PLANS AND THE PHYSICAL CONDITIONS OF THE LOCALITY, OR ANY ERRORS OR OMISSIONS IN THE PLANS OR THE LAYOUT AS GIVEN BY THE ENGINEER, IT SHALL BE HIS DUTY TO IMMEDIATELY INFORM THE ENGINEER, IN WRITING, AND ENGINEER WILL PROMPTLY VERIFY THE SAME. ANY WORK DONE AFTER SUCH DISCOVERY, UNTIL AUTHORIZED, WILL BE AT THE CONTRACTOR'S RISK.
12. IT SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER IF HISTORICAL ARTIFACTS OR ENDANGERED SPECIES OF
PLANTS ARE ENCOUNTERED DURING CONSTRUCTION.
13. A CONSTRUCTION TRAILER SHALL BE PERMITTED THROUGH THE TROUP COUNTY WHEN REQUIRED AND COORDINATED WITH
THE OWNER IN ORDER TO NOT IMPEDE ANY CURRENT OPERATIONS.
14. THE CONTRACTOR SHALL PROVIDE SHEETING AND SHORING FOR ALL TRENCH CONSTRUCTION IN ACCORDANCE WITH O.S.H.A. GUIDELINES. THERE SHALL BE NO OPEN TRENCHES AT THE END OF THE DAY'S WORK.
15. CONTRACTOR SHALL MAINTAIN ACCESS FOR EMERGENCY VEHICLES AROUND AND TO ALL BUILDINGS UNDER CONSTRUCTION. IN TIMES OF RAIN OR MUD, ROADS SHALL BE ABLE TO CARRY A FIRE TRUCK BY BEING PAVED OR HAVING A CRUSHED STONE BASE WITH A MINIMUM WIDTH OF 25 FEET. THIS ACCESS TO BUILDINGS THAT HAVE SPRINKLER OR STANDPIPE SYSTEMS SHALL BE TO WITHIN 40 FEET OF THE FIRE DEPARTMENT CONNECTOR. (NFPA 1141 3-1 AND GCFO-15)
16. CONTRACTOR SHALL PROVIDE THE OWNER AND ENGINEER WITH A CONSTRUCTION SCHEDULE FOR THE WORK.
GEOTECHNICAL
1. SOILS TESTING AND ON-SITE INSPECTION MAY BE PERFORMED BY AN INDEPENDENT GEOTECHNICAL ENGINEER SELECTED AND PAID BY THE OWNER. IN THE EVENT OF CONFLICT BETWEEN THE INSTRUCTIONS BY THE ENGINEER AND RECOMMENDATIONS PROVIDED BY THE OWNER'S GEOTECHNICAL ENGINEER, THE CONTRACTOR WILL ADHERE TO THE MOST
STRINGENT.
2. CONTRACTOR SHALL PROVIDE ANY EXCAVATION AND MATERIAL SAMPLES NECESSARY TO CONDUCT REQUIRED SOIL TESTS.
ALL ARRANGEMENTS AND SCHEDULING FOR TESTING SHALL BE THE CONTRACTOR'S RESPONSIBILITY.
3. GEOTECHNICAL ENGINEER SHALL PROVIDE COPIES OF TEST REPORTS TO THE CONTRACTOR, THE OWNER, AND THE OWNER'S REPRESENTATIVE AND SHALL NOTIFY THE OWNER, HIS REPRESENTATIVE AND THE CONTRACTOR PROMPTLY
SHOULD WORK PERFORMED BY THE CONTRACTOR FAIL TO MEET THESE SPECIFICATIONS.
4. MOISTURE-DENSITY RELATIONSHIPS (STANDARD PROCTOR) SHALL BE DETERMINED FOR EACH SOIL TYPE ENCOUNTERED ONSITE TO PROVIDE DATA FOR QUALITY CONTROL. THE GEOTECHNICAL ENGINEER SHALL REVIEW THE TEST RESULTS AND ADVISE ON THE SUITABILITY OF THE PROPOSED FILL MATERIAL. THE MOISTURE CONTENT AT THE TIME OF COMPACTION
SHALL BE WITHIN 3 PERCENTAGE POINTS OF OPTIMUM MOISTURE CONTENT.
4. SUITABLE FILL MATERIAL SHALL BE FREE OF ORGANICS, STONES GREATER THAN ONE INCH IN DIAMETER, OR OTHER DELETERIOUS MATERIAL AS DETERMINED BY THE GEOTECHNICAL ENGINEER. SOILS MIXED WITH BLAST ROCK SHALL
GENERALLY NOT BE CONSIDERED SUITABLE.
5. ALL FILLS SHALL BE COMPLETED IN LIFTS NOT TO EXCEED EIGHT INCHES IN LOOSE THICKNESS. EACH LIFT SHALL BE
COMPACTED UTILIZING APPROPRIATE MECHANICAL MEANS.
6. COMPACT SOIL TO NOT LESS THAN THE FOLLOWING PERCENTAGES OF MAXIMUM DRY DENSITY ACCORDING TO ASTM D 698, AASHTO T-99:
A. UNDER STRUCTURES, BUILDING SLABS, STEPS, AND PAVEMENTS, COMPACT THE TOP 12 INCHES BELOW SUBGRADE AT 98 PERCENT MAXIMUM DRY DENSITY, AND EACH LAYER OF BACKFILL OR FILL MATERIAL AT 95 PERCENT MAXIMUM
DRY DENSITY.
B. UNDER WALKWAYS, COMPACT THE TOP 6 INCHES BELOW THE SUBGRADE AND EACH LAYER OF BACKFILL OR FILL
MATERIAL AT 95 PERCENT MAXIMUM DRY DENSITY.
C. UNDER LAWN OR UNPAVED AREAS, COMPACT THE TOP 6 INCHES BELOW SUBGRADE AND EACH LAYER OF BACKFILL
OR FILL MATERIAL AT 95 PERCENT MAXIMUM DENSITY.
EARTHWORK/GRADING
1. EARTHWORK AND GRADING SHALL BE PERFORMED IN ACCORDANCE WITH THE GEOTECHNICAL ENGINEER'S
SPECIFICATIONS AND RECOMMENDATIONS, OR WITH SECTIONS 201-221 OF GA DOT'S STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION IF NOT COVERED BY THE GEOTECHNICAL ENGINEER'S SPECIFICATIONS, EXCEPT AS
OTHERWISE NOTED.
2. MAXIMUM SLOPE FOR CUT OR FILL IS 2H: 1V. ANY SLOPES AT 2:1 OR STEEPER SHALL BE STABILIZED WITH APPROPRIATELY
DESIGNED SLOPE MATTING.
3. THE FOLLOWING CLASSIFICATIONS WILL BE USED FOR DESCRIBING DIFFICULT EXCAVATION MATERIAL.
A. TRENCH ROCK - ANY MATERIAL THAT CANNOT BE EXCAVATED WITH A TRACKED BACKHOE HAVING A BUCKET CURLING FORCE OF AT LEAST 30,000 POUNDS (CATERPILLAR 320 OR EQUIVALENT) AND OCCUPYING AN IN-PLACE VOLUME OF AT
LEAST 0.5 CUBIC YARDS
B. DIFFICULT EXCAVATION - ANY MATERIAL THAT CANNOT BE REMOVED BY NORMALLY USED GRADING EQUIPMENT, AND REQUIRES THE USE OF A SINGLE-TOOTH RIPPER ATTACHED TO A DOZER HAVING A DRAW BAR PULL OF AT LEAST 90,000 POUNDS (CATERPILLAR D-8 OR EQUIVALENT) AND OCCUPIES AN IN-PLACE VOLUME OF AT LEAST ONE CUBIC
YARD.
C. BLAST ROCK - ANY MATERIAL THAT CANNOT BE RIPPED WITH A SINGLE-TOOTHED RIPPER ATTACHED TO A DOZER HAVING A DRAW BAR PULL OF AT LEAST 90,000 POUNDS (CATERPILLAR D-8 OR EQUIVALENT) AND OCCUPIES AN
IN-PLACE VOLUME OF AT LEAST ONE CUBIC YARD.
4. EXCESS EARTH CUT MATERIALS, UNSUITABLE MATERIALS OR ROCK, IF ANY, SHALL BE PLACED AT A LOCATION ON OR NEAR
THE SITE AS DESIGNATED BY THE OWNER.
5. STRIP EXISTING TOPSOIL FROM AREAS THAT WILL BE EXCAVATED OR GRADED PRIOR TO COMMENCEMENT OF EXCAVATION OR GRADING AND PLACE IN WELL DRAINED STOCKPILES AT LOCATIONS APPROVED BY THE OWNER AND/OR ENGINEER.
6. BASE MATERIAL SHALL BE CLEANED, SHAPED AND INSPECTED BEFORE ASPHALT LAYER IS ADDED.
7. ELEVATIONS SHOWN ON THE PROFILES ARE CENTERLINE PAVEMENT ELEVATIONS, MEASURED TO THE TOP OF FINISHED
PAVEMENT, UNLESS OTHERWISE NOTED.
8. ALL OFFSITE DISTURBED AREAS SHALL BE RESTORED TO PRECONSTRUCTION CONDITION OR BETTER.
9. CONTRACTOR IS RESPONSIBLE FOR DISPOSING OF ALL WASTE MATERIALS CONSISTENT WITH REGULATIONS APPLICABLE TO
THE MATERIALS.
EROSION AND SEDIMENT CONTROL
1. SEE "EROSION SEDIMENT AND POLLUTION CONTROL PLAN," NOTES AND DETAILS SHEETS, FOR ADDITIONAL EROSION AND
SEDIMENT CONTROL NOTES.
2. CONSTRUCTION EXIT PADS SHALL BE INSTALLED BY THE CONTRACTOR AT EACH CONSTRUCTION ACCESS POINT.
3. EROSION AND SEDIMENT CONTROL MEASURES SHALL BE MAINTAINED AT ALL TIMES. ADDITIONAL EROSION AND SEDIMENT
CONTROL MEASURES SHALL BE INSTALLED IF DEEMED NECESSARY BY ON-SITE INSPECTION.
4. PROVISIONS TO PREVENT EROSION OF THE SOIL FROM THE SITE SHALL CONFORM TO THE REQUIREMENTS OF THE "MANUAL FOR EROSION AND SEDIMENT CONTROL IN GEORGIA," LATEST EDITION AND SHALL BE FOLLOWED AND INSTALLED IN A MATTER SO AS TO MINIMIZE EROSION OF THE DISTURBED AREAS AND PREVENT SEDIMENT FROM LEAVING THE SITE.
5. THE CONTRACTOR WILL BE REQUIRED TO INCORPORATE ALL TEMPORARY AND PERMANENT EROSION CONTROL MEASURES INTO THE PROJECT AT THE EARLIEST PRACTICABLE TIME DURING CONSTRUCTION. THE EROSION CONTROL MEASURES DETAILED HEREON SHALL BE CONTINUED UNTIL THE GRASS ON PLANTED SLOPES IS SUFFICIENTLY ESTABLISHED TO BE AN EFFECTIVE EROSION DETERRENT. THE SEDIMENT REMOVED FROM THE CONTROL STRUCTURES SHALL BE EVENLY DISTRIBUTED INSIDE CONSTRUCTION LIMITS. DISPOSED SEDIMENT SHALL BE PERMANENTLY GRASSED.
6. TEMPORARY AND PERMANENT VEGETATIVE COVER SHALL BE INSTALLED PER THE "EROSION SEDIMENT AND POLLUTION
CONTROL PLANS" FOR THIS PROJECT.
7. ALL EROSION AND SEDIMENT CONTROL MEASURES MUST REMAIN IN PLACE UNTIL FINAL STABILIZATION IS ESTABLISHED, AS
SHOWN ON THE "EROSION SEDIMENT AND POLLUTION CONTROL PLANS."
STORMWATER
1. STORM SEWER PIPE SHALL BE CIRCULAR, REINFORCED CONCRETE OR ALL ALLOWABLE PIPE MATERIAL, WALL B, CLASS III
PIPE OR APPROVED EQUAL WITH A MAXIMUM "n" VALUE OF 0.013.
2. END TREATMENT SHALL BE REINFORCED CONCRETE HEADWALLS, OR APPROVED EQUAL, SIZED TO MATCH THE STORM
SEWER PIPE.
3. ALL DRAINAGE PIPE LENGTHS SHOWN ON THE PLANS ARE HORIZONTAL MEASUREMENTS FOR CENTER-TO-CENTER OF THE
RELATED STRUCTURES.
4. ALL PROPOSED DRAINAGE STRUCTURES SHALL CONFORM TO TROUP COUNTY OR GEORGIA DEPARTMENT OF
TRANSPORTATION (GDOT) STANDARD DETAILS UNLESS NOTED OTHERWISE.
5. ALL PIPES UNDER PAVEMENTS: TRENCHED BACKFILL SHALL BE MECHANICALLY TAMPED FOR THE ENTIRE DEPTH OF TRENCH TO 95% STANDARD PROCTER. THE UPPER 12” SHALL BE COMPACTED TO A MINIMUM OF 98% STANDARD PROCTER.
REFER TO THE TROUP COUNTY STANDARD SPECIFICATIONS AS NECESSARY.
DAMS AND EMBANKMENTS
1. ALL DAM AND EMBANKMENT CONSTRUCTION SHALL BE MONITORED BY THE GEOTECHNICAL ENGINEER.
2. IN AREAS WHERE DAMS OR EMBANKMENTS ARE PROPOSED THE SITE SHALL BE STRIPPED OF ALL EXISTING TOPSOIL, VEGETATION, AND ROOTS.
3. WHERE POSSIBLE, CLEARING AND GRUBBING SHALL EXTEND 50 FEET BEYOND THE DOWNSTREAM TOE OF THE PROPOSED
EMBANKMENT TO ALLOW FOR ACCESS AND CLEARANCE FOR FUTURE INSPECTIONS.
4. AT THE COMPLETION OF CLEARING AND GRUBBING ACTIVITIES, THE FOOTPRINT OF THE PROPOSED EMBANKMENT SHALL BE PROOF-ROLLED USING A FULLY LOADED TRI-AXLE DUMP TRUCK, 20 TON ROLLER, OR OTHER SIMILAR EQUIPMENT.
5. ANY AREAS WHICH PUMP OR RUT EXCESSIVELY AND CANNOT BE DENSIFIED BY CONTINUED ROLLING, SHOULD BE UNDERCUT AND REPLACED WITH STRUCTURAL FILL TO AT LEAST 10 FEET OUTSIDE OF THE EMBANKMENT FOOTPRINT.
6. SURFACE WATER CONTROL SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL EMPLOY
MEASURES TO KEEP SURFACE WATER AWAY FROM CONSTRUCTION EXCAVATIONS AND FILLS.
7. SHOULD DE-WATERING ACTIVITIES BE REQUIRED DURING CONSTRUCTION, THE CONTRACTOR SHALL BE REQUIRED TO PREPARE AND SUBMIT A SURFACE WATER AND GROUNDWATER CONTROL PLAN TO THE GEOTECHNICAL ENGINEER. THIS PLAN MUST BE REVIEWED AND APPROVED BY THE GEOTECHNICAL ENGINEER PRIOR TO THE COMMENCEMENT OF
DE-WATERING ACTIVITIES.
8. CONTRACTOR SHALL INSTALL TOE DRAINS ALONG ANY EMBANKMENTS AND DAMS IN ACCORDANCE WITH THE
CONSTRUCTION PLANS.
9. TOE DRAIN OUTLETS SHALL BE CONSTRUCTED IN SUCH A MANNER AS TO ALLOW FOR THE MEASUREMENT OF SEEPAGE
FLOWS THROUGH THESE DRAINS.
10. EMBANKMENTS SHALL BE CONSTRUCTED WITH A SLOPE OF 3:1 OR FLATTER, UNLESS NOTED OTHERWISE.
11. THE CONTRACTOR SHALL COORDINATE WITH THE GEOTECHNICAL ENGINEER ON THE PLACEMENT AND OR MIXING OF ALL
PROPOSED FILL MATERIALS.
12. IN GENERAL, STRUCTURAL FILLS SHALL HAVE A LIQUID LIMIT LESS THAN 50, PLASTIC INDEX LESS THAN 30 AND A STANDARD
PROCTOR MAXIMUM DRY DENSITY (ASTM D 698) GREATER THAN 90 PCF.
13. STRUCTURAL FILLS SHOULD BE COMPACTED TO AT LEAST 95 PERCENT OF THE STANDARD PROCTOR MAXIMUM DRY
DENSITY (ASTM D 698).
14. STRUCTURAL FILLS SHALL BE PLACED IN A MAXIMUM OF 8 INCH THICK LOOSE HORIZONTAL LIFTS AND COMPACTED TO THE
SPECIFIED COMPACTION.
15. STRUCTURAL FILL LIFTS SHALL NOT BE LEFT IN A SMOOTH CONDITION PRIOR TO THE PLACEMENT OF THE SUBSEQUENT LIFT. ANY SMOOTH SURFACE LIFTS SHALL BE LIGHTLY SCARIFIED PRIOR TO THE PLACEMEN OF THE NEXT LIFT.
16. SHOULD AN EXPOSED FILL SURFACE BECOME EXCESSIVELY WET OR DRY DURING BREAKS IN GRADING ACTIVITIES, THE CONTRACTOR SHALL, AT THE DIRECTION OF THE GEOTECHNICAL ENGINEER, EITHER…